Calculations of the connection: Beam/Beam - Clip -


Calculations1

General Information

Main beam: HEA 300

Material: S 235
Hb1 = 290 mm Beam height
Wb1 = 300 mm Beam width
twb1 = 8.5 mm Web thickness
tFb1 = 14 mm Flange thickness
Ab = 112.53 cm2 Section area
Iby = 18263.5 cm4 Moment of inertia
fyb = 235 MPa Resistance


Secondary beam IPE 300

Material: S 235
Hb1 = 300 mm Beam height
Wb1 = 150 mm Beam width
twb1 = 7.1 mm Web thickness
tFb1 = 10.7 mm Flange thickness
Ab = 53.81 cm2 Section area
Iby = 8356.11 cm4 Moment of inertia
fyb = 235 MPa Resistance

Fin Plate:

Material: S 235
hs = 150 mm Stiffener height
bs = 80 mm Stiffener width
22-09-2017

BIMware

ts = 15 mm Stiffener thickness
fys = 235 MPa Resistance


Welds:

as = 6 mm Thickness of weld connecting stiffener with secondary beam


Safety factors:

M0 = 1
M1 = 1
M2 = 1.25
M3 = 1.25

Case: Case 1:

Nodal forces:

N= 0 kN
M= 0 kNm
V= 0 kN

_________________________________________________________________________________________________

Verification of welds joining stiffener with secondary beam


Aw = 25.2 cm2 Total area of welds
Awz = 18 cm2 Area of vertical welds
Awx = 7.2 cm2 Area of horizontal welds
lx = 573.97 cm4 Moment of inertia of welds about X axis
ly = 417.01 cm4 Moment of inertia of welds about Y axis
lo = 990.98 cm4 Polar moment of inertia of welds
em = 75 mm Distance between center of gravity of weld joining stiffener with main
beam and center of the secondary beam web
M0 = 0 kNm Moment raising from vertical force
M0t = 0 kNm Moment raising from vertical force and bending
Mx = 0 MPa Tangent stress in x direction from moment M 0
Mz = 0 MPa Tangent stress in z direction from moment M 0
vz = 0 MPa Tangent stress in z direction from vertical force
w = 0.8 Appropriate correlation factor [tab.4.1]

Verification of welds:

Sqrt [3(( Mx + Nx)2 + ( Mz + vz)2)] <= fu / (w* M2); 0 MPa < 360 MPa The condition is satisfied (0%)

_______________________________________________________________________________________

Final verification

Verification of connection FEd force FRd - capacity Ratio FEd/FRd


22-09-2017

BIMware

Weld connecting fin plate with main beam 0 MPa 360 MPa 0%
Weld connecting fin plate with secondary
0 MPa 360 MPa 0%
beam
Shear resistance of the notch section 0 kN 217.22 kN %
Design moment resistance of the notch
0 kN 144.56 kN %
section

Connection verification:

The connection conforms to the (EN 1993-1-8:2005/AC:2009)

Calculations of the connection: Beam/Beam - Clip -


Calculations2

General Information

Main beam: HEA 300

Material: S 235
Hb1 = 290 mm Beam height
Wb1 = 300 mm Beam width
twb1 = 8.5 mm Web thickness
tFb1 = 14 mm Flange thickness
Ab = 112.53 cm2 Section area
Iby = 18263.5 cm4 Moment of inertia
fyb = 235 MPa Resistance


Secondary beam IPE 300

Material: S 235
Hb1 = 300 mm Beam height
Wb1 = 150 mm Beam width
22-09-2017

BIMware

twb1 = 7.1 mm Web thickness


tFb1 = 10.7 mm Flange thickness
Ab = 53.81 cm2 Section area
Iby = 8356.11 cm4 Moment of inertia
fyb = 235 MPa Resistance

Fin Plate:

Material: S 235
hs = 150 mm Stiffener height
bs = 80 mm Stiffener width
ts = 15 mm Stiffener thickness
fys = 235 MPa Resistance


Welds:

as = 6 mm Thickness of weld connecting stiffener with secondary beam


Safety factors:

M0 = 1
M1 = 1
M2 = 1.25
M3 = 1.25

Case: Case 1:

Nodal forces:

N= 0 kN
M= 0 kNm
V= 0 kN

_________________________________________________________________________________________________

Verification of welds joining stiffener with secondary beam


Aw = 25.2 cm2 Total area of welds
Awz = 18 cm2 Area of vertical welds
Awx = 7.2 cm2 Area of horizontal welds
lx = 573.97 cm4 Moment of inertia of welds about X axis
ly = 417.01 cm4 Moment of inertia of welds about Y axis
lo = 990.98 cm4 Polar moment of inertia of welds
em = 75 mm Distance between center of gravity of weld joining stiffener with main
beam and center of the secondary beam web
M0 = 0 kNm Moment raising from vertical force
M0t = 0 kNm Moment raising from vertical force and bending
Mx = 0 MPa Tangent stress in x direction from moment M 0
Mz = 0 MPa Tangent stress in z direction from moment M 0
vz = 0 MPa Tangent stress in z direction from vertical force
22-09-2017

BIMware

w = 0.8 Appropriate correlation factor [tab.4.1]

Verification of welds:

Sqrt [3(( Mx + Nx)2 + ( Mz + vz)2)] <= fu / (w* M2); 0 MPa < 360 MPa The condition is satisfied (0%)

_______________________________________________________________________________________

Final verification

Verification of connection FEd force FRd - capacity Ratio FEd/FRd


Weld connecting fin plate with main beam 0 MPa 360 MPa 0%
Weld connecting fin plate with secondary
0 MPa 360 MPa 0%
beam
Shear resistance of the notch section 0 kN 217.22 kN %
Design moment resistance of the notch
0 kN 144.56 kN %
section

Connection verification:

The connection conforms to the (EN 1993-1-8:2005/AC:2009)