Sei sulla pagina 1di 1

GRC BANGI

CALCULATION FOR EXHAUST FAN SYSTEM

For Fume Hood 1 :

Type of hood : Wall mounted canopy


Type of equipment : Medium duty
Minimum exhaust flow rate : 0.35 m3/s (refer Table 1)
Length of Hood :6m

Hence, Q = 6 m x 0.35 m3/s per linear meter of hood


= 2.1 m3/s
= 4,443 cfm
4,500 cfm

For Fume Hood 2 & 3 :

Type of hood : Wall mounted canopy


Type of equipment : Medium duty
Minimum exhaust flow rate : 0.35 m3/s (refer Table 1)
Length of Hood : 1.2 m

Hence, Q = 1.2 m x 0.35 m3/s per linear meter of hood


= 0.42 m3/s
= 889 cfm
900 cfm

Table 1 : Typical Minimum Exhaust Flow Rates for Listed Hoods by Cooking Equipment Type

Minimum Exhaust Flow Rate, m3/s per Linear Metre of Hood


Light Duty Medium Duty Heavy Duty Extra Heavy
Type of Hood Equipment Equipment Equipment Duty
Equipment
Wall mounted canopy 0.23 to 0.31 0.31 to 0.46 0.31 to 0.62 0.54+
Single Island 0.39 to 0.46 0.46 to 0.62 0.46 to 0.93 0.85+
Double Island (per side) 0.23 to 0.31 0.31 to 0.46 0.39 to 0.62 0.77+
Eyebrow 0.23 to 0.39 0.23 to 0.39 - -
Backshelf/ Pass-over 0.15 to 0.31 0.31 to 0.46 0.46 to 0.62 Not
recommended

Reference : 1995 ASHRAE Applications Handbook (SI)