Sei sulla pagina 1di 3

Automatic Energy Optimization

Whitepaper

Energy savings and process control are the main reasons products require tedious manual adjustment and still are not
to use variable frequency drives in Water, Wastewater, and effective at optimizing motor efficiency under all conditions.
Irrigation systems. Energy savings are significant because a
slight reduction in the speed of a centrifugal pump or blower The VLT AQUA Drive has a unique control feature called
can have a very large impact on its energy consumption. The Automatic Energy Optimization (AEO). Utilizing this function,
efficiency of a pump or blower, when used in conjunction with the drive automatically maximizes motor efficiency under all
a drive, will increase at reduced speeds. But, motor efficiency operating conditions.
will decrease as the motor becomes lightly loaded.
The following examines the cause of reduced motor efficiency
Drive manufacturers have attempted to help improve the at light loads and the way that AEO counteracts this natural
low speed efficiency of motors using a number of different tendency. The application and limitations of this function are
innovations in their drive designs. Unfortunately, most of these also examined.

Motor operation The relationship between voltage and frequency


In an AC induction motor, torque is created on the motor For motors with constant torque loads, the motors
shaft by a magnetic field within the motor. The strength of magnetization current should remain constant throughout
this magnetic field, and the resulting torque, varies with the the entire drive controlled speed range. Since the inductive
load demand on the motor. A greater load requires more reactance (XL) of the motors stator coils is proportional to
torque which means the motor draws more current from the the applied frequency, (XL = 2fL), a constant ratio between
supply voltage. Although the motor speed remains relatively the applied voltage and frequency is necessary in order to
constant, the current used can vary a great deal. maintain a constant motor current. This is the constant volts to
hertz (V/Hz) ratio that is commonly mentioned in conjunction
If full motor torque is not required, neither is the full magnetic with variable frequency drives.
field. The current that produces an excess magnetic field within
the motor provides no positive effect and also generates This is appropriate for drives which are designed for constant
reactive current which wastes energy and introduces thermal torque loads, such as positive displacement pumps, positive
stress. Excess current is even more pronounced at low torque displacement blowers, belt presses or other constant torque
where reactive current increases in comparison to real, or loads. A constant value of V/Hz is shown in figure 1.
variable, current. This is the main reason why lightly loaded
motors exhibit poor efficiency. When a drive with a constant V/Hz characteristic is applied to
a variable torque load, the full magnetizing current provided at
To limit the current through the motor, the voltage to the low speeds is greater than is required by the load. This over-
motor must be limited. While this seems simple, it isnt. Too magnetization, as previously mentioned, produces heat in the
little voltage causes excessive motor slip which will cause a motor.
large current draw and the heat generated by this current can
severely damage the motor. Carelessly reducing the voltage The solution is to determine what voltage the motor needs for
can damage a motor, so most drive manufactures avoid proper operation. Since this requires specialized programming
reducing the motors voltage. within the drive, some drive manufacturers simply ignore it and

www.danfossdrives.com Copyright Danfoss VLT Drives | AS | 10 2014


Whitepaper Automatic Energy Optimization

Drive output V/Hz characteristics Drive output V/Hz characteristics


Voltage

Voltage
Frequency Frequency
Figure 1. Constant V/Hz characteristics. Figure 2. Approximate V/Hz characteristics.

their drives produce only a constant V/Hz ratio over the entire ensurewithout the need of user interactionthat the voltage
speed range. While this doesnt maximize the motors efficiency, and frequency relationship is always optimum for the motors
it does avoid under-magnetizing the motor and creating load.
excessive slip.
In order to automatically provide the correct voltage at
Because variable torque loads are all somewhat different, a any operating frequency and load, the drive continuously
fixed V/Hz pattern will not work for all loads. When an attempt monitors the motor and responds to variations in application
is made to improve motor efficiency, the actual adjustment requirements. The VLT AQUA Drives unique VVC+ control
of the V/Hz profile is often the responsibility of the end-user. process provides this real-time correction. Current is monitored
This method (shown in figure 2), requires the user to define so that both the real current (that which varies with load) and
an intermediate point in the drives V/Hz profile. What this the reactive current (that which magnetizes the motor stator)
requires is extensive experimentation and evaluation over the are known at all times.
speed range and load of the system. In addition, if the system
characteristics change, it is necessary to repeat the process. The result is that the drive automatically maintains peak
Clearly, this isnt a very practical solution. motor efficiency under all operating conditions. During initial
acceleration, up to 110% output voltage can be applied to
Some drive manufacturers offer the user a choice between a provide additional torque to overcome the inertia of the
number of pre-defined variable torque V/Hz profiles. While this load. This also provides the soft-start and smooth ramp-up
simplifies the procedure, it is still necessary to manually run the characteristics of variable frequency drives designed for pump
motor throughout its operating speed range and determine the and blower applications. After the motor reaches the desired
lowest V/Hz profile that will drive the load without excessive slip speed, the VLT AQUA Drive automatically detects the steady-
or motor heating. state load level and reduces the output voltage to maximize
motor efficiency. If the load changes, such as when a valve
Again, the load characteristics of the application can change due in a pumping system suddenly opens, the drive detects the
to plant loading or usage requirements. In this case, the manual load change and immediately increases the output voltage to
profile procedure must be repeated. Because of the work maintain control of the motor.
involved, most users simply choose a high V/Hz profile, knowing
that it will drive the load. Unfortunately, choosing a higher V/Hz In addition, the VLT AQUA Drive Automatic Motor Adaptation
profile than is necessary will result in energy being wasted. (AMA) function, which accurately determines critical motor
parameters, allows the drive to calculate the current readings to
Automatic Energy Optimization determine the amount of magnetizing current required by the
The best solution to optimizing the voltage to the frequency/ load. The result is exceptional low load motor performance, an
power curve would be if it were automated. This is exactly what area where most drives underperform. The VLT AQUA Drive can
the VLT AQUA Drive does. The VLT AQUA Drive uses its unique actually reduce the reactive portion of the motor current. This
Automatic Energy Optimization control process to automatically component, often 25% of motor current and much greater at

www.danfossdrives.com Copyright Danfoss VLT Drives | AS | 10 2014


Whitepaper Automatic Energy Optimization

low load, is typically ignored by other variable frequency drive


manufacturers.

Automatic energy optimization allows the VLT AQUA Drive to


control voltages over a wide range in order to match the drive
output with the load. The range of voltages over which AEO
operates can be seen in figure 3. As shown, AEO allows the drive
to reduce the motors voltage by as much as 50% in order to
save energy. The variable V/Hz feature saves an additional 5% of
energy in a typical pump or blower application.

Advantages of AEO
Automatic energy optimizations major benefit is in variable
torque loads. As the motors speed is decreased, the load on the Figure 3. AEO operational range and savings.
motor drops dramatically. If a constant V/Hz ratio is supplied
to the motor, its efficiency will suffer. Knowing how much the
motor voltage can be reduced before motor performance Reduced motor heat generation also reduces the ambient
begins to suffer is difficult to determine manually. AEO calculates motor heat which can lead to longer motor life. In installations
this automatically and continuously. If the load profile changes, with large motors in temperature controlled areas, the additional
AEO responds to the change and adjusts the voltage supplied to saving in cooling costs can be significant.
the motor.
Reduced current flow also has an additional benefit, reduced
Even without changes in speed, AEO can still produce energy energy losses in the variable frequency drive as well as all
savings. To provide an operational safety margin and ensure other components supplying current to the motor, such as
against design error, most motors for Water/Wastewater systems transformers or line reactors.
are sized larger than is required to drive the load.
Summary
As a result, even under full speed, full flow conditions, the motor Motors used in Water, Wastewater, and Irrigation systems are
operates at less than full load. Without the voltage reduction seldom fully loaded. The motor is generally oversized for the
that AEO provides, the motor is operating inefficiently. With the application and because the motor load drops dramatically as
VLT AQUA Drive, it is not unusual to have an output voltage flow rates are reduced. Normally, motor efficiency is low at low
from the drive which is less than the motors nameplate rating, loads.
even when the drive is producing full frequency. Rather than
being an indication that there is a problem, this is savings To improve motor efficiency, some variable frequency drives
derived from AEO compensating for a motorbeing oversized for require the system operator to adjust the drives output V/Hz
the application. characteristics. These manual methods are both cumbersome
and inaccurate and, as a result, they are seldom used. In addition,
Variable speed, constant pressure applications benefit from AEO if application requirements change, the operator must readjust
as well. An example of such an application is an irrigation system the programming of the variable frequency drive to compensate
that has multiple zones. Each zone has a different number of for those changes.
sprinkler heads and thus needs different flow rates to maintain
the pressure required to optimize the output flow. AEO ensures The unique VVC+ algorithm of the VLT AQUA Drive monitors
that sufficient torque is always available on the motor shaft the real-time requirement of the current demands of the
while maintaining maximum motor efficiency. motor. Using this real-time information, the drive determines
the motors load and the automatic energy optimization feature
Although maximizing the motors efficiency is the main design ensures that the motor receives the ideal voltage at all times.
goal of AEO, other benefits are also provided. Heat generation This ensures peak motor and system efficiency even at low
within the motor, the primary cause of motor failure, is reduced speed operation. All of this is accomplished automatically and
and by reducing the thermal stress on the motor, motor life is without need for user intervention.
extended.

www.danfossdrives.com Copyright Danfoss VLT Drives | AS | 10 2014

Potrebbero piacerti anche