Sei sulla pagina 1di 2

FEATURES DUMW

System total capacity up to 48/50H System


12KW output for
DUMW-48/50H.

Suitable for outdoor


application with various
protection measures.

Wide AC input range 90V to


300V.

PFC technique features the


system high efficiency,
energy-saving and up to
0.99 power factor.

Intelligent fan-cooling
technique brings good
cooling performance, low INTRODUCTION
failure rate and high DUMW-48/50H outdoor power system is compact and intelligent power
reliability. system containing max.4 rectifier modules, controller module, LVD, AC and
DC distributions. Special protection measures ensure it could be applied in
Fast on-line expansion of outdoor environment.
rectifier modules enabled
by hot-swap.

N+1 rectifier module


redundancy. PPLICATIONS
Fiber optic network
Automatic management of Broadband and network access
battery charging and Transmission equipment
temperature Mobile communication/2G, 3G,4G base station
compensation function Satellite communication ground station

RS232 or RS485
communication interface.

Switch Mode Power System Distribution Cabinet Inverter


Remote Monitoring System DC/DC Converter UPS/EPS
Renewable Energy Solution Hybrid Power System HVDC UPS

Beijing Dynamic Power Co.,Ltd.


www.dpc.com.cn
NO.8 Xinghuo Road, Science City, Fengtai District, Beijing, P. R. China
SPECIFICATIONS
AC Input Monitoring and Control
Nominal:186-285Vac, 1phase Monitoring unit DKD48
AC supply Tolerance:90-300 VAC, 1phase Local Menu driven software via keypads
1 phase three wires input operation and LCD or PC (PowerSuite)
Frequency 45-65Hz
Remote
Power Factor 0.99 RS232 or RS485/SNMP
operation
Voltage wave LCD system status
<5%
distortion Visual Green LED System ON
Current Distortion5% @50~100% load indications Yellow LED Minor alarm(s)
Soft start Red LED Major alarm(s)
Surge protection (SPD: Class B or C) Alarm relays 8 relays
Protection
Internal fuses (L & N)
4 to 8 options (for monitoring of external
Over voltage protection Digital inputs
equipment), Custom options available
AC Distribution Options Current Battery current
AC input 1*100A/2P for MCB, one set of SPD measurements Rectifier current
AC output One AC10-30A/220V 3P socket AC failure alarm
DC Output Rectifier failure alarm
Voltage -48VDC (-42--58VDC adjustable) Load fuse alarm
Battery fuse alarm
Current 200A ultimate capacity (48/50H) LVD operated
Voltage Low output voltage alarms
1%
regulation Alarms High output voltage alarms
Current Symmetry alarm
5% Fan fail
Sharing
Door
Typical:94%; (DZY-48/50H)
Efficiency Water
Typical:96%;(DZY-48/50HI)
Smoke
Ripple and
200mV p-p Infrared
Noise
Psophometric Other Specifications
2mVrms
noise Air cooling
Over/under voltage shutdown Cooling Heat exchange
Protection Short circuit proof DC Air-conditioner
High temperature protection
Protection level IP55
DC Distribution Options
Operating temp -40 to +75C (-40 to +167F)
No.of Load MCB:8*16/1P; 6*63A/1P
Fuse Custom options available Temp range
-40 to +50C)
(when full load)
No.of Battery
MCB:2*100A Storage temp -40 to +85C (-40 to +185F)
Fuse
LLVD:1*100A DC contactor Operating: 95% non-condensing
LVD Humidity
BLVD:1*200A DC contactor Storage: 99% non-condensing
Rectifier Dimensions 650W*650D*1700H(mm)
Type DZY-48/50H Weight 90kg excl. rectifiers

Beijing Dynamic Power Co.,Ltd.


www.dpc.com.cn
NO.8 Xinghuo Road, Science City, Fengtai District, Beijing, P. R. China

Potrebbero piacerti anche