Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Topic Page
Important User Information 2
North American Hazardous Location Approval 3
European Hazardous Location Approval 4
Environment and Enclosure 5
Prevent Electrostatic Discharge 6
Before You Begin 6
Power Requirements 7
Install the Module 8
Wiring Diagrams 16
Installing the RTB onto the Module 18
Uninstall the RTB and Module 20
Interpret the LED Indicators 22
Specifications 23
Additional Resources 30
Solid state equipment has operational characteristics differing from those of electromechanical
equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls
(publication SGI-1.1 available from your local Rockwell Automation sales office or online at
http://literature.rockwellautomation.com) describes some important differences between solid state
equipment and hard-wired electromechanical devices. Because of this difference, and also because of
the wide variety of uses for solid state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the
many variables and requirements associated with any particular installation, Rockwell Automation, Inc.
cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an explosion in
a hazardous environment, which may lead to personal injury or death, property
damage, or economic loss.
IMPORTANT Identifies information that is critical for successful application and understanding of
the product.
ATTENTION Identifies information about practices or circumstances that can lead to personal
injury or death, property damage, or economic loss. Attentions help you to identify a
hazard, avoid a hazard and recognize the consequences.
SHOCK HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert
people that dangerous voltage may be present.
BURN HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert
people that surfaces may reach dangerous temperatures.
The following Information applies when operating Informations sur l'utilisation de cet quipement en
this equipment in hazardous locations: environnements dangereux:
Products marked "CL I, DIV 2, GP A, B, C, D" are Les produits marqus "CL I, DIV 2, GP A, B, C, D"
suitable for use in Class I Division 2 Groups A, B, ne conviennent qu' une utilisation en
C, D, Hazardous Locations and nonhazardous environnements de Classe I Division 2 Groupes A,
locations only. Each product is supplied with B, C, D dangereux et non dangereux. Chaque
markings on the rating nameplate indicating the produit est livr avec des marquages sur sa plaque
hazardous location temperature code. When d'identification qui indiquent le code de
combining products within a system, the most temprature pour les environnements dangereux.
adverse temperature code (lowest "T" number) Lorsque plusieurs produits sont combins dans un
may be used to help determine the overall systme, le code de temprature le plus
temperature code of the system. Combinations of dfavorable (code de temprature le plus faible)
equipment in your system are subject to peut tre utilis pour dterminer le code de
investigation by the local Authority Having temprature global du systme. Les combinaisons
Jurisdiction at the time of installation. d'quipements dans le systme sont sujettes
inspection par les autorits locales qualifies au
moment de l'installation.
Parts List
You received these components with your module.
1756-IF4X0F2F module
Module-specific RTB door label
Additional Hardware
ATTENTION The ControlLogix system has been agency certified using only the
ControlLogix RTBs (1756-TBCH, 1756-TBNH, 1756-TBSH and
1756-TBS6H). Any application that requires agency certification of the
ControlLogix system using other wiring termination methods may
require application specific approval by the certifying agency.
Power Requirements
This module receives power from the 1756 chassis power supply and
requires two sources of power from the backplane:
375 mA at 5.1V dc
100 mA at 24V dc
Add this current/power value (4.3 W) to the requirements of all other
modules in the chassis to prevent overloading the power supply.
WARNING When you insert or remove the module while backplane power is on,
an electrical arc can occur. This could cause an explosion in hazardous
location installations.
1. Align the circuit board with the top and bottom chassis guides.
Printed
Circuit
Board
20861-M
2. Slide the module into the chassis slot until the modules
locking tabs click.
U-shaped
Bands
20850
Wedge-shaped Tab
20851-M
WARNING If you connect or disconnect wiring while the field-side power is on,
an electrical arc can occur. This could cause an explosion in hazardous
location installations. Be sure that power is removed or the area is
nonhazardous before proceeding.
20104-M
To See
Connect the Shield Ground at the Field Device (Recommended) page 11
Connect the Shield Ground at the ControlLogix Chassis page 12
(Alternate)
IMPORTANT Use only shielded, 2.5 mm2...0.25 mm2 (14...22 AWG) wire rated at
75 C (167 F) or greater than 1.2 mm (3/64 in.) insulation, max.
After you have prepared the shield ground, complete the following
steps to connect the shield ground at the field device.
Field
Device
Ground Wire
43183
M4 or M5 (#10 or #12)
Phillips Screw and Star
Washer (or SEM Screw)
Chassis Mounting Tab
4. Prepare the opposite end of the cable for the field device
connection using the following procedure.
A. Remove a length B. Pull the foil shield C. Cut foil shield and ground wire
of cable jacket and bare the back to the cable casing and
from the ground wire from apply shrink wrap, exposing
connecting cable. the insulated wire. only the insulated wires.
43182
IMPORTANT Use only shielded, 2.5 mm2...0.25 mm2 (14...22 AWG) wire rated at
75 C (167 F) or greater than 1.2 mm (3/64 in.) insulation, max.
IMPORTANT Do not wire more than two conductors on any single terminal.
When two wires are used they must be of the same gauge and type,
stranded or solid, 0.25... 2.5 mm2 (22...14 AWG).
20859-M
IMPORTANT Do not wire more than one conductor to any single terminal.
20860-M
Wiring Diagrams
1756-IF4FXOF2F Current Mode Wiring Diagram
(+) (-) i
+IN-1/V 2 1 +IN-0/V
2-Wire A IN-1/I 4 3
Transmitter IN-0/I
-IN-1 6 5 -IN-0
A +IN-3/V 8 7 +IN-2/V
IN-3/I 10 9 IN-2/I
-IN-3 12 11 -IN-2
Not used 14 13 Not used
Not used 16 15 Not used
V OUT-1 18 17 V OUT-0 i
I OUT-1 20 19 A Current
I OUT-0
RTN-1 22 21 RTN-0 Output
Not used 24 23
Load
Not used
Not used 26 25 Not used Shield
Not used Ground
28 27 Not used
Not used 30 29 Not used
Not used 32 31 Not used
Not used 34 33 Not used
Not used 36 35 Not used
42742
(+) (+)
User +IN-1/V 2 1 +IN-0/V
Analog
IN-1/I 4 3 IN-0/I
Input
Device -IN-1 6 5 -IN-0
(-) +IN-2/V
+IN-3/V 8 7
Shield IN-3/I 10 9 IN-2/I
ground -IN-3 12 11 -IN-2
Not used 14 13 Not used
Not used 16 15 Not used
(+)
V OUT-1 18 17 V OUT-0
I OUT-1 20 19 I OUT-0
RTN-1 22 21 RTN-0
Not used 24 23 Not used (-) Shield
26 25 Not used Ground
Not used
Not used 28 27 Not used
Not used 30 29 Not used
Not used 32 31 Not used
Not used 34 33 Not used
Not used 36 35 Not used
42743
Groove
Side edge of the RTB
Groove
20852-M
2. Slide the RTB into the housing until it snaps into place.
Module
Guide
2. Press quickly and evenly to seat the RTB until the latches snap
into place.
Locking Tab
20854-M
WARNING When you connect or disconnect the RTB with field side power
applied, an electrical arc can occur. This could cause an explosion in
hazardous location installations.
42517
2. Open the RTB door and pull the RTB off the module.
20855-M
WARNING When you insert or remove the module while backplane power is on,
an electrical arc can occur. This could cause an explosion in hazardous
location installations.
20856-M
20857-M
ANALOG INPUT
ANALOG OUTPUT
CAL
OK
42741
During power up, an indicator test is done. During the test. the OK
LED indicator turns red for 1 second and then turns to flashing green
if it has passed the self-test.
Use the following table to interpret your LED indicators.
Specifications
Attribute Value
Module location 1756 ControlLogix chassis
Enclosure type rating None, (open-style)
Intrinsically safe No
Backplane current 375mA @ 5.1V dc & 100mA @ 24V dc
(No module-external power
requirements.) (Total backplane power = 4.3 W)
Power dissipation 4.7 W, current mode
4.3 W, voltage mode
Thermal dissipation 16.02 BTU/hr, current mode
14,66 BTU/hr, voltage mode
Data format Floating-point, IEEE 32- bit
Isolation voltage 250V (continuous), Basic Insulation Type
125V (continuous), Reinforced Insulation Type
Type Tested at 3100V dc for 60 s, I/O to system
Routine Tested at 2121V dc for 2 s, I/O to system
No isolation between channels
RTB screw torque 0.497 Nm (4.4 lb-in)
Module keying Electronic
RTB keying User-defined
RTB arm and housing 36-position RTB (1756-TBCH or 1756-TBS6H)(1)
Wire size 0.25... 2.5 mm2 (22...14 AWG) solid or stranded shielded
copper wire rated at 75 C (167 F) or greater 1.2 mm (3/64
in.) insulation max
Wiring category 2 - on signal ports(2)
Attribute Value
RTB screwdriver width 8 mm (5/16 in.)
Temp codes IEC Temp Code:
T4
North American Temp Code:
T4A
Weight, approx. 233.6 g (8.24 oz)
(1) Maximum wire size use requires extended housing, 1756-TBE.
(2)
Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication 1770-4.1
Environmental Specifications
Attribute Value
Conductive RF immunity IEC 61000-4-6:
Group 1, Class A
ESD immunity IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity IEC 61000-4-3:
Environmental Specifications
Attribute Value
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
595% non-condensing
Shock, non-operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Shock, operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Surge, transient immunity IEC 61000-4-5:
2 g @ 10500 Hz
Input Specifications
Attribute Value
Number of Inputs Four differential inputs
Input range selections +/- 10.5V, 0-10.5V, 0-5.25V, 0-21 mA
overrange indication when exceeded
Voltage Resolution Approximately 14 bits across +/-10.5V dc (21V total)
Input Specifications
Attribute Value
Input error over full 0.2% of range
temperature range
Minimum scan time for all 1756-IF4FX0F2F, Series A(2), firmware revision 1.x:
channels (RTS period)
400 S
1756-IF4FX0F2F, Series B(2), firmware revision 3.x or
greater:
300 S
Input conversion method Successive approximation
(1)
Repeatablity is defined as the stability of the input channel reading when a steady state signal is
applied (for example, +/- 1 LSB is one count [1.3mV] from the nominal reading).
(2) The High-speed Analog Module series is determined by the firmware revision. Modules at firmware
revision 1.x are at series A. Modules at firmware revisions 3.x and greater are at series B.
Output Specifications
Attribute Value
Number of outputs 2 voltage or current outputs
Output range 0 - 21 mA, voltage mode
+/-10.4V, current mode
Resolution 13 bits across 21 mA = 2.8 A/bit
14 bits across 20.8V = 1.3 mV/bit
Open circuit detection Current output only (Output must be set to >0.1 mA)
Output overvoltage 24V dc
protection
Output short circuit Current limited electronically to 21 mA or less.
protection
Drive capability >2000 , voltage mode
0...750 , current mode
Output Specifications
Attribute Value
Output settling time <2 mS to 95% of final value with resistive loads.
Accuracy at 25C (77F) 0.05% of selected range immediately after calibration.
Better than 0.1% of range with calibration interval.
Current (4 mA...21 mA
range)
Certifications(1)
The following certifications apply when the product is marked.
Certification Value
C-Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
CE European Union 89/336/EEC EMC Directive, compliant with:
Resource Topic
Allen-Bradley I/O Modules Wiring Diagrams, Wiring diagrams for Allen-Bradley I/O
publication CIG-WD001B modules.
Industrial Automation Wiring and Grounding Guidelines for installing components of
Guidelines, publication 1770-4.1 Allen-Bradley systems.
ControlLogix High-speed Analog Module User Provides descriptions of features,
Manual, publication 1756-UM005 guidelines for programming, and
high-speed analog module application
information.
ControlLogix Series B, High-speed Analog Describes enhancements and corrected
Module, Firmware Revision 3.4, publication anomalies that correspond to the
1756-RN639 firmware revision.