Vertical distance between stairway landings are limited to 3.69 m (12 ft) in
MEANS OF EGRESS 29
assembly occupancies, distance is 2.43 m (8 ft)
8 Provide protected/enclosed horizontal exits with self-closing fire doors. 35 Ramp slopes should not exceed 30.3 cm. (1 ft) in 3.03 m (10 ft.).
Travel distance to an exit shall not be more than ________________ No openings other than the required exits are permitted and exit passageways
9
meters. should be one (1) hr fire resistive construction for a three (3) storey building or
36
less and two (2) hrs for four (4) storey building or more. Any opening therein shall
10 Exit doors shall swing in the direction of exit travel. be protected with an approved self-closing fire doors.
Revolving doors shall not be used as means of egress except
11 37 Exit illumination and directional EXIT signs shall be provided.
__________________________
Exit door/s should be openable from the inside without the use of keys, Panic hardware is required on exit doors. In lieu of this, doors shall have no locks
12 38
special knowledge or effort flush bolts or surface bolts are prohibited. or latches.
19 Dead-end corridors and exit balconies is limited to 6.08 m (20 ft). 44 Provide fire stopping for all concealed spaces.
Walls and ceilings of corridors should be fire resistive construction Provide standard fire wall with at least 100 cm (39.38 in) high parapets on all
21 45
materials. portion of the building on the property line.
Interior openings into corridor should be protected as set forth in
22 46 Extend exterior masonry walls to form parapets or wings.
___________________________.
Main stairways should have a minimum width of 112 cm. Trims and
Provide protection of all exterior walls. All exterior walls facing approved alleys
23 handrails should not project more than 8.90 cm (3 1/2 in) into the 47
which are dead-ended must have a fire resistance of _____ hours.
required width.
Doors between guests rooms and corridors shall be self-closing and Provide approved emergency alarm bell system on each floor with adequate
26 49
shall have a fire protection rating at least twenty (20) minutes. number of sending stations.
Openings in corridor partitions other than door openings shall be
27 50 Provide approved type heat and smoke detection system.
prohibited.
Basement portion of stairways should be provided with an approved Provide efficient communication system for warning occupants and calling fire
28 51
barrier where continuous to upper floor in an exit enclosure. department.
Provide approved type portable fire extinguisher (dry chemical) ABC 70 Provide fire protection/suppression during construction.
52 type, ________ lbs. capacity for every 278 m 2. (3000 ft2) of floor area or Provide fire exit plan for each floor of the building showing the routes from each
22.8 m (75 ft) travel distance on every floor level. 71
room to appropriate exits, displayed prominently on the door of each room.
Provide dry & wet standpipe system with ___ mm riser and coupling
No heating or lighting apparatus or equipment capable of igniting flammable
of fire department standards with pumps of reliable pressure &
53 72 materials shall be used in any storage or work area where rags, excelsior, hair or
connected to an adequate water supply tank. Hose and hose cabinet
other highly flammable or combustible materials are stored or used.
shall be provided at every hose gate valve on all floors.
Provide Fire Service connection with a standard outlet of 64 mm , and Provide/post "NO SMOKING" sign/s where combustible materials are stored or
54 73
102 mm dry standpipe, and shall located on a street front. handled. Such signs shall be conspicuously and suitable located.
Provide automatic fire extinguishing system where kitchen equipment is If high hazard commodities will be stored/handled, automatic fire suppression
55 74
located (Kitchenhood). system shall be provided
Provide automatic chemical extinguishing system on all areas where
56 75 Provide/post "DO NOT USE ELEVATOR IN CASE OF FIRE" sign/s.
electronic/electrical equipment are located.
Provide approved-type automatic fire extinguishing system in
LPG tank/s must be installed outside the building and should be provided with
57 accordance with NFPA 13. Approval of system plan is required prior to 76
safety devices that automatically stop the flow of gas should a leak develop.
installation
MISCELLANEOUS 77 Provide fire resistive walls between stair & kitchen area.
ADDITIONAL REQUIREMENTS (Subject to compliance with pertinent provisions of the Fire Code of the Philippines of 2008
and Philippine Standard)
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________________
____________________________________________________________________________________________
These sheets are part of the plans and shall remain attached thereto. Corrections as above indicated must be complied.
ACKNOWLEDGE BY:
APPROVED/DISAPPROVED
_______________________
City/Municipal Fire Marshal
Original (Applicant/Owners copy)
Duplicate (BO/BPLO copy as the case maybe)
Triplicate (BFP copy)