Sei sulla pagina 1di 1

WIKA Alexander Wiegand SE & Co.

KG

Pressure and
Temperature Measurement
Customer: PT. PERTAMINA GAS Name: ADJI
WIKA Alexander Wiegand SE & Co. KG

Alexander-Wiegand-Strae
Project: JARINGAN GAS ACEH Date: 29/09/2015
63911 Klingenberg

Ref. -No.: THERMOWELL


phone: +49 9372 132-0
fax: +49 9372 132-406
Calculation email: info@wika.de
Tag-No.: TW MRS 2 good
result: web: http://www.wika.de

WIKA thermowell calculation program v2.2


Results to ASME PTC 19.3 TW - 2010
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42
Description Description
WIKA / ASME WIKA / ASME
Result: Process data: 0
Result Eval. good Temperature T 60,00 C
Frequency ratio r 0,10 fw/fnc Pressure P 5,00 bar
Ratio limit fw/fnc rmax_ 0,40 inline? Max.velocity v 20,00 m/s
Safety fatigue dyn 80,63 / Med.density rho 29,79 kg/m3
Safety bending stat 572,56 / Dyn.viscosity eta mm2/s
Safety pressure Sp 69,93 /
Reduced length (rmax) Ured / Lred mm
Note code /
Pipe data:
Inner diameter Di 102,300 mm
Shielded length SL / Lo mm
Usable nozzle length *) UNL / mm
Nozzle inner diameter *) NID / mm
*) for support collar
Thermowell sketch

Thermowell data:
WIKA model TW15 Name
Connection screwed
Shape tapered Name
Insertion length U/L 63,500 mm
New insertion length Unew / mm
Reduced length Ured / mm
Stepped length US / Ls 0,000 mm
Step radius RS / rB 0,000 mm
Root radius RQ / rA 0,000 mm
Bore diameter B / db 6,600 mm
Root diameter Q/B 22,000 mm
4a aw taperedV / TW15,
Tip diameter A TW50
mm 14,000
Tip thickness Tt / Tt 5,000 mm

Material data:
Grade mat 316L Name
Spec. weight D(T) 7,999 kg/dm3
Youngs modul E(T) 192,2 GPa
Factor for temp. FT 0,978 /
Fatigue strength Sf(T) 36,4 MPa
Max.all.stress 1.5S(T) 162,4 MPa
Press. strength S(T) 108,2 MPa
Fatigue class class B

WIKA has made every reasonable attempt to validate the calculation procedure contained in this spread sheet, however, responsibility for validation rests solely with the user.
This WIKA ASME PTC 19.3 TW 2010 spread sheet copyright 2010 (compatible with Excel 2007/2010) is intended to assist the experienced designer of thermowells and should
not be considered as a replacement for professional engineering.The end user is responsible to assure that the calculation method is compatible to the process conditions.
For further information see Operation Instruction.