10f

Load span tables for wall panels EN Restrict span by fixing:

panel type FR/FH (2015) END MIDDLE

thickness 175 mm secret fix (load distribution plate)


ext. steel 0,6 mm secret fix (one screw 22mm)
int. steel 0,5 mm through fix
ext. facing profile M = micro -number of screws [pcs] 3 4
int. facing profile Q = minibox -constraining force (char.value)[kN] 2,10 2,10
deflection limit (SLS) 1/100 walls = 1/100 design value for selected fixing [kN]

FR/FH (2015) 175 mm 0,6/0,5 M/Q (end support: through fix, middle support: through fix) - according to EN 14509
characteristic uplifting load, e.g. wind SUCTION [kN/m2]
System Colour group
0,25 0,50 0,75 1,04 1,25 1,45 1,75 2,00 2,25 2,50 2,75 3,00 3,25 3,50 3,75 4,00 4,25 4,50 4,75 5,00
I. 11,51 8,14 6,65 5,65 5,12 4,41 3,66 3,20 2,85 2,56 2,33 2,14 1,97 1,83 1,71 1,60 1,51 1,43 1,35 1,28
Single
II. 11,51 8,14 6,65 5,65 5,12 4,41 3,66 3,20 2,85 2,56 2,33 2,14 1,97 1,83 1,71 1,60 1,51 1,43 1,35 1,28
Span
SUCTION

III. 11,51 8,14 6,65 5,65 5,12 4,41 3,66 3,20 2,85 2,56 2,33 2,14 1,97 1,83 1,71 1,60 1,51 1,43 1,35 1,28
I. 7,77 6,36 5,60 5,07 4,80 4,41 3,66 3,20 2,85 2,56 2,33 2,14 1,97 1,83 1,71 1,60 1,51 1,43 1,35 1,28
Double
II. 4,99 4,52 4,23 3,99 3,86 3,75 3,62 3,20 2,85 2,56 2,33 2,14 1,97 1,83 1,71 1,60 1,51 1,43 1,35 1,28
Span
III. 3,15 3,08 3,01 2,95 2,91 2,87 2,82 2,79 2,75 2,56 2,33 2,14 1,97 1,83 1,71 1,60 1,51 1,43 1,35 1,28
I. 10,75 7,83 6,56 5,65 5,12 4,41 3,66 3,20 2,85 2,56 2,33 2,14 1,97 1,83 1,71 1,60 1,51 1,43 1,35 1,28
Tripple
II. 6,63 5,29 4,67 4,23 4,01 3,84 3,64 3,20 2,85 2,56 2,33 2,14 1,97 1,83 1,71 1,60 1,51 1,43 1,35 1,28
Span
III. 2,87 2,78 2,71 2,64 2,59 2,55 2,50 2,46 2,43 2,39 2,33 2,14 1,97 1,83 1,71 1,60 1,51 1,43 1,35 1,28
* the minimum end-support width for uplifting load (e.g. wind suction) is 40 mm; the minimum middle-support width is 60 mm

FR/FH (2015) 175 mm 0,6/0,5 M/Q (end support: through fix, middle support: through fix) - according to EN 14509
characteristic
System Colourdownwards
group load, e.g. wind PRESSURE [kN/m2]
0,25 0,50 0,75 1,06 1,25 1,50 1,75 2,00 2,25 2,50 2,75 3,00 3,25 3,50 3,75 4,00 4,25 4,50 4,75 5,00
Single I., II., III. 44 63 77 91 91 91 91 91 91 91 91 91 91 91 91 91 91 91 91 91
12,40 8,77 7,16 6,03 5,12 4,27 3,66 3,20 2,85 2,56 2,33 2,14 1,97 1,83 1,71 1,60 1,51 1,43 1,35 1,28
Double I. 40 40 49 64 73 84 91 91 91 91 91 91 91 91 91 91 91 91 91 91
5,56 4,92 4,55 4,24 4,10 3,95 3,66 3,20 2,85 2,56 2,33 2,14 1,97 1,83 1,71 1,60 1,51 1,43 1,35 1,28
60 70 97 128 146 168 183 183 183 183 183 183 183 183 183 183 183 183 183 183

II. 40 40 49 64 73 84 91 91 91 91 91 91 91 91 91 91 91 91 91 91
PRESSURE

5,56 4,92 4,55 4,24 4,10 3,95 3,66 3,20 2,85 2,56 2,33 2,14 1,97 1,83 1,71 1,60 1,51 1,43 1,35 1,28
60 70 97 128 146 168 183 183 183 183 183 183 183 183 183 183 183 183 183 183

III. 40 40 49 64 73 84 91 91 91 91 91 91 91 91 91 91 91 91 91 91
3,23 3,23 3,23 3,23 3,23 3,23 3,23 3,20 2,85 2,56 2,33 2,14 1,97 1,83 1,71 1,60 1,51 1,43 1,35 1,28
60 70 97 128 146 168 183 183 183 183 183 183 183 183 183 183 183 183 183 183

Tripple I. 40 43 55 70 78 88 91 91 91 91 91 91 91 91 91 91 91 91 91 91
7,77 5,98 5,19 4,61 4,37 4,12 3,66 3,20 2,85 2,56 2,33 2,14 1,97 1,83 1,71 1,60 1,51 1,43 1,35 1,28
60 85 111 140 156 176 183 183 183 183 183 183 183 183 183 183 183 183 183 183

II. 40 43 55 70 78 88 91 91 91 91 91 91 91 91 91 91 91 91 91 91
7,77 5,98 5,19 4,61 4,37 4,12 3,66 3,20 2,85 2,56 2,33 2,14 1,97 1,83 1,71 1,60 1,51 1,43 1,35 1,28
60 85 111 140 156 176 183 183 183 183 183 183 183 183 183 183 183 183 183 183

III. 40 43 55 70 78 88 91 91 91 91 91 91 91 91 91 91 91 91 91 91
7,77 5,98 5,19 4,61 4,37 4,12 3,66 3,20 2,85 2,56 2,33 2,14 1,97 1,83 1,71 1,60 1,51 1,43 1,35 1,28
60 85 111 140 156 176 183 183 183 183 183 183 183 183 183 183 183 183 183 183

The values in these load tables represent the maximum span for the given load, static system and colour group, calculated according to the proof procedures given in EN 14509.
The small numbers above the span values represent the minimum required width of supports at panel ends.
The small numbers below the span values represent the minimum required width of intermediate supports.
All loads have to be considered as characteristic loads. Element dead loads have been considered in the span calculations. Possible errors and omissions are excepted. Please consider that this table does not replace a
verifiable structural design.