Sei sulla pagina 1di 6

Grid Voltage Regulation Utilizing Storage

Batteries in PV Solar Wind Plant based


Distributed Generation System
V. Khadkikar, Member, IEEE, Rajiv K. Varma, Member, IEEE and Ravi Seethapathy, Senior Member,
IEEE

daylight hours are less. On the other hand, the power


AbstractIn this paper, a novel night-time application of a generation from wind plants is generally more during night-
photovoltaic (PV) solar power farm bidirectional inverter as a times due to higher wind speeds.
battery charger, is presented. It is shown that a combination of In recent years, as the sizes of wind and solar plants are
PV solar farm and storage batteries can be advantageous in a
increasing in distribution systems, efforts are being made to
distribution system having wind farm in close vicinity to the solar
farm. Under such a condition, the PV solar farm inverter can improve the reliability of these systems. One of the attractive
regulate the grid voltage (if allowed by the code) by charging/ solutions is to incorporate storage batteries with these DG
discharging the batteries as well as provide better asset systems such that when excess power is produced, it can be
utilization and return on investments. The PV solar farm stored and delivered during peak hours when required [1-2].
inverter is operated as a three-phase fully controlled rectifier to Fig. 1 (a) shows a system configuration for a directly coupled
charge the batteries which draws sinusoidal currents at unity
wind turbine system with battery storage facility [3-4]. The
power factor operation. MATLAB/SIMULINK based simulation
results are provided to show the effectiveness of the proposed directly coupled wind turbine system however requires an
indirect grid voltage regulation utilizing the PV solar farm and additional bidirectional converter to charge/discharge the
storage batteries. batteries. Fig. 1(b) shows the system configuration of a
converter inverter based wind energy system with storage
Index Terms Battery storage, converter/inverter, battery directly integrated on DC side of the converter [3], [5].
photovoltaic (PV) system, solar power, voltage regulation, wind This topology has advantage as the additional generated power
power.
can be directly stored and delivered whenever required by
utilizing the grid side inverter.
I. INTRODUCTION

A S the penetration level of the renewable energy resources


(such as wind, solar, fuel cells, etc) is increasing,
dependence on these resources to support load demand in
modern power distribution system is also growing. However,
due to the intermittent nature of wind and solar resources, the
reliability of distributed generation (DG) is a major concern. A
backup battery, if integrated with these resources, may help to
store the excess energy produced by them and deliver it
whenever needed.
A photovoltaic (PV) solar farm produces power during the
day-time. However, it generates close to rated maximum (a)
power only during part of the day-time (late morning to late
afternoon/early evening) hours. The power generation
capacity of a solar farm also depends on the weather and the
season, for example, during cloudy days the power output
reduces significantly and in non-tropical country winters the

Financial support from Ontario Centres of Excellence, Centre of Energy, is


gratefully acknowledged. (b)
V. Khadkikar and Rajiv K. Varma are with the Electrical and Computer
Engineering Department, The University of Western Ontario, London,
Ontario, Canada (e-mails: vkhadkik@uwo.ca, rkvarma@uwo.ca). Fig.1. Wind energy systems with battery storage.
Ravi Seethapathy is with Hydro One Networks Inc., Toronto, Ontario,
Canada (e-mail: ravi.seethapathy@hydroone.com).

2009 IEEE Electrical Power & Energy Conference


978-1-4244-4509-7/09/$25.00 2009 IEEE
Similar to the wind energy system, storage batteries can Stored battery energy can be utilized for peak
also be incorporated in solar farms. In case of solar farms the shaving or as an emergency backup
full capacity of bidirectional inverter especially during night
Improved PV solar power dispatchability and PV
can be utilized as a battery charger [6-9]. This paper present a
output smoothing.
novel approach for a solar wind plant based DG system in
which the bidirectional solar farm inverter is utilized to Increased DG and Distribution system reliability.
charge/discharge the batteries and thus regulate the feeder Possibility of utilizing the system configuration as
voltage indirectly by extracting excess power generation by uninterruptible power source (UPS) when used
wind farm or by supporting load active power peak demand captive (behind the meter).
when output from PV solar system is not at its rated
maximum.
The paper is arranged as follows: section-II describes the
utilization of PV solar farm as a battery charger; section-III
discusses the proposed utilization of a PV solar farm
combined with storage batteries to regulate the PCC voltage;
in section-IV simulation results are given to validate the
proposed utilization of a PV solar farm; and section-V outlines
conclusive remarks of this research work.

II. PV SOLAR FARM AS BATTERY CHARGER


A typical PV solar farm is basically inactive during night-
time and the bidirectional inverter used to deliver the PV DC
power as three-phase AC power to the grid, remains unutilized
as well. Fig. 2 shows the possible operational modes of the
solar farm. The point at which the solar farm is connected to (a)
the grid is called the point of common coupling (PCC). In Fig.
2, vS and iS represents the voltage and current at the secondary
of the distribution transformer; vPCC and vL denote voltages at
PCC and load terminal respectively; and iPV is the current
delivered by the PV solar panels. AC current drawn/delivered
by the solar farm inverter and the DC current flowing through
the storage battery are represented by iSF and iBatt, respectively.
Fig. 2 (a) shows the block diagram representation of
traditional utilization of a PV solar farm. The PV solar farm in
this case supplies power to the main grid during the day-time
(remaining unutilized during the night). Fig. 2 (b) shows a
system configuration to utilize the solar farm inverter as a
battery charger [6-9]. In this case, a storage battery is
connected on DC side of the solar farm inverter. Switch S1
(b)
in Fig. 2 (b) is utilized to disconnect the PV solar panels
especially during night-time and to charge the storage batteries Fig. 2. Utilization of PV solar farm bidirectional inverter: (a) Normal
from the main grid. In some cases, the battery charging operation during day-time to inject real power and (b) Solar farm inverter as
battery charger system configuration.
process can be incorporated in the maximum power point
tracking (MPPT) algorithm [10-11]. An additional DC to DC
III. PROPOSED UTILIZATION OF COMBINED SOLAR FARM AND
converter, such as a buck/boost converter may be required to
STORAGE BATTERY SYSTEM TO REGULATE PCC VOLTAGE
enhance the battery charging/discharging operation. An
automatic mechanism or control loop may also be essential to If the power generated by a DG is more than load demand
avoid excessive overcharging of the batteries and low battery connected downstream of the PCC, the excess power flows
voltage condition during discharging process. back towards the main grid. A substantial amount of this
The advantages offered by the consideration of a battery or reverse power flow may cause voltage to rise on the
sets of batteries on the DC side of the PV solar farm inverter distribution feeder. The voltage rise due to reverse power flow
are highlighted below: is one of the major concerns in any DG system
(wind/solar/other) as it may cause the distribution feeder
Better utilization of solar farm inverter asset
voltage to rise more than the allowable limit (typical 5%)
24/7/365 with multiple value streams i.e. as solar specified by the utility standards [12-15].
PV generator, energy storage and voltage regulator
Fig. 3. Block diagram representation of proposed utilization of solar farm during night time.

Since wind velocity is generally higher during the night- rapid charging to extract power at different rates if the power
times, a wind plant may produce more power causing generation from wind farm increases suddenly.
significant amount of reverse power to flow towards main The operational modes of proposed utilization of solar farm
grid. Furthermore, during the night-time the condition worsens are explained below:
as the load on the system is generally lower as compared to (i) The voltage and flow of power at PCC is monitored.
the day time levels. On the other hand, it may be noted that During night-time, if the PCC voltage is observed to
solar farms do not produce any real power and remain increase beyond a certain level, for example 1.025 pu, or a
unutilized during the night-time. significant amount of reverse power flow is detected, the
It is quite likely in the near future that wind and solar farms battery charging loop is activated. Part of the wind
may be located on the same distribution feeder. This generated real power (PWF) is extracted and utilized to
complementary operational condition of wind farm producing charge the batteries such that the voltage at PCC will be
excessive power while solar farm remaining in idle condition, regulated. Several batteries can be charged simultaneously
especially during the night-time, can be utilized to enhance the if very high amount of reverse power flow causing
overall system performance by using the solar farm inverter to significant voltage rise at PCC is noticed.
perform additional tasks. In this paper, this approach is (ii) During the day-time, this stored energy in the batteries is
utilized to regulate the feeder voltage. The concept is to delivered back to the PCC. For example, during early
exchange (store/deliver) the real power from the feeder by morning hours or late afternoon hours when the power
incorporating storage batteries on the DC side of the solar generated from PV solar farm is not at its peak, the battery
farm inverter. In the future as more AC-DC-AC converter- will be connected in parallel with solar farm generated
inverter based wind plants are employed, such battery systems output. Thus the PV solar farm and storage battery will
can be incorporated in wind plants (to store excess solar/other simultaneously support the load power demand.
power)
Fig. 3 shows the block diagram representation of the IV. SIMULATION RESULTS
proposed system operational configuration. The distribution To validate the concept presented in the paper, MATLAB/
system consists of PV solar and wind farms connected on the SIMULINK based simulation study is carried out. A
same feeder. Several rechargeable batteries are connected to SIMULINK model is developed for the system discussed in
DC side of the solar farm inverter. Switches S1 and S2 are Fig. 3. The length of line L1, L2 and L3 are: 5 km, 1 km and
utilized to select one or multiple operational modes. The 0.5 km, respectively. The impedance of each of the line is:
bidirectional inverter of the solar farm is operated as fully 0.055 + j0.0395 (positive sequence value) and 0.1763 + j1.029
controlled active rectifier to charge the batteries at unity (zero-sequence value).The simulation results are given in Figs.
power factor operation. Further, with adequate control, the 4 to 7.
batteries can be charged by drawing constant charging current
to extract power at fixed rate or variable charging current for
(a) (a)

(b) (b)

Fig. 4 System feeder voltage control using PV solar farm inverter and storage Fig. 6 System feeder voltage control using PV solar farm inverter and storage
battery (during battery charging). battery (during battery discharging).

Fig. 5 PV solar farm inverter current and grid current profiles during battery Fig. 7 PV solar farm inverter and grid current profiles during battery
charging. discharging.

Fig. 4 shows the simulation results when wind farm respectively [Fig. 4 (b)]. At time t=1.25 sec, the solar farm
generates a 30 kW active power (PWF). The load on the system inverter is controlled as battery charger to charge sets of
is considered as 20 kW (PL). Till time t=1.25 sec, the solar batteries. Initially a single battery is charged to 2.5 kW (PBatt).
farm inverter is not controlled to charge the batteries. This reduces the amount of reverse power flowing towards
Therefore, as noticed from Fig. 4 (a), 10 kW power flows main grid from 10 kW to 7.5 kW [Fig. 4 (a), after time
towards the main grid (PS). The allowable variation in feeder 1.25sec]. As noticed from the Fig. 4 (b), this charging causes
voltage is considered as 0.05 pu. Due to the reverse power the load and PCC voltages to reduce to 1.061 pu and 1.052 pu,
flow, the voltage at load end (VL) and PCC (VPCC) is noticed to respectively. However, these voltages are not within the
exceed the specified limit, as 1.073 pu and 1.061 pu, specified limits. Therefore, at time t=1.5 sec, second battery is
put on charging and thus extracting a total of 5 kW active In future work, the proposed approach will be expanded for
power from the PCC (PSF). This restores the voltage at load a medium voltage large-scale PV solar wind power based
and PCC buses to 1.044 pu and 1.034 pu, respectively. Fig. 5 distribution system.
shows the profile of current drawn by the solar farm inverter
(iSF) to charge the batteries. As noticed, the solar farm inverter VI. REFERENCES
draws sinusoidal current at unity power factor with respect to [1] B. Roberts, "Capturing grid power," IEEE Power and Energy Mag.,
the PCC voltage. The solar farm inverter current is in-phase vol.7, no.4, pp. 32-41, July-Aug. 2009.
[2] R. Fioravanti, V. Khoi, W. Stadlin, "Large-scale solutions," IEEE Power
with the PCC voltage indicating that active power is being and Energy Mag., vol.7, no.4, pp.48-57, July-Aug. 2009.
consumed by the batteries. The profile of current flowing [3] L. Wei and G. Joos, Comparison of Energy Storage System
towards the grid (iS) is also shown in the Fig. 5. Technologies and Configurations in a Wind Farm," in Proc. IEEE
Power Electr. Spec. Conf., 17-21 Jun., 2007, pp. 1280-1285.
Fig. 6 shows the simulation results when the stored battery [4] S. Teleke, M. E. Baran, A. Q. Huang, S. Bhattacharya, S. and L.
energy is delivered to the network. In this case the generation Anderson, "Control Strategies for Battery Energy Storage for Wind
from the wind farm is reduced to 10 kW while keeping the Farm Dispatching," IEEE Trans. Energy Conver., vol.24, no.3, pp.725-
732, Sept. 2009.
identical load of 20 kW. Before time t=1.25, the batteries are [5] X. Y. Wang, D. M. Vilathgamuwa and S. S. Choi, "Determination of
not connected to the system. Under such a condition, as Battery Storage Capacity in Energy Buffer for Wind Farm," IEEE
viewed from Fig. 6 (b), the load and PCC voltages are noticed Trans. Energy Convers., vol.23, no.3, pp. 868-878, Sept. 2008.
[6] S. Kim, Y. Gwonjong and J. Song, "A bifunctional utility connected
as 0.944 pu and 0.95 pu, respectively. Due to reduced voltage
photovoltaic system with power factor correction and UPS facility," in
at load terminal the load draws 17.7 kW power [Fig. 6 (a)]. Proc. IEEE Photovolt. Spec. Conf., 13-17 May, 1995, pp. 536-541.
The wind farm supports 10.6 kW power to the load while [7] K. Hirachi, M. Yamanaka, T. Takada, T. Mii and M. Nakaoka, "Feasible
remaining power is supplied by the main grid. developments of utility-interactive multi-functional bidirectional
converter for solar photovoltaic generating system incorporating storage
At time t=1.25 sec, first battery (2.5 kW) is connected to batteries," in Proc. IEEE Power Electr. Spec. Conf., 18-22 Jun., 1995,
the system. At this point it is assumed that the PV solar farm pp. 536-541.
does not produce any real power. As noticed from Fig. 6 (a), [8] C. V. Nayar, M. Ashari and W. W. L. Keerthipala, "A grid-interactive
photovoltaic uninterruptible power supply system using battery storage
after time 1.25 sec, the solar farm inverter delivers 2.5 kW and a back up diesel generator," IEEE Trans. Energy Convers., vol.15,
power to PCC and this power is provided from the stored no.3, pp. 348-353, Sep. 2000.
battery energy. This reduces the amount of power delivered [9] Y. Lo, T. Lee and K. Wu, "Grid-Connected Photovoltaic System with
Power Factor Correction," IEEE Trans. Indust. Electr., vol.55, no.5, pp.
from the main grid to 5.35 kW. Due to this operation, the 2224-2227, May 2008.
voltages at PCC and load terminals improve to 0.965 pu and [10] M. Matsui, K. Kanghoon, Y. Byunggyu and T. Kitano, "A solar battery
0.958 pu, respectively. charging module by means of Limit-Cycle MPPT control," in Proc.
IEEE Int. Conf. Power Electr., 22-26 Oct., 2007, pp. 572-575.
At time t=1.5 sec, the second battery is also connected to [11] W. Jian, L. Jianzheng, W. Libo, Z. Zhengming, "Optimal control of
the system such that total 5 kW of active power is supplied solar energy combined with MPPT and battery charging," in Proc.
from the storage battery and solar farm inverter combination. Electr. Mach. Sys., 9-11 Nov., 2003, pp. 285-288.
[12] C. L. Masters, "Voltage rise: the big issue when connecting embedded
This further improves the PCC and load voltages to 0.979 pu generation to long 11 kV overhead lines," IEEE Power Engineering
and 0.972 pu, respectively. The PV solar farm with battery Journ., vol.16, no.1, pp. 5-12, Feb 2002.
system supports the 5 kW power to the load while remaining [13] R. A. Walling, R. Saint, R. C. Dugan, J. Burke, L. A. Kojovic,
power is drawn from the main grid. The profile of currents Summary of Distributed Resources Impact on Power Delivery
Systems, IEEE Trans. Power Del., vol. 23, no. 3, pp. 1636-1644, Jul.
delivered by the solar farm inverter (iSF) during battery 2008.
discharge process is shown in Fig. 7. As noticed, the solar [14] D. Patel, R. K. Varma and R. Seethapathy, Impact assessment of
farm inverter delivers the stored battery power to the main distribution generation on medium voltage distribution systems of
Hydro One Networks Inc., Proc. CIGRE Canada Conf. on Power
grid at unity power factor. This is indicated by the solar farm Systems, Winnipeg, October 19-21, 2008, Paper 544, pages 6.
inverter current being out of phase with the PCC voltage. [15] IEEE P1547 Standard for Distributed Resources Interconnected With
Electric Power Systems, IEEE P1547 Std., Sep. 2002.
V. CONCLUSION
A PV solar and wind plant based distributed generation VII. BIOGRAPHIES
system with battery storage is studied in this paper. The
bidirectional inverter of PV solar farm is utilized as a battery Vinod Khadkikar (S06-M09) was born in
charger especially during the night-time to charge the Aurangabad, Maharashtra, India, in 1978. He
batteries. A new concept of indirect feeder voltage control is received his B.E. degree in electrical engineering
from the Government College of Engineering, Dr.
presented in which the voltage rise (due to a substantial Babasaheb Ambedkar Marathwada University,
amount of reverse power flow from the wind farm) is Aurangabad, in 2000, the M. Tech. degree in
controlled by utilizing the solar farm inverter to charge the power electronics from the Indian Institute of
batteries. The solar farm inverter is operated as a three-phase Technology (I.I.T.), New Delhi, India, in 2002 and
Ph.D. degree in electrical engineering from the
controlled rectifier which draws sinusoidal currents at unity cole de Technologie Suprieure, Montral, QC,
power factor operation. MATLAB/SIMULINK based Canada, in 2008.
simulation results confirm the feasibility and effectiveness of He is currently a Postdoctoral Fellow in the Department of Electrical and
the proposed approach to regulate the feeder voltage by Computer Engineering, The University of Western Ontario, London, ON,
Canada. His research interests include applications of power electronics in
exchanging real power through the storage batteries. distribution systems, power quality enhancement, active power filters,
applications of power electronics in renewable energy resources and grid
interconnection issues.

Rajiv K. Varma (Member 1996) obtained


B.Tech. and Ph.D. degrees in Electrical
Engineering from Indian Institute of Technology
(IIT), Kanpur, India, in 1980 and 1988,
respectively. He is currently an Associate
Professor at the University of Western Ontario
(UWO), Canada. Prior to this position, he was a
faculty member in the Electrical Engineering
Department at IIT Kanpur, India, from 1989-
2001. While in India, he was awarded the
Government of India BOYSCAST Young
Scientist Fellowship in 1992-93 to conduct
research on Flexible AC Transmission System (FACTS) at the University of
Western Ontario (UWO). He also received the Fulbright grant of the U.S.
Educational Foundation in India, to conduct research in FACTS at Bonneville
Power Administration (B.P.A.), Portland, Oregon, USA, during May-Aug.
1998. He is the Chair of IEEE Working Group on "FACTS and HVDC
Bibliography" and is active on a number of other IEEE working groups. He
has received several Teaching Excellence awards both at the Faculty of
Engineering and University level at UWO. His research interests include
FACTS, power systems stability, and grid integration of wind and
photovoltaic solar power systems.

Ravi Seethapathy (SMIEEE, P.Eng, MBA) is


Manager Systems Innovation & Advance Grid
Development in the Asset Management Division
at Hydro One, a large electric T&D utility in
Ontario. His accountability includes RD&D in
advanced systems to enable the future grid,
integrate distributed renewable energy sources,
and prescribe an integrated roadmap to achieving
this. He sits on several international T&D
committees such as IEEE/CIGRE/others. He has a
B.Tech (Hons) from IIT Kharagpur, an M.Eng
degree from the University of Toronto and an MBA from the Schulich School
of Business, York University.

Potrebbero piacerti anche