Typical Utility Power Line
Problems and Failures
3
Typical Utility Power Line
Problems and Failures
4
Introduction to the Astronic No Break
Uninterruptible Power Supply System
The Astronic No Break is an uninterruptible power supply (UPS) system patented in the
U.S. and Mexico. The system prevents costly damages to equipment and downtime
losses caused by disruptions in commercial power lines. It supplies uninterrupted,
dynamically generated energy of unlimited continuity, true sinusoidal power, completely
isolated from the problems of the commercial power line.
The Astronic No Break is a rugged, heavy duty electric machine system designed to
offer lifelong continuous service, free from batteries. The superiority of the Astronic No-
Break design in comparison with battery-powered electronic static UPS systems has been
proven for over 25 years by clients in many areas, including commercial, industrial,
military and government operations, throughout several countries. This UPS system is the
only one that offers a 10 year warranty.
The Astronic No Break can be configured according to the needs of each client, with a
capacity of 10 to 1,000 kVA per unit, and with larger capacities on synchronized units.
None of these three power sources are directly connected to the system!s power output,
which is fed directly from the generator on the motor-generator-flywheel set. This
generator is electrically independent from the three sources.
5
Figure I. Astronic No Break.
B A C
MOTOR
GENERATOR
AUTOMATIC FLYWHEEL
CONTROL
DIESEL MOTOR
Automatic
Control Board GENERATOR
Backup Diesel
Power Plant
Continuity
Unit
6
Beneficial Features of the
Astronic No Break System
" Unexpected power shortages are eliminated trough the use of the Astronic No Break.
Critical applications that benefit include:
! Uninterrupted
! Unlimited
! Protected from high voltage spikes and low voltages
! Protected from wave harmonics and deformations
! Protected from lightning strikes on the power lines
" The continuity of power provided by the Astronic No Break is very reliable because:
! It uses kinetic energy stored in a forged steel flywheel, spinning at 1,800 rpm
! Uses no batteries, therefore eliminating the risks involved with battery reliability
! It!s robust construction and simple design replaces delicate electronics and complicated
circuits
! A fast diesel engine startup is ensured by kinetic energy
! Uses no transfer switches on the critical load
! It!s diesel power plant unlimited continuity depends only on fuel availability
7
" The Astronic No Break supplies adequate loads for demanding applications such as
large electric motor startups:
! Up to 200% overload
! No DC to AC inverter required since power is delivered from an electric generator
! Appropriate for resistive, inductive and capacitive loads
" The Astronic No Break provides several commercial advantages such as:
8
Advantages of the Astronic No Break
Over Static Battery UPS Systems
10 year warranty. ! #
9
Some Applications
of the Astronic No Break
10
Some Clients and Users
of the Astronic No Break
Motorola, Kellogg's, Pepsico, Cadbury Adams, Good Year Oxo, Dowell Schlumberg,
Cynamid, Mead Johnson, Fuller, Ferro Mexican, Shering Plough, Moore Business Forms,
Sidney Ross, Crouse Hinds, Fester, Kendall, Pilgrims Pride, Ford Motor Company,
Qumica Fluor, Dupont, Merck,
USA UPS Systems, Inc., Marathon Electric, Basler Electric, Computer Power Products,
Instituto Costarricence de Electricidad, YF Internacional de Taiwan, Mitsubishi Heavy
Industries Japan
Casa de Bolsa del Valle de Mxico, Multivalores, Factoraje Bancomer, Casa de Bolsa
AVKA, Inversora Burstil, Ruiz Urqiza & Co., Seguros Monterrey Aetna, Afianzadora
Insurgentes, Caf Orin.
11
Description of Components
of the Astronic No Break
As described above, the Astronic No Break UPS system integrates a Continuity Unit (A),
an Automatic Control Board (B), and a Backup Diesel Power Plant (C). The Continuity
Unit (A) is composed of an induction motor, a synchronous generator and a flywheel, with
all rotors mounted on a common shaft. The Automatic Control Board (B) is composed of
transfer switches automatically operated by a Programable Logic Control. The Backup
Diesel Power Plant (C) is composed of a diesel engine and a synchronous generator.
A. Continuity Unit
Heavy duty, continuous operation, vertical axis construction, self-ventilated ODP, long life
bearings with oil level indicators, grounding terminals, and temperature protection on both
bearings. Cobalt blue industrial grade finish paint.
High efficiency AC induction motor, squirrel cage, high torque, 4 pole, 3 phase, voltage
according to customer specification from 208 to 440 volts and 50, 60 or 400 Hz. Reinforced
Class F insulation system, embedded winding temperature detectors.
High efficiency AC synchronous generator, 3 phase, voltage according to customer specification
from 208 to 440 volts and 50, 60 or 400 Hz. Reinforced Class F insulation system, embedded
winding temperature detectors.
Inertial flywheel made from special steel, precision machined and dynamically balanced.
12
UTILITY
POWER LINE
AUTOMATIC
CONTROL B
MOTOR
GENERATOR
FLYWHEEL
DIESEL MOTOR
A GENERATOR STARTER
C
UPS
LOAD
Figure II. Diagram of the uninterruptible power supply system Astronic No Break.
1,800 rpm. diesel engine with high speed governor, battery-free automatic electric starter. Liquid
cooled with radiator and fan, electric heater for liquid. Temperature detectors on oil, coolant and
starter. Directly coupled to generator, engine exhaust silencer.
AC synchronous generator, 4 pole, 3 phase, 0.8 P.F., high frequency brushless exciter, 4 pole,
voltage according to customer specification from 208 to 440 volts and 50, 60 or 400 Hz.
Reinforced Class F insulation. Grease lubricated low friction bearings.
13
Astronic No Break Operation
During normal operation of the utility power lines, the electric motor on the Continuity Unit
(A) is fed by the utility line. The A motor keeps the Continuity Unit spinning as the flywheel
ensures a constant turning speed for the A generator.
The A generator, spinning at a very constant speed, converts the kinetic energy on the
flywheel into healthy electric power, with excellent waveform and voltage regulation.
The A generator is electrically independent from the A motor and from the utility power
line, separating the critical load from any problems on commercial power line.
14
Operation during utility line interruptions
When a power interruption occurs in the commercial utility line, the energy stored in the
flywheel maintains the Continuity Unit (A) spinning, and therefore the A generator
continues to supply electric power to the critical load. At this moment, the Automatic
Control Board (B) detects the failure and commands the Backup Power Plant (C) to start.
A successful Backup Power Plant (C) startup is crucial to the operation of the Astronic
No Break system. The most common cause for diesel power plant startup failure are
faulty batteries on the starter. Because of this, the system has the most reliable startup for
its diesel motor (C), accomplished by two design features unique to this system: the
elimination of batteries from the diesel starter and the startup aid provided by the
Continuity Unit to the diesel motor.
To further aid the Backup Power Plant startup, at the same moment that the diesel starter
is activated, a transfer switch is closed between the induction motor on the Continuity Unit
(A) and the synchronous generator on the Backup Power Plant (C). Because the motor A
is spinning faster than the generator C, these two will inherently switch places. The faster
spinning motor A will become a generator and supply energy to the slower moving
generator C that in turn acts as a motor and therefore drives the diesel engine to nominal
speed. As the diesel motor (C) reaches its nominal speed, the synchronous generator C
will transition from receiving power to supplying it, and thus the induction motor on the
Continuity Unit (A) will transition back to its operation as a motor.
The Backup Power Plant running on diesel will continue providing uninterrupted power
until the the Automatic Control Board (B) detects nominal levels on the utility line. The
Control will then transfer the utility line feed back to the motor A and will order the Backup
Power Plant (C) to shut down.
During utility line failure, transfer and Backup Power Plant startup, the A generator on the
Continuity Unit will never stop generating energy at constant speed and power rate.
15
Astronic No Break
Electrical Specifications
Phases 3
Wires 3 or 4
16
Astronic No Break
Available Models
FOR MORE INFORMATION AND QUOTES PLEASE CONTACT OUR SALES DEPARTMENT AT
sales@potenciaindustrial.com.mx
17
Potencia Industrial
History
18
In 1975 Potencia Industrial initiated the development of cage
induction and permanent magnet generators for wind applications,
and in 1976 obtained a patent for the world's first direct drive
permanent-magnet wind generator.