SIEMENS QURAYAT EXT - III PROJECT DCS LOOP TEST RECORD

Digital Inputs Commissioning Protocol :


1- Open functional diagram and related HMI screen
2- Simulate the signal from field side
3- Check indication on HMI and ASD.

Test steps
S/No. Cabinet SLOT CH KKS Signal Description Range Type Date Test Status
1 2 3 4 5
1 00CPC02 FA011 16 Y0BTM03 XM01 RECTIFIER FAILURE --- DI --- --- OK

2 00CPC02 FA011 17 Y0BTM03 XM04 HIGH DC VOLTAGE --- DI --- --- OK

3 00CPC02 FA011 18 Y0BTM03 XM05 LOW DC VOLTAGE --- DI --- --- OK

4 00CPC02 FA011 19 Y0BTM03 XM06 DC EARTH FAULT --- DI --- --- OK

5 00CPC02 FA011 20 Y0BTM03 XM07 BATTERY BCB OPEN/FUSE FAILURE --- DI --- --- OK

6 00CPC02 FA011 21 Y0BTM03 XM08 CHARGER OVERLOAD --- DI --- --- OK

7 00CPC02 FA011 22 Y0BTM03 XM09 CIRCUIT BREAKER OPEN --- DI --- --- OK

8 00CPC02 FA011 23 Y0BTM03 XM10 BATTERY LOW VOLTAGE --- DI --- --- OK

9 00CPC02 RC004 13 Y0BTM03 XM02 COMMOM ALARM --- DI --- --- OK

10 00CPC02 RC004 14 Y0BTM03 XM03 CHARGER FAILURE --- DI --- --- OK

11 00CPC02 FB011 16 Y0BTM04 XM01 RECTIFIER FAILURE --- DI --- --- OK

12 00CPC02 FB011 17 Y0BTM04 XM04 HIGH DC VOLTAGE --- DI --- --- OK

13 00CPC02 FB011 18 Y0BTM04 XM05 LOW DC VOLTAGE --- DI --- --- OK

14 00CPC02 FB011 19 Y0BTM04 XM06 DC EARTH FAULT --- DI --- --- OK

15 00CPC02 FB011 20 Y0BTM04 XM07 BATTERY BCB OPEN/FUSE FAILURE --- DI --- --- OK

16 00CPC02 FB011 21 Y0BTM04 XM08 CHARGER OVERLOAD --- DI --- --- OK

17 00CPC02 FB011 22 Y0BTM04 XM09 CIRCUIT BREAKER OPEN --- DI --- --- OK

18 00CPC02 FB011 23 Y0BTM04 XM10 BATTERY LOW VOLTAGE --- DI --- --- OK

19 00CPC02 RD004 13 Y0BTM04 XM02 COMMOM ALARM --- DI --- --- OK

20 00CPC02 RD004 14 Y0BTM04 XM03 CHARGER FAILURE --- DI --- --- OK

21 00CPC02 FB010 19 Y0BTM07 XM01 RECTIFIER FAILURE --- DI --- --- OK

22 00CPC02 FB010 22 Y0BTM07 XM04 HIGH DC VOLTAGE --- DI --- --- OK

23 00CPC02 FB010 23 Y0BTM07 XM05 LOW DC VOLTAGE --- DI --- --- OK

1OF3
SIEMENS QURAYAT EXT - III PROJECT Test steps DCS LOOP TEST RECORD
S/No. Cabinet SLOT CH KKS Signal Description Range Type Date Test Status
1 2 3 4 5
24 00CPC02 FB010 24 Y0BTM07 XM06 DC EARTH FAULT --- DI --- --- OK

25 00CPC02 FB010 25 Y0BTM07 XM07 BATTERY BCB OPEN/FUSE FAILURE --- DI --- --- OK

26 00CPC02 FB010 28 Y0BTM07 XM08 CHARGER OVERLOAD --- DI --- --- OK

27 00CPC02 FB010 29 Y0BTM07 XM09 CIRCUIT BREAKER OPEN --- DI --- --- OK

28 00CPC02 FB010 30 Y0BTM07 XM10 BATTERY LOW VOLTAGE --- DI --- --- OK

29 00CPC02 RD005 12 Y0BTM07 XM02 COMMOM ALARM --- DI --- --- OK

30 00CPC02 RD005 13 Y0BTM07 XM03 CHARGER FAILURE --- DI --- --- OK

SSEM I&C ENGINEER: DATE: SEC I&C ENGINEER:

2OF3
SIEMENS QURAYAT EXT III PROJECT LOOP TEST RECORD

DRIVE CONTROL MODULE TEST


1) Check that the application software is programmed according to the drive specification.
2) Select the plant display and the related operation window on the OM screen
3) Check the drive information in the detail operation window
4) Operate and monitor by OM
5) Simulate faults for the drive and show the faults and the alarm on ASD

Test steps SEC


S/No. Cabinet SLOT CH KKS Signal Description Range Type Date Insp.
1 2 3 4 5 Sign.
DI
DI
AI
AI
5 00CPC02 RC005 9 Y0BUD01GS001 XB33 125V DC MAIN DB I/C-1TRIP DI
6 00CPC01 RA009 0 Y0BUD01GS001 YB01 125V DC MAIN DB I/C-1OPN CMD DO
7 00CPC01 RA009 1 Y0BUD01GS001 YB02 125V DC MAIN DB I/C-1CLS CMD DO
8 00CPC02 FB006 27 Y0BUD01GS002 XB01 125V DC MAIN DB BC ON FB DI
9 00CPC02 FB006 28 Y0BUD01GS002 XB02 125V DC MAIN DB BC OFF FB DI
10 00CPC02 FB006 29 Y0BUD01GS002 XB14 125V DC MAIN DB BC LOCAL/REMOT DI
11 00CPC02 FB006 30 Y0BUD01GS002 XB36 125V DC MAIN DB BC ATS OPERATED DI
12 00CPC02 RC005 8 Y0BUD01GS002 XB33 125V DC MAIN DB BC TRIP DI
13 00CPC02 RC005 9 Y0BUD01GS002 XB34 125V DC MAIN DB BC BUS 1 COMMON TRIP DI
14 00CPC02 RC005 10 Y0BUD01GS002 XB35 125V DC MAIN DB BC BUS 2 COMMON TRIP DI
15 00CPC02 RB004 13 Y0BUD01GS002 YB01 125V DC MAIN DB BC OPN CMD DO
16 00CPC02 RB004 14 Y0BUD01GS002 YB02 125V DC MAIN DB BC CLS CMD DO
17 00CPC02 FA010 18 Y0BUD02GS001 XB01 125V DC MAIN DB I/C-2 ON FB DI
18 00CPC02 FA010 19 Y0BUD02GS001 XB02 125V DC MAIN DB I/C-2OFF FB DI
19 00CPC02 RB008 0 Y0BUD02GS001 XQ12 125V DC MAIN DB I/C-2CURRENT AI
20 00CPC02 RB008 1 Y0BUD02GS001 XQ13 125V DC MAIN DB I/C-2VOLT AI
21 00CPC02 RD005 9 Y0BUD02GS001 XB33 125V DC MAIN DB I/C-2TRIP DI
22 00CPC02 RB004 9 Y0BUD02GS001 YB01 125V DC MAIN DB I/C-2OPN CMD DO
23 00CPC02 RB004 10 Y0BUD02GS001 YB02 125V DC MAIN DB I/C-2CLS CMD DO
24 00CPC02 FB010 16 Y0BUD07GS001 XB01 125V DC EMG LIGHTING DB I/C ON FB DI
25 00CPC02 FB010 17 Y0BUD07GS001 XB02 125V DC EMG LIGHTING DB I/COFF FB DI
26 00CPC02 RB008 3 Y0BUD07GS001 XQ12 125V DC EMG LIGHTING DB I/CCURRENT AI
27 00CPC02 RB008 4 Y0BUD07GS001 XQ13 125V DC EMG LIGHTING DB I/CVOLT AI
28 00CPC02 RC004 15 Y0BUD07GS001 XB33 125V DC EMG LIGHTING DB I/CTRIP DI
29 00CPC02 RD005 11 Y0BUD07GS001 XB34 125V DC EMG LIGHTING DB I/CCommon TRIP DI
30 00CPC02 RB004 15 Y0BUD07GS001 YB01 125V DC EMG LIGHTING DB I/COPN CMD DO
31 00CPC02 RB004 16 Y0BUD07GS001 YB02 125V DC EMG LIGHTING DB I/CCLS CMD DO
32 00CPC02 RC005 10 Y0BRA06GS002 XB35 125V DC MAIN DB I/C-2OPN CMD DO

SSEM I&C ENGINEER: DATE: SEC I&C ENGINEER: