Sei sulla pagina 1di 5

{PART 1}

BACK TO
BASICS:
The Fundamentals of
4-20 mA Current Loops

1
{PART 1}
BACK TO
BASICS:
The Fundamentals of
4-20 mA Current Loops

In the world of process


control, there are a myriad Not knowing fact, the formula we need is
relatively simple: V = I x R
of different types of process the basics could This is Ohms Law. What
inputs. Thermocouples
and RTDs provide direct potentially cost you this is saying is that the
temperature reading while money... voltage (V) is equal to the
current (I) multiplied by the
digital signals such as
Modbus provide exacting resistance (R) ("I" stands for
you money when it comes
control over process variables Intensit de Courant, French
time to make decisions about
and display. Analog signals, for Current Intensity). This is
process display and control.
where information about the the fundamental equation in
Having a grasp on the history,
process is transmitted via electrical engineering.
workings, pros and cons of
varying amounts of voltage or + V1 -
the 4-20 mA loop will help
current, are the predominant you to understand why it is
R1
type of input in industries the dominant standard for
requiring process control the industry and allow you
today. Of all possible analog to make informed decisions + +
signals that can be used to about your process control. Vtot R2 V2
transmit process information, - -
the 4-20 mA loop is, by far, What is a 4-20 mA
the dominant standard in the Current Loop? R3

industry.
In order to understand
- V3 +
As major as the 4-20 mA what a 4-20 mA direct current
loop standard has become in (DC) loop is and how it Consider the simple DC
the process control industry, works, we will need to know circuit above, consisting of
many do not understand the a little bit of math. Dont a power supply and three
fundamentals of its setup and worry; we wont be delving loads. A current loop requires
use. Not knowing the basics into any advanced electrical voltage to drive the current.
could potentially cost engineering formulas. In This is provided by the power

2
supply, with the voltage of the limit the amount of flow in
supply labeled as Vtot. Current the pipe, similar to how a
then flows through the loop, resistor limits the current. The
passing through each load. flow through the pipe, and
The voltage drop at each load likewise the current through
can be calculated from Ohm's the wire, remains constant A Little Bit
Law. The voltage drop V1 throughout the system, of History
across R1 is: even though pressure, and
likewise voltage, will drop
Before the advent of
at various points. This is
electronic circuitry, process
why using current as a
V1 = I x R1 means of conveying process
control was a wholly
mechanical endeavor.
information is so reliable.
Facilities used pneumatic
Components of a control signals where
controllers were powered
Every element in the loop 4-20 mA Loop by varying pressures of
either provides voltage, or Now that we have an compressed air.
has a voltage drop. However, understanding of how and
the current, I is the same why current is used, we can
Ultimately, air
everywhere in the loop. This compression of 3-15 psi
begin to understand what
is the critical principle of the became the standard for a
exactly the loop is for.
4-20 mA loop. Current is the few reasons:
same in all places throughout 1 Sensor
Very expensive to
the loop. First, there needs to be engineer systems
It may be difficult to some sort of sensor which detecting pressure
understand why the current measures a process variable. signals under 3 psi
remains constant, so consider A sensor typically measures
temperature, humidity, Signals below 3 psi
your homes water system
flow, level or pressure. The would be unrecognizable
as a comparison. There is a
certain amount of pressure in technology that goes into the Easier to differentiate a
the water pipes pushing the sensor will vary drastically live zero (3 psi) signal
water towards your house. depending on what exactly it from a failure in the
Voltage, in a similar fashion, is intended to measure, but system (0 psi)
acts as a pressure, pushing this is not relevant for this
current through the circuit. discussion. In the 1950s, as
When a tap inside your electronic systems
2 Transmitter became less expensive,
home is turned on, there is a
subsequent flow of water. The Second, whatever the current input became
flow of water is analogous sensor is monitoring, there the preferred and more
to the flow of electrons, or needs to be a way to convert efficient process control
current. The ability of the its measurement into a signal. The 4-20 mA range
pressure to push the water current signal, between four later became the standard
through the pipes is limited and twenty milliamps. This is for similar reasons as 3-15
by bends and restrictions in where a transmitter will come psi did.
the pipe. These restrictions into play. If, for instance, a
sensor was measuring the

3
2 Transmitter 3 Power Source
Converts sensor's measurement Supplies a voltage
into a current signal

+ -
+ 4-20 mA -

- +

4 Loop 5 Receiver
Wire connecting the sensor to the Receives and interprets
device receiving the 4-20 mA signal the current signal
and then back to the transmitter

1 Sensor
Measures a
process variable

Components of a
4-20 mA Current Loop

height of a fifty foot tank, many common voltages device receiving the 4-20 mA
the transmitter would need that are used with 4-20 mA signal and then back to the
to translate zero feet as the current loops (9, 12, 24, etc.) transmitter. The current signal
tank being empty and then depending on the particular on the loop is regulated by
transmit a four milliamp setup. the transmitter according to
signal. Conversely, it would the sensors measurement.
translate fifty feet as the tank When deciding on what This component is typically
being full and would then voltage of power supply to overlooked in a current
transmit a twenty milliamp use for your particular setup, loop setup because wire is
signal. If the tank were half be sure to consider that the so intrinsic to any modern
full the transmitter would power supply voltage must electronic system, but
signal at the halfway point, or be at least 10% greater than should be considered
twelve milliamps. the total voltage drop of the in our exploration of the
attached components (the fundamentals. While the wire
3 Power Source transmitter, receiver and even itself is a source of resistance
wire). The use of improper that causes a voltage drop
In order for a signal to be
power supplies can lead to on the system, it is normally
produced, there needs to be
equipment failure. not a concern, as the voltage
a source of power, just as
in the water system analogy 4 Loop drop of a section of wire is
there needed to be a source minuscule. However, over
of water pressure. Remember In addition to an adequate long distances (greater than
that the power supply must VDC supply, there also 1,000 feet) it can add up to a
output a DC current (meaning needs to be a loop, which significant amount, depending
that the current is only flowing refers to the actual wire on the thickness (gauge) of
in one direction). There are connecting the sensor to the the wire.

4
5 Receiver Pros & Cons of 4-20 mA Loops
Finally, at someplace Part of the challenge of working in an industry which
in the loop there will be a requires process control is determining if the pros outweigh
device which can receive and the cons. Making the right decision can save both time and
interpret the current signal. money.
This current signal must be
translated into units that
can be easily understood
by operators, such as the
feet of liquid in a tank or the The 4-20 mA current loop Current loops can only
degrees Celsius of a liquid. is the dominant standard in transmit one particular
This device also needs to many industries. process signal.
either display the information
received (for monitoring It is the simplest option to Multiple loops must be
purposes) or automatically connect and configure. created in situations
do something with that where there are numerous
information. Digital displays, It uses less wiring and process variables that
controllers, actuators, and connections than other require transmission.
valves are common devices signals, greatly reducing Running so much wire
to incorporate into the loop. initial setup costs. could lead to problems
with ground loops if
These components are all Better for traveling long independent loops are not
it takes to complete a 4-20 distances, as current does
not degrade over long properly isolated.
mA current loop. The sensor
measures a process variable, connections like voltage. These isolation
the transmitter translates It is less sensitive to requirements become
that measurement into a background electrical noise exponentially more
current signal, the signal complicated as the number
travels through a wire loop to Since 4 mA is equal to of loops increases.
a receiver, and the receiver 0% output, it is incredibly
displays or performs an action simple to detect a fault in
with that signal. the system.

Summary
The 4-20 mA current loop is the prevailing process control
signal in many industries. It is an ideal method of transferring by Simon Paonessa - Technical Writer
process information because current does not change as it and Bruce McDuffee - Technical Writer
Precision Digital Corporation
travels from transmitter to receiver. It is also much simpler
and cost effective. However, voltage drops and the number
of process variables that need to be monitored can impact
its cost and complexity. By knowing these fundamentals you
will be able to make more informed decisions about process
control in your facility which could affect your bottom line.

Potrebbero piacerti anche