coefficient. 4
0 FEM analysis
-0,25 -0,2 -0,15 -0,1 -0,05 0 0,05 0,1 0,15 0,2 0,25 experimental after endurance test
-2
6
Endurance test induces high stress levels that
4
2
cause low cycle fatigue. Even if transformer
passes endurance test and low cycle fatigue do
experimental
V [l]
FEM analysis
0
-0,3 -0,2 -0,1 0 0,1 0,2 0,3
-2
not provoke transformer failure, its impact on
transformer is clearly visible on p-V chart.
-4
-6
-8
5. References
-10
p [bar]
Fig. 3: Results comparison for experimental [1] EN 50464-4 Three phase oil-immersed
testing and FEM analysis for 250 kVA distribution transformers - part 4:
transformer requirements and tests concerning
It is visible that there is a good compliance pressurized corrugated tanks, April 2007.
between experimental and numerical results.
Experimental results shows divergence from
linearity, and that is possible to explain by
residual stresses due to welding, hot-dip
galvanizing etc.
Maximum deformation of transformer rib is
also measured during experimental tests.
Comparison between measured deformation
and deformation calculated by FEM analysis is
shown in Tab. 1.