Sei sulla pagina 1di 8

OMICRON PTL ABB/Westinghouse CO PTT User Manual

OMICRON PTL

ABB/Westinghouse CO PTT

User Manual

V1.000

OMICRON electronics GmbH 1/8


OMICRON PTL ABB/Westinghouse CO PTT User Manual

Content
1. General ...................................................................................................................................................3
1.1 Supported Relays .................................................................................................................................3
2. Software and Hardware Requirements ...............................................................................................3
3. Hardware ................................................................................................................................................4
4. Functional Range...................................................................................................................................8
5. XRIO Converter ......................................................................................................................................8
6. Test Interface .........................................................................................................................................8
7. Specific Protection Tests ......................................................................................................................8
7.1 IT unit pickup/IIT unit pickup.................................................................................................................8

OMICRON electronics GmbH 2/8


OMICRON PTL ABB/Westinghouse CO PTT User Manual

1. General
This user manual describes the details of testing Westinghouse Type CO relays with the OMICRON
Protection Test Template. General information on the usage of OMICRON Protection Testing Library
items can be found in the OMICRON PTL user manual.

The template has been tested with the following relay:


Manufacturer: ABB/Westinghouse
Model: CO-7

1.1 Supported Relays


The following relays can be tested with the Protection Test Template:
ABB/Westinghouse CO-2
ABB/Westinghouse CO-4
ABB/Westinghouse CO-5
ABB/Westinghouse CO-6
ABB/Westinghouse CO-7
ABB/Westinghouse CO-8
ABB/Westinghouse CO-9
ABB/Westinghouse CO-11

2. Software and Hardware Requirements


To use this template, you must have a valid test license for the OMICRON Test Universe 2.40 software or
higher versions and the following test modules:
Control Center
Pulse Ramping
Overcurrent

Any CMC test set can be used with this Protection Test Template.

OMICRON electronics GmbH 3/8


OMICRON PTL ABB/Westinghouse CO PTT User Manual

3. Hardware
There are multiple possibilities of wiring a CO relay to a CMC test set. The advised connections are
shown in Figure 1 to Figure 4. These connections are the default settings in the Hardware Configuration
of the PTT.

Figure 1: ABB/Westinghouse CO double trip relay with IIT (Indicating Instantaneous Trip)

OMICRON electronics GmbH 4/8


OMICRON PTL ABB/Westinghouse CO PTT User Manual

Figure 2: ABB/Westinghouse CO double trip relay with IIT connected to separate terminals

Figure 3: ABB/Westinghouse CO double trip relay without IIT

OMICRON electronics GmbH 5/8


OMICRON PTL ABB/Westinghouse CO PTT User Manual

Figure 4: ABB/Westinghouse CO single trip relay with IIT

Figure 5: ABB/Westinghouse CO single trip relay with IIT connected to separate terminals

OMICRON electronics GmbH 6/8


OMICRON PTL ABB/Westinghouse CO PTT User Manual

Figure 6: ABB/Westinghouse CO single trip relay without IIT

Figure 7: ABB/Westinghouse CO-4 relay

OMICRON electronics GmbH 7/8


OMICRON PTL ABB/Westinghouse CO PTT User Manual

4. Functional Range

Supported functions:
Overcurent protection

5. XRIO Converter
The Test Object already contains the ABB/Westinghouse CO XRIO Converter, which includes the
setting parameters of the modelled protection relay. The setting parameters are built as an image of the
tap setting on the front panel of the relay.

6. Test Interface
The ABB/Westinghouse CO PTT is equipped with a Test Interface to support the user in using the test
plan. The Test Interface dialog automatically starts up when the template is loaded. The Test Interface
dialog can be started again anytime by pressing the Test Wizard button in the Test Universe menu bar.

7. Specific Protection Tests

7.1 IT unit pickup/IIT unit pickup


The Pulse Ramping test module is used to test the Instantaneous Trip (IT) and Indicating Instantaneous
Trip (IIT) pickup. All CO relay variants can be equipped with an IIT unit, whereas CO-4 relays are the only
CO relays equipped with an IT unit. The IT and the IIT unit can be enabled or disabled for testing in the
relay parameter section of the XRIO converter.

OMICRON electronics GmbH 8/8

Potrebbero piacerti anche