Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
As an electrical engineer, acquiring basic knowledge about the constituents of power systems is
important. A power plant is at the heart of power systems as it generates the power and also
distributes it. BUET, one of the top engineering universities of our country, has a power plant of
its own which meets up the power demand of the university during the peak hours. The BUET
Power Plant has 3 units and a combined generation capacity of a little over 4 MW. Two of these
are of 1MW capacity per unit. The latter is the running unit with 2 MW capacity or load 1.5 MW.
1.8 MW is the safe highest load of this unit as it is advised to load a generator at 90% of its rated
load.
The power plant is located south of the ECE building. It uses gas as its primary source of energy.
The power plant supplies electricity to three substations via underground cable. The substations
distribute this to every building and street light at 230 V. The peak demand of BUET campus is
1.75 MW at present. The plant supplies power from early morning till late night and during the
rest of the hours the energy is supplied through the DESA distribution system. The change is done
using Automatic Transfer Switches (ATS) located at the substation.
This part consists of generator engines which use natural gas as fuel and synchronous generators.
The gas engine driving the 1MW generator has 16 cylinders whereas the one driving 2MW
generator has 20 cylinders. The synchronous generators start with the help of DC motors which
use 24V DC batteries for excitation. At present, 2 generators are operating in parallel and another
generator (2MW) is supposed to be installed very soon. The cooling system that is being used to
cool down the generators is air cooling system. Water is circulated in a closed path and it is cooled
by fan from 100C down to 90C. Each of the generators has its own radiator which helps to
accelerate the cooling process. Lubricant oil is used for smooth running of machines and rated
pressure of supply gas is 11 psi. The machines operate at 60% rated KW for better efficiency of
the power plant.
Manufacturer: Caterpillar
Capacity: 1030 KW
Number of cylinder: 16
Number of radiator fan: 10 (for each generator)
Number of ventilation fan : 4
Fuel : Natural gas.
Speed of machine: 1500 rpm.
DC battery voltage: 24 V.
Generating voltage: 400V (LL).
Frequency: around 50 Hz.
Power factor (pf): > 0.8
Temperature inside cylinder: 600-700 degree Celsius.
Rated pressure of the supply gas: 11 psi.
Observed pressure of supply gas: 7 psi.
Sub-transient X .1539pu(.0101ohms)
Transient X .2422pu(.0159ohms)
Excitation 19V 5A
Insulation Class F
Before supplying electricity to the load, the control panel analyses the line voltage, line current,
amount of production, power factor etc. to ensure that right amount of power is being supplied. If
any fault occurs during the production, the control panel will identify it to protect generators from
unexpected accidents. If necessary, it will shut down the generator.
The power plant has two control panels. Control panel 1 is recently out of service as the
generator which was under its inspection has been replaced by another 2MW generator. But control
panel 2 is in service.
There are 10 radiator fans for cooling down each generator. Maintaining a moderate
temperature is important for efficient production of power and ensuring safety of
operation.Radiator fans have to be controlled carefully so as to not allow the temperature of the
generators go beyond certain specified maximum temperature. This section ensures that the
radiator fans are switched on as soon as any hint of overheating appears.
Page |7
One of the generators is monitored by a computerized control system. If any problem (such as
pressure drop or rise, voltage fluctuation etc.) occurs, it can be easily detected by this system.
Generator switching system, fan control, gas flow speed and amount of gas are controlled by this
system.
Protection system is another important part of generator. Protection devices are set in
generator control panel. Protection systems keep generator safe from damages. Emergency
protection is taken against:
1 Reverse power trip
2 Over voltage
3 Under voltage
4 Frequency drop
5 Emergency stop
6 Failure to start
7 Over speeding of turbine
8 Low pressure of lubricating oil
9 High coolant (water) temperature
10 EMCP diagnostic fault
If one of these faults occur then corresponding light and alarm will switch on.
Page |8
Generation unit generates power in a controlled way. Then the power is distributed to different
substations to distribute power to the load. Power is distributed to the substations through feeder
switchgears.
Feeder switchgear is mainly ACB (Air Circuit Breaker) which is being used to distribute power
to different substations. Each Feeder is connected to a substation.
Power distribution system consists of two parts namely-
1. Feeder
2. Substation
There are 9 feeder switchgears in BUET POWER PLANT. Among them only data of 5 feeders
were taken as the rest dont have any display. The data and covering area are given below.
Line Currents 85 A, 91 A, 90 A
Other feeders had no display and so we were unable to collect data of those feeders.
Figure: Switchgears
P a g e | 14
There are circuit breakers connected in series with each of the phase serves the purpose of
saving the system from danger occurred from fault current. These circuit breakers are automated;
however, feature manual control is also associated with those.
Frequency 50Hz
Rating 1250A
Serial Number 1509
Observed current 500A, 725A, 500A
Observed voltage 420V
P a g e | 16
Every PFI is automated, hence it doesnt require any manual support to improve the power factor
of the system.
Rating: 325Kvar
Serial Number: 1402
Type: Auto
Number of steps: 6
P a g e | 17
The DPDC line is connected to the power system through ATS (Auto Transfer Switch). It takes
only a few seconds to switch on the power supply of DPDC if the generator power supply is
stopped. The system is built in a way so that either generators or DPDC can supply the necessary
power at a time. It is SPDT type switch which switches line from DPDC to BUET and vice versa.
Current 440A
Voltage 395V
Frequency 50Hz
P a g e | 18
The rating of other transformers besides the ones at ECE building are as given below.
Transformer Rating
Cooling system is an important part of power station. In absence of this system, the generator may
be damaged to the excessive heat produced during power generation. We need to cool down the
whole system to get uninterrupted power supply. It is placed on the roof of the building.
The cooling system has a gear driven centrifugal pump. Four temperature regulators regulate the
temperature of the coolant.
P a g e | 20
There are two types of cooler to cool the system namely water cooled and oil cooled. Both of these
are extensively used for cooling purposes but the type of cooling method to be used is selected
based on the type of circuit i.e. amount of heat to be handled and other relevant factors. The
cogeneration uses energy from the engines heat in addition to the electrical energy that is
generated. The oil cooler is not in the jacket water circuit because the jacket water is too hot. The
circuit for the oil and the circuit for the after cooler may be either a combined system, where the
auxiliary pump circulates water through both the after cooler and oil cooler cores. The combined
system uses a thermostatic control to regulate the oil temperature. This prevents over cooling.
Because of the excessive heat produced by the generator, temperature of vapour can rise to
about 600 degree Celsius. The water of 100 degree Celsius goes to the cooler and decreases the
temperature to 90 degree Celsius. The hot water exchanges heat with the surroundings in the heat
exchanger and goes back to the generator. Two different coolers are used for the generators.
P a g e | 22
P a g e | 23
The BUET power plant is a well maintained fully functional power plant with all necessary checks
and preventive measures in place. In case of any emergency there are multiple safety mechanisms
in place to prevent power from ever going out in the BUET campus. It has served efficiently thus
far and will hopefully continue to keep doing so as it is under constant renovation and maintenance.
Hopefully as time goes its capacity will increase with the demand and further safety precautions
will be in place for accidents not to occur.