FM 200 - CLEAN AGENT SYSTEM

The amount of FM200 require to achieve the design concentration is calculated from the
following formula :

V C
W= 100 C
S

S = 1.885 + 0.0046 t

where ;

W = pounds of agents required per cubic foot of protected volume


to produce indicated concentration at temperature specified

t = the design temperature in hazard area (F)

s = specific volume of superheated FM200 vapor

C = design concentration, % by volume = 7%

V = net volume of hazard, ft3 (enclosed volume minus fixes structures)

Available FM200 cylinder in the market :

Capacity Discharge Outlet


10 lb. 1
20 lb. 1
40 lb. 1
70 lb. 1
125 lb. 1
200 lb. 2
350 lb. 2
600 lb. (old style) 2
600 lb. (new style) 3
900 lb. 3

S/FM/1
FM200/ MDKL
1) CONSUMER MSB ROOM (GRD FLR)

Area : (8.3 x 8.5) m2


Height :4m
Room volume : 282.2 m3 = 9951 ft3

Take t = 25C = 77F


Required Amount :
9951 7
W=
1.885 0.0046(77) 100 7

= 335 lb

= 152 kg

2) GENSET ROOM (GRD FLR)

Area : (8.3 x 5.9) m2


Height :4m
Room volume : 195.9 m3 = 6907 ft3

Take t = 25C = 77F


Required Amount :
6907 7
W=
1.885 0.0046(77) 100 7

= 233 lb

= 106 kg

3) SERVER ROOM (5TH FLR)

Area : (4.9 x 5.9) m2


Height :4m
Room volume : 115.64 m3 = 4078 ft3

Take t = 25C = 77F


Required Amount :
4078 7
W=
1.885 0.0046(77) 100 7

= 138 lb

= 63 kg

S/FM/2
FM200/ MDKL
4) TNB BATTERY ROOM (TNB SUBSTATION)

Area : (2.9 x 5.8) m2


Height : 3.6 m
Room volume : 60.55 m3 = 2135 ft3

Take t = 25C = 77F


Required Amount :
2135 7
W=
1.885 0.0046(77) 100 7

= 72 lb

= 33 kg

5) SWITCHGEAR ROOM (TNB SUBSTATION)

Area : (7.9 x 7.8) m2


Height : 3.6 m
Room volume : 221.8 m3 = 7822 ft3

Take t = 25C = 77F


Required Amount :
7822 7
W=
1.885 0.0046(77) 100 7

= 263 lb

= 120 kg

6) CONSUMER SWITCHGEAR ROOM (TNB SUBSTATION)

Area : (4.4 x 7.8) m2


Height : 3.6 m
Room volume : 123.55 m3 = 4357 ft3

Take t = 25C = 77F


Required Amount :
4357 7
W=
1.885 0.0046(77) 100 7

= 147 lb

= 67 kg

7) CONSUMER TRANSFORMER ROOM (TNB SUBSTATION)

S/FM/3
FM200/ MDKL
Area : (2.8 x 7.8) m2
Height : 3.6 m
Room volume : 78.62 m3 = 2773 ft3

Take t = 25C = 77F


Required Amount :
2773 7
W=
1.885 0.0046(77) 100 7

= 94 lb

= 43 kg

8) MAIN SWITCH ROOM (TNB SUBSTATION)

Area : (2.8 x 7.8) m2


Height : 3.6 m
Room volume : 78.62 m3 = 2773 ft3

Take t = 25C = 77F


Required Amount :
2773 7
W=
1.885 0.0046(77) 100 7

= 94 lb

= 43 kg