COMPARISON BETWEEN THREE

DIFFERENT CFD SOFTWARE AND


NUMERICAL SIMULATION OF AN
AMBULANCE HALL

Ning Li

Master of Science Thesis


KTH School of Industrial Engineering and Management
Energy Technology EGI-2015-017MSC
Division of Energy Technology
SE-100 44 STOCKHOLM

I
Master of Science Thesis EGI 2015: 017MSC

Comparison between three different CFD


software and numerical simulation of an
ambulance hall

Ning Li
Approved Examiner Supervisor

2015-03-05 Joachim Claesson Joachim Claesson


Commissioner Contact person

SWECO Systems AB David Burman


Liu Ting

Abstract
Ambulance hall is a significant station during emergency treatment. Patients need to be transferred from
ambulance cars to the hospitals building in the hall. Eligible performance of ventilation system to supply
satisfied thermal comfort and healthy indoor air quality is very important. Computational fluid dynamic
(CFD) simulation as a broadly applied technology for predicting fluid flow distribution has been
implemented in this project.
There has two objectives for the project. The first objective is to make comparison between the three
CFD software which consists of ANSYS Fluent, Star-CCM+ and IESVE Mcroflo according to CFD
modeling of the baseline model. And the second objective is to build CFD modeling for cases with
difference boundary conditions to verify the designed ventilation system performance of the ambulance
hall.
In terms of simulation results from the three baseline models, ANSYS Fluent is conclusively
recommended for CFD modeling of complicated indoor fluid environment compared with Star-CCM+
and IESVE Microflo. Regarding to the second objective, simulation results of case 2 and case 3 have
shown the designed ventilation system for the ambulance hall satisfied thermal comfort level which
regulated by ASHRAE standard with closed gates. Nevertheless, threshold limit value of the contaminants
concentration which regulated by ASHRAE IAQ Standard cannot be achieved. From simulation results of
case 4.1 to 4.3 shown that the designed ventilation system cannot satisfy indoor thermal comfort level
when the gates of the ambulance hall opened in winter. In conclusion, measures for decreasing
contaminants concentration and increasing indoor air temperature demanded to be considered in further
design.

-II-
Table of Contents
Abstract ..........................................................................................................................................................................II
Acknowledgements ...................................................................................................................................................... V
List of Figures ............................................................................................................................................................. VI
List of Tables............................................................................................................................................................ VIII
Nomenclature.............................................................................................................................................................. IX
1 Introduction .......................................................................................................................................................... 1
1.1 Background .................................................................................................................................................. 1
1.2 Objectives ..................................................................................................................................................... 2
1.3 Method.......................................................................................................................................................... 3
2 Numerical principle of simulation ..................................................................................................................... 4
2.1 Governing Equations ................................................................................................................................. 4
2.1.1 Conservation laws of fluid flow. ...................................................................................................... 4
2.1.2 Thermal equations of wall boundary condition. ........................................................................... 4
2.2 Turbulence modeling.................................................................................................................................. 5
2.2.1 Different choice of k- Model ......................................................................................................... 5
2.2.2 Near Wall functions ....................................................................................................................... 7
2.3 Meshing ........................................................................................................................................................ 8
2.3.1 Shapes of Cell ..................................................................................................................................... 8
2.3.2 Classification of Grids ....................................................................................................................... 8
2.3.3 Mesh Quality....................................................................................................................................... 9
2.4 Solver...........................................................................................................................................................10
2.4.1 Finite Volume Method ....................................................................................................................10
2.4.2 Upwind scheme ................................................................................................................................11
2.4.3 SIMPLE Scheme ..............................................................................................................................11
3 Baseline model and Comparison between Software ....................................................................................13
3.1 Data of ventilation system for baseline model. ....................................................................................13
3.1.1 Design Concept ................................................................................................................................13
3.1.2 Parameter of supply air diffuser ....................................................................................................13
3.1.3 Parameter of Exhaust Grilles .........................................................................................................13
3.2 Geometry....................................................................................................................................................14
3.3 Meshing ......................................................................................................................................................15
3.3.1 Meshing Independency ...................................................................................................................15
3.3.2 Meshing Method ..............................................................................................................................17
3.4 Numerical Setup ........................................................................................................................................19
3.4.1 Selection of simulation models ......................................................................................................19
3.4.2 Boundary conditions .......................................................................................................................19

-III-
3.4.3 Solution Control...............................................................................................................................21
3.5 Simulation results ......................................................................................................................................23
3.5.1 Assessment of thermal comfort in an arbitrary point. ...............................................................23
3.5.2 Velocity Distribution .......................................................................................................................24
3.5.3 Temperature Distribution...............................................................................................................28
4 Ventilation Performance in Different Situations ..........................................................................................33
4.1 Geometry....................................................................................................................................................33
4.1.1 Case 2: Improved ventilation system. ...........................................................................................33
4.1.2 Case 3: Polluted emission from tailpipes of the ambulance cars. ............................................34
4.1.3 Case 4.1-4.3: With opened gates and installed air curtains. .......................................................34
4.2 Meshing ......................................................................................................................................................36
4.3 Boundary Conditions Setup ....................................................................................................................36
4.3.1 Case 2: Improved ventilation system. ...........................................................................................36
4.3.2 Case 3: Polluted emission from tailpipes of the ambulance cars. ............................................36
4.3.3 Case 4.1-4.3: With opened gates and installed air curtains. .......................................................37
4.4 Simulation Results and Analysis. ............................................................................................................38
4.4.1 Case 2: Improved ventilation system. ...........................................................................................38
4.4.2 Case 3: Polluted emission from tailpipes of the ambulance cars. ............................................40
4.4.3 Case 4.1-4.3: With opened gates and installed air curtains. .......................................................43
4.5 Optimized approaches for improving thermal comfort. ....................................................................48
4.5.1 One more supply air diffuser on the specified wall. ...................................................................48
4.5.2 Exhaust extraction system. .............................................................................................................49
4.5.3 Supplement of heat in winter. ........................................................................................................49
5 Conclusion and future improvement ..............................................................................................................51
6 Bibliography ........................................................................................................................................................52
Appendix A: Data sheet/Dimension of Jet Nozzle Diffuser ..............................................................................54
Appendix B: Data and Dimension of Exhaust Grilles ..........................................................................................55
Appendix C: Data and Type of Air curtain. ............................................................................................................56
Appendix D: CO Level vs. Condition&Health Effects. .......................................................................................57

-IV-
Acknowledgements
Foremost I would like to express my fully gratitude to Will Sibia from SWECO systems AB, Stockholm
Sweden for giving me the opportunity to do my master thesis within such interesting and cutting edge
field by a practical project.
Specially, I would like to extend my deepest thanks to Liu Ting, who is my thesis supervisor from
SWECO in the field of CFD simulation. Encouragements, professional and theoretical supports from her
were very beneficial and helpful for me to complete the project.
Sincerely, I would also very thankful to David Berman, who is my thesis supervisor from SWECO in the
field of energy technology and ventilation systems design. Professional advices and positive feedbacks
from him supervised me done the project in the right way.
Moreover, I would like to express my grate gratitude to my supervisor, Associate Professor Joachim
Claesson, at the Royal Institute of Technology (KTH) for your fully helpful supports, responsible
feedback and all the fantastic knowledge were taught from you during the graduate study.
Finally, I am deep appreciate to my parents, my friends for their love and supports.

-V-
List of Figures
Figure 1, 3D layout of SS ambulance hall. ..................................................................................................................... 1
Figure 2, Project Outline .................................................................................................................................................... 2
Figure 3, Velocity distribution near a wall (Versteeg & Malalasekera, 2007) ............................................................... 7
Figure 4, Typical 2D control volume (Versteeg & Malalasekera, 2007). ....................................................................... 8
Figure 5, Block-structured mesh (left) and Unstructured mesh (right) of aerofoil (Versteeg & Malalasekera, 2007) ........ 8
Figure 6, Comparison between coarse, medium and fine hybrid grid. .................................................................................... 9
Figure 7, Misalignment of midpoints for skewed grid. ......................................................................................................... 9
Figure 8, Conservation of general flow variable within finite volume method (Versteeg & Malalasekera, 2007).............10
Figure 9, Evaluation of face value according to Upwind Scheme (Cho, et al., 2010). ......................................................11
Figure 10, Calculation process of SIMPLE Scheme (Versteeg & Malalasekera, 2007)...............................................12
Figure 11, Air motion of Group A outlets (ASHRAE, 1997).......................................................................................13
Figure 12, Geometry of the ambulance hall .......................................................................................................................14
Figure 13 Face sizing for air inlet (Left: Element size is 0.05m; Right: Element size is 0.03m) ..................................15
Figure 14, Face sizing for air outlet (Left: Element size is 0.1m; Right: Element size is 0.05m) ......................................16
Figure 15, Velocity distribution for the two different meshing cases. ...................................................................................16
Figure 16, Generated mesh of the ambulance hall in IESVE Microflo. ...........................................................................17
Figure 17, Generated mesh of the ambulance hall in ANSYS mesh. ................................................................................17
Figure 18, Section plane of (a) Air Inlet; (b) Air Outlet; (c) Exterior Wall; (d) Internal space ........................................18
Figure 19, Mesh metrics control of ANSYS mesh (Left: Skewness; Right: Aspect Ratio) ................................................18
Figure 20, Cell Monitor of point in Case 1.3. ..................................................................................................................23
Figure 21, PPD as a function of PMV (ISO, 1994). ....................................................................................................23
Figure 22, Thermal comfort zone display in Psychronmetric chart. ....................................................................................24
Figure 23, Vector of velocity distribution (h=3m) of case 1.1. ..........................................................................................25
Figure 24, Velocity Magnitude (h=3m) of case 1.1. (Left: 0 to 5.02m/s, Right: 0 to 1 m/s)..........................................25
Figure 25, Vector of Velocity distribution (h=1m) of case 1.1. ........................................................................................25
Figure 26, Zoomed-in views of velocity distribution at plant (h=1m).s ..............................................................................26
Figure 27, Vector of velocity distribution (h=3m) of case 1.2. ..........................................................................................26
Figure 28, Vector of velocity distribution (h=1m) of case 1.2. ..........................................................................................27
Figure 29, Vector and contour of velocity distribution (h=3m and h=1m) of case 1.3.......................................................27
Figure 30, Local mean age of air (h=1m) of case 1.3. ......................................................................................................28
Figure 31, Temperature distribution (h=1m, local temperature)........................................................................................29
Figure 32, Temperature distribution (h=1m, specified temperature). .................................................................................29
Figure 33, Temperature distribution (h=1m, global temperature) with isosurface...............................................................30
Figure 34, Temperature distribution (Left: x=3.6m, 11m and 18.3m; Right: y=10.3m, 15.5m and 21m). ...................30
Figure 35, Temperature distribution on envelop of ambulance hall.....................................................................................30
Figure 36, Temperature distribution of case 1.2. ...............................................................................................................31
Figure 37, Temperature distribution of case 1.3. ...............................................................................................................32
Figure 38, Geometry of case 2 with 4 exhaust grilles. .......................................................................................................33
Figure 39, Geometry of case 3 with tailpipe emission (Left: whole room; Right: zoomed-in to the tailpipe) .........................34
Figure 40, Configuration of air curtain which installed in case 4.1-4.3. ............................................................................34
Figure 41, Geometry of case 4.1 - 4.3. .............................................................................................................................35
Figure 42, Zoomed-in views of geometry for case 4.1-4.3. ..................................................................................................35
Figure 43, Meshing of case 4.1-4.3 (Left: Global: Right: Section cut view). ......................................................................36
Figure 44, Velocity distribution at h=3m over the ground (Local Velocity). .....................................................................38
Figure 45, Velocity distribution at h=1m (Local Velocity). .............................................................................................38
Figure 46, Zoomed-in views to figure 45. ..........................................................................................................................39
Figure 47, Temperature distribution of case 2 at h=1m (Left: local temperature, Right: Specified temperature). ................39
Figure 48, Temperature distribution of case 2 (Left: h=0.1m, isosurface=18C; Right: Room Envelope). .........................40
Figure 49, Velocity distribution of case 3 (Left: h=3m; Right: h=0.4m) .........................................................................40

-VI-
Figure 50, Velocity distribution of case 3 (h=1m). ...........................................................................................................41
Figure 51, Temperature distribution of case 3 h=0.4m (Left: Local temperature; Right: specified temperature) .................41
Figure 52, Temperature distribution of case 3 at h=1m (Specified Temperature). ..............................................................42
Figure 53, CO concentration distribution of case 3 (h=1.5m)...........................................................................................42
Figure 54, CO2 concentration distribution of case 3 (h=1.5m). .......................................................................................43
Figure 55, Velocity distribution of case 4.1 (h=1m).........................................................................................................44
Figure 56, Specified velocity of case 4.1 at h=1m (Left: Velocity 0m/s - 0.2m/s; Right: Velocity 0m/s - 1m/s). ...........44
Figure 57, Velocity distribution of case 4.1 around the opened gates. ................................................................................45
Figure 58, Temperature distribution of case 4.1 (Left=3m; Right=1m). ..........................................................................45
Figure 59, Temperature distribution of case 4.1 (Transection view at gate). .......................................................................46
Figure 60, Pressure distribution at h=1m of case 4.2(Left) and case 4.3 (Right). .............................................................46
Figure 61, Pressure change along the line of case 4.2(red line) and case 4.3 (blue line). ......................................................46
Figure 62, Velocity distribution at h=1m of case 4.2(Left) and case 4.3 (Right). .............................................................47
Figure 63Zoomed-in Velocity distribution at h=1m of case 4.2(Left) and case 4.3 (Right). .........................................47
Figure 64, Temperature distribution at h=1m of case 4.2(Left) and case 4.3 (Right). ......................................................48
Figure 65, Install position of the additional supply air diffuser. .........................................................................................48
Figure 66, Conventional exhaust extraction system (Left) and "in ground" exhaust extraction system (Right)...................49
Figure 67, Working principle of "in ground" exhaust extraction system (Nenerman, 2014). .........................................49

-VII-
List of Tables
Table 1, Cade name of different cases.................................................................................................................................. 2
Table 2, Skewness range and cell quality (Fluent, 2006). ...............................................................................................10
Table 3, Input dimensions of geometry of the ambulance hall. ............................................................................................14
Table 4, Performance of 3D modeling for different tools. ...................................................................................................15
Table 5, Comparison of Mass flow rate and Total heat transfer rate between the two meshing cases .........16
Table 6, Statistics of mesh which generated from ANSYS mesh and IES VE CFD Grid. .........................................18
Table 7, Performance of meshing for the three software. .....................................................................................................18
Table 8, Boundary Conditions set up in ANSYS Fluent and Star - CCM+. .................................................................20
Table 9, Solution control for the three software. .................................................................................................................22
Table 10, Performance of numerical setup for the three software. ........................................................................................22
Table 11, Thermal sensation scale for PMV Method. ......................................................................................................23
Table 12, Simulation results of the three software. ............................................................................................................32
Table 13, Different between the two types of exhaust grilles in two cases. ...........................................................................33
Table 14, Additional parameters of geometry for case 4.1 to 4.3. ......................................................................................34
Table 15, Input parameters for boundary conditions of tailpipes. .......................................................................................37
Table 16, Air curtain boundary conditions of case 4.1-4.3. ..............................................................................................37

-VIII-
Nomenclature
Symbols
A area
Cp specific heat
Ci contaminant concentration
Cu k-epsilon model constant
g gravitational constant
hext external heat transfer coefficient
hf heat transfer coefficient of the fluid side
I tensor of unit
k thermal conductivity
P pressure
Q heat transfer rate
Sm source of mass
T Temperature
t time
u velocity
V volumetric flow rate
y+ dimensionless wall distance
dissipation rate of k
ext emissivity
k turbulence kinetic energy
Stefan-Boltzmann constant
T ,l laminar Prandtl number
T ,t turbulent Prandtl number
flow variable
under-relaxation factor
near-wall temperature equation constant
density
ij rate-of-rotation tensor
i local mean age of air
stress tensor

viscosity of molecular
Abbreviations
CFD Computational Fluid Dynamic
FVM Finite Volume Method
LMA Local Mean Age
PMV Predicted Mean Vote
PPD Percentage of Dissatisfied
RNG Re-Normalization Group
SIMPLE Semi-Implicit Method for Pressure-Linked Equations

-IX-
1 Introduction
1.1 Background
Numerical visualization is a platform provides a simpler way to analysis of large, complex and muti-
dimensional information. Computational fluid dynamic, also called CFD, has combined fluid mechanic
with this platform to simulate both compressible and incompressible fluid flow behavior. Distribution of
temperature, velocity, pressure, contaminant concentration and other fluid properties can be calculated
and displayed from results of CFD simulation (Stamou, et al., 2007). Output results help engineers to
improve and consummate their design quickly and effectively.
In this project, three different CFD commercial software have been employed by the author to evaluate
indoor thermal comfort of an ambulance hall which is belong to SS hospital renovation project from
SWECO, in Stockholm, Sweden. As defined by international standard ISO 7730, thermal comfort as
condition of mind which expresses satisfaction of thermal environment has explained that comfort level
need to be determined by subject method (ISO, 1994). According to the criteria ISO 7730, metabolic rate
(MET) and thermal insulation of clothing index (CLO) will be introduced for obtain thermal comfort
indexes which are predicted mean vote (PMV) and predicted percentage of dissatisfied (PPD) (ISO, 1994).
The three different CFD commercial software consist of ANSYS - Fluent, IES VE Microflo and Star
CCM+. Internal analyses of the ambulance hall were established by the three tools for baseline case.
Thereafter, three additional modeling cases which include improvement of ventilation system, hall with
tailpipe emissions and opened gates with natural ventilation were implemented by ANSYS Fluent
independently.

Figure 1, 3D layout of SS ambulance hall.

Ambulance hall is a significant station during emergency treatment. Patients need to be transferred from
ambulance cars to the hospitals building in the hall. High performance of ventilation system which supply
fresh and comfortable indoor environment is required to achieve.
As shown in Figure 1, during peak operation condition there has 8 ambulance cars parking in the hall.
Consider walls of the ambulance hall, 2 exterior wall are exposed directly to ambient environment and 2
interior walls are connected to internal corridors. For sake of simplifying the model and emphasize
performance of fluid flow within the main hall, interior rooms and internal corridors will be removed in
further 3D modeling.

1
1.2 Objectives
Two main objectives of the project had been set up.
The first objective is to build CFD modeling in three different numerical simulation software which have
been specified as ANSYS-Fluent, IES VE - Microflo and Star-CCM+. Thereafter, made comparison of
performance among these three software.
The second objective is to optimize ventilation system according to output results from baseline model,
simulate the optimized model while involving exhaust emission from the ambulance cars or natural
ventilation with opening gates.
The outline of the project is illustrated in Figure 2, the two objectives are highlighted as orange at the bottom
of the chart.

Figure 2, Project Outline

For simplify the names of each scenarios in further discussion, code name of each scenario list as in Table 1.
Table 1, Cade name of different cases.

Code Name Circumstance Description Operation Software


Case 1.1 2 exhaust grilles, without tailpipe emission, without opened gates ANSYS Fluent
Case 1.2 2 exhaust grilles, without tailpipe emission, without opened gates Star CCM+
Case 1.3 2 exhaust grilles, without tailpipe emission, without opened gates IES VE - Microflo
Case 2 4 exhaust grilles, without tailpipe emission, without opened gates ANSYS Fluent
Case 3 4 exhaust grilles, with tailpipe emission, without opened gates ANSYS Fluent
Case 4.1 4 exhaust grilles, without tailpipe emission, with opened gates, ANSYS Fluent
Outside wind blow perpendicular into the gates with 1m/s
Case 4.2 4 exhaust grilles, without tailpipe emission, with opened gates, ANSYS Fluent
Outside wind produce negative pressure (-0.3Pa)
Case 4.3 4 exhaust grilles, without tailpipe emission, with opened gates, ANSYS Fluent
Outside wind produce negative pressure (-1Pa)

-2-
1.3 Method
Numerical simulation based on computational fluid dynamic (CFD) has become broadly used for
predicting fluid behavior within the objective domain. With foreseeable fluid distribution, undesirable
fluids have the possibility to be decreased or avoided through improvement of the design.
All the simulated cases implemented in this project were built in terms of computational fluid dynamic.
However, turbulence model, boundary conditions, mesh method, simulation scheme and etc. regarding to
modelling setup have to be decided for each case.
In order to decide adaptable modeling schemes implemented during the setup, literature review from
relative scientific papers and corresponding international standards was applied in Chapter 2 and setup of
boundary conditions in Chapter 3 and 4. For comparison among the cases in different circumstances, case
studies with different boundary conditions will be analyzed and disused in Chapter 3 and Chapter 4.
Finally, improved approaches for optimizing the design of the cases will be analyzed briefly.

-3-
2 Numerical principle of simulation
Numerical method for calculating air flow behavior and heat transfer performance is a more beneficial
approach compared with corresponding experiments. Both spending of time and cost can be saved
significantly. Among with multi-fields application, numerical simulation of internal air pattern of building
is developed rapidly during recent years. Detailed information of air temperature, velocity components,
and pressure drop and turbulence intensity within the modeling domain can be generated simultaneously
by CFD software.

2.1 Governing Equations


2.1.1 Conservation laws of fluid flow.
The conservation laws of fluid flow defined by Versteeg and Malalasekera (Versteeg & Malalasekera, 2007)
applies on three fundamental variable quantities which are momentum, energy and mass of fluid particle.
On the base of Newtons second law, the sum of the forces on a fluid particle is equaled to the rate of
change of momentum. According to first law of thermodynamics, energy changing rate on a fluid particle
is equal to the work done by the particle plus the rate of heat added to it. Meanwhile, mass of fluid is
conserved. Conservation equations which required for simulation are list as followed:
For conservation of mass (Eleni, et al., 2012):

( u ) Sm (1)
t
Where Sm is the source from dispersed second phase and to be added to the continuous phase.
For conservation of momentum (Fluent, 2006):

( v) ( vv) P ( ) g F (2)
t
Where is stress tensor and expressed as below (Fluent, 2006):



v v

T
23 vI (3)

In equation (3), is the viscosity of molecular, I is the tensor of unity.


For energy equation in three dimension, four terms are associated with energy changed in the fluid particle
(Versteeg & Malalasekera, 2007):

u xx u xy u zx v xy v yy

DE x y z x y
div pu div kgradT S E (4)
Dt
v zy
w xz
w yz
w zz
z x y z

2.1.2 Thermal equations of wall boundary condition.


Five types of thermal condition which includes fixed heat flux, fixed temperature, convection, radiation
and mixed for wall boundary layer are provided by ANSYS Fluent. Considering to predict fluid flow
within the ambulance hall be more accurate, heat transfer through wall (and near wall) boundary by
conduction, convection and radiation are overall calculated.

-4-
Heat transfer rate through boundary of wall by conduction:
dT
Qcond kA (5)
ds
Where k is the average thermal conductivity of material of wall.
For walls which with external radiation boundary condition, heat transfer rate expresses as:

Qrad h f Tw T f qrad ext T4 Tw4 (6)


Where both ext (emissivity of external wall) and T (temperature of external domain) are required to be
defined manually in ANSYS FLUENT and Star-CCM+.
For walls which with boundary condition of combined external convection and radiation, equation of heat
transfer rate shows as:

Qmixed h f Tw T f qrad hext Text Tw ext T4 Tw4 (7)


Where hext is the external heat transfer coefficient that to be defined according to dry-bulb temperature of
outside environment.
For equation 6 and 7, Tw is the surface temperature of the wall, h f is the heat transfer coefficient of the
fluid side, is Stefan-Boltzmann constant.

2.2 Turbulence modeling


The Navier Stokes equations which arise from Newtons second law is to describe viscous flow in
multiply application. A suitable model for viscous stresses component ij and pressure term are introduced
to the conservation equations. As formed by Versteeg and Malalasekera (Versteeg & Malalasekera, 2007),
the Navier Stokes equations can be written for finite volume method (which will be discussed in section
2.5) in the most useful form as:
Du p
div gradu S Mx (8)
Dt x
For three dimensional fluid flow, the equation 8 also identically applies on y and z direction with velocity
vectors v and w .

2.2.1 Different choice of k- Model


Supplemented with turbulence model based on Navier Stokes equations which implemented in practical
CFD applications, the most appropriate viscous model for numerical simulation of high Reynold number
is k-epsilon (2eqn) viscous model (Calautit, et al., 2012). In ANSYS Fluent there has three transport
equations related to k-epsilon model, the standard k-epsilon model, RNG k model and the Realizable
k Model. As demonstrated by Tsan-Hsing and et al. (Shih, et al., 1994), realizable k Model
performs the best of all versions of k Model from several validations of flows with complex
secondary features and separated flows. In Star-CCM+, there has eight different transformation equations
for choice of k turbulence model. However, only standard k turbulence model provided by IES
VE Microflo. Therefore, both standard and realizable k model have been implemented during
numerical modeling in this project.
For standard k model, the turbulence kinetic energy k and its dissipation rate , can be calculated
from equations below (Fluent, 2006):

-5-
t k
k kui Gk Gb YM Sk (9)
t xi x j k x j
And

t 2
kui C1 Gk G3 Gb C2 S (10)
t xi x j x j k k
The term Gk as shown in above equations is the production of turbulence energy due to mean velocity
gradients which defined as:

u j
Gk ui'u 'j (11)
xi
The term Gb as shown represents production of turbulence energy due to buoyancy effect which defined
as:
t T
Gb gi (12)
Prt xi
The viscosity of turbulence flow, t is calculated by combination of k and as follow:

k2
t C (13)

And for constants in the equations 9 and 10 are listing as (Markatos , 2004):

C1 = 1.44, C2 =1.92, C =0.09, k =1.0 and =1.3

For realizable k model, the turbulence kinetic energy k and its dissipation rate , can be calculated
from equations below (Shih, et al., 1994):

t k
k ku j Gk Gb YM Sk (14)
t x j x j k x j
And

t 2
u j C S C C1 C3 Gb S (15)
t x j x j x j
1 2
k v k
Where,

k
C1 max 0.43, , S , S 2 Sij Sij (16)
5
Differ from standard k model, C is not constant any more, it need to be computed from:
1
C
kU * (17)
A0 AS

Where,
U * Sij Sij ij ij (18)
And
ij ij 2 ijkk ; ij ij ijk k ; A0 =4.04, AS 6 cos
Where,

-6-
1 u j ui

1 Sij S jk S kt
cos 1 6W , W , S Sij Sij , Sij (19)
3 S
3
2 xi x j
And for constants in the equations 14 and 15 are listing as (Fluent, 2006):
C1 = 1.44, C2 =1.9, k =1.0 and =1.2
The generation of the turbulence kinetic energy is calculated in the same way for both standard and
realizable k model except for value of constants, with the same Gk and Gb representation which
shows in equation 11 and 12.

2.2.2 Near Wall functions


Gradient of velocity changed in near-wall region is usually strong for no-slip walls. As shown in Figure 3,
according to mathematical and experiments analysis, near-wall region can be separated into two layers
which are laminar flow (linear sublayer) and turbulence flow (Versteeg & Malalasekera, 2007). Regions are
subdivided by point P shown in Figure 3.

Figure 3, Velocity distribution near a wall (Versteeg & Malalasekera, 2007)

When value of y is larger than 11.63 (above point P), mean velocity of turbulence flow is considered to
be in log-law region and can be yielded as:

ln Ey
1
U (20)

Where y+ shows as equation below:
yu *
y (21)
v
And temperature distribution for turbulence flow in near wall region is computed as (Launder & Spalding,
1973):


T T ,t u P T ,l (22)

T , t

Where in equation 20 and 21, is 0.4187, E is constant shear stress 9.793 for smooth walls, T ,l and
T ,t are laminar and turbulent Prandtl number.
In order to obtain the most accurate velocity profile in near-wall region, not only computational equations
but also intensive mesh with high equality are required to be applied during the simulation. Therefore,
inflation layers which can help to improve mesh quality will be discussed later in following chapters.

-7-
2.3 Meshing
2.3.1 Shapes of Cell
Mesh quality during pre-processing is very significant for CFD simulation results. Grid of simulation
object is generated upon the completed geometry. Both polygonal and polyhedral mesh is practicably
applied. As some simple examples list by (Versteeg & Malalasekera, 2007) and shown in Figure 4, different
shapes of control volumes are used for surface meshing (2D). And in volume meshing (3D), triangular or
quadrilateral surface elements helps to bind the 3D control volume.

Figure 4, Typical 2D control volume (Versteeg & Malalasekera, 2007).

2.3.2 Classification of Grids


Different types of grids implement on different shapes of geometry. There are three main classifications
of grid commonly used for meshing the object. Block-structured grid, unstructured grid and hybrid grid.
For block-structured grid, which have the most space efficient, the equations are simpler to be discretized
and it is very recommendable for solving complex geometries. As explained by Versteeg and Malalasekera
(Versteeg & Malalasekera, 2007), unstructured grid is being advantage that no implicit structure of co-
ordinate lines is created by the grid and this type of mesh is also simple to concentrated wherever
necessary. Therefore, time spent for mesh generation and mapping is much shorter through unstructured
grid. Appearances of block-structured and unstructured grid are shown in Figure 5.

Figure 5, Block-structured mesh (left) and Unstructured mesh (right) of aerofoil (Versteeg & Malalasekera,
2007)

-8-
A mixture of structured gird and unstructured grid can be classified as hybrid grid. In 2D, the mixture
contains of triangular and quadrilateral elements and in 3D the mixture combined tetrahedral and
hexahedral elements for calculation of fluid flow (Crippa, 2011). In Figure 6, comparison between coarse,
medium and fine hybrid grid of aerofile is shown from left to right.

Figure 6, Comparison between coarse, medium and fine hybrid grid.

Observed from figure above, region near the boundary layer have been generated to a high mesh quality
by creating structured grids. Within near wall regions the velocity changed very fast, for capture right
gradient of the change, inflation layers is required to be added near the boundary layers.
In this project, for achieving an accurate and time efficient meshing model, hybrid grids which combined
both advantages of structured and unstructured grids was selected to be implemented during pro-
processing.

2.3.3 Mesh Quality


As defined by user guide of ANSYS Fluent (Fluent, 2006), skewness is the different between shape of cell
and shape of an equilateral cell of equivalent volume. For instance, as illustrated by Versteeg and
Malalasekera (Versteeg & Malalasekera, 2007) shown in Figure 7, when the line PA and ab is not intersect at
the midpoint m of ab and the grid is non-orthogonal, lower accuracy of the simulation will be obtained
due to the increased skewness. Therefore, in order to get a more precise results, control of skewness
during meshing is very important.

Figure 7, Misalignment of midpoints for skewed grid.

Different cell quality can be indexed by different range of skewness value. According to reference given by
ANSYS, ranks of cell quality from degenerate to equilateral with corresponding range of skewness lists in
Table 2:

-9-
Table 2, Skewness range and cell quality (Fluent, 2006).

Skewness Cell Quality


1 degenerate
0.9 1 Bad(sliver)
0.75 0.9 poor
0.5 0.75 fair
0.25 0.5 good
0 0.25 excellent
0 equilateral

The other control index of mesh quality is ASPECT RATIO. Which is the ratio between the length of
longest edge and the length of the shortest edge. This control method of mesh quality is the only supplied
selection for IES VE - Microflo.

2.4 Solver
2.4.1 Finite Volume Method
Distinguish with finite element and finite difference method, Finite Volume Method (FVM) which is the
most widely applied for final solution method of computational fluid dynamic today. As described by
Charles (Hirsch, 2007) finite volume method is given to technique which is directly discretize integral
formulation of the conservation laws in physics space. Once the geometry was meshed and divided into
small cells which is also called control volume, the integrated governing equations of fluid flow within
computational domain are satisfied with conservation of each relevant properties for the control volume.
Distinct connections between the underlying physical conservation principle forms and the numerical
algorithm makes finite volume method be simpler than other methods (Versteeg & Malalasekera, 2007).
The conservation of a general flow variable within finite volume method can be expresses in words and
shows in equation in Figure 8 (Versteeg & Malalasekera, 2007).

Figure 8, Conservation of general flow variable within finite volume method (Versteeg & Malalasekera, 2007).

As shown in Figure 8, the total net change of the flow variable due to convection, diffusion and inside source
term is contained by change in the control volume with respect to time. In reality simulation, the involved
physical phenomena are usually non-linear and diverse, iterative solution approach is demanded (Cehlin,
2006).
Concerning the three CFD codes which are employed in this work, the Finite Volume Method (FVM) is
the common solver that applies for all three participated software.

-10-
2.4.2 Upwind scheme
Differ from central differencing scheme, the upwind differencing scheme has the capability to identify the
flow direction. As shown in figure below, the convective quantities are defined as ( ) f . The direction of
the fluid is flow from cell i to cell j (Cho, et al., 2010).

Figure 9, Evaluation of face value according to Upwind Scheme (Cho, et al., 2010).

For the first order upwind differencing scheme, value of convective qualities are equal to the value at the
previous node as shown in follow:

i if f 0
( ) f (23)
j if f 0
For the second order upwind differencing scheme, assumption of value for convection qualities is
replaced by the linear distribution. Higher accuracy is consequently obtained at the cell faces by
implemented Taylor series expansion to the cell centers (Barth & Jesperson, 1989):

i i dx fi if f 0
( ) f (24)
j j dx fj if f 0
Where the factor dxf is indicating the vector is from center of the cell to the center of the face.
In this project, second upwind differencing scheme was employed for spatial discretization of momentum,
turbulent kinetic energy, and turbulent dissipation rate and energy computation.

2.4.3 SIMPLE Scheme


SIMPLE scheme was selected for pressure-velocity coupling scheme in solution methods. SIMPLE is
represented for Semi-Implicit Method for Pressure-Linked Equations. The initial value of pressure and
velocity for calculation is guessed as p* and u* to initiate the calculation process (Versteeg & Malalasekera,
2007). To obtain the correct pressure and velocity field, the correction factor of pressure p and u are
introduced:

p new p* p p ' (25)


For a two-dimensional laminar steady state flow, the correct velocity unew and vnew can be improved from
the equations:

u new u* u u ' (26)

-11-
v new v* v v ' (27)
The defined as under-relaxation factor for iterated calculation. This factor which taken from 0 to 1
helps to improve the iterative process move forward while influence the stability of the fluid flow
calculation. If the under-relaxation factor equal to zero, there will be no correction applied to the
computation. If the under-relaxation factor equal to one, the guessed field of pressure and velocity is far
away from the final solution.
According to the diagram which was illustrated by Versteeg and Malalasekera (Versteeg & Malalasekera,
2007), the computed process of SIMPLE algorithm is shown as Figure 10,

Figure 10, Calculation process of SIMPLE Scheme (Versteeg & Malalasekera, 2007).

The initial guessed values were assumed and set manually during solution initialization. The more
realizable of the initial value, the faster of the convergence time cost. Each iteration takes from step 1 to
step 4, convergence absolute criteria for residual of each equations were set in monitor. When the
residuals did not achieve the criteria, value of convective qualities were replaced by the corrected value for
the next iteration until the criteria had been achieved.

-12-
3 Baseline model and Comparison between Software
In this chapter, baseline model would be initially built by ANSYS Fluent. According to ventilation system
had been implemented on ambulance hall of NKS (Nya Karolinska Solna) hospital, similar design concept
would be applied on the baseline model of the SS (Sdersjukhuset) ambulance hall. Baseline models
which set up by IES VE Microflo and Star CCM+ were also discussed later in this chapter.

3.1 Data of ventilation system for baseline model.


3.1.1 Design Concept
According to requirements of design which supplied by the constructor of NKS hospital, the minimum
indoor air temperature of an ambulance hall which located in Stockholm, Sweden is not allowed be lower
than 18 and the air flow level should not lower than 3 l/s-m2.
As classified by ASHRAE Handbook (ASHRAE, 1997), group A of diffuser type that is Diffusers
mounted in or near the ceiling that discharge air horizontally is very popular to be applied in commercial
implementations. Figure 11 gives air stream performance of group A when the air jet diffusers are installed
on the opposite walls. Diffusers in this project were also installed for providing colliding airstreams.

Figure 11, Air motion of Group A outlets (ASHRAE, 1997).

3.1.2 Parameter of supply air diffuser


The total area of the ambulance hall is 645.12 m2. Therefore, minimum total volumetric flow rate is
obtained as 1935.36 l/s. Length of the hall is around 31m, read from data sheet of jet nozzle diffuser
which obtained from supplier and listed in Appendix A, considering isothermal throw length (L0.2) of
each diffuser type, APL/N -250 with L0.2 equal to 15m was selected for air supply of ventilation system.
The volumetric flow rate of supply air from APL/N 250 is 250 l/s as list in Appendix A. In order to
reach the minimum total volumetric flow rate of the ambulance hall, 8 units of air diffuser required to be
installed consequently.

3.1.3 Parameter of Exhaust Grilles


The baseline model is setting as no natural ventilation and tailpipe emission involved, in accordance with
mass balance equation which is input equals to output, the total volumetric flow rate of exhaust grilles is
same to the value of supply air diffuser. According to data sheet of exhaust grilles from Appendix B, two
units of AGC - 800400 with qv equal to 1099 l/s have been chosen for installation.

-13-
3.2 Geometry
With removed internal rooms and corridor, the geometry of the ambulance hall for further simulation is
drew and shows in Figure 12. There are maximum of eight ambulance cars parking in the hall which
displayed as rectangular boxes in the room. Smaller squares that locating on both north and south face of
the room envelope are the eight supply air diffusers. Two larger rectangles that locating on the east face of
the room envelope are the exhaust grilles. The two faces which showing on the west wall are the gates of
the ambulance hall.

Figure 12, Geometry of the ambulance hall

Shape of the jet nozzle diffusers is designed as circle by manufacture as shown in Appendix A, but
because of limitation of IES VE Microflo, which cannot draw circle for representing air inlet in the
software, quadrate with same area is used for representing faces of supply air diffusers instead.
For 3D modeling of geometry of the ambulance hall, input dimensions which obtained from constructor
lists in Table 3.
Table 3, Input dimensions of geometry of the ambulance hall.

Ambulance Hall Length 31.407 m


Width 21.892 m
Height 3.8 m
Ambulance Car Length 5.477 m
Width 1.927 m
Height 2.5 m
Gate Width 4m
Heigth 3.1 m
Supply air diffuser (Air Inlet) Length 0.224 m
Width 0.224 m
Height of installed positions 3m
above the floor
Exhaust Grille (Air Outlet) Length 0.776 m
Width 0.376 m
Height of installed positions 3m
above the floor

Different geometry modelers is bound with each CFD software. For 3D modeling tools which had been
employed by author to build the same geometric model of the ambulance hall, grade level of modeling
efficiency according to the authors using experience is shown as in Table 4:

-14-
Table 4, Performance of 3D modeling for different tools.

3D Modeling
ANSYS Fluent IES VE - Microflo Star CCM+
Tools DesigeModeller SpaceClaim ModelIT SketchUp 3D-CAD SpaceClaim
(Default) (collaborate) (Default) (Plug-In) (Default) (export .stp
file )
Manipulate 3 5 1 4 2 5
Difficulty of
Interface
Degree of 3 5 1 4 2 5
precision
Time 3 4 1 5 2 4
Spending
In Table 4, software performance is divided into 5 level. 3D modeling tool with the best efficiency and
performance gained 5 point, on the contrary, tools with less satisfaction are gained lower points. From
results of comparison, the geometry modeling tools of ANSYS has the capability to performance easier,
more intuitively and faster than the rest. Since the main functions of IES VE is to establish energy
performance for buildings, ModelIT is easier to be used for build building block without complex
geometry.
During simulation of baseline models, both ANSYS Fluent and Star CCM+ shared same geometry file
which built by SpaceClaim, and SketchUp 2014 was employed for 3D modeling to IES VE Microflo.

3.3 Meshing
3.3.1 Meshing Independency
Before continue with different circumstances of the ambulance hall, meshing independency study of
baseline scenario is strongly recommended to be implemented for obtain a more confident simulated
results. Therefore, two simulations of case 1.1, which is the baseline model modeled by ANSYS Fluent,
were generated as different number of cells. One with 380587 cell elements, the other one has 505743 cell
elements.
The following two groups of figures are shown face sizing for boundary face of supply air diffuser (Air
Inlet) and Exhaust Grilles (Air Outlet). In the baseline cases, four places were applied as specified face
sizing, where are air inlet faces, air outlet faces, exterior walls and the two gates. Since air temperature and
velocity are changed significantly at these locations, quality of mesh at these locations required higher than
the rest.

Figure 13 Face sizing for air inlet (Left: Element size is 0.05m; Right: Element size is 0.03m)

-15-
Figure 14, Face sizing for air outlet (Left: Element size is 0.1m; Right: Element size is 0.05m)

After both simulation completed, results of mess flow rate and total heat transfer rate of each boundary
face were computed and list in Table 5.
Table 5, Comparison of Mass flow rate and Total heat transfer rate between the two meshing cases

Model with 380587 cells Model with 505743 cells


Air Inlets 2.449327 2.449327
Mass Flow Air Outlets -2.44993 -2.44925
Rate (kg/s) Net Results 1.73*10-5 7.22*10-5
Ambulance Car 0 0
Exterior wall -1961 -1957
Total Heat Gates -1001 -997
Transfer Rate Air Inlet -13285 -13285
(W) Interior wall -52 -43
Air Outlet 16258 16186
Net Results -41 -97
Percentage 0.25% 0.6%

Results of indoor air flow velocity (vector) also shown in Figure 3, for helping to verify the simulation results
are independent from current degree of mesh quality.

Figure 15, Velocity distribution for the two different meshing cases.

Both results from Table 5 and in Figure 15 have illustrated there has only extremely small differences between
the two meshing cases. The simulation results are independent from mesh quality at this degree.

-16-
3.3.2 Meshing Method
Mesh from ANSYS workbench was employed for meshing to case of ANSYS Fluent and Star-CCM+
with its efficient and high-quality characteristics. Meanwhile the meshing tool from Star-CCM+ also
performed with eligible meshing, but the generation period required more times. IESVE Microflo has its
own meshing tool which called CFD Grid. In this project, default grid spacing which set as 0.13m for
global sizing was applied. Figure 16 shows the generated mesh of the ambulance hall in IESVE Microflo,
where the right figure is zoom-in of the top corner of the left figure.

Figure 16, Generated mesh of the ambulance hall in IESVE Microflo.

Not only global sizing can be restricted in ANSYS mesh, but size of face and inflation can be specified. In
the areas with large changing of fluid properties, the higher of the mesh quality, the more accurate of the
obtained results. In ANSYS mesh, intensive mesh at areas of air inlets, air outlets, exterior walls, gates and
building envelope have been generated since both air temperature and velocity changed significant at these
places. The meshing outcome produced by ANSYS mesh of the ambulance hall express as figures below.

Figure 17, Generated mesh of the ambulance hall in ANSYS mesh.

(a) (b)

-17-
(c) (d)
Figure 18, Section plane of (a) Air Inlet; (b) Air Outlet; (c) Exterior Wall; (d) Internal space

The statistics of mesh given in both meshing tools are listed in Table 6, because it is the educational version
of ANSYS, the maximum number of cells that allowed to be generated is 512000.
Table 6, Statistics of mesh which generated from ANSYS mesh and IES VE CFD Grid.

ANSYS mesh IESVE Microflo - CFD Grid


Number of cells 505743 1130304
Max. Aspect Ratio 85:1 25:1
Max. Skewness 0.88 Not be provide by the software
The maximum aspect ratio for ANSYS mesh case is 85:1. Meanwhile as shown in Figure 19, aspect ratio of
the most elements are between 1.17 to 12.5 and rarely aspect ratio of elements are higher than 50.

Figure 19, Mesh metrics control of ANSYS mesh (Left: Skewness; Right: Aspect Ratio)

Another advantage of ANSYS mesh compared with IES VE Microflo (CFD Grid) is Mesh metrics
control. Since with clicking bar of elements which has poor mesh quality, the elements can be highlighted
apparently at the geometry. With this function, quality of the elements can be improved directly.
Table 7, Performance of meshing for the three software.

Meshing
ANSYS Mesh Star CCM+ IESVE Microflo
Manipulate Difficulty of Complicate Intermediate Simple
Interface
Degree of precision High Intermediate Low
Time Spending Intermediate Slow Fast
As shown in Table 7, comparison between meshing of the three software has been made. IESVE Microflo
costs the least times during generation of mesh, meanwhile mesh quality generated from Microflo is much
poorer than the mesh which generated by ANSYS. An advantage of Star-CCM+ meshing is this software
can generate polyhedral mesh which improves mesh quality significant.

-18-
3.4 Numerical Setup
Selection of simulation models and boundary condition setup with accurate values is very important for
pro-processing. In this section, the pro-processing set will be discussed for the three CFD software.
Although the sequence of setting is different in different software, values of boundary conditions is the
same.

3.4.1 Selection of simulation models


In general setting, the gravitational acceleration is -9.81m/s2 for all cases. Cases in this project are
simulated as steady state thermal analysis. Energy models were turned on for all cases since temperature
distribution is act as a very important factors for consideration of indoor thermal comfort. The realizable
k-epsilon model was selected for viscous model in ANSYS Fluent and Star-CCM+. However, in IESVE
Microflo only standard k-epsilom model and model with Constant effective viscosity are available for
selection of turbulence model. Therefore, standard model was setting in IESVE Microflo. Difference
between these two models have been discussed in section 2.2.1. The near wall treatment with standard
wall function was applied for case of ANSYS Fluent and two-layer all y+ wall treatment was selected for
case of Star-CCM+. Full buoyancy effects have been choose for additional option of viscous model, since
the gravity force and non-isothermal flow has effect to generation of turbulence kinetic energy because of
buoyancy effect.
Surface to surface radiation model was selected in ANSYS Fluent and Star CCM+ for computing total
heat transfer of exterior wall, interior walls and the two gates. In setting of boundary thermal condition,
radiation was calculated combined with conduction and convection to obtain heat transfer through
exterior walls and gates of the ambulance. However, in IESVE Microflo only temperature is used to
define thermal condition of the building envelopes.

3.4.2 Boundary conditions


In the baseline model case 1.1 and case 1.2 which are simulated by ANSYS Fluent and Star CCM+,
there has six defined zone treated as boundary of the model. Which are boundary of ambulance cars, air
inlets, air outlets, exterior walls, interior walls and gates. Since the ambulance cars are parking in the
ambulance hall, no heat transfer occurred. The heat flux for boundary conditions of the cars is zero.
Type of boundary condition for the 8 air inlets were set as velocity-inlet. The direction of the air supply to
the domain is air flow normal to the wall. According to Appendix A, the area of each air supply diffuser is
50086 mm2 and the volumetric flow rate is 250 l/s. Hence the velocity magnitude of air inlet is figured out
as 4.99 m/s. Pressure-outlet was applied for type of boundary condition of air outlet. -10Pa was set as
gauge pressure for each air exhaust unit based on appendix B. Backflow total temperature of air outlet is
same as the minimum indoor air temperature 18.
The U values of exterior wall and gates of the ambulance hall are assumed according to the general value
of commercial building. U value of exterior wall is assumed as 0.5 W/m2K while U value of gate is 1.5
W/m2K. The supply air temperature of air inlet is calculated upon energy balance. In order to maintain
the indoor air temperature higher than 18, Qloss through the exterior wall and the two gates is equal to
Qsupply to the ambulance hall.

Q1 U * A *(Tindoor Tamb ) (28)


Q2 *V*Cp*(Tsupply Tindoor ) (29)
According to equation 23, heat loss through the exterior walls shows as equation30.

Qwall 0.5W / m2 K *133.34m2 *(18 (18)) K 2400.12W (30)


Where the total area of the exterior walls is 133.34 m2.
The heat loss through the gates shows as equation 31.

-19-
Qgate 1.5W / m 2 K * 25.98m 2 *(18 ( 18)) K 1402.92W (31)
Where the total area of the two gates are 25.98m2.
Hence, the total heat loss of the ambulance hall for indoor to ambient environment shows as equation 32.

QTotal Qwall Qgate 2400.12W 1402.92W 3803.04W (32)


Finally, the supply temperature of air inlet is computed according to equation 24 shows as equation 33.

3803.04W 1.225kg / m3 * 2m3 / s *1.0063*(Tsupply 18)


(33)
Tsupply 19.543 .
In summary, the boundary conditions set up in ANSYS Fluent and Star-CCM+ are shown as in Table 8.
Table 8, Boundary Conditions set up in ANSYS Fluent and Star - CCM+.

Air Inlet (Velocity Inlet)


Velocity Specification Method Magnitude, Normal to Boundary
Velocity Magnitude (m/s) 4.99
Turbulent Intensity (%) 5
Turbulent Viscosity Ratio 5
Temperature (C) 19.543
Air Outlet (Pressure-Outlet)
Gauge Pressure (Pascal) -10
Backflow Direction Specification Method Normal to Boundary
Backflow Total Temperature (C) 18
Exterior Walls (Wall)
Wall Motion Stationary Wall
Thermal Conditions Mixed
External Heat Transfer Coefficient (w/m2-k) 25
Free Stream Temperature (C) -18
External Emissivity 0.9
External Radiation Temperature (C) -18
Internal Emissivity 0.9
Wall Thickness (m) 0.4
S2S Faces per Surface Cluster 10
U value 0.5 W/m2K
Interior Walls(Wall)
Wall Motion Stationary Wall
Thermal Conditions Radiation
External Emissivity 0.9
External Radiation Temperature (C) 18
Internal Emissivity 0.9
Wall Thickness(m) 0.2
S2S Faces per Surface Cluster 10
Gate (Wall)
Thermal Conditions Mixed
External Heat Transfer Coefficient (w/m2-k) 25
Free Stream Temperature (C) -18
External Emissivity 0.9
External Radiation Temperature (C) -18
Internal Emissivity 0.9
Thickness (m) 0.2
S2S Faces per Surface Cluster 10
U value 1.5W/m2K
Ambulance Cars(Wall)
Thermal Conditions Heat Flux
Heat Flux (w/m2) 0

-20-
Differ from thermal properties setting in ANSYS Fluent, thermal resistance (R-value) of exterior walls and
gates were implied in Star-CCM+ instead of thermal conductivity (U-value). Therefore, thermal resistance
2 m2K/W of exterior walls and 0.67 m2K/W of gates were input for calculation of heat loss through the
building envelope of the ambulance hall.
The boundary condition setting process is completely different in IESVE Microflo. The thermal
properties of building envelopes were edited in IESVE ModelBuilder. It is another application which
included in IESVE workbench. The U-value of building envelopes were set up with building geometry
simultaneously in IESVE ModelIT. After modification in APlocate, data of weather for the building
location was downloaded from ASHRAE design weather database v4.0. Therefore, the annual dry-bulb
and wet-bulb temperature of Stockholm, where the ambulance hall located, had been obtained as outdoor
temperature for computing heat transfer through the walls and gates.
For drawing of boundary conditions of air inlet and outlet, only shapes of rectangular and polygonal are
validate for add these kind of boundaries after complication of building geometry. The supply air with
velocity inlet and exhaust air with pressure outlet were applied in IESVE Microflo which all the values are
same as setting in the previous two software.
The thermal conditions of exterior walls, interior walls and gates are selected with Mixed and Radiation in
ANSYS Fluent and Star-CCM+ as shown in Table 8, but considering thermal conditions of building
envelopes in IESVE Microflo only Default Surface Temperature (C) is available for the heat loss
calculation. Here in the baseline case 1.3 which the model built in Microflo, 18 as surface temperature
was set in CFD settings.

3.4.3 Solution Control


As discussed in section 2.4, SIMPLE scheme as pressure-velocity coupling scheme was selected for
solution method in ANSYS Fluent. With higher order accuracy, second order upwind scheme was
employed for spatial discretization of momentum, turbulent kinetic energy, and turbulent dissipation rate
and energy of the indoor fluid in ANSYS FLUENT. Same as coupled model in Fluent, IESVE Microflo is
also implied pressure-velocity coupled model of fluid flow.
Unlike the other two software, case 1.2 which simulated in Star CCM+ was used segregated flow. Since
for most of cases which does not have problem of supersonic flow, segregated flow can saved more
computational time and memories, but on contrary it might be unstable. Combined with segregated flow
model, segregated fluid temperature model which solves energy equation with temperature as the variable
(CD-adapco, 2013).
In summary, solution control of the three software is illustrated as in Table 9. The under-relaxation factors
( ) of the convective properties also shows in the table. Because of educational version of ANSYS
Fluent, mesh quality of the case 1.1 did not reached the optimized. Hence, in order to converge the
residual with less iteration, lower under-relaxation factors had been set.

-21-
Table 9, Solution control for the three software.

ANSYS Fluent Star-CCM+ IESVE Microflo


Solution Methods Pressure-Velocity Segregated Flow Model Coupled Flow Model
Coupled Flow
(SIMPLE Scheme)
Discretization Scheme Upwind Second Order Segregated Temperature Upwind First Order
of Pressure 0.3 0.3 -
of Velocity - 0.7 0.1
of Density 1 - -
of Momentum 0.7 - -
of Turbulent Kinetic 0.2 0.8 0.05
Energy
of Turbulent 0.2 0.8 0.05
Dissipation Rate
of Turbulent 0.4 1 0.05
Viscosity
of Energy 0.9 0.9 1
The convergence absolute criteria of residual for case 1.1 in ANSYS Fluent is 1*10-4 for x-/y-/z-velocity.
And for the rest equations like continuity, energy, k and epsilon, 1*10-3 was set as residual convergence
criteria. For case 1.2 in Star-CCM+ and case 1.3 in IESVE Microflo, 1*10-4 was applied as the criteria.
Table 10, Performance of numerical setup for the three software.

Numerical Setup
ANSYS Fluent Star CCM+ IESVE Microflo
Manipulate Difficulty of Complicate Intermediate Simple
Interface
Degree of precision High Intermediate Low

Compare with the other two CFD simulation software, ANSYS Fluent provides more selections of
schemes to adapt computations of variety fluid dynamics with higher precision. On contrary, IESVE
Microflo was specified designed to simulate environment of building for both internal and external
analysis with lower precision.

-22-
3.5 Simulation results
Baseline Case 1.1 and 1.2 which operated in ANSYS Fluent and Star-CCM+ have achieved the
convergence absolute criteria of residual. For case 1.3 which operated in IESVE Microflo, the
convergence absolute criteria of residual did not achieved below 1*10-4. However, according to cell
monitor at point (x=4.258m, y=15.702m, z=1.9m), results of each convective properties were turned into
steady state as shown in Figure 20. Therefore, result of simulation for case 1.3 with lower accuracy than the
others also be validated for practical application.

Figure 20, Cell Monitor of point in Case 1.3.

3.5.1 Assessment of thermal comfort in an arbitrary point.


According to ASHREA standard 55-1992 (McQuiston, et al., 2005), Predicated mean vote (PMV) is used
as thermal comfort index for assess the indoor environment thermal conditions. The scale of PMV is list
in Table 11.
Table 11, Thermal sensation scale for PMV Method.

Value +3 +2 +1 0 -1 -2 -3
Thermal hot warm slightly neutral slightly cool cold
Sensation warm cool
The PPD index is predicted percent dissatisfied which induced by PMV and illustrated from ISO Standard
7730 (ISO, 1994) as shown in Figure 21.

Figure 21, PPD as a function of PMV (ISO, 1994).

The author picked an arbitrary point (x=10m, y=15m, z=1.5m, in the middle of the domain) from the
CFD simulated result of the ambulance hall to evaluate if the indoor thermal conditions have been
achieved thermal comfort standard which required by ASHRAE Standard 55-2010. An online thermal
comfort evaluation tool which designed by Hoyt Tyler and et al. (Tyler, et al., 2013) has been employed.

-23-
Before calculating the PMV and PPD, several parameters have to be measured from the simulation results
of case 1.1. The air temperature (Ta) of the selected point is 18.47, the global temperature (Tg) is 18.62
, air flow velocity is 0.46m/s. Since the case is in winter, lower value 30% of humidity was assumed for
humidity of the indoor air. The metabolic rate of occupants is assumed as walking inside with 1.7 met.
The clothes insulation is assumed as 1.5 clo for occupants in the ambulance hall in winter. The mean
radiant temperature (Tr) has to be determined.

T Ta
1/2
4
Tmrt Tg4 CV g
(34)

Where, C in SI Unit is 0.247 109 , Tmrt is mean radiant temperature, and V is air velocity.

Calculated from equation 30, the mean radiant temperature at the selected point is 18.87.

Figure 22, Thermal comfort zone display in Psychronmetric chart.

After inputting the measured parameters combined with the calculated mean radiant temperature to the
online thermal comfort tool (Tyler, et al., 2013), the red point as shown in Figure 22 indicate the selected
point has satisfied the thermal comfort standard of ASHRAE 55-2010. The PMV value is 0.06 which is
neutral thermal sensation. The PPD value of the selected point is 5% which represents the occupants has
the lowest dissatisfied percentage of the indoor thermal conditions.

3.5.2 Velocity Distribution


Indoor air distribution at velocity fluid will be shown in this section. Planes at height equal to 3m and 1m
are the two main field of velocity distribution of the indoor air. Where at 3m height, supply air diffusers
and exhaust grilles were installed. Zone lower than 1.8m is the movement area of the most occupants,
therefore, height at 1m of the plane will be implemented for assessing the indoor environment of thermal
comfort.

3.5.2.1 Case 1.1 in ANSYS Fluent.


reflects the vectors of air flow at the plane h equal to 3m. As shown in the figure, air supplied from
Figure 23
opposite walls and intersected in the center of the room. A swirl flow produced at the center area and air
finally running out to the two exhaust grilles with low speed at the indoor side.
Range of air velocity around the swirl flow in the center area is from 0 to 0.7m/s. The inlet velocity is 4.99
m/s as supplied by the 8 air diffusers and the outlet velocity computed after the simulation and showed
around 4.5 m/s. Air velocity of the area near the gates and the interior is very small.

-24-
Figure 23, Vector of velocity distribution (h=3m) of case 1.1.

The velocity magnitude between 0 to 5.02 m/s and 0 to 1 m/s at h equal to 3m are shown in Figure 24.
Flows represented by red color in Figure 24 (right) means the velocity magnitudes are not lower than 1 m/s.

Figure 24, Velocity Magnitude (h=3m) of case 1.1. (Left: 0 to 5.02m/s, Right: 0 to 1 m/s)

Plane at height of 1m represent the occupants zone in this project. Figure below is the velocity vector of
air flow at the plane.

Figure 25, Vector of Velocity distribution (h=1m) of case 1.1.

-25-
As shown in Figure 25, local velocity range is between 0 to 0.51m/s. The swirl flow in the center area still
exists at the height of 1m, however compared with velocity at h equal to 3m, the velocity magnitude
decreased from 0.7m/s to 0.51m/s. Figure 26 are the zoomed-in views of Figure 25, the left view is showed
area near the gate and the right view shows fluid flow performance for one of corner areas.

Figure 26, Zoomed-in views of velocity distribution at plant (h=1m).s

Ventilation performance near the areas of gate and corners of the ambulance hall are displayed with poor
qualities according to Figure 25 and Figure 26. Since occupants are rarely stay at the corner areas, unsatisfied
ventilation at the corner areas slightly influents the overall thermal comfort of the indoor domain. On
contrary for area near the gates, performance of ventilation is required to be improved further since the
area is the main part which need to be taken into account for the integrated thermal comfort of the indoor
domain.

3.5.2.2 Case 1.2 in Star-CCM+.


Same as the previous section, velocity distribution at the two plane (h=3m and h=1m) from simulation
results of Star-CCM+ shows in the follow.
shows the velocity distribution path and magnitude of the air flow at height equal to 3m. Read
Figure 27
from the figure, range of local velocity is from 0 to 5.1766m/s.

Figure 27, Vector of velocity distribution (h=3m) of case 1.2.

-26-
At the height of 1m, the changing range of velocity is between 0m/s to 0.596m/s.

Figure 28, Vector of velocity distribution (h=1m) of case 1.2.

Compared between Figure 25 and Figure 28, the output results of velocity distribution which simulated from
ANSYS Fluent and Star-CCM+ are similarity for both air flow path and air velocity magnitude.

3.5.2.3 Case 1.3 in IESVE Microflo.


Velocity distribution path which shows in Microflo Viewer of case 1.3 is performed slightly different
compared with the previous two cases. Vector and contour of the flow velocity distribution at the planes
(h=1m and h=3m) are displayed in Figure 29.

(a)Velocity vector, h=3m (b) Velocity contour, h=3m

(c) Velocity vector, h=1m (d) Velocity Contour, h=1m


Figure 29, Vector and contour of velocity distribution (h=3m and h=1m) of case 1.3.

-27-
Differ from case 1.1 and 1.2, case 1.3 has performed local mean age (LMA) of air which provided by
Microflo Viewer directly. As discussed by Hach and Katoh (Hach & Katoh , 2010), the indicator of LMA
is generally defined as time required for the air which flow started from air supply diffuser to the specific
areas. Computation of LMA base on the equation as follow:
Ci t
i 1 dt (35)
0
Ci
Where,

i -the local mean age of air (s).

Ci t , Ci - the contaminant concentration at sampling position i at time t at infinite time. (kg/kg)


t -time(s).
The output figure of LMA at height equal to 1m is shown as in Figure 30, LMA values of the red areas are
around 25-28 min, and value of the blue areas are approximate 18-20 min. which demonstrated the blue
areas have better ventilation performance than the red areas which near the gates of the ambulance hall.

Figure 30, Local mean age of air (h=1m) of case 1.3.

In summary, all simulated results of velocity distribution from the three cases have reflected the weak
locations of ventilation performance. However, case 1.1 provided the most detailed and accurate data of
velocity distribution. Case 1.3 with LMA distribution performance has given the directly and visually
understanding of contaminant concentration in the room.

3.5.3 Temperature Distribution


As required in chapter 3, the minimum air temperature of the indoor environment is 18. Simulated
results of temperature distribution from the three baseline cases are given in the following sections.

-28-
3.5.3.1 Case 1.1 in ANSYS Fluent.
Profiles of air temperature distribution for baseline case 1.1 are shown as followed. In Figure 31, range of
temperature is specified within local temperature at the plane (h=1m). The highest temperature is 18.59
and the lowest temperature is 2.57. There is no big variation shown in Figure 31 since the range of
temperature is relatively larger than the temperature changing at the plane.

Figure 31, Temperature distribution (h=1m, local temperature).

After specifying the appeared lowest temperature to 18 and the highest temperature contain as 18.59
in Figure 32. Temperature distribution can be showed evidently. Locations rendered by blue are the areas
with local temperature lower than 18. Heat losses through the exterior walls and gates conclusively
influents gradient of temperature distribution. The other factor which affects temperature distribution is
due to installed position of supply air diffusers. Since the supply air with temperature of 19.543
performed heating effect. However being proportional to the ventilation performance in the areas near the
gates (as discussed in section 3.5.2.), heating effects by the ventilation system performs poor as well.

Figure 32, Temperature distribution (h=1m, specified temperature).

In Figure 33, isosurface with constant temperature equal to 18 has been introduced. The legend view
expresses global temperature in the ambulance hall. The highest temperature is 19.54 as same as the
supplied air temperature. According to the legend view, orange represent temperature equal to 18 .
Hence, volume areas within the orange isosurface indicates air temperature is larger than 18 which
corresponded to the required criteria of indoor temperature.

-29-
Figure 33, Temperature distribution (h=1m, global temperature) with isosurface.

In Figure 34, vertical views of temperature distribution have been built. The range of temperature changing
was specified between 18C to 18.7C for all planes. The temperature difference on vertical is not larger
than 1C. ASHRAE (ASHRAE, 1997) has defined when the air temperature difference between humans
head and feet is lower than 1C, the dissatisfied percentage of thermal comfort is smaller than 1%.

Figure 34, Temperature distribution (Left: x=3.6m, 11m and 18.3m; Right: y=10.3m, 15.5m and 21m).

In Figure 35, temperature distribution for the envelope of the ambulance hall has been showed. Heat loss
through the two gates is the largest. Surface temperature of the gates is around 2.06C to 4C. For the
exterior walls, surface temperature is between 8.37C to 15.09C. Surface temperature for the interior
walls is around 17.5C to 19.27C.

Figure 35, Temperature distribution on envelop of ambulance hall.

-30-
3.5.3.2 Case 1.2 in Star-CCM+.
As shown in Figure 36 (a) and (b), gradient of temperature distribution for simulated results of case 1.2 is
similar as in case 1.1. The mean indoor air temperature expressed by case 1.2 at height equal to 1m is
around 18.5C. Temperature increased from the exterior walls to interior walls. In the profiles with
specified temperatures, regions with temperature lower than 18C have been removed.

(a) Local temperature (h=1m) (b) Specified temperature (h=1m)

(c) Specified temperature (y=3m, 10.5m and 15.5m) (d) Specified temperature (x=3.7m, 11m, 18.3m)
Figure 36, Temperature distribution of case 1.2.

Compared with Figure 34, temperature distribution on vertical planes in Figure 36 (c) and (d) shows the
changing is essentially similar between the two cases.

3.5.3.3 Case 1.3 in IESVE Microflo.


In Microflo viewer of IESVE, the maximum and minimum value of temperature in the simulated domain
does not given by the program automatically. It requires manually setting for possible temperature range.
The temperature distribution is also inconspicuous.
As shown in Figure 37 (a) and (b), two expression method were provided by Microflo Viewer of temperature
contour distribution. The temperature range which specified by the author is from 17.5C to 18.5C. The
main regions on the plane (h=1m) shows temperature changed between 18.14C to 18.5C.
In Figure 37 (c) and (d), temperature distribution on vertical planes is mainly same as the other two cases.
However, compared with Figure 34 and Figure 36 the temperature changing is not obviously as the other two
cases.

-31-
(a) Filled temperature contour (b) Temperature contour

(c) Temperature (y=3m, 10.5m and 15.5m) (d) Temperature(x=3.7m, 11m, 18.3m)
Figure 37, Temperature distribution of case 1.3.

Conclusively, profiles of temperature distribution from the three cases are significantly help the author to
assess the thermal comfort of the indoor environment conditions. More beneficially, code of CFD Post
which provided by ANSYS has capability to supply precise point value of any variable at any location
within the simulated domain (included temperature value), but CFD viewers of Star-CCM+ and Microflo
only can obtain the temperature value of the selected point from approximately measured on the
temperature distribution profiles.
Post of CFD results is very important for supplying the engineers an explicit and clear understanding of
the fluid flow behaviors. In summary, comparison between the CFD results views of the three CFD codes
are illustrated in Table 12. The comprehensive functions of visualization in CFD post of ANSYS is the most
recommended tool for presenting the simulation results.
Table 12, Simulation results of the three software.

Simulation Results
ANSYS Fluent Star CCM+ IESVE Microflo
(CFD Post) (Microflo Viewer)
Manipulate Difficulty of Intermediate Complicate Simple
Interface
Functions Comprehensive Intermediate Basic
Degree of precision High Intermediate Low

-32-
4 Ventilation Performance in Different Situations
After comparison between the three alternative CFD codes, ANSYS Fluent with the best performance
was selected for further simulations of the ambulance hall in different situations of indoor environment.
Based on the baseline model case 1.1, five more simulation models were implemented in this chapter. As
listed in Table 1, numerical simulations of case 2 with improved ventilation system, case3 with polluted
emission from tailpipes of the ambulance cars and case 4.1-4.3 which introduced natural ventilations
through the gates will be present. All the geometries of the cases in this chapter were created by
SpaceClaim.

4.1 Geometry
All the geometry model of the five cases were modified and built upon the 3D model of baseline case.
Geometries which applied for case 4.1, case 4.2 and case 4.3 is identical since the only difference between
these three cases is changing in boundary conditions.

4.1.1 Case 2: Improved ventilation system.


Due to the big swirl flow produced in the center of the ambulance hall, the author originally intended to
eliminate it by implementing more exhaust grilles to the model. Therefore, differ from the baseline model
with 2 exhaust grilles as air outlets, four exhaust grilles as air flow outlets have been implemented to case 2.
Considering mass flow balance of the model, type of exhaust grille is required to be changed as well.
Different between the two types of exhaust grilles according to Appendix B which used in case 1.1 and
case 2 are listed in Table 13.
Table 13, Different between the two types of exhaust grilles in two cases.

Case code Case 1.1 (2 air outlets) Case 2 (4 air outlets)


Exhaust Grilles Type AGC 800*400 AGC 600*300
Volumetric flow rate of one unit 1099 453
(l/s)
Installed number 2 4
Ptot (Pa) -10 -6
LpA 35 dB(A) 25 dB(A)
As shown in Figure 38, 4 air flow outlets installed on the wall which is opposite to the wall with gates and
indicated with color pink. For the rest part of the geometry is same as in case 1.1.

Figure 38, Geometry of case 2 with 4 exhaust grilles.

-33-
4.1.2 Case 3: Polluted emission from tailpipes of the ambulance cars.
Built geometry of case 3 with polluted emission from tailpipes of the 8 ambulance cars is show in Figure 39.
2
The area of each tailpipe is 0.0036 m . The height of the tailpipe is 0.4m over the ground. In this case, the
8 ambulance cars were assumed idling at steady state. Hence, emissions are produced by the entire 8 cars
continuously.

Figure 39, Geometry of case 3 with tailpipe emission (Left: whole room; Right: zoomed-in to the tailpipe)

4.1.3 Case 4.1-4.3: With opened gates and installed air curtains.
Even in winter with cold outdoor temperature, sometimes gates of the ambulance hall have to be keep
opened during the daytime. Consideration of natural ventilation through the opened gates with installation
of air curtains are discussed in case 4.1 to case 4.3.
Configuration of the air curtain is obtained from the product datasheet. As shown in Figure 40, the lower
arrow in the right figure is the heated air flow inlet from the air curtain to the room. The higher arrow
indicate air flow back to the air curtain (air outlet to the air curtain).

Figure 40, Configuration of air curtain which installed in case 4.1-4.3.

In this cases, outside domain need to be taken into consideration as well. Outside wind with higher flow
speed and much lower temperature affected the inside thermal condition significantly. Additional
parameters of generated geometry for case 4.1 to 4.3 list in Table 14.
Table 14, Additional parameters of geometry for case 4.1 to 4.3.

Area of air inlet from air curtain. 0.0677 m2


Air Curtain Area of air outlet to air curtain. 0.2191 m2
Number of installed air curtain. 4
Door Height 3.1m
Width 4m
Length 16m
Outside Domain Width 8m
Height 8m

-34-
Geometry of case 4.1 to 4.3 were built base on the baseline 3D model. As shown in Figure 41, the blue box
indicate the outside domain and air curtain over the two gates. The yellow box represents the 8 ambulance
cars without tailpipe emission.

Figure 41, Geometry of case 4.1 - 4.3.

(a)Wind Inlet (Blue face). (b)Pressure Outlets or Symmetry (Blue faces)

(c)Heated air inlet from air curtain (Red faces) (d) Air outlet to air curtain (yellow faces)
Figure 42, Zoomed-in views of geometry for case 4.1-4.3.

-35-
Wind inlet with wind velocity or pressure of the outside domain is shown in Figure 42 (a). The red faces in
Figure 42 (c) indicated areas of air inlets from air curtains. Height of the air inlets equals to the height of the
gates. Faces of gates have been removed from these cases, therefore, as shown the outside domain is
connected directly to the inside domain of the ambulance hall. The yellow faces in Figure 42(d) represent
areas of air outlets to air curtains.

4.2 Meshing
Since no big geometry changed in case 2 and case 3 compared with baseline model. Set up of meshing in
these two cases is similar as meshing in case 1.1 as discussed in previous section 3.3.2. Meshing quality of
model in case 4.1-4.3 has been modified because of the additional patterns. In Figure 43, hexahedron mesh
was implemented for outside domain which has helped to reduce total element numbers and improve
total mesh quality. The right figure is the view on section plane. Inflation layers near walls and intensive
meshing at air outlet and boundary of air curtain can be seen in the section cut view.

Figure 43, Meshing of case 4.1-4.3 (Left: Global: Right: Section cut view).

4.3 Boundary Conditions Setup


In order to obtain correct simulation results from CFD modeling, boundary conditions have to be set in
accordance with the physical conditions of the subject. In this section, boundary conditions setup of
model in case 2, case 3, case 4.1 to case 4.3 will be introduced.

4.3.1 Case 2: Improved ventilation system.


According to boundary conditions of baseline model which were listed in Table 8, the only changed factor is
the boundary conditions of air outlets. As shown in Table 13, since the installed number of exhaust grilles is
increased from 2 to 4, total pressure drop of the air outlet is decrease from 10P to 6Pa. For the rest
boundary conditions of air inlets, exterior walls, interior walls and ambulance cars are maintained same as
list in Table 8.

4.3.2 Case 3: Polluted emission from tailpipes of the ambulance cars.


Two types of contaminant gas concentration which exhaust from tailpipe of cars have to be controls in
parking garage. Describe by H. Xue and J.C.Ho (Xue & Ho, 2000), carbon monoxide due to incomplete
combustion of cars engines is one of critical contaminant when the cars is parking at idling state. The

-36-
other contaminant gas influents indoor air quality is carbon dioxide concentration. Hence, both CO and
CO2 concentration level are dominated by requirement of vehicle exhaust in ASHRAE Standard.
For ambulance cars at idling state or low speed state, the exhaust temperature of the gas from tailpipe is
reached to 35C in 10 minutes. The emit velocity of the exhaust gas as measured by U. Uhrner and et al.
(Uhrner, et al., 2007) is 3.84 m/s. Mass fraction of species contained by the exhaust gas from tailpipe
when the car is idling are listed in Table 15 according to description by SUN Maskin (Maskin, 2014) .
Table 15, Input parameters for boundary conditions of tailpipes.

Velocity (Exhaust to the ambulance hall ) 3.84 m/s


Temperature 35 C
CO2 13%
CO 0.5%
Species Mass Fractions H2O 10%
O2 1.5%
N2 75%
For the rest boundary conditions of air inlets, air outlets, exterior walls, interior walls, gates and ambulance
cars were set identically as case 2 with 4 air outlets.

4.3.3 Case 4.1-4.3: With opened gates and installed air curtains.
Considering boundary conditions of air curtain, type of air curtain is selected according to selection guide
provided by Frico (Frico, 2014) and Appendix C. Type code PA3520E16D with air flow rate equal to
1530/3200 m3/h and temperature different equal to 35/13 C was selected. The given temperature
different is between the supply air and backflow air of the air curtain. With lower air flow rate, higher
temperature of the supply air is required. On the contrary, with higher air flow rate, lower temperature of
supply air took into account.
In case 4.1 to 4.3, air flow rate supplied by each air curtain is 3200 m3/h. Since air inlet area of the air
curtain is 0.0677m2, the supply air velocity was obtained to 13.124 m/s. The backflow air to air curtain is
equal to the indoor air temperature, according to temperature different equal to 13 C, the supply air
temperature from air curtain was computed as 31C. For velocity of air back to the air curtain, assumed
the volumetric flow rate of backflow air is equal to the supplied air and air outlet area to air curtain is
0.219m2. Velocity of the backward air flow is calculated as 4.057m/s. Data of boundary conditions
regarding to air curtain is summarized in Table 16.
Table 16, Air curtain boundary conditions of case 4.1-4.3.

Air Inlet from the air curtain (Velocity Inlet)


Velocity Specification Method Magnitude, Normal to Boundary
Velocity Magnitude (m/s) 13.124
Turbulent Intensity (%) 5
Turbulent Viscosity Ratio 5
Temperature (C) 31
Air Outlet to the air curtain (Velocity Inlet)
Velocity Specification Method Magnitude, Normal to Boundary
Velocity Magnitude (m/s) -4.057
Turbulent Intensity (%) 5
Turbulent Viscosity Ratio 5
Temperature (C) 18
Number of air curtains 4
For boundary condition of wind in outside domain, face shown in Figure 42 (a) was assigned as wind inlet
boundary. Velocity inlet with 1m/s as wind blow normal into the gates is defined in case 4.1. In case 4.2
and 4.3, pressure outlet with -0.3Pa and -1Pa were considered as the boundary condition of wind in
ambient environment. For the rest boundary conditions of air inlets, air outlets, exterior walls, interior
walls, gates and ambulance cars were set identically as case 2 with 4 air outlets.

-37-
4.4 Simulation Results and Analysis.
In this section, output results from CFD simulation of case 2, case 3, case 4.1to 4.3 will be presented and
discussed. Analysis of thermal comfort base on temperature distribution, velocity distribution and
distribution profiles of contaminants concentration will be carried out and compared with ASHRAE
standard of ventilation requirement.

4.4.1 Case 2: Improved ventilation system.


Velocity distribution profiles of indoor air flow for case 2 are shown as followed.

Figure 44, Velocity distribution at h=3m over the ground (Local Velocity).

At plane with height equal to 3m, the maximum velocity is produced around the supply air diffusers.
Compared with Figure 23, maximum velocity increased from 5.02m/s to 5.04m/s. The swirl flow still exist
after increase number of air flow outlets as shown in Figure 44.

Figure 45, Velocity distribution at h=1m (Local Velocity).

-38-
(a) (b)

(c)
Figure 46, Zoomed-in views to figure 45.

Figure 45 presents velocity distribution at the plane with height equal to 1m. Local velocity range is between
0m/s to 0.61m/s. Most part of areas have air flow velocity larger than 0.1m/s. However as shown in Figure
46, (a) and (c) which are zoomed-in views of red rectangular marked areas in Figure 45 have low air flow rate.
The rage of the flow rate is between 0 to 0.1 m/s. In the center areas of the swirl flow which shows in
Figure 46 (c), velocity of the air flow is also lower than 0.1m/s. Concern indoor air quality, air flow velocity
for areas which indicated in Figure 46 are recommended to be improved.
Temperature distribution at the plane with height equal to 1m is shown in following figures.

Figure 47, Temperature distribution of case 2 at h=1m (Left: local temperature, Right: Specified temperature).

As shown in Figure 47 Left, the local temperature indicator shows temperature range is between 2C to 18.6C
at the plane. Since the minimum temperature is not allowed to be lower than 18C for considering thermal
comfort, specified range of temperature between 18C to 18.6C is shown in Figure 47 Right. Blue areas means
air temperature lower than 18 C. For the mort part of indoor domain, air temperature have achieved the
requirement.

-39-
Figure 48, Temperature distribution of case 2 (Left: h=0.1m, isosurface=18C; Right: Room Envelope).

Isosurface with colored in orange shows in Figure 48 Left represents temperature on the surface is constantly
equal to 18C. Air temperature of space contained in the isosurface is higher than 18C. Plane showed in
Figure 48 Left is at 0.1m over the ground with local temperature indicated. Figure 48 Right expressed surface
temperature of exterior walls, interior walls and gates for case 2. The lowest temperature occurs in the
gates of the ambulance hall, where has the largest heat loss.

4.4.2 Case 3: Polluted emission from tailpipes of the ambulance cars.


Two types of air inlets contained in this case. At h=3m, supply air diffuser with velocity equal to 4.99m/s.
At h=0.4m, exhaust gas from tailpipes to the room is 3.84m/s. Indoor air flow behaviors on the planes
which has air inlets to the ambulance hall are shown in Figure 49. From the left figure, velocity at the air
outlets is around 3m/s-4.33m/s.

Figure 49, Velocity distribution of case 3 (Left: h=3m; Right: h=0.4m)

Velocity distribution at height equal to 1m for case 3 is shown in Figure 50. Velocity of air is performed in a
higher speed around 0.37m/s to 0.49m/s near the tailpipes of the cars and in the center of the room.
Areas marked by red rectangular in Figure 50 have velocity lower than 0.1m/s which are locations near the
gates, center of the swirl flow, corners of the room and areas near the left-top car.

-40-
Figure 50, Velocity distribution of case 3 (h=1m).

For temperature distribution of case 3, temperature of air inlets at the plane where h=3m is 19.543C and
h=0.4m is 35C. Air temperature distribution for the plan which contain exhaust gas is shown in Figure 51.
The left figure shows range of air temperature is between 4.8C to 32.9C, after specified temperature
between 18C to 19C, large gradient of temperature changing is obviously given. Areas near the tailpipes
have higher temperature.

Figure 51, Temperature distribution of case 3 h=0.4m (Left: Local temperature; Right: specified temperature)

For air temperature distribution at the plane with height equal to 1m, the range of temperature is between
5.6C to 20.4C. Considering areas with temperature higher than 18C, temperature distribution with
specified temperature between 18C to 20.04C is shown in Figure 52.

-41-
Figure 52, Temperature distribution of case 3 at h=1m (Specified Temperature).

Compared Figure 52 with temperature distribution of case 2 Figure 47, the highest temperature increased from
18.6C to 20.04C. The mean indoor temperature also increased from 18.5C to 19.3C. Areas with air
temperature lower than 18C which colored by blue is decreased.
Distribution of contaminant concentration for assessing indoor air quality is very important. Carbon
monoxide and carbon dioxide concentration in ppm are presented as followed.

Figure 53, CO concentration distribution of case 3 (h=1.5m).

As shown in Figure 53, the range of co concentration at plane with h=1.5m is between 216ppm to 551ppm.
According to form listed in Appendix D, the threshold limit value (TLV) of CO level regulated by OSHA
(OSHA, 2014) is 50ppm. Compared with the CO level of the case 3, the regulated TLV is not achieved.
However, since the simulated case was built on steady state condition and in reality the polluted emission

-42-
gas from the ambulance cars are not continuously exhaust, situation of CO level regarding to occupational
safety can be improved a little but not significantly.

Figure 54, CO2 concentration distribution of case 3 (h=1.5m).

Carbon dioxide concentration level at the plane with h=1.5m is shown in Figure 54. Range of CO2 level is
between 5613ppm to 14317ppm. According to ASHRAE IAQ guide (ASHRAE, 2010), the threshold
limit value of co2 level for parking garage is 5000ppm. Compared with range of CO2 level indicated in
Figure 54, criteria of co2 concentration level is not achieved. Same as the situation of co level, co2 level can
be improved a little bit in practical circumstance but not significantly.
CO and CO2 concentration are changed proportional to each other and both contaminant level can be
applied for sensing to control the indoor air quality. However, concentration of carbon dioxide can be
sensed much easier than carbon monoxide concentration. Practically, co2 sensor for controlling is
implemented generally.
Considering poor performance regarding to indoor contaminant level of the ambulance hall, measures for
improvement will be discussed in the next section 4.5.

4.4.3 Case 4.1-4.3: With opened gates and installed air curtains.
Weather condition in outside domain is changing all the time. In this section, three cases with different
boundary condition of ambient wind have been simulated. Case 4.1 is with wind blow normal into the
ambulance hall through the opened gates. Case 4.2 and case 4.3 were simulated with produced negative
pressure by outside wind. Outside pressures produced by the wind are -0.3Pa and -1Pa in the two cases.
With outside temperature equal to -18C, wind with -0.3Pa and -1Pa can be converted as wind flow
outlets with 0.68m/s and 1.24m/s. Simulation results of the three cases which were involved natural
ventilation analysis are presented as followed.

4.4.3.1 Case 4.1: Velocity inlet of wind with 1m/s.


Velocity distribution of case 4.1 are shown as figures below.
As shown in Figure 55, heated air provided by the air curtains have effectively interrupt outside wind blow
into the inside domain directly through the opened gates.

-43-
Figure 55, Velocity distribution of case 4.1 (h=1m)

The local range of air velocity at the plane where h=1m is between 0m/s to 5.67m/s. After being
specified velocity lower than 0.2m/s and 1m/s, the velocity distribution at h=1m shows in Figure 56.
As shown in the left figure, areas with air velocity lower than 0.2m/s is around the corners and near
tailpipe of the right-top ambulance car as marked by red rectangular. Therefore with opened gates,
emissions from the right-top ambulance car required to be concerned handling separated. As shown in the
right figure, the outside wind velocity is 1m/s with marked as red arrows. With interrupted by the strong
air flow from the air curtain, air velocity is meanly lower than 1m/s for inside domain.

Figure 56, Specified velocity of case 4.1 at h=1m (Left: Velocity 0m/s - 0.2m/s; Right: Velocity 0m/s - 1m/s).

In Figure 57, air flow behaviors around the opened gates are shown. The left figure is the vertical air flow
supplied by the air curtains. The range of the velocity is between 0m/s to 11.5m/s. The right figure is
transection view of one gate. As shown in the right figure, the vertical air flow from the air curtain with
high velocity, magnitude of the velocity decreased along downward of the vertical plane and turned into
separated flow to both side of the gate. Partial indoor air flow towards to the air outlets of the air curtains
in the up space of the ambulance hall.

-44-
Figure 57, Velocity distribution of case 4.1 around the opened gates.

Consideration of temperature distribution in case 4.1-4.3. All the cases are simulated as in winter, with the
assumed cold outside temperature -18 C. The air temperature distributions of the domains in case 4.1 at
h=3m and h=1m are shown in Figure 58.

Figure 58, Temperature distribution of case 4.1 (Left=3m; Right=1m).

As presented in the figures, the main air temperature of inside domain is around 14C where h=3m and
around 8.8C where h=1m. Although the air curtains have stopped partial heat loss through the opened
gate, the big temperature difference between indoor and outdoor have essentially made heat of the indoor
air transferred to the outside domain with lower temperature. According to the minimum required indoor
air temperature should not lower than 18C, additional measures for improving indoor air temperature
have to be implemented and will be discussed in the section 4.5.
The transection views of temperature distribution at gate are shown in Figure 59. The left figure is the overall
view contains temperature distribution at gate and the right figure is the zoomed-in view at the gate.
Obtained from the figures, heat supplied by the air curtain distributed to both side of the gate. However,
the heated air from the air curtains are not sufficient for stopping heat loss from indoor to outdoor.

-45-
Figure 59, Temperature distribution of case 4.1 (Transection view at gate).

4.4.3.2 Case 4.2 and 4.3: with negative pressure of outside wind.
In this section, pressure, velocity and temperature distribution for both case 4.2 and 4.3 will be presented
together. Comparison between case 4.2 with lower pressure drop -0.3Pa and case 4.3 with higher pressure
drop -1 Pa are analyzed.
With negative pressure outlet of wind, pressure distributions for both cases at the plane h=1m are shown
in Figure 60. For understanding pressure change in terms of more precision values, line with start point at
x=-8.4m, y=12m, z=1m and end point at x=21.89, y=12m, z=1m as shown in Figure 61 left has been
introduced. Pressure change along with the line of case 4.2 (red line) and case 4.3(blue line) are shown in
Figure 61 right. The lowest pressure along the line for both cases occur at x =1.2m where is near the downside
of air curtain.

Figure 60, Pressure distribution at h=1m of case 4.2(Left) and case 4.3 (Right).

Figure 61, Pressure change along the line of case 4.2(red line) and case 4.3 (blue line).

-46-
At plane h=1m, velocity field of case 4.2 and case 4.3 are showed in Figure 62. The local range of velocity for
both cases is between 0 m/s to 5.86 m/s. After limiting the highest velocity is not larger than 1m/s,
velocity distribution between 0m/s to 1m/s are shown.

Figure 62, Velocity distribution at h=1m of case 4.2(Left) and case 4.3 (Right).

As illustrated in the figures, the mainly air flow of inside domain for both cases are lower than 1m/s.
Velocity magnitude of areas colored by red is around 0.8m/s to 1.05m/s.

Figure 63Zoomed-in Velocity distribution at h=1m of case 4.2(Left) and case 4.3 (Right).

As shown in Figure 63, with higher negative outdoor wind pressure, total mass of indoor air flow from
inside to outside is increased. Effect of air curtain resist indoor air flow to outdoor in case 4.2 performed
better than in case 4.3.

-47-
Considering temperature distribution of the two cases. As shown in Figure 64 the temperature range for both
cases between -18C to 15.7C. Reading from the figures, mainly indoor air temperature for case 4.2 and
4.3 are around 8.9C to 12.3C. According to areas indicated by yellow for inside domain and areas
colored by light blue for outside domain, heat losses of indoor air from inside to outside of case 4.3 is
higher than case 4.2.

Figure 64, Temperature distribution at h=1m of case 4.2(Left) and case 4.3 (Right).

Compare Figure 64 of case 4.3 with wind pressure outlet to Figure 58 right of case 4.1 with wind velocity inlet,
heat loss through the opened gates is higher when the outside cold wind blowing normal to the gates than
extracting indoor air to outdoor through the opened gates.

4.5 Optimized approaches for improving thermal comfort.


Regarding to the previous analysis of the ambulance hall, weakness of thermal comfort and indoor air
quality level obtained by simulation results from each case will be discussed in this section. Corresponding
measures for improving the weak performances of the ventilation system are recommended as well.

4.5.1 One more supply air diffuser on the specified wall.


From simulation results of case 2, as shown in Figure 46 and Figure 47. Around the areas near the gates, air flow
velocity is lower than 0.1m/s and partial air temperature is not higher than regulated 18C. For improving
the weak ventilation performance around the areas, an additional supply air diffuser is recommended to be
installed on the wall as marked in Figure 65.

Figure 65, Install position of the additional supply air diffuser.

-48-
4.5.2 Exhaust extraction system.
According to simulation results of case 3, polluted emission from tailpipe of ambulance cars, as mentioned
in Figure 53 and Figure 54 in section 4.4.2. The carbon monoxide (CO) and carbon dioxide (CO2)
concentrations have exceeded the threshold limit level for parking garage which regulated by ASHRAE
IQA standard. In order to decrease and avoid health hazard caused by unqualified CO and CO2
concentration of indoor air, exhaust extraction system operate combined with ventilation system is
suggested to be implemented.
Compared with conventional exhaust extraction system which usually applied in vehicle workshop, in
ground exhaust extraction system is more adaptable to be applied in ambulance hall in this project.
Working conditions of the two system are illustrated in Figure 66.

Figure 66, Conventional exhaust extraction system (Left) and "in ground" exhaust extraction system (Right).

According to datasheet of in ground exhaust extraction system designed by Nederman Nordic AB


(Nenerman, 2014), the working principle of the systems is shown in Figure 67.

Figure 67, Working principle of "in ground" exhaust extraction system (Nenerman, 2014).

With installation of the in ground exhaust extraction system, exhaust from the tailpipes of the stationary
ambulance cars can be removed completely.

4.5.3 Supplement of heat in winter.


As shown of the indoor air temperature distribution for case 4.1 to case 4.3 in Figure 58 and Figure 64, with
initial design of supply air temperature equal to 19.543 C, the required minimum air temperature is
exceeded in cases with opened gates in winter. Therefore, measures for supplement of heat to the
ambulance hall in winter have to be implemented for maintain the indoor thermal comfort.
Two approaches regarding to the supplement of heat are recommended for the project. One is combined
ventilation system with installation of temperature sensor in the room. The other is implementation of
floor heating to the ground of the ambulance hall. With installation of temperature sensor to the room,
temperature of air can be sensed in time. When the indoor temperature is lower than the regulated

-49-
minimum temperature 18C, signal obtained from the sensor induced increasing of supply air
temperature. Compared with conventional heating method as installation of radiators, floor heating
combined with recovery of waste heat which collected from the exhaust of stationary ambulance cars is a
more energy efficient approach.

-50-
5 Conclusion and future improvement
The objective of this master thesis is to build numerical simulation of an ambulance hall for assessing
indoor fluid flied and thermal comfort. The main contents of the thesis are divided into two main parts.
The first part is to make comparison between the three CFD software which are ANSYS Fluent, Star-
CCM+ and IESVE Microflo. The second part is CFD modeling of the ambulance hall by ANSYS Fluent
with different boundary conditions.
In the first part, after simulated the baseline model by the three software, the presented results from each
cases shows that all the selected CFD software are qualitatively to compute convection diffusion problems.
However, IESVE Microflo performs less precision, lower correctness and more time cost for CFD
modeling compared with ANSYS Fluent and Star-CCM+. In contrast to case 1.2 and 1.3, case 1.1 with
CFD modeling by ANSYS Fluent have saved simulating time with accurate and efficient simulation
processing. In summary, for analyzing complicated indoor fluid environment by numerical simulation,
ANSYS Fluent is recommended for its best performance.
In the second part, five types of boundary conditions for three cases have been implemented. Simulation
results of case 2 and case 3 have shown the designed ventilation system for the ambulance hall satisfied
thermal comfort level which regulated by ASHRAE standard with closed gates. Nevertheless, threshold
limit value of the contaminants concentration which regulated by ASHRAE IAQ Standard cannot be
achieved. From simulation results of case 4.1 to 4.3 shown that the designed ventilation system cannot
satisfy indoor thermal comfort level when the gates of the ambulance hall opened in winter. In conclusion,
measures for decreasing contaminants concentration and increasing indoor air temperature demanded to
be considered in further design and three recommended measures for optimizing the design introduced in
the end as a reference.

-51-
6 Bibliography
ASHRAE, 1997. ASHRAE Handbook. Fundamentals Volume ed. GA: ASHRAE.
ASHRAE, 2010. ASHRAE Indoor Air Quality Guide.. U.S.: ASHRAE.
Barth, T. J. & Jesperson, D. C., 1989. The design and application of upwind schemes on unstructured meshes, Reno:
AIAA.
Calautit, J. K., Hughes, B. R. & Ghani, S. A., 2012. A numerical investigation into the feasibility of integrating green
building technologies into row houses in the Middle East, London: Taylor & Francis.
CD-adapco, 2013. Star-CCM+ User Guide. [Online]
Available at: file:///C:/Program%20Files/CD-adapco/STAR-CCM+9.02.005-
R8/doc/online/index.htm#page/STARCCMP/navigatingHelp.001.1.html
Cehlin, M., 2006. Visualization of Airflow, Temperature and Concentration Indoors Whole-field measuring methods and
CFD , Stockholm: Centre of Built Environment, KTH.
Cho, H. K., Lee, H. D., Park, . I. . K. & Jeong, J. J., 2010. Implementation of a second-order upwind method in a
semi-implicit two-phase flow code on unstructured meshes., Republic of Korea: ELSEVIER.
Crippa, S., 2011. Improvement of Unstructured Computational Fluid Dynamics Simulations Through Novel Mesh
Generation Methodologies, Braunschweig: JOURNAL OFAIRCRAFT.
Eleni, D. C., Athanasios, T. I. & Dionissios, M. P., 2012. Evaluation of the turbulence models for the
simulation of the flow over a National Advisory Committee for Aeronautics (NACA) 0012 airfoil. Journal
of Mechanical Engineering Research , 4(3)(2141-2383), pp. 100-111.
Fluent, A., 2006. ANSYS Fluent User Guide. [Online]
Available at: http://aerojet.engr.ucdavis.edu/fluenthelp/html/ug/node155.htm
[Accessed 20 09 2006].
Frico, 2014. Air curtain selection guide.. [Online]
Available at: http://www.frico.se/en/products/Air-curtain-selection/
Hach, L. & Katoh , Y., 2010. THE AIR CHANGE RATE CONTROL BY LOCAL MEAN AGE OF
AIR IN VENTILATED SPACES., Prague: Institute of Chemical Technology.
Hirsch, C., 2007. Numerical Computation of Internal and External Flows - Fundamentals of Computational Fluid
Dynamics. (2nd Edition) ed. India: Elsevier.
ISO, 1994. ISO 7730 : 1994 Ergonomics of the thermal environment -- Analytical determination and interpretation of
thermal comfort using calculation of the PMV and PPD indices and local thermal comfort criteria, Switzerland:
International Organization for Standardization.
Launder, B. E. & Spalding, D. B., 1973. THE NUMERICAL COMPUTATION OF TURBULENT
FLOWS, London: North-Holland Publishing Company.
Markatos , C. N., 2004. The mathematical modelling of turbulent flows, London: Centre for Numerical Modelling
and Process Analysis.
Maskin, S., 2014. SUN Avgasskola. [Online]
Available at: http://sunmaskin.se/utbildningar/sun-avgasskola
McQuiston, F. C., Parker, J. D. & Spitler, J. D., 2005. Heat, ventilating, and air conditioning (Anlysis and
Design).. Sixth Edition ed. U.S.: WILEY.
Nenerman, 2014. In Ground Exhaust Extraction System for stationary vehicles.. [Online]
Available at: http://www.nederman.com/products/exhaust-extraction/vehicle-exhaust-
extraction/~/media/ExtranetDocuments/PublishedTechnicalLeaflet/150390_00__In_Ground.ashx

-52-
OSHA, 2014. Occupational Safety & Health Administration of U.S. Department of Labor.. [Online]
Available at: https://www.osha.gov/
Shih, T.-H.et al., 1994. A new k- eddy viscosity model for high reynolds number turbulent flows, U.S.A: Elsevier.
Stamou, A., Katsiris, I. & Schaelin, A., 2007. Evaluation of thermal comfort in Galatsi Arena of the Olympics
Athens 2004 using a CFD model, Switzerland: ScienceDirect.
Tyler, H. et al., 2013. CBE Thermal Comfort Tool. [Online]
Available at: http://cbe.berkeley.edu/comforttool/
Uhrner, U. et al., 2007. Dilution and aerosol dynamics within a diesel car exhaust plumeCFD simulations of on-road
measurement conditions., Germany: ELSEVIER.
Versteeg, H. K. & Malalasekera, W., 2007. A introduction to computional fluid dynamics - The finite volume method.
Second edition ed. London: PEARSON.
Xue, H. & Ho, J. C., 2000. Modelling of Heat and Carbon Monoxide Emitted from Moving Cars in an Underground
Car Park., Singapore: Elsevier.

-53-
Appendix A: Data sheet/Dimension of Jet Nozzle Diffuser

-54-
Appendix B: Data and Dimension of Exhaust Grilles

-55-
Appendix C: Data and Type of Air curtain.

-56-
Appendix D: CO Level vs. Condition&Health Effects.

-57-