Sub: Technical specification for UPS-Regarding.

The specification
of UPS to be used in BSNL network has been
modifiedandisenc|osedat@.Further,itiStomentionthatthisis
in supersession of UPSissuedfrom this office.As decided
of the specifications
by the competentauthority it is reiteratedthat for the UPSsystem of more
than 60KVAcapacityonly modulartype UPSshouldbe purchased.

Enclosure:As above.

( M r i n a lJ a i n )
AGM (MS rr)
c{rffi{qrtFr.rq tdfi{ig
( qKd 1T{sRqr rc;Fq)

BHARAT I'IIGAM
SANCHAR LIMITEI)
(A Go!,t. of lndia Enterpr'se) UNINTERRUPTED POWER
SUPPLY (UPS) SYSTEM
ISSUE- I: May'2015

SPECIFICATION ON
UNINTERRUPTEDPOWER SUPPLY
(UPS)SYSTEM
No. : BSNl/Specification/UPS - 001/01/May'2015

BHARAT SANCHARNIGAM LIMITED


(A Government of India Enterprise)'
Bharat SancharBhawan,JanPath,
Website:www.bsnl.co.in
NEW DELHI_ l IOOO1,
INDIA

All Rights Reservedand no part of this publicationmay be reproduced,stored in a retrieval


systemor transmitted,in any form or means,electronicor mechanical,photocopied,recorded,
scanned,without written perrnissionfrom the Bharat sanchar Nigam Ltd., New Delhi (A
Governmentof India Enterprise),Bharat SancharBhawan,Janpath, New Delhi - 110 001'
Website:www.bsnl.co.in

llPage
ClauseNo. DescrfutionOf Ile4C PageNo.
INTRODUCTION 3
J
1.0 Scope
1.1 IIPS SystemConceP!
-t
1.2 UPS SystemRequircment
1.3 UPS SystemConfiguration 4-6
1.4 UPS SystemRating 7
2.0 TECHMCALREOUIREM ]T{TSOF UPS SYSTEM 8-12
Table- 1 OperatingNoise t2
Table- 2 CorrectionFactorfc : OperatingNoise 12
GENERAL REQT]IREMEI\ rS OF UPSSYSTEM 13-17
4.0 SAFTYREQUIREMENTS)FIJPS SYSTEM 18
Block Schematicof Standalor: UPSor Standalone(1+1)UPS l9
-
Svstem Fis.l
Block Schematicof Modular IPSSystem- Fig.2 20

2 l Pa g e
Introduction

1.0 Scope:

ofUPS (UnintemrptedPowerSupply)Systemsbased
This documentcontainsthe GenericRequirements
on switch Mode Power Supply (sMPS) tecbniquesfor providing unintemrptedAC power to the
equipment with varioustelecomsystems.
associated

1.1 UPS SystemConcePt:

UPssystemusedfortelecomapplication,envisagedinthisspecification,workson..oNLINE,'concept
In this concept,undernormaloperatingconditions, the AC load is fed by the inverterunit of the UPS
across
system,whicirin tum derivesits DC powerfrom Rectifierunit, while thebatteryremains-floated
mainsor
the outputofthe Rectifier unit. The i{ectifier unit drawsAC power ffom the commercialAC
standby DG set.

IntheeventofintenuptionintheACinputtotheuPs,theDCpowertotheinverterunitgets
under
instantlytransferredto battery,so that AC output of the inverterunit remainsuninterrupted'
this conditionthe batterygetsdischarged.
'oN" the DC powerto
when the commercialAC mainsis restoredor the EngineAltemator is switched
the
the inverter unit, again, gets instantly transferredback (without any interruptionto the.load) to
Rectifierunit. On reitorationofAC miins, Rectifier unit alwaysoperatesin "ChargeMode".

It enablesthe Rectifier to give higher currentto the batteryto recoupits lost capacity-faster.when the
batterygetsfully recouped-the Reitifier unit revertsbackto the float mode,automatically.

1.2 UPS system requirements:

UPSsystemconsistsmainly of the followingbuildingblocks:

1. Distribution, Switching,Control & Alarm @SCA) unit: Providesfor Distribution,Switching,


Monitoring,Controlandalarmof the UPSunit / System'
DC'
ofAC intoregulated
2. Rectifier:Rectifierunit is usedfor conversion

3, BatteryBank Batteryof suitablecapacityfor providingpowerto the inverterwhenRectifierunit is


not working dueto anyreason.

4. Inverter Unit: lnverter unit shall be capableof providing unintem.rptedAC powerto the Telecom
Equipment.

5. Static Transfer Slvitch: Static TransferSwitch is for transferringthe load, automaticallyto AC


mains(regulatedor unregulated). Transferof loadbackto UPS shall be auto/ manualbut it shall
andis withinthespecifiedlimits.
takeplicel only afterthe inverteroutputhasstabilized

6. ManualTransferSwitch:Manualtrarsferswitchis for thetransferofload frominverterto Standby


power and back to Inverterunit, manuallywithout the interruptionof power to the load' The
ffom unsynchonized
inverteroperationshouldbeprevented
interlocking switches.

T.VoltageRegu|ator:VoltageRegulator(VR)isforprovidingStandbyregulatedACpower(asperthe
requirement)to the telecomequipment.
purchaseCs

3lPage
1.3UPSSystemConfigurations:

UPSsystemsenvisagedin this specificationmay be:


UPS OR
a) A Standalone
(1+1)UPSSYstem OR
b) Standalone
c) ModularUPSSYstem.

[.3.1 StandaloneUPS or Standalone(1+l) UPS Systems:

Thistypeof systemshallbe a singleunitofrequiredcapacitywithoutredundancy or two similarunitsin


(1+1)-configurationwith redundircycapableof sharingload with otherUPS unit of sameratingand
lnat in syi.h.onousloadsharingmode.Thistypeof syitemshallhavethe components asinverterunit,
", unit and DSCA, Static iransfer Switih, and Manual Transfer Switch, all housedin a single
rectiirer
cabinet.Thesystemshallhavethebatteryofthe desiredratingasperbackuprequir.ements. ReferBlock
DiagramFig. 1. In caseof Standatone (t+t; upS system,separate AC input shallbe madeavailable
from the LT Panelfor eachUPS'
of smaller
Note: The standaloneUPS systemof given capacityshall be a singleunit. Paralleling
capacityUPSsystemsto achievetherequiredcapacityis not allowed'

1.3.2Modular UPS SYstems:

In thesetypesof systems, uPS is composed of the pluggabletypebasicmodules_ andeachmodulehas


the builclirgblock as: One rectifierunit, on" inverterunit. Static Transfer Switch, ManualTransfer
switchandDSCAunit in this conceptwill be commonfor the ultimate system capacity (asenvisaged by
the user)proposed by parallelingof theseUPS unit. DSCA
to be constituted rmit provides for all the
alarm function, und n""".ru.y terminations/switches as per the specification. In
control,monitoring
additionto this, th; DSCA shall alsohavethe capabilityof operatingits inverterunit in sYnchronous
modewith the inverterunitsof otherUPSunitsofiame makeandrating.This t)?e of LIPSunit shallbe
capableof sharingload with otherUPS unitsof sameratingand make,in synchronous load sharing
.od". R.f., Block DiagramFig. 2. The AC input to the rack shall be separatefor each rack from LT
Panel,if mofe than one rack is-used.The batteryshall be as per the desiredratingof the UPS' The
batteryAH capacitywill be accordingto the batterybackuprequirement'
Note: Any loweimodule shall becomethe part of functionalbus only after successful
completionof built in self testingof power moduleby commoncontroller;otherwiseit
shali deactivate/disconnect itself from commonbus and raiseappropriatealarm.

1.3.2.1Redundancy criteria for Modular UPS System:

The maximumnumberof UPS modulesin a systemshallbe N, whereN is the numberof basicUPS


ofthe user/ purchaser,
unitsdecidedaspertheloadrequirement unit.
andI is redundant

1.3.3Distribution,Switching,Control & Alarm Monitoring @SCA)unit:


DSCAunit shallbe partof individualuPS unit.It shallbe basedonly on menudrivenMicro Processor
controlledTechniquesfor control,monitoring& alarms.DSCA shall displayits Softwareversion.
Settingof all the parametersstrattUe ttlrough menu-drivenmicroprocessor control only. Use of
poteniiometer at any stageis precluded. The fiilure of Micro processor
or DSCA shall.notaffectthe
ietting of individuai inverteroi Rectifier.No parameterof inverteror Rectifier units shall be disturbed
on thJ f.il*" of DSCA. In this conditionall the inverterand Rectifiershalltake care of the load on
default settingsand sharethe load collectively(whereverapplicable).Only the setting of new
Darameters from DSCA shall be affected'

4lPage
UPSSystemconfigurations

The followingUPSSystemconfigurationsare proposed:

(i) STANDALONEUPSor STANDALONE(1+1)IIPS SYSTEMConfiguration:

Category Typeof Ratings


No. Svstem
Input / System Basic Basic Static Manual Battery
Output (Ultimate) Inverter rectifier Transfer Transfer Capacity
Switch Switch
1a lPh/1Ph l KVA lKVA *Inveder+ 1.1KVA 1.1KVA As per
battery back-up
requirement
1b lPh/lPh 2 KVA 2KVA -do- 2.2KVA 2,2KVA Asper
back-up
1c lPh/1Ph 3 KVA 3KVA -do- 3.3KVA 3.3KVA As per
back-up
2a 1Ph/1Ph 5 KVA 5KVA -do- 5.5KVA 5.5KVA As per
back-up
2b 1Ph/1Ph 6KVA 6KVA -do- 6.6KVA 6.6KVA As per
back-up
2C lPl/1Ph lOKVA lOKVA -do- l1KVA 1lKVA As per
back-up
3a 3Ph/lPh lOKVA lOKVA -do- l1KVA 11KVA As per
back-up
15KVA lsKVA -do- 16.5KVA 16.5KVA As per
back-up
2OKVA 15KVA -do- 22KVA 22KVA As per
back-up
3OKVA 2OKVA -do- 33KVA 33KVA As per
back-up
3b 3Ph/3Ph lOKVA lOKVA -do- 1lKVA l I K V A As per
back-up
l5KVA I5KVA -do- 16.5KVA 16.5KVA As per
back-up
2OKVA 1sKVA -do- 22KVA 22KVA As per
back-up
3OKVA 2OKVA -do- 33KVA 33KVA As per
back-up
3c 3Ph/3Ph 40/60/80/1004OKVA -do- 110Vr 1l0o/o As per
-do- r20t1601 back-up
KVA
2OO

5lPage
AnnexureI
(ii) MODULAR UPSSYSTEMConfisuration:

Category Type of Ratings


No. Svstem
InpuU System Basic BasicStatic Manual Battery
Output Conliguration UPS Transfer
Rectifier Transfer Capacity
**cN+1) Switch Switch
la Three 4OKVA *Inverter
r0/t6t20Ky + 44KVA 44KVA Asper
Phase (N+l) A battery backup
requirement
1b Three 6OKVA 10/16/20 66KVA 66KVA As per
Phase 61..1+r) KVA backup
1c Three 8OKVA 10n6/20 -do- 88KVA 88KVA As per
Phase 6g+l) KVA backup
2a Three IOOKVA 16120/25 -do- As per
Phase 15+l) KVA 1 1 0K V A 1 1 0K V A backup
2b Three 16OKVA 16t20/25 -do- 176KVA 176KVA As per
Phase (N+1) KVA backup
(max2 Raoks)
2c Three 2OOKVA 16120/25 -do- 220KVA. 220KVA As per
Phase (+N+1) KVA backup
(max2 Racks)
3a Three 250KVA l6/20/25 -do- As per
Phase (N+1) KVA 27sKVA 275KVA. backup
(max3 Racks)
3b Three 3OOKVA 16120125 -do- 33OKVA 33OKVA As per
Phase (N+1) KVA backup
(max3 Racks)

+ The rating ofrectifier shall be sufficientto take careof 1.1times the Inverter DC load and battery
load asper back-upand rate ofcharging. 6

** In this configuration N is the desired rating of Basic UPS units for load as decided by
purchaser,and I is redundant.

Note:
1. TSEC approvalshall be accordedfor ultimatecapacityonly. The versionofthe microprocessor
Soft-wareshall be indicatedin TSEC alongwith the model numberand category.
2. Hot swappability ofpower modules,staticswitchmodule,controllermodule,power
& userreplaceability
supplymoduleetc.mustbe ensured.
3. Tenderingauthority may chooseany of the abovecategories(ultimatecapacity)asper load
requirements.Load shall includethe equipmentload and any other load. While choosingthe UPS
it may also be ensuredthat the redundancyrequirementhasbeentaken careof.
4. Tenderingauthorityshall give the capacityof the batteryto be usedand batteryback up in hours.
5. Tenderingauthorityshall specifyStandaloneUPS Systemor l+1 configurationUPS Systemor
Modular UPS Systemwhile Orderingthe System.

6lPage
f.4 UPSSystemRating: Specifiedratingsof UPSsystemsare:
Type of StandaloneIJPSor Standalone Modular UPSSystems
IJPS (1+1)UPSSvstems
Input / lPh/lPh 3Ph/lPh 3Ph/3Ph 3Ph/3Ph 3Ph/3Ph
Outnut )
UPS lKVA lOKVA lOKVA 4OKVA,6OKVA IOOKVA,16OKVA,
ratings 2KVA l5KVA 15KVA & 80KVA with 200KvA,250KVA &
3KVA 2OKVA 2OKVA basicUPS 300KVAwith basicUPS
5KVA 3OKVA 3OKVA moduleratingof modulerating of
6KVA 4OKVA l0KvA/ 16KVA/2OKVA/25KVA
lOKVA 6OKVA 16KVA/
8OKVA 20KVA
lOOKVA
I2OKVA
l6OKVA
200KvA

Note:
capacity.The static
l. The rating of charger (Rectifier unit) shall be as per back-upandbattery-orde_red
TransferSwitchandtrlanualTransfeiswitchshalibe rated at 1.1timesof the UPSrating(i.e 110%of
Load).The ratingofthe batteryshallbe asperback-uprequirement'

2. It is agreedthat for morethan60KVA capacityonly modulartypeUPSshallbe procured

3. Singlephaseandthee phaseUPSsystemshallbe configuredby singlephaseandthreephase


UPSunit only at bothUPSunit aswell asrack level.

1,5 IIPS systemcompatibilitywith EngineAlternator:

TheUpSsystem(includingRectifiers,andDSCA,Inverters), fromA.C
shallbe suitablefor operation
mainsor a DG set(of capacity1.25timesAC loadof UPSSystem)'

TlPage
CHAPTER-2

2.0 TechnicalRequirementsof UPSSysteml

Sl. No. TechnicalRequirements SinglePhaseoutput ThreePhaseoutput

AC Input OperatingRange l70V to 270V(Nom.230V) 320Vto 480V(Nom.400V)


tAl 48 to 52Hz
& Frequency 48 to 52IIz
I ol(Flz and above'
IBI Charger@R/FC) @requencies

1 Operation Auto Float-cum-Chargemode.

2 ChargerVoltage Depending uPonthenumber Dependinguponthe number


(Float/Charge) of CellsusedandCell Voltage of CellsusedandCellVoltage
(2.25Y12.3VPercell or 13.5V/ (2.25Y12.3Ypercellor 13.5V/
13.8Vpermono-block). 13.8Vpermono-block).

3 ChargerEfriciency
i). At nominalinput, Betterthan89% Betterthan90%
outputandloadbetween
75o/olo 100Vo
ii). For otherspecifiedInPut, Betterthan85% Betterthan87%
outputconditions& load
between50%to 100%.
4 Peakto PeakRipple <1oloof DC Bus Voltage

J Battery ThFery shallbe SealedMaintenanceFree\IRLA Battery'


In case of 12V (6 cells) mono-blockVRLA Battery maximum
nermissiblecapacitvis - 200AH. For batteriesof capacityhigherthan
iooag, onty )V iells shall be used.Parallelingof 2V cells of AH
capacityup to 1500AH is not permitted.
tn' cus" of Mono-blockVRLA Battery parallelingof two Banks
(maximum)is Permitted.
Note:
1). PluggableModularMono-BlocktypesVRLA Batteriesare also
acceptable.
2). Onlv TSEC/TECapprovedBatteriesshallbs qpqqqqgl-
6 BatteryBackup Sfrallbe asmentionedin theOrderinglnlormation'
-
7 Battery monitoringFeature Bafte,ymonitortngFeatureshallbe providedfor
i). BatteryUnderVoltage
ii). BafteryCurrentLimiting
iii). BatteryTemperature compensatron.

8lPage
7t,t
Sl. No. Technical Requirements Single Phaseoutput ThreePhaseoutput
tcl Output Characteristics
flnverter) :
8 Inverter Output Power UPSSYstem
(i) Standalone or (i) Standalone UPSSystemor
Capacity Standalone(1+1)UPS Standalone(1+1)UPS
System: System:
a).1KVAto 10KVA- Single a). 10KVAto 30KVA- Three
PhaseinputandSinglePhase PhaseinputandThreePhase
outpuI. oulpur.
b).10KVAto 30KVA - Three b). 40KVA to 200KVA- Three
PhaseinputandSinglePhase Phaseinput andThreePhase
output. output.
(ii). ModularUPSSystem:
Detailsol UPSConfiguration and 40KVA to 300KVAwith
-
ratingsare given in Table 3 of BasicModuleratingof 10KVA,
Specification. 16KVA, 2OKVA& 25KVA iN
(N+1) configuration.ThreePhase
input andThreePhaseOutput.
DetailsofUPS Configuration and
ratings are given in Table - 3 of
Specification.
- fromL I Panel. lor
Note:Separate AC inputshallbe madeavallable
individualrack.In caseofmodularUPSsystem, SeparateAC
inputshallbe madeavailablefromLT Panel,for individual
rack if morethanonerack is used.
9 Output Voltageof Inverter Shalldelivercontinuous Shalldelivercontinuous
unintenupted singlePhasePure uninterruptedthrcephasepuresine
sinewaveoutputat 230Y/50H2. waveoutputat 400V/50H2.
10 Output VoltageSettable Shall be settablein stePsof Shall be settablein stepsof
210122012301240v 380/400/415V

1l Output VoltagStability + 2% ofthe SetVoltage


for -
1.Inputvoltagevariationin therangespecified.
2. Load cunentvariationsfrom zeroto 100%(full load)
3. Loadpowerfactor
Betterthan0.8

t2 Output Frequency The o,.rtputfrequencyshallbe synchronisedto Mainsat all times' It


shall revert Io a frequency of 50Hz+ 0'5Hz on battery operation
mode/duringfailureof Mains

13 Load PowerFactor Betterthan0.8

t4 Inverter Efficiency O. F- L""d b"tt ?5% to 100%andInputDC Voltageof


2.1SV/Cell "ett
to 2.3V/Cellor
12.9Vlmono-block to 13.8V/Mono-blockandOutputvoltageof
230V : Not lessthan 857.
(ii). For otherInput,OutputandLoadConditions: Not lessthan 80%o

15 Total Harmonic ffi shallnot bemorethan30loin


distortion
Distortion conformity with CIGREs (hrtemationalConferenceon Large Higl
) limits
VoltageElectricSyslems
9lPage
furr\u"
Sl.No. TechnicalRequirements SinqlePhaseoutput ThreePhaseoutPut
16 Soft Start Feature: ffiuch thattheinputcurrentand
of Rectifrerunit
inputvoltages reachtheir nominalvaluewithin 10
seconds.Themaximuminstantaneous cunentduringstartup shallnot
exceedthepeakvalueofthe Rectifierinputcurrentat full loadandthe
lowest specifiedinPutvoltage.
17 TransientResponse The transientovershootshall not exceedl07o wlth batteryrloateo
under the following conditions,provided it gets restoredwithin
rangewithin 100ms:
regulating

1. SwitchON
2.Stepchangeof inputvoltagespecifiedandvice-versa
3.Loadchangefrom 100%to 10oZandvice-versa

Note: Fortestpurposes, Transientovershoot at theoutputcanbe up to


30% when the battery not floated at the input, providedit is restored
withinthe limit of 10%under two cycles (40ms) andregulatingrange
withinl00ms
18 Static Transfer Switch ffihandling 110%Loadof the rated
systemcapacityshall be providedto transferthe loadautomatically
within 5 mS to AC Commercial/Stand-byMainsthroughisolation
arrangement, in casethe inverterfails to takeloaddueto anyreason'
The tiansfer Loadbackto Invertershallbe automaticin casethe
of
inverter has tripped momentarilydue to suddenOver Load or
transients.Thetransfertime in this caseshallalsobewithin5ms'
It shalltakeplace,only afterthe inverteroutputhasstabilized
and is within the specifiedlimits Howevertransferof loadbackto
invertershallbe Manualin casetheInverterhasdeveloped a Fault'
19 Manual Transfer Switch ffif handling11o%Loadofthe rated
systemcapacity shall be provided to transferthe loadto AC
iommercial / Stand-by Mains and back to UPSwithouttheinterruption
of oowerto the load.
20 Over Load Shallbec"pabkoftaking105%for 1 Hour/110%for 30minutes
of its full ratedload.In caseofexcessiveoverloador shortcircuit
at theoutputthe Invertershalltrip'
2l OperatingNoise ftt" n tty equippedUPSsystemat full load shallnot contributenoise
UPSSystemup to : (weighted) asperthelimitsmentioned in the!4bp;-!.
1OKVA< 5OdBA ihe ieference ambient noiselevelis taken as45dBA.Thenoiselevel
10KVAto 40KVA <55dBA shallbe measured at a distanceof 1 metre from the unit and 1.25m
40KVA to 100KVA<60dBA abovethe floor level in the Acoustic Range. The correctionfactor
100KVAto for TotalNoisewhenthe ambientnoiselevel is morethan45dBA
2OOKVA< 65dBA shallbe asgivenin theTable- 2.
200KVAandabove<70dBA Note:Correction Factorshallbe addedto thelimit specified to arrive
ForModularUPSSystem: at the limit when the Ambient Noise is greater than45dBA.
20 KVA to 60 KVA <70dBA
up to 120KVA <73dBA
22 Elevated Burn-in Test Th" UPS.y.t"m shallbe capableofwithstanding a Bum-in
".-pt"t"
testof50"C for 72 Hours duringTSEC and24 Hoursduring Bulk QA
testing.Thistestmaybe conducted in a controlled
temperature bumin
temoeiature controlledburnin chamb.ta1JQ[+ 2C with free air
circulationinsidethechamber

l 0l P a g e
Sl. No. TechnicalRequirements SinglePhaseoutput ThreePhaseoutput
)a CoolingArrangement NaturalConvention Coolingor ForcedCooling.Fanscanonly beused
on the front/topandrearofthe unit. -se offans on the sidesofthe unit
or rack is not permitted.Manufacturershallalsoensurethat the failure
ofthe fan doesnot causeanyfire hazard.Failureoffan shalldraw
Immediateattentionofthe maintenancestaff. Fanshallbe switchedoff
whenoutputofthe unit fails dueto anyreasonandshallstart
automaticallyon the restorationoftheir output.

24 Metering Thereshallbeprovisionon UPSlevelto monitorthefollowing:


i) AC Input Voltageto UPS
ii) AC OutputVoltage& Currentof UPS
iii) Outputfrequency
iv) OutputPowerof UPSin Watts/ K. Watts(above5 KVA)
v) DC Voltageto Inverter
vi) BatteryCunent(charge/ discharge).
The aboveanangementshall be madethrougha Digital meterwith
LED/LCDdisplay.TheDigital meter'sdisplay/Resolution shouldbe
suchthat it is clearlyandunambiguouslyreadablefrom a distanceof 1
meter.The displayunit shallbe providedat a convenientheightfor
easyreadout.

t< Protections AdequateProtectionsshallbe providedfor :

1.DC Reverse Polarityat input(ThroughFuse).


2. DC UnderVoltage
3. DC OverVoltage
4. OutpulVoltageHigh
5. OutputVoltageLow

26 Functional& Alarm Functional& AlarmIndications shallbe providedby meansofvisual


Indications display(LED/LCD):
A).FunctionalIndications:
1) Mainsavailable
2) Chargeron (Boost/ Float)
3) Loadon Inverter
4) Loadon StandbyPower
B) Alarm Indications:
1) AC MainsInputoutof rangeor AC MainsFail
2) Charger(FR/FC)Fail
3) InverterFail
4) FanFail
5) BatteryLow or No Battery(separatefor eachBattery)
6) SystemOverLoad
7) Temp.SensorFail/Open
8) Lightning ProtectionStage- 2 Devicefail (tlrough PFC)

Audio alarm Every Alarm conditionshall be accompaniedwith an Audio alarm,with


a non locking type Key or pushbutton having audiocut-offfacility.

28 &
OperatingTemperature 0 to 50 DegC & RH 95%Non condensing
RII

1 1| P a g e
Sl. No. Technical Requirements SinglePhaseoutput ThreePhaseoutput
29 Dimensions rmt=tm;iamr*tr;t not be more thani000mmfromfrontdoor
(whenprovided)
to rearwith doorfitted.Thewidthshallnotbemore
thani 100mm(max)andheightshallnotbemorethan2200mm
(max).
30 Stage-2 Protection This protectionagainst,low voltagesurgesof up to 1.5-KV, shail be
providedat the UPS systemlevel.This protectionshallbe equipped
with thermal disconnectionand potential free contactfor arresto(s)
connectedbetweenlive & neutraland neutral& earth.This protection
shallbe in compliance of IEC 62305& 60364-5-53 for the following
valuesof current:
BetweenR Y. B & N: > In: IOKA,8/20pSfor eachphase.
BetweenN&PE : > In: 20KA,8/20PS.
WhereIn: Valueofnominaldischarge current8/20pS.
Note: Voltagerating of MOVs shall be 320V minimum.Response
time of the StageII deviceshallbe < 25 nanoseconds' The Stage-2
ProtectionDeviceshallbeCACT approved

Table- 1: Operating Noise

UPSSystem Noise
Equipment PermissibleMax Noise(weighted)
w.r.t AmbientNoiselevelof 45dBA
Up to 10KVA <5OdBA 5dB
10KVAto 40KVA <55dBA 1OdB
40KVA to 100KVA <60dBA 15dB
100KVAto 200KVA < 65dBA 20dB
200KVAandabove <7OdBA 25dB
For ModularUPSSystem
i). 20KVA to 60 KVA <7OdBA 25dB
ii). Up to 120KVA < 73dBA 28dB

Table - 2: Correction Factor (C.F) for Total Noise

AMBT. C.F AMBT. AMBT.


C.F C.F AMBT. C.F
NOISE NOISE NOISE NOISE
45dBA 0dB 0.86dB
49dBA 53dBA 2.07d8 57dBA 3.69dB
46dBA 0.18dB5OdBA Ll2dB 54dBA 2.47d8 58dBA 4.17d8
47dBA 0.39dB 51dBA 1 . 4 1 d B 55dBA 2.82d8 59dBA 4.68d8
48dBA 0.61d8 52dBA 1.73dB 56dBA 3.25dB 6OdBA 5.2ldB

Note: The conection Factorshall be addedto the limit specifiedof60dBA to arrive at the
limit when the ambientis greaterthan 45dBA.

1 2 l Pa g e
CIIAPTER3

3.0 GeneralRequirements

3.1 ConstructionalFeatures: The rackstructureshallbe madeup of rigid andself-supporting


structureof steelprofiles.It shall be free of sharpedgesor comers.The sidesshall have
suitableventilating arrangements. The fiont door (if provided) & rear door shall be hinged
type. Reardoor dfront door (if provided) shall havepropervntilationarangement.Use of
ianr on th" sidesfor forcedventiiation is precluded as the racksare mountedside-by-sidein
thefield.Thegaugeof panelsshallbe 2 mm (minimum).

3.1,1 The structuralstrengthof the rack shall be suchasto withstandits ultimatemechanicalload


(with all the individualunitsmounted)without anydeformity.

3,1.2 The baseof rack shall ensureuniform floor loading of not more than 320 kg/sq. meter.
Lifting facilities shall be providedby removableeyebolt,locatedat the top of the rack/unit.
The nicessaryarrangement for fixing the rack/uniton the floor shall alsobe provided.

3.1.3 Thetop ofthe rackshallbe flrlly coveredexceptfor ventilation& cableentries'Eachair flow


vent shall be coveredby a grill to preventthe entry of foreignmateriallargerthan5mrn.

3.1.4 with doorsin position,all the commonvisualalarmsandmetersshallbe clearlyvisible.In


caseof hinged door, metersand alarm indicationsare permittedon door also.However,the
fixtureson thedoorshallnotrestrictthemovement ofdoor in anyway'
3.1.5 The rackshallbe designed for easymaintenance & irstallation.Rackmourtingarrangement
shall be such as to provide .*y u"."r, ftom front, rear and top for Installation and
Maintenance.
3.1.6 Therackshallbe madestandalone with a rigid frameworkwith bottomclearance of 110mm
with a toleranceof +/- 10mm.

3.1.7 In caseof Modularsystemif morethanoneuPS canbe accommodated in a rackthereshall


be provisionof easilymountingtolremoving from the fron1sideof the rack.In suchcase
UPb unit shallbe designedto slideinto the rackon a suitablemechanicalarrangement. The
associatedAC, DC connections, control, alarms& interfacecableconnectingthe unit shall
be connected/disconnectedeasily without causing any interruption in the suPPlY and
damage to loador other workingunis. TheunitsasperthisGR shallnot besitespecific.

3.1.8 the unitsshallbe removable


In caseof Modularsystems, fromthe frontofthe rackonly.All
AC and DC input, DC and AC output and control, alarm and monitoring cables
by plugsor connectors.
theunitsandracksshallbe easilydisconnected
interconnecting

3.1.9 Accessibility:

3.1.9.1 from front,rearor top'


All theterminationpointsshallbe easilyaccessible

3.1.9.2 by physicalbarriersto ensuresafety'


AC andDC terminalsshallbe separated

3.r.9.3 All theterminalsexceptAC earthshallbeelectricallyisolated'

3,1.10 Terminations: The Input & outputAC terminalsfor singlephasesystems shall be clearly
markedas L and N and for threephase as
systems R, Y, B & N and Input DC terminalsas
+ve& -ve respectively.

1 3l P a g e
/^l .-afuKfr1
3.1.10.1 AC Termination:

3.1.10.1.1AC terminationshall be suitably protected against the accidental touch/contactwith the


workingstaff for their protection and shattalsohaveclear and prominent"DANGER"
Marking.
3.1.10.1.2Screeningshallbe providedbetweenAC & DC components to preventaccident'

3.1.10.1.3All the connectionsbetweenDSCA unit and individual units shall be tfuough properrated
cablesonly.

andproperlyrated'
providedshallbe easilyaccessible
3.1.10.1.4Fuses& Circuit-breakers

3.1.10.2 DC Terminations:
proper
3.1.10.2.1All the connection betweenthe individual units and DSCA unit shall be thlough a
ratedluggedandcablesonlY.

3.1.r0.2.2All theAC, DC andControl,alarmcablingshallbe suppliedwith thesystem'

3.1.10.2.3All conductorsshall be properlyratedto preventexcessiveheating'

3.r.10.2.4 DC output ofthe Rectifierunit & input to the Inverterunit shall.bethroughproperratedhot


plug-in connectorson the unit andluggedterminationon the terminationend'

3.1.11 Mounting ofComponent& Layout :

mountingandfixing methodsshallbe secured'


3.1.11.1 Component

3.1.1r.2 Suitablemechanicalstructure/arrangement for holding units in position shall be providedso


thattheunit is heldfirmly by slidingthroughit.

3.2 Bus-bars: Tinned bus-barsor tinnedHigh conductivityelectrollic copperstripswith purity


of99.90%(min.)asper815-613latestissueshallbe ableto withstandmaximumloadcurrent.
The bus-baisshall be capableof carryingcurrentdensityof 2 Amp/mmzand sizeshall not be
lessthan25mmX5mmin anycase.Nuti & golts shallbe of stainless steelalongwith tinned
copperwashers.Thetinningshallbe in compliance ofIS 1359: 1992& its thicknessshallbe
10 pm(minimum).

J.J Cables& wiring: All insulatedconductorsexcept those within the confines of a


printed circuit board assembly, shallbe ofthe rating enoughto withstandthemaximum
cunent and voltageduring fault and overload. All the wires and cablesusedshall be fire
asperIS1554with amendment
retardant I (June94).All thecables& wiresusedshallalsobe
Rodent& reptilesrepellent.

3.3.r All wiring shallbe neatlysecuredin positionand adequatelysupported'Wherewirespass


throughaiy part of metal panelor coverthe hole through which they passshall be suitably
bushed.

3.4 Earthing: Proper Ea.rth terminal ( two in each rack ), with effective electrical contact
with frameworhshallbe provided.All metalpartsof the componentsJ whichdo not_carry
cunent, shall be bondedthereto.Nominal cross-sectional area of earth conductor
continuity
(coppei only), not containedwithin the cable, shall be half (minimum) of each cunent
canying conductorto be protectedbut in no caseit shall be less than 3 mm diameter.Suitable

1 4l P a g e
^NKl'
terminals shall be providedfor terminatingea(h conductor.Continuity conductor.usedfor
purposeshall only be of copper.Suitableierminals shall be providedfor terminatingearth
The manufactureiihall clearly speci! the earthingrequirementsfor trouble-free
"ondu"to..
performance ofthe UPSsystem.

3.5 Documentation:Technicalliteraturein Englishand Hindi with completelayout,detailed


block schematicand circuit diagramsof its assemblieswith test voltagesat different test
pointsofthe unitsshallbeprovidid.A softcopyaswell asa hardcopyofthe aboveshallalso
te provided.All aspectsoi installation,operation,maintenance,trouble shootingand repair
shil be coveredin ihis manual.Themanualshallalsoincludethefollowing:

a) Installation,Operationand Maintenancemanual part shallinclude :


D Safetymeasuresto be observedin handlingofthe equipment.
at thetimeofinstallation,operation
iD Precautions andmaintenance'
iiD RequiredTestJigsandfixtures.
iv) Proceduresfor routine maintenance,preventive maintenance,trouble shooting and
replacemenl
v) Illustrationof intemalandextemalmechanical parts.
vij Completelayout,detailedblock and
schematic with test
circuitdiagramsof its assemblies
voltagesat differenttest points
vii) circuit descriptionandworkingof UPS System(Inverter,Rectifier,DSCA units,Static
TransferSwitch and vR unit) ai variousstagesstadngfrom AC input to Rectifier to the
AC outputwith BlockSchematic.
viii) Circuitdescription& workingof DSCA.
ix) A Tablegiving detailsof sizeldimension of maintenance of cables& Bus-barusedin the
design.
x) EarthingGuidelinesfor theUPSsystemasperBIS Specifrcation'
xi) Testmethodfor testingeachandeveryparameterof the unit andwhole system'

b) Repair manual :
i) List ofreplaceable partsusedwith thesourceofprocurement'
iil Detailedorderinginformationfor all replaceable partsfor orderingof sparesasandwhen
reouired.
iii) hlcedure with flowchartfor troubleshootingandsub-assembly replacement'
ivjTest Instruments,Test fixtures,accessories andtools requiredfor maintenanceandrepair.
vj Systematic troubleshooting charts(faulttree)for probablefaults andtheirremedialaction.
vi) Addressandtelephonenumbers ofMainlenance centre.

3.5.1 Hard copy of the documentationshall be preparedusing goodquality paperwith clear1nd


crispprinting.All the drawingsin clearprintingshallbe attachedto the hand-book binding.
fhe Uinaingof the manualshall be long lastingand presentable. One set of flow chart
drawingsneiessary shallbeprovidedwith lamination,
for trouble-shooting with eachmanual.

3.6 Quality Requirenents

3.6.r Components : The componentparts of the equipment shall be of professiorralgade of


reputid manufacturerto ensurepromptand continuousservice and delivery of spareparts.
is precluded.
Uie ofpotentiometer ThelistedCACTcomponents only shallbeused'

3.6.1.1 Power Transformersand chokes: Powertransformers and chokesshall useclassB or


highergradeof insulation.Theseshallbe woundwith copperwire andadequateinsulation
shallbe provided.

1 5l P a g e
t'flF,,1eru
3.6.1.2 Fuses or circuit breakers shall be provided wherever appropriate to protect against
circuit' Fusesshallconformto BIS specification'
failure of control/sensing
after
3.7 Quality AssuranceTests:Eachof the UPS systemsuppliedagainstthe specificorder
and
type approvalshall be inspected testedto ensurethat the of
requirements this document
havebeenmet. Thesetestsshallbe carriedoutby QA wing ofBSNL'

3.8 Finish and Painting: Thefinish of the structureandpanelsshallconformto the latestissue


ofIS 101& IS 168. Thestructure andpanelsshallonly be powderedcoated.Thethickness of
powdercoatingshallbebetween50 to 70 micrometers. TheColourusedshallconform to IS 5
latestissue.Colourscheme shallbe asfollows :
Outsideexceptftont panel - SatinBlue,No. 177.
Insideandfrontpanei. - ShallharmoniouslymatchtheoutsideColour'
-
ups flnverter& Rectifierunits)units Shall harmoniouslymatchwith rackcolour.

3.9 Marking & Labeling:

3.9.1 It shallbe possibleto locateeachcomponent on the PcB by the layout& circuitdrawing._All


terminalsshall be properly sign-writtenand all componentsproperly labeledto enabletheir
identificationwith ieferenteto the supplier'sInstallationoperation,maintenance manualand
repair manuals. Designationof keys, switches ald components mounted on the
9th9r 'The
front/insidepanelandtieir operating positionsshall be clearly engravedor sign- written'
wiring shallbe clearlyandp"*-"-ntly identifiedwith the designation or colourcodewhich
correi'pondsto the equipmint circuit diagram.Where non-standard colours are used cable
functionsshall be clearly& permanentlylabelledat both ends'

3.9.2 Fuseholderidentificationshallincludedetailsof fuseratingandtype.In caseof fuseson PCB


theratingshallbe eitheron fuseor PCBat thebaseofthe fuse'

3.9.3 A screenprinted,circuit& cablingdiagramshallbe placedin sideof the front dooror any


otherconvenientplacefor readyreferenceofthe maintenancestaff'

3.9.4 Danger Label : Each unit shall have a screenprinted "Danger"label duly fixed in
prorn'inentplacewith RED charactersagainstWHITE background'

3.9.5 Name plate : A name plate,anodisedor screenprinted,shall be suitably fixed on each


rack/unit and contain following information:
l. GR Number:
2. TACNo. :
3. Typeofthe Unit :
4. Manufacturer'snameandidentification:
5. ModelNo. :
6. Unit SerialNo. :
7. Input voltage :
8. OutputVoltage& rating :
9. Yearof manufacture:

3.9,5.1 on the front top of the Rack, an etchedengravedor anodiseddesignationplate in BoLD


lettersshowingisystemConfiguration & theratingofthe system"shallbeprovided.
3.10 MTTR & MTBF:

3.10.1 MTTR:Themeantimetorepair/replaceafaultyunitshallbelessthan20minutes.

1 6l P a g e
.-fuiv
3.10.2 MTBF (Mean fime BetweenFailures): MTBF of the systemshall not be lessthan 100'000
houn. Tile MTBF for fans shall be betterthan 70,000hoursat 40 degreeC. The concurence
of cACT of QA wing of BSNL in this regardis mandatory.The MTBF shall be verified as
per QM-115. MTBF, predicted and observed values shall be fumished along with
calculationsby the manufacturer.Basedon thesefigurestlree yearsmaintenance sparesshall
be specifiedby the equipmentsupplier.The equipmentavailability shall 99
exceed '9/o'

3.11 Fietd Observations: For new productsfield observationwill be carriedout for the first
5 systemsprocured by the departmen! to assessthe performanceofthe equipmentfor a
period nof exceeding6 monthsfrom the date of commissioning.The manufacturershall
undertaketo repair/replacethe systemwithout any financial obligationto the user,in casethe
performanceoi the systemis not found satisfactoryduring the period of observation.User
.hull ulro provide the feed-backto BSNL HQ, so that necessaryimprovementmay be
incorporatedin the GR.

3.12 with latestguidelinesfor UPS system,issued


Packing: Packingshall be donein accordance
by QA wing of BSNL.

: End of Chapter3 :

lTlPage
'64-t1<tn
CHAPTER4

Safetyrequirements

4,0 Safetyrequirements

4,1 Operatingpersonnelsafetyrequirements

4,1.1 Theoperating personnel shallbe protectedagainstshockhazardsasperIS 8437{1993\-


"Guideon the effectsof currentpassingthroughthe humanbody" [equivalentto IEC
publication60479-1(1984).TheManufacturer/supplier shallsubmita ceftiflcatein
respectof complianceto theserequirements.

4.1.2 The equipmentshall conformto IS-13252{2003} - "safety of informatiort9th"9]9ry


equipmentincludingelechicalbusiness equipment"[equivalentto IEC_publication 60950
,.Safety of radio transmittingequipments"
requirements
1ZbOilana IS 10417 {1986}
to
iequivalent IEC 602151.The shall submit a certificatein respect
Manufacturer/supplier
of complianceto theserequiremenls.

4.1.3 Theequipment practiceto minimizeunintended


shallfollow properconstruction radiation
dueto'leakagefrom anygapor monitoring points.All unused ports andmonitoring points
shouldbe terminated.TG powerflux densityshall not exceed 1 mwcm2 at a distanceof
2.5cms.

4,1.4 protectionagainstshortcircuiVopen pointsshallbe provided.All


circuitin theaccessible
on
switches/controls front panelshatlhavesuitablesafeguardsagainstaccidental
oDerations.

: End of Chapter4 :

lSlPage ll /vt:;-tt'.
_-4a(
Bg
E.gB
@=J

sg
: @

t
gu-
E3=
=
eg
@
F @ a t
o
c
o
lt)
I
o
o
o
(o
tur.- .9
.E
.o
(E

=
(J