global.kawasaki.com/en/energy/equipment/gas_turbines/index.html
L30A
INDEX
Introduction 1. 2
History and Order Record of Kawasaki Gas Turbines 3. 4
Baseload Model 5. 6
M1A Series Gas Turbine Generator Specifications 7. 8
M7A Series Gas Turbine Generator Specifications 9 . 10
L20A / L30A Series Gas Turbine Generator Specifications 11. 12
Standby Model Introduction 13
Standby Model (GPS Series) 14
Mobile / Trailer Model (MGP / TGP Series) 15. 16
Kawasaki Techno-Net 17
Installation Examples 18
3 4
Baseload Model
Basic Specifications
Note: Mark "D" after Gas Turbine Model stands for Dry Low Emission
Condition : ISO Rating 1. Inlet Air Temperature : 15C 2. Atmospheric Pressure : 101.3 kPa 3. Inlet / Exhaust Pressure Losses : No Duct Loss
4. Fuel Type : Natural Gas (100% CH4) 5. LHV of Fuel : 35.9 MJ/Nm3
The Kawasaki GPB Series is designed for baseload applications, for both parallel operation with the grid
and island mode operation. In addition, the Kawasaki GPB Series are able to operate in Co-generation ser- L30A : The Worlds Most Efficient 30 MW Gas Turbine
vice, with automatic operation capability supplying both electricity and heat (steam, hot water, direct heat) In June 2012, Kawasaki introduced a new gas turbine named L30A as a
by collecting waste heat with a heat recovery steam generator (HRSG), heat exchanger, or dryer, and in flagship model of its industrial gas turbine fleet. Based on Kawasakis well
Combined Cycle with a steam turbine generator. With high total thermal efficiency, the Kawasaki GPB proven design technology, this machine is said to be the most efficient
Series are capable of highly efficient operation. 30 MW class gas turbine in the world, combined with very low emission
output, high reliability and availability.
Gas Turbine Illustration In addition, with its modular system design, the L30A has realized
excellent on-site maintainability. The L30A is able to provide
Centrifugal Compressor for a highly flexible solution for power generation and mechanial
M1A Gas Turbine Series drive applications.
M7A
Ultimate Solution
40.1%
M1A-17
L20A
5 6
M1A Series Gas Turbine Generator Specifications
Site Condition for Normal Perfor
Elevation above sea level :0m
Inlet Air Temperature : 15 C
Inlet Air Pressure Loss : 0.98 kPa
Exhaust Gas Pressure Loss : 2.45 kPa
LHV of Natural Gas Fuel : 35.9 MJ/Nm3
(100% CH4)
M1A/T-13 Series Reduction Gear Box Enclosed Package M1A-17 Series Starting and Turning Motor System Enclosed Package
Standard Package Configuration - Epicyclic (M1A), Parallel (M1T) - Carbon Steel Common Base Frame Standard Package Configuration - Various Frequency Drive (VFD) - Carbon Steel Common Base Frame
- Output Speed : 1,500 / 1,800 rpm (50/60 Hz) - Outdoor Carbon Steel, Acoustic Enclosure - (Option : Air Starter, DC Motor) - Outdoor Carbon Steel, Acoustic Enclosure
M1A-13A Gas Turbine - Noise Level : 85 dBA at 1 m to the side of Enclosure M1A Gas Turbine - Turning Motor - Noise Level : 85 dBA at 1 m to the side of Enclosure
Starting and Turning Motor System - Industrial Single-Shaft
- Industrial Single-Shaft - Forced Ventilation Fan with Filter and Inlet Screen - Forced Ventilation Fan with Filter and Inlet Screen
- Various Frequency Drive (VFD) Lube Oil System
- Rotor Speed : 22,000 rpm - Maintenance Stage, Ladder, Beam (Option) - Rotor Speed : 22,000 rpm - Maintenance Stage, Ladder, Beam (Option)
- (Option : Air Starter, DC Motor) - Lube Oil : Synthetic Ester Oil
M1T-13 Gas Turbine - Turning Motor Intake Silencer & Filter Compressor - Turbine Driven Main Lube Pump Intake Silencer & Filter
- Twin M1A GT with Combined Gear Box - Painted Carbon Steel (Outer Skin and Structure) - 2 Stage Centrifugal - Pre-Post Lube Pump - Painted Carbon Steel (Outer Skin and Structure)
Lube Oil System - Pressure Ratio : 10.5 (-17,-17D)
Compressor - Lube Oil : Synthetic Ester Oil - 2 Stage Filter with Insect Screen - Air Cooled Oil Cooler with Temp. Control Valve - 2 Stage Filter with Insect Screen
- 2 Stage Centrifugal - Pulse Self Cleaning Filter (Option) - IGV (-17D Option) - Water Cooled (Option) - Pulse Self Cleaning Filter (Option)
- Turbine Driven Main Lube Pump
- Pressure Ratio : 9.4 (-13A), 9.6 (-13D) - Pre-Post Lube Pump - Noise Level : 85 dBA in front of Filter Combustor - Integral Oil Reservoir - Noise Level : 85 dBA in front of Filter
- IGV (-13D Option) - Air Cooled Oil Cooler with Temp. Control Valve Exhaust Silencer and Stack (Option) - Single Can Combustor - Simplex Filter (Option : Duplex Type) Exhaust Silencer and Stack (Option)
Combustor - Water Cooled (Option) - Single Ignition - Stainless Steel Piping : Down Stream of Filter
Controls - Conventional Diffusion (-17) Controls
- Single Can Combustor - Integral Oil Reservoir : 210 liter (GPB15) - Microprocessor Based Programable Logic Generator - Microprocessor Based Programable Logic
: 160 liter (GPB30) - Dry Low Emission (DLE) (-17D) - Continuous Duty Rating
- Single Ignition Controller (PLC) Controller (PLC)
- Simplex Filter (Option: Duplex Type) - Applicable Fuel : Natural Gas, Diesel, Dual fuel
- Air Cooled Open Drip-Proof Construction
- Conventional Diffusion (-13A) (CPU, Power Module : Option Redundant) (CPU, Power Module : Option Redundant)
- Steam Injection to Diffusion Combustor Generator - Gas Turbine and Generator Control Turbine Water Cooled (Option) - Gas Turbine and Generator Control
(-13A Option) - Continuous Duty Rating GT start / shutdown Control - 3 Stage Axial Turbine - 3 Phase, 3 Wire (Option 4 Wire) GT start / shutdown Control
- Dry Low Emission (DLE) (-13D) - Air Cooled Open Drip-Proof Construction Speed / kW / Power Factor Control Coupling Shaft & Cover - Standard Voltage : 0.4 kV, 3.3 kV, 6.6 kV Speed / kW / Power Factor Control
- Applicable Fuel : Natural Gas, Diesel, Dual Fuel Water Cooled (Option) Auto Synchronizing and Auto Sharing - Flexible Coupling with Shear Pin and Cover - Power Factor : 90% (Option 85%, 80%) Auto Synchronizing and Auto Sharing
(-13A) - 3 Phase, 3 Wire (Option 4 Wire) - Touch Panel Operation - Bearing : Ball (Roller) Bearing - Touch Panel Operation
Reduction Gear Box - Lubrication : Grease Pack
Turbine - Standard Voltage : 3.3 kV, 6.6 kV - Industrial Ethernet - Epicyclic - Industrial Ethernet
- Power Factor : 90% (Option 85%, 80%) - Remote Monitoring (Option) - IEC Standard, Class F Insulation with F rise - Remote Monitoring (Option)
- 3 Stage Axial Turbine - Output Speed : 1,500 / 1,800 rpm (50/60 Hz)
- Bearing : Ball (Roller) Bearing Graphics Monitoring - Exciter : Diverted Field Brushless (Option PMG) Graphics Monitoring
Coupling Shaft & Cover
- Lubrication : Grease Pack Historical Trend & Event Logger Historical Trend & Event Logger
- Flexible Coupling with Shear Pin and Cover
- Exciter : Diverted Field Brushless (Option PMG) Daily and Monthly Reports Daily and Monthly Reports
GPB17 Typical Layout : m GPB17 Typical Package Outlook : m
(Reference) (Reference)
7 8
M7A Series Gas Turbine Generator Specifications
Site Condition for Normal Perfor
Elevation above sea level :0m
Inlet Air Temperature : 15 C
Inlet Air Pressure Loss : 0.98 kPa
Exhaust Gas Pressure Loss : 2.45 kPa (GPB60/60D)
3.43 kPa (GPB70/70D)
2.94 kPa (GPB80/80D)
LHV of Natural Gas Fuel (100% CH4) : 35.9 MJ/Nm3
Typical Steam Condition
Steam Pressure : 0.83 MPaG
Steam Temperature (Saturated) : 177 C
Feed Water Temperature : 80 C
Blowdown from HRSG : 0 %
9 10
L20A Series Gas Turbine Generator Specifications L30A Series Gas Turbine Generator Specifications
Site Condition for Normal Perfor Site Condition for Normal Perfor
Elevation above sea level :0m Elevation above sea level :0m
Inlet Air Temperature : 15 C Inlet Air Temperature : 15 C
Inlet Air Pressure Loss : 0.98 kPa Inlet Air Pressure Loss : 0.98 kPa
Exhaust Gas Pressure Loss : 3.43 kPa (GPB180/180D) Exhaust Gas Pressure Loss : 3.43 kPa(GPB300/300D)
LHV of Natural Gas Fuel : 35.9 MJ/Nm3 LHV of Natural Gas Fuel : 35.9 MJ/Nm3
(100% CH4) (100% CH4)
L20A Series Starting and Turning System Intake Silencer & Filter L30A Series Starting and Turning System Intake Silencer & Filter
- Various Frequency Drive (VFD) - Painted Carbon Steel (Outer Skin and Structure) Standard Package Configuration - Various Frequency Drive (VFD) - Painted Carbon Steel (Outer Skin and Structure)
Standard Package Configuration
Lube Oil System - Stainless Steel Inner Punching Metal Sheet Lube Oil System - Stainless Steel Inner Punching Metal Sheet
L20A Gas Turbine - 3 Stage Filter with Insect Screen L30A Gas Turbine - 3 Stage Filter with Insect Screen
- Lube Oil : Turbine Oil ISO VG32 (optional VG46) - Lube Oil : Turbine Oil ISO VG32 (optional VG46)
- Industrial Single-Shaft - Pulse Type Self Cleaning Filter (Option) - Industrial Twin-Shaft - Pulse Type Self Cleaning Filter (Option)
- Turbine Driven Main Lube Oil Pump - Motor Driven Main Lube Oil Pump
- Rotor Speed : 9,420 rpm - Noise Level : 85 dBA at 1 m to Filter inlet - Power Turbine Rotor Speed : 5,600 rpm - Noise Level : 85 dBA at 1 m to Filter inlet
- Pre-Post Lube Oil Pump - Standby Lube Oil Pump
Compressor - Emergency Lube Oil Pump Exhaust Silencer Stack (Option) Compressor - Pre-Post Lube Oil Pump Exhaust Silencer Stack (Option)
- 11 Stage Axial Flow - Water Cooled Oil Cooler with Temp. Control Valve - 14 Stage Axial Flow - Emergency Lube Oil Pump
Controls Controls
- IGV & 4 Stage VSV - Oil Reservoir integrated with Baseplate : 5,900 liter - IGV & 4 Stage VSV - Water Cooled Oil Cooler with Temp. Control Valve
- Microprocessor Based Programable Logic - Microprocessor Based Programable Logic
Combustor - Stainless Steel Piping : Down Stream of Filter Controller (PLC) Combustor - Oil Reservoir integrated with Baseplate : 11,700 liter Controller (PLC)
- 8 Can Combustors - Filter (CPU, Power Module : Option Redundant) - 8 Can Combustors - Stainless Steel Piping : Down Stream of Filter (CPU, Power Module : Option Redundant)
- Dual Ignition System - Oil Vapor Fan - Gas Turbine and Generator Control - Dual Ignition System - Duplex Full-flow Filter - Gas Turbine and Generator Control
- Conventional Diffusion (GPB180) Generator GT start / Shutdown Control - Conventional Diffusion (GPB300) - Oil Vapor Fan GT start / Shutdown Control
(Option De-NOx : Steam Injection) - Continuous Duty Rating Speed / kW / Power Factor Control (Option De-NOx : Steam Injection) Generator Speed / kW / Power Factor Control
- Dry Low Emission (DLE) (GPB180D) - 3 Phase, 3 Wire (Option 4 Wire) Auto Synchronizing and Auto Sharing - Dry Low Emission (DLE) (GPB300D) - Continuous Duty Rating Auto Synchronizing and Auto Sharing
- Applicable Fuel : Natural Gas, - Voltage : 6.6 kV, 11.0 kV - Touch Panel Operation - Applicable Fuel : Natural Gas - 3 Phase, 3 Wire (Option 4 Wire) - Touch Panel Operation
Diesel (Standby Only) Dual Fuel - Power Factor : 90% (Option 85%, 80%) - Serial Link User Interface (Option) Turbine - Voltage : 11 kV - Serial Link User Interface (Option)
Turbine - IEC Standard, Class F Insulation with F rise - SCADA System (Option) - Gas Generator Turbine : 2 Stage Axial Turbine - Power Factor : 90% (Option 85%, 80%) - SCADA System (Option)
- 3 Stage Axial Turbine - Exciter : Brushless PMG - Redundant Control System (Option) - Power Turbine : 3 Stage Axial Turbine - IEC Standard, Class F Insulation with F rise - Redundant Control System (Option)
Coupling Shaft & Cover Enclosed Package - Remote Monitoring (Option) Coupling Shaft & Cover - Exciter : Brushless PMG - Remote Monitoring (Option)
- Flexible Coupling with Shear Pin and Cover - Carbon Steel Common Base Frame Graphics Monitoring - Flexible Coupling with Shear Pin and Cover Enclosed Package Graphics Monitoring
- Painted Carbon Steel Acoustic Enclosure Historical Trend & Event Logger (Reduction Gear and Generator connection) - Carbon Steel Common Base Frame Historical Trend & Event Logger
Reduction Gear Box
- Noise Level : 85 dBA at 1 m to the side of Enclosure Daily and Monthly Reports - Painted Carbon Steel Acoustic Enclosure Daily and Monthly Reports
- Parallel Shaft Reduction Gear Box
- Forced Ventilation Fan with Filter - Parallel Shaft - Noise Level : 85 dBA at 1 m to the side of Enclosure
- Maintenance Stage, Ladder, Beam (Option) - Forced Ventilation Fan with Filter
- Maintenance Stage, Ladder, Beam (Option)
GPB180 Typical Package Outlook : m GPB300 Typical Package
(Reference) Outlook : m
(Reference)
11 12
Standby Model Introduction Standby Model ( GPS Series )
Excellent Features of Standby generator sets must start and supply power in the event of the loss of power from the utility.
These functions depend greatly on the prime-mover of the standby system. Starting and providing power
Kawasaki Standby Gas Turbine Generators Sets are often more important than financial conditions such as the initial cost of equipment.
Kawasaki standby GPS Series are suitable for standby power supply when utility power fails.
Kawasaki has installed over 7,000 Standby Gas Turbine Generator Sets rated from 200 kVA to 6,000 kVA All the models are designed for automatic operation ( start/power supply/stop ) and equipped with
worldwide. The reliability of Kawasaki Standby Gas Turbine Generator Sets has allowed to install in alarm/protection systems.
Internet Data Centers, Hospitals, and Key Facilities where uninterrupted power is certainly required.
Basic Specifications
- High Performance, and very reliable, with the low cost gas turbine solution
- Easy Maintenance
- Dual Fuel Capability
- Low Noise Operation
- Low Vibration
- No Cooling Water
- High Starting Reliability, and quick start
- Light Weight, and space saving, easy transportation and installation
- Clean Exhaust Gas
- Excellent frequency control, even with large step loads
13 14
Mobile / Trailer Model ( MGP / TGP Series )
Kawasaki MGP/TGP Series are gas turbine generators mounted on trucks or trailers for mobile Basic Specifications
application. MGP/TGP integrate all necessary equipment and enable fully automatic operation without
the need for external power supply. High durability against vibration and shock, and reliable operation
are important for this application. Kawasaki MGP/TGP is designed to fully meet such demands.
Advantages
1. Developed with Vast Field Experience 3. Compact Integration
Gas Turbines on trucks or trailers need to withstand large MGP/TGP incorporate all necessary equipment, including
vibration/shock when the trucks run on roads. fuel tank, batteries, exhaust silencer, cable reel, etc.,
Kawasaki meets mobile installation condition with gas inside a compact aluminum enclosure.
turbines experience and technology from Kawasaki aircraft This feature enables easy maintenance.
jet engines operating under similar severe environmental
conditions. 4. Blackout Start Capability
MGP/TGP can start up and supply electricity without any
2. Low Center of Gravity and Large Tumble-down Angle external utility supply, such as electric power and fuel.
Thanks to light weight of gas turbines, the center of gravity of
MGP/TGP is low, and this makes it possible to have stable
maneuverability.
(Note)
1 : Output : Up to 40C of ambient temp., 150 m above sea level.
Installation Example
TGP3000 MGP1250
MGP2000 MGP2000
15 16
Kawasaki Techno-Net Installation Examples
Full Time Support Kawasaki Gas Turbine has been installed to....
Maintenance Management Data Center Paper Mill Hospital
Predictive services based on trending data and asset maintenance management Food Process College Campus Oil & Gas
What to do When to do it How to do it Who's to do it Tire Manufacturer District Heat & Cooling AND MORE !!!
Improvement of Availability and Quality of Maintenance In 2010 Kawasaki accumulated 10,000th Kawasaki Gas Turbine Engines
Minimum down time and good quality with adequate maintenance strategies and execution. in all over the world !!!
Remote Maintenance System by a GT Expert
Proven effectiveness by most Kawasaki remote maintenance users
Fleet wide analysis
Internet / Intranet
The Kawasaki World Business Center in the USA, Germany, Malaysia, China, Korea and Japan are connected
by the Internet and by the KHI intranet to monitor gas turbines remotely and globally.
Attended monitoring
All system data is monitored and recorded hourly, as well as all start signals and first out malfunction signals.
Predictive and preventative maintenance is accomplished by analysis of thermal cycles and unit vibration.