www.tyco-fire.com
www.tyco-fire.com Contacts
13
17
6
20
18 15
9 16
11
14
7
8
3
4
1
2
19
1 - DV-5 Deluge Valve 9 - System Drain Valve (N.C.) 17 - System Shut-Off Valve (N.O.)
2 - Main Control Valve (N.O.) 10 - Main Drain Valve (N.C.) 18 - Air Pressure Gauge
3 - Diaphragm Chamber Supply (Shown at Rear of Valve) 19 - Automatic Air/Nitrogen Supply
Control Valve (N.O.) 11 - Fail-Safe Valve 20 - Low Pressure Alarm Switch
4 - Local Manual Control Station 12 - Waterflow Pressure Alarm Switch 21 - Dry Pilot Actuator
5 - Automatic Sprinklers (Shown at Rear of Valve)
6 - Heat Detectors, Smoke Detectors, 13 - Water Motor Alarm (Optional)
etc. (Fire Detection) 14 - Solenoid Valve
7 - Water Supply Pressure Gauge 15 - Deluge Valve Releasing Panel
8 - Diaphragm Chamber Pressure 16 - Riser Check Valve
Gauge
FIGURE 1 (1 OF 2)
DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC ACTUATION
SYSTEM SCHEMATIC (FRONT VIEW)
TFP1460
Page 3 of 16
5
6
17
20
9
13
21
16
14
12
15
19
1 10
1 - DV-5 Deluge Valve 7 - Water Supply Pressure Gauge 15 - Deluge Valve Releasing Panel
2 - Main Control Valve (N.O.) (Shown at Front of Valve) 16 - Riser Check Valve
3 - Diaphragm Chamber Supply 8 - Diaphragm Chamber Pressure 17 - System Shut-Off Valve (N.O.)
Control Valve (N.O.) Gauge (Shown at Front of Valve)
18 - Air Pressure Gauge
(Shown at Front of Valve) 9 - System Drain Valve (N.C.) (Shown at Front of Valve)
4 - Local Manual Control Station 10 - Main Drain Valve (N.C.) 19 - Automatic Air/Nitrogen Supply
(Shown at Front of Valve) 11 - Fail-Safe Valve 20 - Low Pressure Alarm Switch
5 - Automatic Sprinklers (Shown at Front of Valve)
21 - Dry Pilot Actuator
6 - Heat Detectors, Smoke Detectors, 12 - Waterflow Pressure Alarm Switch
etc. (Fire Detection) 13 - Water Motor Alarm (Optional)
14 - Solenoid Valve
FIGURE 1 (2 OF 2)
DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC ACTUATION
SYSTEM SCHEMATIC (REAR VIEW)
TFP1460
Page 4 of 16
PREACTION
To ease field assembly of the trim ar-
WATERFLOW DOUBLE rangement, the trim components are
PRESSURE INTERLOCK provided partially assembled as shown
ALARM ELECTRIC/ in Figure 3B.
SWITCH LOW AIR PNEUMATIC
PRESSURE ACTUATION The trim arrangement is provided with
ALARM TRIM galvanized or black nipples and fittings.
SWITCH
The galvanized trim is intended for
CHECK non-corrosive or corrosive conditions,
VALVE whereas the black trim is principally in-
tended for use with AFFF systems.
NOTES:
1. SEE FIGURE 3, PER VALVE SIZE
NOTE: When the system pressure is
AS APPLICABLE, FOR TRIM greater than 175 psi (12,1 bar), provision
ARRANGEMENT WITH BILL OF is to be made to replace the standard
MATERIALS AND COMPONENT order 300 psi (20,7 bar) Water Pres-
PART NUMBERS. sure Gauges, shown in Figure 3A/3B
2. TRIM SHOWN FULLY ASSEMBLED; with separately ordered 600 psi (41,4
COMPONENTS SUCH AS GAUGES bar) Water Pressure Gauges.
DV-5 AND SWITCHES MAY REQUIRE
DELUGE ASSEMBLY IN TRIM AT VALVE System Design Considerations
VALVE INSTALLATION.
Because a double interlock preaction
system requires time for a drop in sys-
SYSTEM tem air pressure to occur (concurrently
GROOVED SHUT-OFF with the response time for the separate
VALVE
COUPLING fire detection system) before it will allow
water to enter the system piping, this
FIGURE 2 system has characteristics similar to a
DV-5 PRE-TRIMMED DELUGE VALVE, dry pipe sprinkler system. Therefore,
ELECTRIC/PNEUMATIC ACTUATION the system design considerations for
a dry pipe system are normally applied
NOTICE Valve Trim to a double interlock preaction system
The Double Interlock Preaction System including a 30% increase in design
The DV-5 Double Interlock Preaction with Electric/Pneumatic Actuation Trim
System with Electric/Pneumatic Ac- area; a maximum 1 minute water deliv-
(Fig. 3A/3B) forms a part of the labora- ery time for system capacities of 750
tuation described herein must be in- tory listings and approvals. The trim is
stalled and maintained in compliance gallons (2800 liters) or more; and, pro-
necessary for proper operation of the hibition of gridded system piping.
with this document, as well as with the DV-5 Valve.
applicable standards of the National In order to readily perform the System
Fire Protection Association, in addition Each package of trim includes the fol- Inspection Procedure described in
to the standards of any other authori- lowing items: the Care and Maintenance section, it
ties having jurisdiction. Failure to do so Water Supply Pressure Gauge is recommended that a System Shut-
may impair the performance of the re- Off Valve be installed above the Riser
lated devices. Diaphragm Chamber Pressure Gauge Check Valve, as shown in Figure 1. The
The owner is responsible for maintain- Diaphragm Chamber Connections System Shut-Off Valve should be a list-
ing their fire protection system and de- ed or approved (as appropriate) indi-
Manual Control Station cating valve with a supervisory switch
vices in proper operating condition.
Contact the installing contractor or Main Drain Valve to monitor the normally open position.
manufacturer with any questions. System Drain Valve Detection System
Alarm Test Valve The Double Interlock Preaction Sys-
Technical Automatic Drain Valve
tem With Electric/Pneumatic Actuation
Trim provides for electric operation of
Data System Air Pressure Gauge the DV-5 Valve by a detection system
consisting of electrical devices such as
Air Supply Connections heat sensitive thermostats, smoke de-
Approvals
UL and C-UL Listed Low Air Pressure Alarm Switch tectors, and/or electric manual pull sta-
FM Approved tions. Information on the various types
Waterflow Pressure Alarm Switch of separately ordered Solenoid Valves
Deluge Valve Dry Pilot Actuator that may be used with this trim pack-
DV-5 age is given in Technical Data Sheet
Pressure Operated Relief Valve TFP2180. Nominal installation dimen-
Riser Check Valve The following items are included in the sions for the Double Interlock Preaction
Model CV-1FR Pre-Trimmed Valve Assembly and can System With Electric/Pneumatic Actua-
NOTE: 1-1/2 inch (DN40) risers utilize be ordered separately for the valve trim: tion Trim are shown in Figure 4.
a 2 inch (DN50) Model CV-1FR Riser Model BFV-N Butterfly Valve The Deluge Valve Releasing Panel (au-
Check Valve connected to the 1-1/2 tomatic control unit) with battery back-
inch (DN40) DV-5 Deluge Valve by a Waterflow Pressure Alarm Switch up, fire detection devices, manual pull
2 x 1-1/2 inch Figure 716 Reducing (PS10-2) stations, and signaling devices that are
Coupling Figure 577 Grooved Coupling utilized with the Double Interlock Pre-
Continued on Page 10
TFP1460
Page 5 of 16
NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa Water Pressure Gauge . . 2 92-343-1-005 35 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH P18 1/2" x 1/2" x 1/4" Tee . . . . . . . . . . . . . . . . . . 1 CH
2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 36 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 11 CH P19 1" x 3/4" x 1/2" Tee. . . . . . . . . . . . . . . . . . . . 1 CH
3 Model MC-1 Manual Control Station . . . . . . 1 52-289-2-001 37 1/2" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH P20 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
4 Model AD-1 Automatic Drain Valve . . . . . . . 1 52-793-2-004 38 1/2" x 2-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 2 CH P21 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH
5 Model FSV-1 Fail-Safe Valve . . . . . . . . . . . . 1 52-343-1-001 39 1/2" x 3-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 2 CH P22 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 8 CH
6 Waterflow Pressure Alarm Switch, 40 1/2" x 5" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH P23 1/2" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH
Model PS10-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25710 41 1/2" x 7" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH P24 1/2" x 9" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
7 Priming Supply Restriction . . . . . . . . . . . . . . 1 92-020-1-009 42 1/2" x 8" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH P25 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
8 1/2" Ball Valve . . . . . . . . . . . . . . . . . . . . . . . 2 46-050-1-004 43 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH P26 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
9 1/2" Spring Loaded Check Valve . . . . . . . . . 1 92-322-1-002 44 3/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 6 CH P27 3/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
10 1/2" Y-Strainer . . . . . . . . . . . . . . . . . . . . . . . 1 52-353-1-005 45 3/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH P28 1" x 2" Nipple . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
11 3/4" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-005 46 3/4" x 4" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
12 3/4" Angle Valve . . . . . . . . . . . . . . . . . . . . . . 1 46-048-1-005 COMPONENTS INCLUDED ONLY IN
13 Drip Funnel Connector . . . . . . . . . . . . . . . . . 1 92-211-1-005 P1 250 psi/ 1750 kPa Air Pressure Gauge . . . . 1 92-343-1-012 PRE-TRIMMED VALVE ASSEMBLIES:
14 Drip Funnel Bracket . . . . . . . . . . . . . . . . . . . 1 92-211-1-003 P2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 A1 Model CV-1FR Check Valve, 2" (DN50) . . . 1 59-590-1-020
15 Drip Funnel . . . . . . . . . . . . . . . . . . . . . . . . . . 1 92-343-1-007 P3 Model DP-1 Dry Pilot Actuator . . . . . . . . . . . 1 52-280-1-001 A2 Butterfly Valve, Power Ball 300:
16 3/32" Vent Fitting . . . . . . . . . . . . . . . . . . . . . 1 92-032-1-002 P4 Low Air Pressure Alarm Switch, 1-1/2" (DN40) . . . . . . . . . . . . . . . . . . . . . . . . 1 51024A
17 1/4" x 18" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH Model PS40-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25730 2" (DN50) . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 51021A
18 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 2 CH P5 Solenoid Valve Ordered Separately Refer to A3 Figure 577 Coupling:
19 1/2" x 12" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH Per Data Sheet TFP2180 . . . . . . . . . . . . . . . 1 Data Sheet 1-1/2" (DN40) . . . . . . . . . . . . . . . . . . . . . . . . 1 57715ACP
20 1/2" x 18" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH P6 1/4" Pressure Relief Valve . . . . . . . . . . . . . . 1 92-343-1-020 2" (DN50) . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 57720ACP
21 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P7 1/2" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-004 A4 Coupling for 1-1/2" (DN40) DV-5:
22 3/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P8 1/2" Globe Valve . . . . . . . . . . . . . . . . . . . . . 1 46-047-1-004 Figure 716 Reducing Coupling, 2" x 1-1/2". . 1 7162015ES
23 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 CH P9 3/4" Angle Valve . . . . . . . . . . . . . . . . . . . . . . 1 46-048-1-005 Coupling for 2" (DN50) DV-5:
24 3/4" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P10 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH Figure 577 Coupling, 2" . . . . . . . . . . . . . . . . 1 57720ACP
25 1/4" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH P11 1/2" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH
26 1/2" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 7 CH P12 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CH
27 3/4" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH P13 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH Select Appropriate Nipple Sizes
28 3/4" x 1/2" 90 Elbow . . . . . . . . . . . . . . . . . . 1 CH P14 1/2" 45 Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH Nipple per DV-5 Deluge Valve Size
29 1/2" Cross. . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P15 1/2" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 4 CH Number
1-1/2" (DN40) 2" (DN50)
30 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH P16 1/2" Cross. . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
31 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 3 CH P17 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 1 CH 43 1/2" x 1-1/2" 1/2" x 2"
32 3/4" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P25 1/2" x 2-1/2" 1/2" x 2"
33 3/4" x 1/2" x 3/4" Tee . . . . . . . . . . . . . . . . . . 2 CH P26 1/2" x 6" 1/2" x 5-1/2"
34 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH
P8 P6
P22 P20
P23 P1
P22 P4
P15 P7 P18 28 P17
P13 P2
44 P14
P22 36 P10 P22
P22 P25 P12
P11
6 P22 P15 P15
16
(GREEN P16 P23 P3
P13 4
TINT) 17 30 P24
P28 P22 P21
P26 P5
31 26
13 (ORDERED
33 P19 SEPARATELY)
22 P27 15 35
PLUG 14 P22
38 P9 23
UNUSED 39
PORTS P21
45 44 26 36
LOCATION P12 P15
FOR OPTIONAL 44
44 32
ELECTRICALLY A1 36 18 23
44 P12 42
SUPERVISED 36 24
N.O. ALARM 11 44 26 20 30
CONTROL 33 39 1
5 36
VALVE A4
43 27 (HEX ENDS,
26 12 46 "FSV-1") 29 36 31
8
41
9
38 1 36 3
A3
NOTES: 23 7
21 2 23
1. Supervised Double Interlock
Preaction Trim with Electric/ 40 26 35
10 37
Pneumatic Release is comprised 36 36 19
of Items 1-46 plus Items P1-P28. 37 18
34 31 36
Items A1-A4 included only in 2" (DN50) 26 26
34 23
pre-trimmed valve assemblies 25 GROOVE x GROOVE A2
as applicable; otherwise DV-5 DELUGE VALVE NOTES:
ordered separately. SHOWN 36 4. See Figure 2 of TFP1305 for
2. All Fittings and Nipples are Deluge Valve Port identification.
galvanized (Standard Order). 8 5. Route all Tubing to Drip Funnel,
3. CH: Common Hardware. Item 15.
FIGURE 3A (1 OF 3)
1-1/2 AND 2 INCH (DN40 AND DN50) DV-5 DOUBLE INTERLOCK PREACTION SYSTEM
WITH ELECTRIC/PNEUMATIC ACTUATION TRIM EXPLODED VIEW
TFP1460
Page 6 of 16
NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa Water Pressure Gauge . . 2 92-343-1-005 28 1/2" Cross. . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P7 1/2" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-004
2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 29 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH P8 1/2" Globe Valve . . . . . . . . . . . . . . . . . . . . . 1 46-047-1-004
3 Model MC-1 Manual Control Station . . . . . . 1 52-289-2-001 30 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 3 CH P9 1-1/4" Angle Valve . . . . . . . . . . . . . . . . . . . . 1 46-048-1-007
4 Model AD-1 Automatic Drain Valve . . . . . . . 1 52-793-2-004 31 3/4" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P10 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH
5 Model FSV-1 Fail-Safe Valve . . . . . . . . . . . . 1 52-343-1-001 32 3/4" x 1/2" x 3/4" Tee . . . . . . . . . . . . . . . . . . 2 CH P11 1/2" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH
6 Waterflow Pressure Alarm Switch, 33 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH P12 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CH
Model PS10-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25710 34 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 1 CH P13 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH
7 Priming Supply Restriction . . . . . . . . . . . . . . 1 92-020-1-009 35 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 14 CH P14 1/2" 45 Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH
8 1/2" Ball Valve . . . . . . . . . . . . . . . . . . . . . . . 2 46-050-1-004 36 1/2" x 2-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH P15 1/2" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 4 CH
9 1/2" Spring Loaded Check Valve . . . . . . . . . 1 92-322-1-002 37 1/2" x 3-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH P16 1/2" Cross. . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
10 1/2" Y-Strainer . . . . . . . . . . . . . . . . . . . . . . . 1 52-353-1-005 38 1/2" x 4" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH P17 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 1 CH
11 3/4" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-005 39 1/2" x 4-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 2 CH P18 1/2" x 1/2" x 1/4" Tee . . . . . . . . . . . . . . . . . . 1 CH
12 1-1/4" Angle Valve . . . . . . . . . . . . . . . . . . . . 1 46-048-1-007 40 1/2" x 5" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH P19 1-1/4" x 1-1/4" x 1/2" Tee. . . . . . . . . . . . . . . 1 CH
13 Drip Funnel Connector . . . . . . . . . . . . . . . . . 1 92-211-1-005 41 1/2" x 7" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH P20 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
14 Drip Funnel Bracket . . . . . . . . . . . . . . . . . . . 1 92-211-1-003 42 1/2" x 8" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH P21 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH
15 Drip Funnel . . . . . . . . . . . . . . . . . . . . . . . . . . 1 92-343-1-007 43 3/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 5 CH P22 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 8 CH
16 3/32" Vent Fitting . . . . . . . . . . . . . . . . . . . . . 1 92-032-1-002 44 3/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH P23 1/2" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 3 CH
17 1/4" x 18" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH 45 1-1/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . 1 CH P24 1/2" x 5" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
18 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 2 CH 46 1-1/4" x 4" Nipple. . . . . . . . . . . . . . . . . . . . . 1 CH P25 1/2" x 10-1/2" Nipple. . . . . . . . . . . . . . . . . . . 1 CH
19 1/2" x 18" Tubing . . . . . . . . . . . . . . . . . . . . . 2 CH P26 1-1/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . 1 CH
20 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P1 250 psi/ 1750 kPa Air Pressure Gauge . . . . 1 92-343-1-012 P27 1-1/4" x 3" Nipple. . . . . . . . . . . . . . . . . . . . . 1 CH
21 3/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002
22 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 CH P3 Model DP-1 Dry Pilot Actuator . . . . . . . . . . . 1 52-280-1-001 COMPONENTS INCLUDED ONLY IN
23 3/4" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P4 Low Air Pressure Alarm Switch, PRE-TRIMMED VALVE ASSEMBLIES:
24 1/4" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH Model PS40-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25730
25 1/2" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 7 CH P5 Solenoid Valve Ordered Separately Refer to A1 Model CV-1FR Check Valve, 3" (DN80) . . . 1 59-590-1-030
26 3/4" x 1/2" 90 Elbow . . . . . . . . . . . . . . . . . . 1 CH Per Data Sheet TFP2180 . . . . . . . . . . . . . . . 1 Data Sheet A2 Model BFV-N Butterfly Valve, 3" (DN80) . . . 1 59300F030N
27 1-1/4" 90 Elbow . . . . . . . . . . . . . . . . . . . . . 1 CH P6 1/4" Pressure Relief Valve . . . . . . . . . . . . . . 1 92-343-1-020 A3 Figure 577 Coupling, 3" (DN80) . . . . . . . . . . 2 57730ACP
P7 P22 P6 P20
P22 P22 P1
P4
P22 P18 26 P17
P15 P2
P13
43 P14
P8 35 P10 P22
P22 P23 P13 P12
P22 P15 P15
6
16 P16 P23 P3
(GREEN 4 P11
17 P23 29 P21
TINT)
P24 P25
30 P26 13 P5
32 P9 25 (ORDERED
P27 15 35
21 PLUG 14 P22 SEPARATELY)
P19 UNUSED
22 39
36 31 PORTS P21
43 P12 25 35
44 23 A1 P15
LOCATION
FOR OPTIONAL 43
43 P12 38 35 18 22
ELECTRICALLY 42
SUPERVISED 35 11
25 19 29
N.O. ALARM 43
CONTROL A3 35 1
32 5
VALVE
35 (HEX ENDS,
27 "FSV-1") 28 35 30
25 8 45 46 41
9
12 35 3
40 35
1
NOTES: 7 22
25
1. Supervised Double Interlock 22 10
Preaction Trim with Electric/ 20 2
37 34
Pneumatic Release is comprised A3 35 19
39
of Items 1-46 plus Items P1-P27. 18
Items A1-A3 included only in 35 25 25
33 22 35
pre-trimmed valve assemblies 30
as applicable; otherwise 33 NOTES:
ordered separately. 24 3" (DN80) 35 4. See Figure 2 of TFP1305 for
2. All Fittings and Nipples are GROOVE x GROOVE Deluge Valve Port identification.
galvanized (Standard Order). DV-5 DELUGE VALVE 8 5. Route all Tubing to Drip Funnel,
3. CH: Common Hardware. SHOWN A2 Item 15.
FIGURE 3A (2 OF 3)
3 INCH (DN80) DV-5 DOUBLE INTERLOCK PREACTION SYSTEM
WITH ELECTRIC/PNEUMATIC ACTUATION TRIM EXPLODED VIEW
TFP1460
Page 7 of 16
NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa Water Pressure Gauge . . 2 92-343-1-005 41 1/2" x 9" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH P29 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 42 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH P30 2" x 3" Nipple . . . . . . . . . . . . . . . . . . . . . . . . 2 CH
3 Model MC-1 Manual Control Station . . . . . . 1 52-289-2-001 43 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
4 Model AD-1 Automatic Drain Valve . . . . . . . 1 52-793-2-004 44 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH COMPONENTS INCLUDED ONLY IN
5 Model FSV-1 Fail-Safe Valve . . . . . . . . . . . . 1 52-343-1-001 45 3/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH PRE-TRIMMED VALVE ASSEMBLIES:
6 Waterflow Pressure Alarm Switch, 46 3/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
Model PS10-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25710 47 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH A1 Model CV-1FR Check Valve:
7 Priming Supply Restriction . . . . . . . . . . . . . . 1 92-020-1-009 48 1" x Close Nipple . . . . . . . . . . . . . . . . . . . . . 2 CH 4" (DN100) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 59-590-1-040
8 1/2" Ball Valve . . . . . . . . . . . . . . . . . . . . . . . 2 46-050-1-004 49 1" x 3" Nipple . . . . . . . . . . . . . . . . . . . . . . . . 1 CH 6" (DN150) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 59-590-1-060
9 1/2" Spring Loaded Check Valve . . . . . . . . . 1 92-322-1-002 50 2" x 3" Nipple . . . . . . . . . . . . . . . . . . . . . . . . 2 CH 8" (DN200) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 59-590-1-080
10 1/2" Y-Strainer . . . . . . . . . . . . . . . . . . . . . . . 1 52-353-1-005 A2 Model BFV-N Butterfly Valve:
11 3/4" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-005 P1 250 psi/ 1750 kPa Air Pressure Gauge . . . . 1 92-343-1-012 4" (DN100) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 59300F040N
12 2" Angle Valve . . . . . . . . . . . . . . . . . . . . . . . 1 46-048-1-009 P2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 6" (DN150) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 59300F060N
13 Drip Funnel Connector . . . . . . . . . . . . . . . . . 1 92-211-1-005 P3 Model DP-1 Dry Pilot Actuator . . . . . . . . . . . 1 52-280-1-001 8" (DN200) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 59300F080N
14 Drip Funnel Bracket . . . . . . . . . . . . . . . . . . . 1 92-211-1-003 P4 Low Air Pressure Alarm Switch, A3 Figure 577 Coupling:
15 Drip Funnel . . . . . . . . . . . . . . . . . . . . . . . . . . 1 92-343-1-007 Model PS40-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25730 4" (DN100) . . . . . . . . . . . . . . . . . . . . . . . . . . 2 57740ACP
16 3/32" Vent Fitting . . . . . . . . . . . . . . . . . . . . . 1 92-032-1-002 P5 Solenoid Valve Ordered Separately Refer to 6" (DN150) . . . . . . . . . . . . . . . . . . . . . . . . . . 2 57760ACP
17 1/4" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH Per Data Sheet TFP2180 . . . . . . . . . . . . . . . 1 Data Sheet 8" (DN200) . . . . . . . . . . . . . . . . . . . . . . . . . . 2 57780ACP
18 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 2 CH P6 1/4" Pressure Relief Valve . . . . . . . . . . . . . . 1 92-343-1-020
19 1/2" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH P7 1/2" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-004
20 Select Tube per Table ..................... 1 CH P8 1/2" Globe Valve . . . . . . . . . . . . . . . . . . . . . 1 46-047-1-004 Select Appropriate Tube Size
21 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P9 2" Angle Valve . . . . . . . . . . . . . . . . . . . . . . . 1 46-048-1-009 Tube per DV-5 Deluge Valve Size
22 3/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P10 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH No. 4" 6" 8"
23 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 CH P11 1/2" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH (DN100) (DN150) (DN200)
24 1" Union . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P12 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CH 20 1/4" x 24" 1/4" x 24" 1/4" x 30"
25 1/4" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH P13 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH
26 1/2" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 7 CH P14 1/2" 45 Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH
27 1/2" Cross. . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P15 1/2" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 4 CH Select Appropriate Nipple Sizes
28 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH P16 1/2" Cross. . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH Nipple per DV-5 Deluge Valve Size
29 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 3 CH P17 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 1 CH
No. 4" 6" 8"
30 3/4" x 1/2" x 3/4" Tee . . . . . . . . . . . . . . . . . . 2 CH P18 1/2" x 1/2" x 1/4" Tee . . . . . . . . . . . . . . . . . . 1 CH
31 1" x 1/2" 90 Elbow. . . . . . . . . . . . . . . . . . . . 1 CH P19 2" x 2" x 1/2" Tee . . . . . . . . . . . . . . . . . . . . . 1 CH (DN100) (DN150) (DN200)
32 1" x 3/4" x 1" Tee . . . . . . . . . . . . . . . . . . . . . 1 CH P20 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 1 CH 42 1/2" x 2-1/2" 1/2" x 5-1/2" 1/2" x 8 -1/2"
33 2" 90 Elbow. . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P21 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH 43 1/2" x 1-1/2" 1/2" x 2" 1/2" x 2"
34 1/4" x Close Nipple ..................... 2 CH P22 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 6 CH 44 1/2" x 4" 1/2" x 5" 1/2" x 6"
35 1/2" x Close Nipple ..................... 1 CH P23 1/2" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
47 3/4" x 2-1/2" 3/4" x 3-1/2" 3/4" x 4-1/2"
36 1/2" x 1-1/2" Nipple . . . . . . . . . . . . . . . . . . . . . 11 CH P24 1/2" x 4-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
37 1/2" x 2-1/2" Nipple ..................... 2 CH P25 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH P25 1/2" x 4-1/2" 1/2" x 4-1/2" 1/2" x 11-1/2"
38 1/2" x 3" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH P26 1/2" x 11" Nipple. . . . . . . . . . . . . . . . . . . . . . 1 CH P27 1/2" x 7" 1/2" x 5-1/2" 1/2" x 10"
39 1/2" x 5" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH P27 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH P28 1/2" x 3-1/2" 1/2" x 6" 1/2" x 8"
40 1/2" x 7" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH P28 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH P29 1/2" x 2" 1/2" x 2-1/2" 1/2" x 4"
P6 P20
P8 P22 P1
P22
P22
P4 P18 P17
P22 P2
P15 P14
P13 31
P10 P22
P12
P22 38 4 P15
P29
P28 P7 48 P23 P3
P24
6 P16 P11
16 P21
P13 P26
(GREEN 28
TINT) 17 P27 P15
P30 P5
13 (ORDERED
29 26 SEPARATELY)
PLUG P25
30 15
UNUSED 43
22 14 P15
P9 P30 PORTS
P19 23 44
37 P12 P21
A1 41 26
32 36
LOCATION 46
24 P12 26
FOR OPTIONAL 36 18
ELECTRICALLY 45 23
SUPERVISED 11 48 28
36 20
N.O. ALARM 47 49
36 1
CONTROL 37 5
30 (HEX ENDS,
VALVE A3
42 "FSV-1") 27 36 29
26 33 40
8 10
50 50 36 3
36
12
7 23
1
NOTES: 40 9
26
1. Supervised Double Interlock 23 35
21 2 39
Preaction Trim with Electric/ 36 19
Pneumatic Release is comprised A3 18
39 26 26
of Items 1-50 plus Items P1-P30. 23
36 36
Items A1-A3 included only in A2
pre-trimmed valve assemblies 34 29
as applicable; otherwise 36 NOTES:
25 34
ordered separately. 4" (DN100)
4. See Figure 2 of TFP1305 for
2. All Fittings and Nipples are GROOVE x GROOVE 8 Deluge Valve Port identification.
galvanized (Standard Order). DV-5 DELUGE VALVE
SHOWN 5. Route all Tubing to Drip Funnel,
3. CH: Common Hardware. Item 15.
FIGURE 3A (3 OF 3)
4, 6, AND 8 INCH (DN100, DN150, AND DN200) DV-5 DOUBLE INTERLOCK PREACTION SYSTEM
WITH ELECTRIC/PNEUMATIC ACTUATION TRIM EXPLODED VIEW
TFP1460
Page 8 of 16
NOTES: Nipple Select Appropriate Nipple and Tube Sizes per DV-5 Deluge Valve Size
1. Use only 2" (DN50) Model CV-1FR Riser Number 1-1/2" (DN40) 2" (DN50) 3" (DN80) 4" (DN100) 6" (DN150) 8" (DN200)
Check Valve in 1-1/2" (DN40) and 2" (DN50)
1 1/2" x 1-1/2" 1/2" x 2" 1/2" x 1-1/2" 1/2" x 2-1/2" 1/2" x 5-1/2" 1/2" x 8-1/2"
assemblies. Use CV-1FR Valve size equal
to mating DV-5 Valve in larger assemblies. 2 1/2" x Close 1/2" x Close 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 2" 1/2" x 2"
2. Nipples 1-8 and Tube 1 vary in length relative 3 1/2" x 3-1/2" 1/2" x 3-1/2" 1/2" x 4-1/2" 1/2" x 4" 1/2" x 5" 1/2" x 5-1/2"
to DV-5 size. Select per table. All other 4 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 2-1/2" 3/4" x 3-1/2" 3/4" x 4-1/2"
nipples and tubing packed unassembled 5 1/2" x 6" 1/2" x 5-1/2" 1/2" x 5" 1/2" x 7" 1/2" x 5-1/2" 1/2" x 3"
shall be installed per appropriate trim 6 1/2" x 2-1/2" 1/2" x 2" 1/2" x 2" 1/2" x 3-1/2" 1/2" x 6" 1/2" x 8"
exploded view, Figure 3A Part 1, 2, or 3.
7 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 2" 1/2" x 2" 1/2" x 2-1/2" 1/2" x 4"
3. Install subassemblies in alphabetical order.
8 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 4-1/2" 1/2" x 4-1/2" 1/2" x 11-1/2"
4. See Figure 2 of TFP1305 for Deluge Valve
Port identification. System
Main Drain 3/4" NPT 3/4" NPT 1-1/4" NPT 2" NPT 2" NPT 2" NPT
5. Route all Tubing to Drip Funnel. Size
6. When DV-5 trips, Fail-Safe Valve opens,
partially diverting diaphragm supply to drain, Main
allowing diaphragm chamber to remain Drain 3/4" NPT 3/4" NPT 1-1/4" NPT 2" NPT 2" NPT 2" NPT
de-pressurized after decrease in system Size
flow. Tube 1 1/2" x 18" 1/2" x 18" 1/2" x 18" 1/2" x 24" 1/2" x 24" 1/2" x 30"
LOW AIR
WATERFLOW VENT FITTING SYSTEM PRESSURE SYSTEM
PRESSURE (GREEN TINT) AIR SUPPLY ALARM SWITCH AIR SUPPLY
ALARM SWITCH CONTROL VALVE PRESSURE
(NORMALLY GAUGE
OPEN) 1/2 INCH NPT
3/4 INCH NPT CONNECTION
CONNECTION FOR F FOR SYSTEM G
DRIP 1/2 INCH
WATER MOTOR FUNNEL AIR SUPPLY
AUTOMATIC CONDUIT
ALARM WITH 1-1/4
DRAIN CONNECTION
B VALVE INCH NPT FOR "ELECTRIC
NIPPLE
CONNECTION DETECTION"
4 DRY PILOT
TO DRAIN
LOCATION ACTUATOR
NIPPLE (NORMALLY
FOR OPTIONAL PLUG 5 NIPPLE NIPPLE SOLENOID
UNUSED 6 7 CLOSED) VALVE,
ELECTRICALLY
SUPERVISED PORTS NIPPLE ORDERED
SYSTEM
N.O. ALARM RISER 8 SEPARATELY
MAIN DRAIN (NORMALLY
CONTROL CONNECTION CHECK VALVE
VALVE (NOTE 1) NIPPLE CLOSED)
(SIZED PER
TABLE) 2
NIPPLE SYSTEM MAIN TUBE
1 DRAIN VALVE 1 DIAPHRAGM
NIPPLE
(NORMALLY CHAMBER
MAIN 3
CLOSED) PRESSURE
DRAIN VALVE
(NORMALLY GAUGE
E
CLOSED)
ALARM MANUAL
TEST VALVE A CONTROL
D STATION
(NORMALLY
CLOSED)
FAIL-SAFE
SYSTEM VALVE
WATER C 4" (DN100) (NORMALLY
DIAPHRAGM CLOSED)
SUPPLY
FLANGE x GROOVE CHAMBER SUPPLY
PRESSURE
DV-5 DELUGE CONTROL VALVE
GAUGE MAIN DRAIN 1/2 INCH NPT
VALVE SHOWN (NORMALLY
CONNECTION CONNECTION FROM OPEN)
(SIZED PER TABLE) WATER SUPPLY
FIGURE 3B
1-1/2 THRU 8 INCH (DN40 THRU DN200) DV-5 DOUBLE INTERLOCK PREACTION SYSTEM
WITH ELECTRIC/PNEUMATIC ACTUATION TRIM OPERATIONAL COMPONENTS
SEMI-PREASSEMBLED TRIM EXPLODED ARRANGEMENT
TFP1460
Page 9 of 16
* MINIMUM CLEARANCE.
A* B C* D*
E*
N
F
G
H J K
0,60
0)
8.0
N4
0,50
(D
7.0
0)
CH
N5
6.0
(D
IN
H 0,40
1/2
NC
5.0
2I
0)
0,30
N8
4.0
(D
)
00
N1
NC
(D
3.0
3I
0,20
H
NC
)
50
4I
N1
(D
2.0
)
00
H
NC
N2
(D
6I
0,10
H
NC
0,09
8I
0,08
1.0 0,07
0.9 0,06
0.8
0.7 0,05
0.6 0,04
0.5
0,03
0.4
50 100 200 400 600 1000 2000 3000
FLOW RATE IN GALLONS PER MINUTE (GPM)
The approximate friction loss, based on the Hazen and Williams formula and expressed in equivalent length of pipe with
C=120, is as follows:
15 feet of 1-1/2 Sch. 40 pipe for the 1-1/2 inch Valve Combination**calculated on a typical flow rate of 100 gpm.
28 feet of 2 inch Sch. 40 pipe for the 2 inch Valve Combination* calculated on a typical flow rate of 175 gpm.
37 feet of 3 inch Sch. 40 pipe for the 3 inch Valve Combination* calculated on a typical flow rate of 350 gpm.
48 feet of 4 inch Sch. 40 pipe for the inch Valve Combination* calculated on a typical flow rate of 600 gpm.
73 feet of 6 inch Sch. 40 pipe for the 6 inch Valve Combination* calculated on a typical flow rate of 1500 gpm.
103 feet of 8 inch Sch. 30 pipe for the 8 inch Valve Combination* calculated on a typical flow rate of 2500 gpm.
GRAPH B
DELUGE AND CHECK VALVE COMBINATION*
NOMINAL PRESSURE LOSS VERSUS FLOW
*DV-5 Deluge Valve combined with Model CV-1FR Riser Check Valve
**1-1/2 inch DV-5 Deluge Valve combined with 2 inch Model CV-1FR Riser Check Valve
TFP1460
Page 12 of 16
pressure as indicated on the Diaphragm control station, switches, and pres- Step 8. Open the Main Control Valve
Chamber Pressure Gauge to drop be- sure maintenance device should be (Fig. 1) one turn beyond the position at
low the supply pressure shown on the reviewed. which water just begins to flow from the
Water Supply Pressure Gauge, since Main Drain Valve.
The following procedures pertain to the
this action may result in tripping of the automatic control valve portion of the Step 9. Close the Main Drain Valve (Fig.
DV-5 Valve. Double Interlock Preaction System. Re- 2B).
After setting a fire protection system, fer to the manufacturers instructions Step 10. Close the Air Supply Control
notify the proper authorities and advise and NFPA 25 for care and maintenance Valve (Fig. 3B).
those responsible for monitoring pro- procedures for all other devices (e.g.,
prietary and/or central station alarms. electric detection, main control and Step 11. Open the Dry Pilot Actuator
system shut-off valves, supervisory by partially opening the System Main
Care and devices, sprinklers, etc.).
Before performing the System Inspec-
Drain Valve (Fig. 3B) to relieve air pres-
sure at the inlet to the Actuator. Verify
Maintenance tion Procedure, which will result in op-
eration of alarms, notify the proper au-
that there is no leakage from the Dry
Pilot Actuator.
The following procedures, inspections, thorities and all personnel who may be NOTICE
and maintenance must be performed affected.
as indicated, in addition to any spe- During this procedure, the Dry Pilot Ac-
cific requirements of the NFPA, and System Inspection Procedure tuator is opened; however, the Solenoid
any impairment must be immediately Step 1. Close the Main Control Valve Valve should remain closed and the
corrected. (Fig. 1) and then open the DV-5 Main DV-5 Deluge Valve Diaphragm Cham-
Drain Valve (Fig. 3B). ber should remain pressurized.
Before closing a fire protection system
main control valve for maintenance Step 2. Manually operate the Deluge This procedure is used to verify that the
work on the fire protection system that Valve Releasing Panel and verify the DV-5 Deluge Valve will remain set if the
it controls, permission to shut down the following: Dry Pilot Actuator operates due to loss
affected fire protection system must be of system air pressure and the electric
The operation of the Releasing Panel
obtained from the proper authorities detection system remains in a normal
and its associated alarms
and all personnel who may be affected condition.
by this action must be notified. That there is no leakage from the Dry
Step 12. Open (energize) the Solenoid
Pilot Actuator (Fig. 3B)
The owner is responsible for the in- Valve by operating the Deluge Valve Re-
spection, testing, and maintenance of NOTICE leasing Panel and verify the following:
their fire protection system and devices That the DV-5 Valve operates as is in-
During this procedure, the Solenoid
in compliance with this document, as dicated by a discharge of water from
Valve is opened; however, the Dry Pilot
well as with the applicable standards the System Main Drain Valve and the
Actuator should remain closed and the
of the National Fire Protection Associa- Automatic Drain Valve. The Automatic
DV-5 Deluge Valve Diaphragm Cham-
tion (e.g., NFPA 25), in addition to the Drain Valve may or may not close de-
ber should remain pressurized.
standards of any authority having juris- pending on the flow past the partially
diction. Contact the installing contrac- This procedure is used to verify that the open Main Control Valve
tor or product manufacturer with any DV-5 Deluge Valve will remain set if the
questions. electric detection system operates but That the Model FSV-1 Fail-Safe Valve
the sprinkler system remains in its nor- has operated as is indicated by water
It is recommended that automatic discharging into the Drip Funnel from
mally pressurized condition.
sprinkler systems be inspected, tested, the 1/2 inch drain tube connected to
and maintained by a qualified Inspec- Step 3. Open the Inspectors Test Con- the Model FSV-1 Fail-Safe Valve
tion Service in accordance with local nection but be prepared to close it im-
requirements and/or national codes. mediately after verifying that the Low That the Waterflow Pressure Alarm
Pressure Alarm Switch (Fig. 3B) and Switch (Fig. 3B) and its associated
It is recommended that the System In- alarms properly operate
its associated alarms operate properly.
spection Procedure be performed at
The Low Pressure Alarm Switch should That the Water Motor Alarm, if appli-
least semi-annually by a qualified In-
operate at the previously established cable, properly operates
spection Service. The Double Interlock
pressure (refer to Installation section,
Preaction System Inspection Procedure
Step 11). NOTICE
may be followed in lieu of performing
any of the operational tests recom- Close the Inspectors Test Connection. This procedure simulates opening of
mended in the Technical Data Sheets Step 4. Close the Diaphragm Chamber both the Dry Pilot Actuator (loss of sys-
for the DV-5 Deluge Valve, Riser Check Supply Control Valve (Fig. 3B). tem air pressure) and Solenoid Valve
Valve, 24 VDC Solenoid Valve, Dry Pi- (operation of the Deluge Valve Releas-
lot Actuator, and Model MC-1 Manual Step 5. Close the System Shut-Off ing Panel) to verify automatic system
Control Station. Valve (Fig. 1) after the system air pres- operation.
sure has been restored to normal.
It is recommended that the individuals Step 13. Reset the Double Interlock
responsible for the care and mainte- Step 6. Manually restore the electric fire Preaction System in accordance with
nance of the Double Interlock Preac- detection system to a normal condition the Resetting Procedure section.
tion System develop a working under- in accordance with the manufacturers
standing of the system, in general, prior instructions. The Solenoid Valve will Fail-Safe Valve
to performing inspection and/or mainte- then be de-energized and returned to If water does not discharge from the
nance procedures. These instructions, its normally closed position. 1/2 inch tube connected to the Model
as well as individual instructions for the Step 7. Open the Diaphragm Chamber FSV-1 Fail-Safe Valve during Step 12 of
deluge valve, riser check valve, sole- Supply Control Valve (Fig. 3B).
noid valve, dry pilot actuator, manual
TFP1460