307-321, 2004
S.K. Chu
Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China
ABSTRACT
In order to protect life and properties of the residents, a proper Fire Safety Management System (FSMS) is
essential in a residential building. An FSMS includes an effective Fire Service System (FSS) and a good
maintenance system. Such a system comprises an appropriate system design of fault detection systems, an
inspection and testing system including an inspection and preventive maintenance schedule, personnel training
and safety awareness of maintenance operation.
This paper presents the factors and the causes using statistical analysis of data and mathematical method of
Downtime Distribution - Lognormal Distribution to estimate the system life period of FSS and to establish a
practicable maintenance method to reduce the downtime and the cost for the FSS.
307
International Journal on Engineering Performance-Based Fire Codes
W: Weekly checks with checklist A: Annual checks with checklist and test certificate
M: Monthly checks with checklist N/S: Not specified
Q: Quarterly checks with checklist
308
International Journal on Engineering Performance-Based Fire Codes
3. CASE STUDY (iii) fire detection and fire alarm system and (iv)
automatic fixed installation / operated approved
A public estate in Kowloon Central District was appliances would be performed quarterly. The
selected in the case study. There are 11 domestic inspection of (v) fire hydrant / hose reel system /
blocks with 3,551 units in this public estate, which street hydrant and (vi) sprinkler system would be
occupied an area of about 202,500 m2. The type carried out half-yearly. The checking of (vii)
and distribution of the breakdown of the FSI in a battery and charger, (viii) portable hand-operated
building were surveyed. Besides, the routine approved appliances and (ix) cleansing of fire
maintenance schedules and details of the fire services and sprinkler tank would be completed
system component (e.g. fire service pump, alarm annually. Details of each system items are listed in
and sprinkler) will be reviewed. Appendix II.
A preliminary survey was carried out to obtain a It is considered that the frequency of inspection
sample of data to check for the validity of the was too high as compared with the statutory
survey methodology and a full survey would be requirement. For example, the frequent inspection
conducted in the next stage of study. of hose reel system may increase to rate of wear
and tear of the hose and lead to unnecessary
In this preliminary survey, two domestic blocks replacement in a shorter period of time.
(Block A and Block B) are chosen as the samples
in this case study. There are a total of 16 floors The characteristics and percentage (no.) of system
with 626 units in the two blocks. Recent fire failure of FSI in building sites were extracted as in
service records from 1999 to 2001 including the Table 3 and Fig. 1.
date, time, location, possible causes, and types of
alarm were studied. The fire protection systems
included automatic sprinkler systems, hose reel and 4. RESULTS
fire hydrant systems, and automatic and manual
detector systems. As there are public institutions in The preliminary research mainly focuses on the
Block A, there is installation of sprinkler system fault and downtime of FSS in two public domestic
which is not usual for residential buildings. buildings in Hong Kong. The fault cases were
classified into FS pumps, hydrant, hose reel,
The existing periodic maintenance schedule of the sprinkler head, detector, manual call point, control
FSS for these two blocks is summarized as follows: value, alarm bell, exit sign and emergency
generator. The findings are summarized in Table 3
Nine categories should be inspected and tested and Fig. 1. The total numbers of system failure for
under the existing maintenance schedule. It was Block A and Block B were 132 and 120
noted that the checking of the remote alarm respectively. It is clearly shown that most fault
transmission system would be carried out in every cases are generated from two FSI, they are detector
two weeks. The testing of (ii) fire services pump, and manual call point.
Table 3: Outline of percentage of system failure and no. of fire service installation for block A & B
(1999-2001)
309
International Journal on Engineering Performance-Based Fire Codes
45
40
Percentage of system failure
35
30 Block A
25
Block B
20
15
10
5
0
FS pump Hydrant Hose reel Sprinkler Detector Manuel Control Alarm bell Exit sign Emergency
(head) call point value generator
Both blocks demonstrate a similar pattern of failure. 32% of fault due to maintenance, a very high
For detector system, the survey revealed 51 fault percentage for system down is by vandalism (28%).
cases in Block A and 49 fault cases in Block B. To lower the fault generated from vandalism,
The overall percentage of fault amount to 39% and proper protection to the manual call point unit was
41% of all FS faults for Block A and B. found not enough. It appears that proper protection
of the FS equipment requires also appropriate
For the manual call point, there were 25 fault cases management measures (e.g. strengthen patrol of
in Block A and 21 fault cases in Block B. The fault important equipment) and civic education to the
percentages are 19 % and 18 % respectively. The public.
third highest number of fault cases was found in
hose reel, with 13% in Block A and 12 % in Block Others 6%
Equipment
B. The fault percentages were low (equal and Renovation
decade 4%
lower than 10%) for other systems. work 20%
Maintenance
From the above, it is decided that a more detailed 30%
Human error
analysis would be carried out on the detector
10%
system and the manual call point.
Panel fault 7% Ambient
condition 23%
The seven major causes of the fault of the detector
system are shown in Fig. 2. They are renovation
work, human error, ambient condition, panel fault, Fig. 2: Cause / percentage of breakdown for
equipment decade and maintenance. detector system
Other than the reason of renovation works (20 %)
and the maintenance works (30 %), it was found
that the highest down rate is caused by the ambient Others
condition (23 %). Such a high percentage may be Equipment 10%
caused by the following situation: Normally, the decade Vandalism
detectors are installed in pumps rooms as FS pump 4% 28%
The causes of breakdown for manual call point are Fig. 3: Cause / percentage of breakdown for
shown in Fig. 3. They are also classified into seven manual call point
categories: maintenance, vandalism, ambient
condition, human error, panel fault and equipment
decade. The figure indicated that, excluding the
310
International Journal on Engineering Performance-Based Fire Codes
Table 4
311
International Journal on Engineering Performance-Based Fire Codes
0.40
0.35
Probability density, g(t)
0.30
0.25
0.20
0.15
0.10
Mean value = 1.9456
0.05
0.00
0.00 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50
Time to restore, t, hr
Fig. 4: Plot of lognormal pdf of the time-to-restore data in Table 2 in terms of the logarithms of t
0.03 0.00000
0.05 0.03307 7. CONCLUSIONS
0.25 0.26576 A preliminary research for the subject was
0.35 0.31567 conducted, which included the following:
312
International Journal on Engineering Performance-Based Fire Codes
7. BS5306: Part 2, Fire extinguisher installations and 26. NFPA 111, Standard on Stored Electrical Energy
equipment on premises, Specification for sprinkler Emergency and Standby Power System, National
system, British Standards Institution, UK (1990). Fire Protection Association, Quincy, Mass (2001).
8. BS5306: Part 5, Fire extinguisher installations and 27. NFPA 1901, Standard for Automatic Fire
equipment on premises, Specification for Halon Apparatus, National Fire Protection Association,
system and total flooding system, British Standards Quincy, Mass (1999).
Institution, UK (1992). 28. NFPA 2001, Standard on Clean Agent Fire
9. BS EN 1634: Part 1, Fire resistance tests for door Extinguishing Systems, National Fire Protection
and shutter assemblies, Specification for fire door Association, Quincy, Mass (2000).
and shutter, British Standards Institution, UK 29. D. Kececioglu, Maintablility, availability and
(2000). operational readiness engineering handbook, Vol. 1,
10. BS IEC 61366: Part 7, Hydraulic turbines, storage Prentice Hall PTR, Chapter 5, pp. 67-74 (1995).
pumps, and pump turbines, Guideline for technical
specification for storage pumps, British Standards
Institution, UK (1998). Q&A
11. BS5839, Fire detection and alarm systems for
buildings, British Standard Institution, UK (2002). Q1: You have selected two residential blocks for
12. BS 5266: Part 1, Emergency lighting, Code of
the study. What is the difference between the two
practice for emergency lighting premises, British residential blocks?
Standard Institution, UK (1999).
Chu: The two blocks are identical, except that in
13. BS5499: Part 3, Fire safety signs, notices and Block A it has an accommodation of public
graphic symbols, British Standard Institution, UK
(1990).
institution on ground floor, which contains
sprinkler installation.
14. BS 2655: Part 1, Specification for lifts, escalators,
passenger conveyors and paternosters, British Q2: What conclusion can you draw from the study
Standard Institution, UK (1970). of the cause of breakdown of the fire services
15. BS5514: Part 3, Reciprocating internal combustion installations for the two blocks?
engines, British Standard Institute, UK (1990).
313
International Journal on Engineering Performance-Based Fire Codes
314
International Journal on Engineering Performance-Based Fire Codes
(
APPENDIX I: CALCULATION METHOD t = e t ' = anti log e t ' (A7)
OF LOGNORMAL DISTRIBUTION
(
t = 0.9932 hr. (A8)
1. To determine the lognormal pdf of the times
to repair given in Table 4, it should be
calculated from This means that in a large sample of ts, half
of the ts will have values smaller than the
N median of time, and the other half will have
t i values greater than the median of time.
t = i =1 (A1)
N 4. The time by which one-half of the restorations
of such systems will be completed is the
for ungrouped data, where median, or
N (
n t t = 0.9932 hr. (A9)
j j
j=1
t = N'
, (t = loget)
5. The most frequency occurring, or observed,
n
j=1
j
time to restore such systems is mode of the
(A2) pdf of the ts, and is given by
N'
N = nj (A3)
j=1
1
N 2 2
n j (t ' j ) N t '
2
()
t' =
j=1
N 1
(A4)
1
t '+ ( t ' )2
t=e 2
(A6)
315
International Journal on Engineering Performance-Based Fire Codes
Fire Services Pump (feed pump, sprinkler pump, booster pump & fixed fire pump set):
Items of Work Observations
1. Inspect the pumping system when the pumps are 1. There should not be sign of leakage.
in operation.
2. Inspect the bearing of pump & motor sets and the 2a. The grease on the grease nipple should be fresh
lubrication system. and soft.
2b. There should be no sign of overheating and
abnormal noise and vibration.
3. Inspect the mounting of pump and motor sets. 3. There should not be sign of excessive
vibration/corrosion.
4. Inspect the packings for pumps and valves 4. There should not be sign of leakage.
including ball valves in sump and roof tanks, gate
valves, non return valves and globe valves, etc.
Replace packing gland by approved non-asbestos
type as necessary.
5. Clean all strainer filter screens 5. They should be free from debris and dirt.
6. Remove dirt and blockage in sump tanks.
7. Inspect the rubber sheets, gaskets to all valves 7. There should not be sign of leakage.
(including ball valves in sump and roof tanks),
pipes and fittings of the pumping system.
8. Warm up the motor and carry out the insulation 8. The insulation value should reach acceptable
test. figure.
9. Make necessary adjustment for pumps, motors,
switch gears, starters, float switches and all other
equipment in connection with the pumping system
both in pump room, the storage tanks and at the
site of submersible pump and surface mounted
pump installation.
10. Check coupling pins and bushes. 10. There should not be sign of excessive wear.
11. Check coupling alignment. 11a. There should be no sign of excessive vibration.
Adjust the alignment if necessary by Contractor. 11b The alignment of pump & motor set to be within
+/- 0.125 mm.
12. Check holding down bolts. 12. They should be fixed properly.
Re-tighten by contractor as necessary.
13. Check the operation of the valves, to grease valve 13. The valves should be operated freely in opening
316
International Journal on Engineering Performance-Based Fire Codes
4. Inspect the activation of common alarm circuits. 4. The alarm bells should be operated, in particular
the furthermost connected bell and signal should
be transmitted to Fire Signal Processing Agent if
equipped with a remote fire station link.
The activation should result in the start/stop of
the fire pumps as desired.
5. Inspect and note the operation of all indicators 5. They should be operated correctly.
including fault warnings and of all alarm bells.
6. Examine the batteries and chargers including 6. They should be in good serviceable condition.
primary batteries with reserves and secondary
batteries when applicable.
Report any necessary replacement.
7. Test all electrical circuits in accordance with the 7. The system should be operated satisfactorily,
contractual requirements. when the control or any indicating equipment is
actuated.
All cabling, fittings and equipment should be
secured, undamaged, adequately protected and
properly serviced.
8. Test each and every heat/smoke detector by 8. All detectors should be maintained in good
injection of inert gas. working condition, clean, free from corrosion and
Report any necessary replacement. not covered with distemper, paint, dust, etc.
9. Isolate the main supply and let the installation 9. During this period, at least one detector should be
maintained by battery for a period of 30 minutes. actuated and functioned properly.
10. Isolate the battery supply and let the installation 10. During this period, at least one detector should be
maintained by main supply via battery charger actuated and functioned properly.
for a period of 30 minutes.
317
International Journal on Engineering Performance-Based Fire Codes
318
International Journal on Engineering Performance-Based Fire Codes
Sprinkler System:
Items of Work Observations
1. Test the system (connected to water supplies) by
the Standard test orifice as stipulated in the
319
International Journal on Engineering Performance-Based Fire Codes
Fire Shutter:
Items of Work Observations
1. Check the condition of the fusible link. 1. The fusible link should not be covered with paint.
2. Check the condition of the chain/rope and 2a. The chain/rope hanging the weight should not be
counter weight. broken.
2a There should be enough space for the counter-
weight to move up and down.
3. Check the free operation of shutter and motor by
simulating a fire signal.
4. Check the lubrication of the moving parts such as 4. Lubricant on the moving parts should be clean
pulley, chain, rope, etc. and fresh.
320
International Journal on Engineering Performance-Based Fire Codes
Risk assessment report shall be prepared by competent persons before performing the cleansing of fire services
and sprinkler water tank and all these works shall be carried out by certified workers as stipulated in the
Factories and Industrial Undertakings (Confined Spaces) Regulation imposed by the Labour Department.
321