Sei sulla pagina 1di 6

NASHPA Gas Processing and LPG Recovery Plant

PROC-FC-CB/NASHPA/PROJ-1247 /2015

PROJECT NO.: NASHPA 1247

DOCUMENT NO.:
HAZARDOUS AREA SCHEDULES PAGE 1 OF 6
NGP-000-ELE-15.08-0007-00

Hazardous Area Schedules

REVISION DETAILS

00 03/05/2016 Approved for Use Zhang XY Liu N Bai HJ Cheng X

B 02/03/2016 Issued for Review Zhang XY Liu N Bai HJ Cheng X

A 25/02/2016 Internal Discipline Check Zhang XY Liu N Bai HJ Cheng X

REV DATE DESCRIPTION PRPD CHKD REVD APPD

DocSize:A4
NASHPA Gas Processing and LPG Recovery Plant

PROC-FC-CB/NASHPA/PROJ-1247 /2015
DOC. NO. NGP-000-ELE-15.08-0007-00
DESCRIPTION Hazardous Area Schedules
REVISION 00
PAGE 2 OF 6

REV. DATE REVISION DESCRIPTION

A 25/02/2016 Internal Discipline Check

B 02/03/2016 Issued for Review

00 03/05/2016 Approved for Use


Process
Extent of Hazardous Zone Equipment Area
Equipment Operating Flammable Material-IP Classification Ventilation
from source Classification
Conditions
Components of
Sr. No. Flash Point of Remarks
Handled Material Auto Natural Adequate Referenc
Press. Temp. Onerous Petroleum Fluid Type of Radius Gas Temp
Tag No. Description Ignition or or In- Zone e in API
(MPa) (C) Flammable Class Category Area R (m) Group Class
Temp (C) Artificial adequate 505
Component (
Condensate /
1 SC-2001 Slug Catcher 7.2 65.6 <21 A / G(i) >200 Open Natural Adequate Zone 2 3 48 IIA T3
Natural Gas
PIG RECEIVER & GATHERING Condensate / Zone 1 1.5
2 N/A 7.2 38.7 <21 A / G(i) >200 Open Natural Adequate 49 IIA T3
MANIFOLD Natural Gas Zone 2 3
Condensate / Zone 1 1.5
3 SR-2011 Mobile Scrapper Receiver 7.2 65.6 <21 A / G(i) >200 Open Natural Adequate 49 IIA T3
Natural Gas Zone 2 3
4 PU-2001 De-Emulsifier Injection Skid 7.2 AMB Chemical HOLD 1 Zone 2 3 48 IIA T3
Condensate /
5 E-2201 Condensate Stabilizer Reboiler 0.52 204.4 <21 A / G(i) >200 Open Natural Adequate Zone 2 3 48 IIA T3
Natural Gas
6 E-2202 Condensate Heat Exchanger 0.62 176.0 Condensate <21 A >200 Open Natural Adequate Zone 2 3 48 IIA T3

7 P-2201A/B Stabilizer Around Pump 0.5 88.2 Condensate <21 A >200 Open Natural Adequate Zone 2 3 51 IIA T3
Condensate /
8 V-2201 Condensate Flash Separator 0.83 57.3 <21 A / G(i) >200 Open Natural Adequate Zone 2 3 48 IIA T3
Natural Gas
9 F-2201A/B Condensate Filter 0.93 48.9 Condensate <21 A >200 Open Natural Adequate Zone 2 3 48 IIA T3

10 F-2202 Condensate Filter/Coalescer 0.93 48.9 Condensate <21 A >200 Open Natural Adequate Zone 2 3 48 IIA T3

11 C-2201 Condensate Stabilizer 0.52 176.1 Condensate <21 A >200 Open Natural Adequate Zone 2 3 48 IIA T3

12 EA-2201 Condensate Air Cooler 0.48 129.4 Condesate <21 A >200 Open Natural Adequate Zone 2 3 48 IIA T3
Not
13 K-2201 A/B Stabilizer Compressor Skid 7.24 143.3 Natural Gas Not Applicable G(i) >400 Open Natural Adequate Zone 2 3 48 IIA T3
Applicable
Condensate Stablizer OVHD Condensate /
14 EA-2203 0.21 138.3 <21 A / G(i) >200 Open Natural Adequate Zone 2 3 48 IIA T3
Compressor Cooler Natural Gas
Condensate Stablizer OVHD Condensate /
15 EA-2202 7.24 143.3 <21 A / G(i) >200 Open Natural Adequate Zone 2 3 48 IIA T3
Compressor Cooler Natural Gas
Condensate /
16 E-2301 Inlet Gas Chiller 7.14 37.8 NA 0 A / G(i) >200 Open Natural Adequate Zone 2 3 48 IIA T3
Natural Gas /
Not
17 E-2304 Inlet Gas Heat Exchanger 7.17 42.2 Natural Gas Not Applicable G(i) >400 Open Natural Adequate Zone 2 3 48 IIA T3
Applicable
Condensate /
18 V-2301 Mol. Sieve Inlet Scrubber 7.17 25.0 <21 A / G(i) >200 Open Natural Adequate Zone 2 3 48 IIA T3
Natural Gas
Not
19 F-2301A/B Feed Gas Filter/Coalescer 7.17 25.0 Natural Gas Not Applicable G(i) >400 Open Natural Adequate Zone 2 3 48 IIA T3
Applicable
Not
20 F-2302A/B Dry Gas Filter 7.13 29.4 Natural Gas Not Applicable G(i) >400 Open Natural Adequate Zone 2 3 48 IIA T3
Applicable
Not
21 V-2304 Mercury Guard Bed 7.13 29.4 Natural Gas Not Applicable G(i) >400 Open Natural Adequate Zone 2 3 48 IIA T3
Applicable
Not
22 E-2302 Regen Gas Sub Cooler 7.1 167.8 Natural Gas Not Applicable G(i) >400 Open Natural Adequate Zone 2 3 48 IIA T3
Applicable
Not Zone 1 1.5
23 V-2303 Regen. Gas Scrubber 7.24 54.4 Natural Gas Not Applicable G(i) >400 Open Natural Adequate 6 IIA T3
Applicable Zone 2 3
Not
24 E-2303 Mol. Sieve Regen. Heater 7.41 323.9 Natural Gas Not Applicable G(i) >400 Open Natural Adequate Zone 2 3 48 IIA T3
Applicable
Not
25 V-2302A/B/C Mol. Sieve Dryers 7.17 300.0 Natural Gas Not Applicable G(i) >400 Open Natural Adequate Zone 2 3 48 IIA T3
Applicable
Not
26 K-2301A/B Regen. Gas Compressor 7.17 32.0 Natural Gas Not Applicable G(i) >400 Open Natural Adequate Zone 2 3 51 IIA T3
Applicable

NGP-000-ELE-15.08-0007-00_00 Hazardous area schedules 3


Process
Extent of Hazardous Zone Equipment Area
Equipment Operating Flammable Material-IP Classification Ventilation
from source Classification
Conditions
Components of
Sr. No. Flash Point of Remarks
Handled Material Auto Natural Adequate Referenc
Press. Temp. Onerous Petroleum Fluid Type of Radius Gas Temp
Tag No. Description Ignition or or In- Zone e in API
(MPa) (C) Flammable Class Category Area R (m) Group Class
Temp (C) Artificial adequate 505
Component (
Not
27 EA-2301 Regen. Gas Cooler 7.27 167.8 Natural Gas Not Applicable G(i) >400 Open Natural Adequate Zone 2 3 48 IIA T3
Applicable
Inlet Gas Multi Pass Heat
28 E-2403 7.1 29.4 LPG / Natural Gas NA 0 A / G(i) >200 Open Natural Adequate Zone 2 3 48 IIA T3
Exchanger
29 V-2404 Low Temperature Separator 7.03 -31 LPG / Natural Gas NA 0 A / G(i) >200 Open Natural Adequate Zone 2 3 48 IIA T3

30 C-2401 Inlet Gas Absorber 2.99 -71 LPG / Natural Gas NA 0 A / G(i) >200 Open Natural Adequate Zone 2 3 48 IIA T3

31 C-2402 De-Ethanizer Column 2.99 102.2 LPG / Natural Gas NA 0 A / G(i) >200 Open Natural Adequate Zone 2 3 48 IIA T3
Not
32 TE/TER-2401 Turbo Expander compressor 7.06 48.6 Natural Gas Not Applicable G(i) >400 Open Natural Adequate Zone 2 3 51 IIA T3
Applicable
33 C-2403 De-Butanizer Column 1.72 162.2 LPG NA 0 A >200 Open Natural Adequate Zone 2 3 48 IIA T3

34 C-2404 De-Propanizer Column 2.03 111.1 LPG NA 0 A >200 Open Natural Adequate Zone 2 3 48 IIA T3
De-Ethanizer Overhead
35 E-2406 3.07 -71 LPG / Natural Gas NA 0 A / G(i) >200 Open Natural Adequate Zone 2 3 48 IIA T3
Condenser
36 P-2401A/B Absorber Bottom Pump 2.99 -67.2 LPG NA 0 A >200 Open Natural Adequate Zone 2 3 51 IIA T3

37 P-2402A/B De-Ethanizer Reflux Pump 2.9 -60.1 LPG NA 0 A >200 Open Natural Adequate Zone 2 3 51 IIA T3

38 P-2403A/B De-Butanizer Reflux Pump 1.67 61.4 LPG NA 0 A >200 Open Natural Adequate Zone 2 3 51 IIA T3

39 P-2404A/B De-Propanizer Reflux Pump 1.98 56.8 Propane NA 0 A 450 Open Natural Adequate Zone 2 3 51 IIA T3
Propane / Natural Zone 1 1.5
40 V-2407 De-Propanizer Reflux Drum 1.98 56.8 NA 0 A / G(i) >400 Open Natural Adequate 6 IIA T3
Gas Zone 2 3
41 E-2408 De-Propanizer Reboiler 1.67 61.4 LPG / Natural Gas NA 0 A / G(i) >400 Open Natural Adequate Zone 2 3 48 IIA T3

42 E-2405 De-Ethanizer Reboiler 3 92.8 LPG / Natural Gas NA 0 A / G(i) >400 Open Natural Adequate Zone 2 3 48 IIA T3

43 V-2405 De-Ethanizer Reflux Drum 2.9 -60.1 LPG / Natural Gas NA 0 A / G(i) >400 Open Natural Adequate Zone 2 3 48 IIA T3

44 E-2407 De-Butanizer Reboiler 1.72 173.9 LPG / Natural Gas NA 0 A / G(i) >200 Open Natural Adequate Zone 2 3 48 IIA T3
De-Butanizer OVHD Reflux Zone 1 1.5
45 V-2406 1.67 61.4 LPG / Natural Gas NA 0 A / G(i) >400 Open Natural Adequate 6 IIA T3
Drum Zone 2 3
46 EA-2401 De-Butanizer O/H Cooler 1.67 72.2 LPG / Natural Gas NA 0 A / G(i) >400 Open Natural Adequate Zone 2 3 48 IIA T3

47 EA-2402 Condensate Cooler 1.72 173.9 Condensate <21 A >200 Open Natural Adequate Zone 2 3 48 IIA T3
Propane / Natural
48 EA-2403 De-Propanizer O/H Air Cooler 1.67 58.9 NA 0 A / G(i) >400 Open Natural Adequate Zone 2 3 48 IIA T3
Gas
49 EA-2404 LPG Cooler 2.03 118.3 LPG NA 0 A >400 Open Natural Adequate Zone 2 3 48 IIA T3
Zone 1 1.5
50 V-4101 Methanol Storage Tank ATM AMB Methanol 12 C 385 Open Natural Adequate 6 IIA T3
Zone 2 3
51 P-4101A/B Methanol Injection Pump 7.24 AMB Methanol 12 C 385 Open Natural Adequate Zone 2 3 51 IIA T3
Not
52 K-1701A/B Propane Compressor 1.9 79 Propane Not Applicable G(i) 450 Open Natural Adequate Zone 2 3 51 IIA T3
Applicable

NGP-000-ELE-15.08-0007-00_00 Hazardous area schedules 4


Process
Extent of Hazardous Zone Equipment Area
Equipment Operating Flammable Material-IP Classification Ventilation
from source Classification
Conditions
Components of
Sr. No. Flash Point of Remarks
Handled Material Auto Natural Adequate Referenc
Press. Temp. Onerous Petroleum Fluid Type of Radius Gas Temp
Tag No. Description Ignition or or In- Zone e in API
(MPa) (C) Flammable Class Category Area R (m) Group Class
Temp (C) Artificial adequate 505
Component (

53 EA-1707 Propane Condenser 1.9 80 Propane NA 0 A 450 Open Natural Adequate Zone 2 3 48 IIA T3

54 V-1702 Propane Suction Scrubber 0.02 -36.5 Propane NA 0 A 450 Open Natural Adequate Zone 2 3 48 IIA T3

55 V-1701 Propane Accumulator 1.9 54.4 Propane NA 0 A 450 Open Natural Adequate Zone 2 3 48 IIA T3

56 V-1703 Economizer 0.75 20 Propane NA 0 A 450 Open Natural Adequate Zone 2 3 48 IIA T3
Not
57 K-2501A/B/C Sale Gas Compressor 8.62 134.3 Natural Gas Not Applicable G(i) >400 Open Natural Adequate Zone 2 3 51 IIA T3
Applicable
Not
58 EA-2501A/B/C Sale Gas Air Cooler 8.62 48.9 Natural Gas Not Applicable G(i) >400 Open Natural Adequate Zone 2 3 48 IIA T3
Applicable
Not
59 V-2501A/B/C Suction Scrubber 3.5 48.6 Natural Gas Not Applicable G(i) >400 Open Natural Adequate Zone 2 3 48 IIA T3
Applicable
Not
60 V-2502A/B/C Discharge Scrubber 8.62 48.9 Natural Gas Not Applicable G(i) >400 Open Natural Adequate Zone 2 3 48 IIA T3
Applicable
61 EA-2701 LPG Inlet Storage Cooler 1.99 48.9 LPG NA 0 A >400 Open Natural Adequate Zone 2 3 48 IIA T3

62 EA-2801 Propane Inlet Storage Cooler 1.98 48.9 Propane NA 0 A 450 Open Natural Adequate Zone 2 3 48 IIA T3
Zone 1 1.5
63 V-2701~2736 LPG Storage Bullet 1.45 37.8 LPG NA 0 A >400 Open Natural Adequate 6 IIA T3
Zone 2 3
Zone 1 1.5
64 V-2737~2738 Off Spec LPG Storage Bullets 1.45 48.9 LPG NA 0 A >400 Open Natural Adequate 6 IIA T3
Zone 2 3
Zone 1 1.5
65 V-2839 Propane Storage Bullets 1.45 37.8 Propane NA 0 A 450 Open Natural Adequate 6 IIA T3
Zone 2 3
66 P-2701A/B/C LPG Loading Pump 1.93 48.9 LPG NA 0 A >400 Open Natural Adequate Zone 2 3 51 IIA T3

67 P-2801A/B Propane Loading Pump 2.32 37.8 Propane NA 0 A 450 Open Natural Adequate Zone 2 3 51 IIA T3

68 P-2702A/B Off-Spec LPG Transfer Pump 1.86 48.9 LPG NA 0 A >400 Open Natural Adequate Zone 2 3 51 IIA T3

69 P-1401A/B Off-Spec Condensate Pump 1.86 48.9 Condensate <21 A >200 Open Natural Adequate Zone 2 3 51 IIA T3
Zone 1 1.5
70 LA-2701A/B LPG Loading Arms 1.93 48.9 LPG NA 0 A >400 Open Natural Adequate 13 IIA T3
Zone 2 4.5
Zone 1 1.5
71 LA-2701A/B Propane Loading Arms 2.32 37.8 Propane NA 0 A 450 Open Natural Adequate 13 IIA T3
Zone 2 4.5
72 LPG Odorizer Unit 1.93 48.9 Tetrahydrothiophene <21 C >200 Open Natural Adequate Zone 2 3 48 IIA T3

73 Propane Odorizer Unit 2.32 37.8 Tetrahydrothiophene <21 C >200 Open Natural Adequate Zone 2 3 48 IIA T3
Not Zone 1 1.5
74 V-3001 Fuel gas knock Out Pot 4.8 15.6 Natural Gas Not Applicable G(i) >400 Open Natural Adequate 8 IIA T3
Applicable Zone 2 3
Zone 1 1.5
75 V-3301 Slop Vessel ATM AMB Condensate <21 A >200 Open Natural Adequate 8 IIA T3
Zone 2 3
76 P-3301A/B Slop Pump ATM AMB Condensate <21 A >200 Open Natural Adequate Zone 2 3 51 IIA T3
Zone 1 1.5
77 T-4001 Diesel Storage Tank ATM AMB Diesel 55 (1) C 220 Open Natural Adequate 8 IIA T3
Zone 2 3
78 P-4001A/B Diesel Transfer Pump ATM 10.0 Diesel 55 (1) C 220 Open Natural Adequate Zone 2 3 51 IIA T3

NGP-000-ELE-15.08-0007-00_00 Hazardous area schedules 5


Process
Extent of Hazardous Zone Equipment Area
Equipment Operating Flammable Material-IP Classification Ventilation
from source Classification
Conditions
Components of
Sr. No. Flash Point of Remarks
Handled Material Auto Natural Adequate Referenc
Press. Temp. Onerous Petroleum Fluid Type of Radius Gas Temp
Tag No. Description Ignition or or In- Zone e in API
(MPa) (C) Flammable Class Category Area R (m) Group Class
Temp (C) Artificial adequate 505
Component (

79 F-4001A/B Diesel Filters ATM 10.0 Diesel 55 (1) C 220 Open Natural Adequate Zone 2 3 48 IIA T3

80 V-3401 Plant Air Vessel 1 43.3 Air Non Hazardous

81 V-3403/3404 Instrument Air Vessel 1 43.3 Air Non Hazardous

82 PU-3401 Instrument Air Package 1 43.3 Air Non Hazardous

83 PU-3901 Inert Gas Generation Package 1 43.3 Nitrogen Non Hazardous

84 N/A MCC Building Non Hazardous

85 N/A CCR Building Non Hazardous

86 N/A Switch Gear Room Non Hazardous

87 N/A Power Generation Building Non Hazardous


Produced Water Treatment Zone 1 1.5
88 TR-3801 ATM AMB Oily Water <21 A >200 Open Natural Adequate 50 IIA T3
Package Zone 2 3
Zone 1 1.5
89 TK-3802 Produced Water Storage Tank ATM AMB Oily Water <21 A >200 Open Natural Adequate 50 IIA T3
Zone 2 3
Zone 1 1.5
90 TK-3801 Oily Water Basin ATM AMB Oily Water <21 A >200 Open Natural Adequate 50 IIA T3
Zone 2 3

NGP-000-ELE-15.08-0007-00_00 Hazardous area schedules 6