Sei sulla pagina 1di 4

JSWEL

Doc. No: EM/F/58/00


Title: TEST REPORT FOR RET 670 RELAY Date: 24.02.2011
Page: PAGE 1 OF 4

TEST REPORT OF TRANSFORMER PROTECTION RELAY RET670

TESTING DATE : 19/01/13


SERVICE : Transformer-7
CURRENT/ VOLTAGE INJECTION UNIT NAME/ MODEL: DOBLE KIT/ F-6150
INJECTION UNIT SL No : 061003858

GENERAL INFORMATION & DATA


TRANSFORMER DATA
Voltage Ratio 220 / 34.5 / 11.5 Vector Group YNd11yn0
MVA FL Current (A) Protection CT Ratio Metering CT Ratio
(Diff-600/1), (REF-500/1),
HV 130MVA 341A 600/1
(StandbyEF-200/1)
LV1 80MVA 1339A 1500/1
(Diff-2500/1), (REF-
LV2 50MVA 2510A
3000/1), (standby400/1)
RELAY DETAILS
Make ABB Software version 1.1Rev01
Auxiliary supply 220V DC Serial Number I0733014
Type RET670 Rating Ir=1A, Ur=110V, 50Hz

A. Differential Protection (87T) :-


1) Pick Up
Master Trip
Setting in % of Set Value in
PHASE Operated Value operated or Remarks
Primary current Amps
Not
R 20%=0.2XIbase 0.1136 0.115 operated
HV SIDE

Y 20%=0.2XIbase 0.1136 0.115 operated

B 20%=0.2XIbase 0.1136 0.115 operated

R 20%=0.2XIbase 0.29 0.291 operated


LV1 SIDE

Y 20%=0.2XIbase 0.29 0.291 operated

B 20%=0.2XIbase 0.29 0.291 operated

R 20%=0.2XIbase 0.5221 0.523 operated


LV2 SIDE

Y 20%=0.2XIbase 0.5221 0.523 operated

B 20%=0.2XIbase 0.5221 0.523 operated

2) Stability
19/01/13 Indra/Nilesh/Murgan M.DEVARAJULU

DATE PERFORMED BY CHECKED BY


JSWEL

Doc. No: EM/F/58/00


Title: TEST REPORT FOR RET 670 RELAY Date: 24.02.2011
Page: PAGE 2 OF 4

PHASE HV LV-1 HV LV-2 REMARKS


R-phase 0.568L0 1.449L210 0.217L0 1L180 STABLE
R-phase 0.568L0 1.449L195 0.217L0 1L150 TRIP
Y-phase 0.568L240 1.449L90 0.217L240 1L60 STABLE
Y-phase 0.568L240 1.449L75 0.217L240 1L30 TRIP
B-phase 0.568L120 1.449L330 0.217L120 1L300 STABLE
B-phase 0.568L120 1.449L315 0.217L120 1L270 TRIP

3)Test Slope ( checked for (a) ES1=1.25,S2=30% & (b) ES1=1.0,S2=30%,ES2=1.5,S3=50%)


a)S2=30%

Current @ 1.3% HV LV-1 I1=443.3A


R-phase 0.738L0 1.884L210 I2=547A
Y-phase 0.738L240 1.884L90 Id1=104A
B-phase 0.738L120 1.884L330 Ib1=495

Current @ 1.5% HV LV-1 I11=511A


R-phase 0.852L0 2.174L210 I22=642A
Y-phase 0.852L240 2.174L90 Id2=131A
B-phase 0.852L120 2.174L330 Ib2=576A

HENCE S2=33% FOUND

b) S3=50%

Current @ 1.6% HV LV-1 I1=545


R-phase 0.909L0 2.319L210 I2=810
Y-phase 0.909L240 2.319L90 Id1=265
B-phase 0.909L120 2.319L330 Ib1=677

Current @ 1.8% HV LV-1 I11=613


R-phase 1.021L0 2.609L210 I22=925
Y-phase 1.021L240 2.609L90 Id2=313
B-phase 1.021L120 2.609L330 Ib2=769

HENCE S3=51% FOUND

4) Harmonic blocking
a) I2/I1
Phase Setting Operated Remark
R-phase 15 0.149/1,100/50Hz
Y-phase % 0.149/1,100/50Hz
B-phase 0.149/1,100/50Hz

b) I5/I1
19/01/13 Indra/Nilesh/Murgan M.DEVARAJULU

DATE PERFORMED BY CHECKED BY


JSWEL

Doc. No: EM/F/58/00


Title: TEST REPORT FOR RET 670 RELAY Date: 24.02.2011
Page: PAGE 3 OF 4

Phase Setting Operated Remark


R-phase 25 0.255/1,250/50Hz
Y-phase % 0.255/1,250/50Hz
B-phase 0.255/1,250/50Hz

B. HV Restricted Earth Fault Protection:-


Master Trip
Setting in % of Set Value in
PHASE Operated Value operated or Remarks
Primary current Amps
Not
40% X I base 200A 200.5 A ( 0.401A) Operated

C. LV Restricted Earth Fault Protection:-


Master Trip
Setting in % of Set Value in
PHASE Operated Value operated or Remarks
Primary current Amps
Not
40% X Ibase 1200A 0.397A Operated

D. HV Timed Over Current (TOC) Protection:-


1) TOC1
Operated Value Master Trip
Setting in % of Set Value
PHASE operated or Remarks
Primary current in Amps I(A) T(sec) Not
Current
R 110%X Ibase 375A 2XIset 2.54 operated Injected in
all the
Y 110% X Ibase 375A 2XIset 2.54 operated Phases.
Operating
B 110% X Ibase 375A 2XIset 2.54 operated as per NI
Curve

2) TOC2
Operated Value Master Trip
Setting in % of Set Value
PHASE operated or Remarks
Primary current in Amps I(A) T(sec) Not
R 550%X Ibase 1875.5 3.2L0 0.03 operated

Y 550%X Ibase 1875.5 3.2L240 0.03 operated

B 550%X Ibase 1875.5 3.2L120 0.03 operated

E. HV Residual Earth Fault Protection based on residual current (TEF-1):-


19/01/13 Indra/Nilesh/Murgan M.DEVARAJULU

DATE PERFORMED BY CHECKED BY


JSWEL

Doc. No: EM/F/58/00


Title: TEST REPORT FOR RET 670 RELAY Date: 24.02.2011
Page: PAGE 4 OF 4

Master Trip
Setting in % of Set Value in
PHASE Operated Value operated or Remarks
Primary current Amps
Not
R 20% x Ibase 68.2A 0.04
Y 20% x Ibase 68.2A 0.04 operated
B 20% x Ibase 68.2A 0.04

F. HV Standby Earth Fault Protection:- CT Ratio:200/1


Master Trip
Setting in % of Set Value in
PHASE Operated Value operated or Remarks
Primary current Amps
Not
20% X Ibase 40A 0.22 operated

G. OVER EXCITATION:
PHASE Setting in % of Operated Value Master Trip
Remarks
V/Hz V/Hz operated or
Not

R 120% 79.26/48 Operated

Y 120% 79.26/48 Operated

B 120% 79.26/48 Operated

19/01/13 Indra/Nilesh/Murgan M.DEVARAJULU

DATE PERFORMED BY CHECKED BY