EQUIPMENT SCHEDULE (OPTION 1)

PIPELENGTH
COOL COOLING
AREA
LOAD CAPACITY
LOCATION MARK QTY DESCRIPTION ODU TO DB BOX DB BOX TO IDU INDOOR TO OUTDOOR

(SQ. M.) (HP) (HP) M FT M FT M FT

HEAD NURSE OFFICE FCU 1 1 7.2 0.6 1.5 WALL MOUNTED 15 49.2

WORKING AREA FCU 3 1 20.0 1.6 2.0 WALL MOUNTED 25 82 10 32.8 N/A

PREMATURE ROOM FCU 5 1 10.7 0.8 1.0 WALL MOUNTED 8 26.24

NURSE STATION INFORMATION FCU 2 1 60.0 4.7 5.0 CEILING CASSETTE 32 104.96

PATHOLOGIC ROOM FCU 6 1 7.3 0.6 1.0 WALL MOUNTED 21 68.88

PATHOLOGIC ROOM FCU 7 1 7.3 0.6 1.0 WALL MOUNTED 16 52.48


N/A
PATHOLOGIC ROOM FCU 8 1 7.3 0.6 1.0 WALL MOUNTED 14 45.92

PATHOLOGIC ROOM FCU 9 1 7.3 0.6 1.0 WALL MOUNTED 10 32.8

OPERATING ROOM 4 FCU 4 1 39.3 3.1 3.0 WALL MOUNTED 20 65.6

OR/DR OPERATING ROOM 1 FCU 14 1 35.8 2.8 3.0 WALL MOUNTED 14 45.92
COMPLEX & 20 65.6
NICU OPERATING ROOM 2 FCU 15 1 35.8 2.8 3.0 WALL MOUNTED 3 9.84
N/A
OPERATING ROOM 3 FCU 16 1 35.8 2.8 3.0 WALL MOUNTED 6 19.68
20 65.6
RECOVERY ROOM FCU 17 1 36.6 2.8 3.0 WALL MOUNTED 13 42.64

NICU FCU 14 1 65.0 5.1 5.0 CEILING CASSETTE 11 36.08

LABOR ROOM FCU 11 1 38.0 3.0 3.0 WALL MOUNTED 16 52.48


N/A
DELIVERY ROOM FCU 10 1 38.0 3.0 3.0 WALL MOUNTED 23 75.44

NICU BACK FCU 13 1 42.0 3.3 3.0 WALL MOUNTED 4 13.12

OBSERVATION ROOM WAC 1 1 1.0 WINDOW TYPE

OBSERVATION ROOM WAC 2 1 30.0 2.3 1.0 WINDOW TYPE N/A

OBSERVATION ROOM WAC 3 1 1.0 WINDOW TYPE


EQUIPMENT SCHEDULE (OPTION 2)

PIPELENGTH
AREA COOL COOLING
LOAD CAPACITY
LOCATION MARK QTY DESCRIPTION ODU TO DB BOX DB BOX TO IDU INDOOR TO OUTDOOR

(SQ. M.) (HP) (HP) M FT M FT M FT

HEAD NURSE OFFICE FCU 1 1 7.2 0.6 1.5 WALL MOUNTED 14 45.92
24 78.72
FCU 2.A 1 2.5 WALL MOUNTED 9 29.52
NURSE STATION INFORMATION 60.0 4.7 N/A
FCU 2.B 1 2.5 WALL MOUNTED 5 16.4
23 75.44
WORKING AREA FCU 3 1 20.0 1.6 2.0 WALL MOUNTED 9 29.52

PREMATURE ROOM FCU 5 1 10.7 0.8 1.0 WALL MOUNTED 22 72.16

PATHOLOGIC ROOM FCU 6 1 7.3 0.6 1.0 WALL MOUNTED 21 68.88

PATHOLOGIC ROOM FCU 7 1 7.3 0.6 1.0 WALL MOUNTED 16 52.48

PATHOLOGIC ROOM FCU 8 1 7.3 0.6 1.0 WALL MOUNTED 14 45.92

PATHOLOGIC ROOM FCU 9 1 7.3 0.6 1.0 WALL MOUNTED 10 32.8

OPERATING ROOM 4 FCU 4 1 39.3 3.1 3.0 WALL MOUNTED 20 65.6


OR/DR
COMPLEX & OPERATING ROOM 1 FCU 14 1 35.8 2.8 3.0 WALL MOUNTED 14 45.92
NICU 20 65.6
OPERATING ROOM 2 FCU 15 1 35.8 2.8 3.0 WALL MOUNTED 3 9.84
N/A
OPERATING ROOM 3 FCU 16 1 35.8 2.8 3.0 WALL MOUNTED 6 19.68
20 65.6
RECOVERY ROOM FCU 17 1 36.6 2.8 3.0 WALL MOUNTED 13 42.64

NICU FCU 14 1 65.0 5.1 5.0 CEILING CASSETTE 11 36.08

LABOR ROOM FCU 11 1 38.0 3.0 3.0 WALL MOUNTED 16 52.48


N/A
DELIVERY ROOM FCU 10 1 38.0 3.0 3.0 WALL MOUNTED 23 75.44

NICU BACK FCU 13 1 42.0 3.3 3.0 WALL MOUNTED 4 13.12

OBSERVATION ROOM WAC 1 1 1.0 WINDOW TYPE

OBSERVATION ROOM WAC 2 1 30.0 2.3 1.0 WINDOW TYPE N/A

OBSERVATION ROOM WAC 3 1 1.0 WINDOW TYPE