UPS Cabinet (Standard)

39"

39" 48"
34.5"
1.5"
32"
(2) .75" or 1"
Conduit
knockouts 5"
18"
(2) 1.5" or 2"
Conduit
knockouts

Top View 18"


5"
9"
1 Air Exhaust 39" 1 Air Exhaust
Clearance Clearance

(2) 1.5" or 2" 1.25"


Conduit
knockouts

48"
(2) .75" or 1" 1.5"
Conduit
knockouts
29.25"

Front View Side View


(Both Sides Typ.)

34.75"

(4) 0.69" Dia. Typ.


Floor Mounting Holes 15"

Bottom View Drawn by: Date:


Chun Chi 7/15/09
Chkd.: Date:
UPS & Battery 1 Phase UPS
Appvd.: Date: Cabinet 3 KW
Installations 6001-033-14 Rev C1
Battery Cabinet
UPS Cabinet (Standard)
39" NOTE:
1. Matching Battery Cabinet has same
physical dimensions.
2. Each battery cabinet includes 1 CB.
39"
3. Each battery cabinet have top and
sides conduit entry and same
68" floor mounting hole dimensions.
4. Optional Seismic Brackets
Battery (P/N: 9100-1317-02) are available.
CB When seismic bracket used, 8" min.
space required between cabinets.
Anchoring hardware to be supply
by customer.
48"
18"

39"
34.5"
1.5"
32"
(2) .75" or 1"
Conduit
knockouts 2.25"
18"
(2) 1.5" or 2"
Conduit Top View
knockouts
18"
9" 5"

1 Air Exhaust 39" 1 Air Exhaust


Clearance Clearance

(2) 1.5" or 2" 1.25"


Conduit
knockouts

Front View
(2) .75" or 1" 1.5"
Conduit
knockouts
68"

46"

Side View
(Both Sides Typ.)
34.8"

Drawn by: Date:


(4) 0.68" Dia. Typ. Chun Chi 7/15/09
Floor Mounting Holes 15"
Bottom View Chkd.: Date:
UPS & Battery 1 Phase UPS
Appvd.: Date: Cabinet 5 KW
Installations 6001-033-01 Rev C1
CRUCIAL POWER PROPRIETARY REVISION
CONFIDENTIAL INFORMATION
REV ECO DESCRIPTION DATE APPROVED

X1 PRELIMINARY 6/21/10 H. BAIK

Using 51 wide cabinet


46
3.5 3.5 5

STD VRLA
BATTERY

30.5
AIR EXHAUST

TOP VIEW
KNOCK OUT 1 AIR INTAKE 1 AIR INTAKE
FOR 1", 1.5" & 2" CLEARANCE CLEARANCE
CONDUIT (TYP) REQUIRED 51 REQUIRED

9.5
49 (BOTH SIDES)

70

NOTE 5 25.5
LEFT VIEW FRONT VIEW
RIGHT VIEW

NOTES: (UNLESS OTHERWISE SPECIFIED)


25

1) DIMENSIONS SHOWN ARE APPROXIMATE.


2) CONSTRUCTION: INDOOR NEMA 1.
3) RATING & WEIGHT: CHARTED.
4) WEIGHT ARE APPROX. DEPENDING
17 4200 LBS ON OPTION(S).
15 4120 LBS MGT HOLES 44.75 5) PROVISION FOR SEISMIC BRACKET
12.5 3370 LBS
10 3050 LBS BOTTOM VIEW
7.5 2300 LBS
KW WT. (NOTE 4)

UNLESS OTHERWISE SPECIFIED,


APPROVED DISAPPROVED DATE: DIMENSIONS ARE IN INCHES.
APPROVED WITH COMMENTS TOLERANCES ARE:
DECIMALS FRACTIONS ANGLES
.XX .03 1/64 1/2 TITLE
.XXX .010 7.5 KW - 17 KW, 1 PHASE
COMMENTS:
INVERTER WITH 90 MIN. BATT.
CADD: HAI NGUYEN 6/21/10
SIZE DWG REV
CHKD: HAI NGUYEN 6/21/10 A 6001-155 C1
APPVD: H. BAIK 6/21/10 SCALE: NONE EST. WT: SHT 1 OF 1
NAME: SIGNATURE:
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
2.1 kW and 3 kW 3.5 kW, 5.0 kW, and 5.25 kW
NOTE:
UPS & Battery Cabinet are UPS & Battery Cabinet are 1. Service Clearance Areas are shaded.
in a Single Cabinet. in a Single Cabinet. 2. Each battery cabinet includes 1 C/B.
3. Each battery cabinet have top and both
sides conduit entry and same floor
39" mounting hole dimensions as UPS cabinet.
39" (See doc #: 6001-032-03 for detail).
4. Optional Seismic Brackets
(P/N: 9100-1317-02) are available.
When seismic bracket used, 8" min.
space required between cabinets.
Anchoring hardware to be supply
68"
by the customer.
48" 5. Optional racks (P/N: 9100-1429-XX)
available for stack battery cabinets.
(see doc #: 6001-032-07).
6. Consult factory for different back-up
times and number of battery
cabinet require.
18"
18"

7.0 kW, 7.5 kW, 8.8 kW, 10 kW, 10.5 kW, 12.5 kW, 14 kW, 15 kW, and 17 kW

Layout Configuration 3 Layout Configuration 1


1"
12" 39" 12" 39"

Battery Cabinet 1 18"


UPS Cabinet
Ba
Ca ttery 18"
bin
1 et 49"

Layout Configuration 2
142"

123.5"

66.25"
U
Optional Racks Ca PS Battery
(P/N: 9100-1429-XX) bin
39"

et Cabinet
UPS 1
Cabinet
56"
28.25"
51"W x 30.25"D
Service Clearance 12"
18" 36" 18"
54"
4"

4" Drawn by: Date:


Bottom 28.25" Chun Chi 2/1/06
Cabinet 26.25"
View Chkd.: Date:
1 Phase UPS Battery Cabinet
56" .56 Dia. (typ.) Appvd.: Date: with 90 Min Installations
Battery Backup 6001-033-02 Rev C1
CRUCIAL POWER PROPRIETARY REVISION
CONFIDENTIAL INFORMATION
REV ECO DESCRIPTION DATE APPROVED

C1 PRELIMINARY 6/22/10 H. BAIK

1.5" TYP
5" TYP
34.37" TYP 3/4" / 1"
31.87" TYP CONDUIT

LONG LIFE
BATTERY 1.5" / 2"
CONDUIT

1" CLEARANCE TOP VIEW 2" CLEARANCE

11"
8" 39" 18"
3.25"

68"
4.5"
46"

LEFT VIEW FRONT VIEW RIGHT VIEW

MTG HOLES
14"

34.75"
BOTTOM VIEW

UNLESS OTHERWISE SPECIFIED,


DIMENSIONS ARE IN INCHES.
TOLERANCES ARE:
DECIMALS FRACTIONS ANGLES
.XX .03 1/64 1/2 TITLE
NOTES: (UNLESS OTHERWISE SPECIFIED) .XXX .010 3KW - 5KW, 1 PHASE
1) ALL DIMENSIONS SHOWN ARE APPROXIMATE.
INVERTER WITH 90 MIN. BATT.
CADD: HAI NGUYEN 6/22/10
SIZE DWG REV
2) CONSTRUCTION: INDOOR NEMA 1.
CHKD: HAI NGUYEN 6/22/10 A 6001-152 C1
APPVD: H. BAIK 6/22/10 SCALE: EST. WT: SHT 1 OF 1

SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE


CRUCIAL POWER PROPRIETARY REVISION
CONFIDENTIAL INFORMATION
REV ECO DESCRIPTION DATE APPROVED

C1 PRELIMINARY 6/21/10 H. BAIK

Using 51 wide cabinet


46
3.5 3.5 5

LONG LIFE
BATTERY

30.5
AIR EXHAUST

TOP VIEW
KNOCK OUT 1 AIR INTAKE 1 AIR INTAKE
FOR 1", 1.5" & 2" CLEARANCE CLEARANCE
CONDUIT (TYP) REQUIRED 51 REQUIRED
AIR INTAKE

9.5
49 (BOTH SIDES)

70

NOTE 5 25.5
LEFT VIEW FRONT VIEW
RIGHT VIEW

NOTES: (UNLESS OTHERWISE SPECIFIED)


25

1) DIMENSIONS SHOWN ARE APPROXIMATE.


2) CONSTRUCTION: INDOOR NEMA 1.
3) RATING & WEIGHT: CHARTED.
17 4640 LBS 4) WEIGHT ARE APPROX. DEPENDING
15 4560 LBS ON OPTION(S).
12.5 3722 LBS
MGT HOLES 44.75 5) PROVISION FOR SEISMIC BRACKET
10 3226 LBS
7.5 2520 LBS BOTTOM VIEW
KW WT. (NOTE 4)

UNLESS OTHERWISE SPECIFIED,


APPROVED DISAPPROVED DATE: DIMENSIONS ARE IN INCHES.
APPROVED WITH COMMENTS TOLERANCES ARE:
DECIMALS FRACTIONS ANGLES
.XX .03 1/64 1/2 TITLE
.XXX .010 7.5 KW - 17 KW, 1 PHASE
COMMENTS:
INVERTER WITH 90 MIN. BATT.
CADD: HAI NGUYEN 6/21/10
SIZE DWG REV
CHKD: HAI NGUYEN 6/21/10 A 6001-150 C1
APPVD: H. BAIK 6/21/10 SCALE: NONE EST. WT: SHT 1 OF 1
NAME: SIGNATURE:
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
CRUCIAL POWER PROPRIETARY
CONFIDENTIAL INFORMATION

C1
SIDE BACK
MOUNT MOUNITNG
PROVSION PROVISION

TO UPS P100 TERMINAL BLOCK


K
SEE INSTALLATOIN
INSTRUCTION SHIPPED
WITH THE ASSEMBL
Y

USE
BUMPERS
FOR
CONSOL
INSTALL

Remote Status Panel displays the following:


NPUT OK: Input power is within acceptable range

INVERTER ON: Inverter is on.

ON BYPASS: Unit is on bypass mode.

ON BATT: Unit is running from Battery.

LOW BATT: Battery voltage is at low voltage before shutdown.


Unit is on critical alarm such as:
SUM ALARM:
Over temperature, DC OV/UV.
HORN: Audible warning for alarm condition.

SILENCE SWITCH: Silences the audible warning.

LED TEST: Tests the LEDs by push in.

REMOTE STATUS PANEL ASSEMBLY:


9100-1020-06: SINGLE PHASE
DISPLAY PANEL 9100-1020-07: THREE PHASE