Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Effects of unbalance:
1. The unbalance decreases the motor efficiency by causing extra heating
in the motor. Heat generated also effect the equipment life by increasing
the operating temperature, which decompose the grease or oil in the
bearing and de-rate the motor windings.
2. In induction motors connected to unbalanced supply, the negative
sequence currents flow along with positive sequence current resulting in
decreased percentage of productive current and poor motor efficiency.
Any unbalance above 3% hampers the motor efficiency.
3. Torque (and thus the speed) produced by the motor becomes
fluctuating. These sudden changes in torque cause more vibration in the
gear box or the equipment connected to it. The vibration and noise
produced damages the equipment and also reduces the efficiency of
equipment.
4. The variable frequency or speed drives connected to an unbalanced
system can trip off. VFD treats high level unbalances as phase fault and
can trip on earth fault or missing phase fault.
5. Unbalances cause de-rating of power cables and thus increase I2R
losses in the cable. For distribution cables de-rating factor represents the
part of total current giving fruitful outcomes.
6. UPS or inverter supplies also perform with poor efficiency and inject
more harmonic currents in case of unbalances in the system.
7. Negative phase sequence current flowing due to unbalance can cause
faults in the motor, resulting in, tripping or permanent damage of the
electrical equipment.
Quantifying the losses-
An unbalance of 1% is acceptable as it doesnt affect the cable. But above
1% it increases linearly and at 4% the de-rating is 20%. This implies
[3]
that- 20% of the current flowing in the cable will be unproductive and
thus the copper losses in the cable will increase by 25% at 4% unbalance.
1. For motors, an unbalance of 5% will result in capacity reduction by
25%. That means, the motor current will increase to match the
[4]
Control Measures-
1. All the single phase loads should be distributed on the three phase
system such that they put equal load on three phases.
2. Replacing the disturbing equipments i.e. with unbalanced three phase
reactance.
3. Reducing the harmonics also reduces the unbalance, which can be done
by installing reactive or active filters. These filters reduce the negative
phase sequence currents by injecting a compensating current wave.
4. In case the disturbing loads cannot be replaced or repaired, connect
them with high voltage side this reduces the effects in terms of percentage
and even controlled disturbance in low voltage side.
5. Motors with unbalanced phase reactance should be replaced and re -
winded.
To identify the exact reasons for unbalance, Zenatix recommends
metering at different loads in the distribution. Zenatix can collect high
resolution data from these metering locations and analyze it to identify
the exact causes and control measures that can result in improvement in
the unbalance. Further, such detailed metering will provide data that can
be used to identify other wastages that happen in the day to day operations
of a facility thus providing further benefits of the installed solution.
Case Study-
For further clarification on the voltage and current unbalance, three phase
currents of two of the zenatixs customers were analyzed. For the purpose
of case study, we can name the two clients as client1 & client2.
First, the readings of three phase currents were taken at the frequency of
15 minutes for a month. Then we need to remove the readings during non-
working hours too, as during such times load current will be quite low
and thus a current unbalance of only 2-3 amps can shown very high
percentage unbalance. After refining the data, percentage of unbalance
was calculated by running simulation on R-software. As all the readings
mentioned are taken at the duration of 15 minutes, we got percentage
unbalance readings for the whole month with the frequency of 15 minutes.
These continuous readings were then plotted.
It is clear by only looking at the plot that for client1s system is more
balanced as compared to client2s. Further analysis was done for getting
consolidated data on what is maximum unbalance, what is the average
unbalance and which phase is causing it.
Following data was tabulated based on the results obtained after analysis.
Fig.1 Shows the plot of percentage unbalance with time for zenatixs
client with balanced system.
Fig.2 Shows the plot of percentage unbalance with time for zenatixs
client with balanced system.
Fig.3 -Shows the comparison between the system of two clients.
References-
[1] De-rating of Induction Motors Operating with a Combination of
Unbalanced Voltages and Over- or Under-voltages- P.Pillay, Jean
Newell Distinguished Professor in Engineering, Clarkson University
AND P.Hofmann, Manager of Power Quality , Manhattan, NY. [2]-
Limits for Voltage Unbalance in the Electricity Supply System, Version
1.0, 30th November 2005, Prepared by- Abu Dhabi Distribution
Company, Al Ain Distribution Company and RASCO. [3]- CHK
GridSense PTY Ltd. Suite 102, 25 Angas Street, Meadowbank, NSW
2114, Australia-
GridSense.com [4]- http://www.larsentoubro.com/lntcorporate/ebg/html/
negative_sequence.html[5]- http://www.iaeng.org/publication/IMECS20
11/IMECS2011_pp948-952.pdf