Sei sulla pagina 1di 8

Insulati o n

Second Issue May 2016

Kingspan FM
Duct Insulation
DUCT INSULATION FOR RECTANGULAR, CIRCULAR AND
FLAT OVAL / BUILDING SERVICES DUCTWORK

Low Energy
Low Carbon Buildings
Kingspan KoolthermTM FM Duct Insulation

Overview
Kingspan Kooltherm FM Duct Insulation is a premium Its rigidity also enables the straightforward application of vapour
performance thermal insulation designed for use on rectangular, barrier tape and finishing materials which, in turn, facilitates the
circular and flat oval ductwork in HVAC / building services creation of a continuous and fully sealed vapour barrier.
applications. It can be used to insulate ductwork, plenums and This can provide a neater, cleaner, closer fitting and more
associated equipment, installed both indoors and outdoors, aesthetically pleasing finish than that achievable with nonrigid
operating within the temperature range of 20C to +80C / glass or rock mineral fibre duct wrap products.
4F to +176F.
Kingspan Kooltherm FM Duct Insulation is available in
Kingspan Kooltherm FM Duct Insulation is suitable for both standard board dimensions of 1200 x 600 mm /
new build and refurbishment projects in the residential, 311 5/32 x 23 5/8 (length x width), and in the following
commercial, institutional, light industrial and leisure sectors. standard thicknesses:
Moreover, it is especially suitable for high specification projects l 20 mm / 51/64;
where nonfibrous insulants may be preferred, for example: the l 25 mm / 1;
food, beverage and pharmaceutical industries; communication/ l 30 mm / 1 3/16;
server rooms in data centres; high relative humidity
l 40 mm / 1 37/64; and
environments, for instance swimming pools; and clean air and
l 50 mm / 1 31/32.
hygiene controlled environments such as sterile areas of
hospitals or laboratories.
Kingspan Kooltherm FM Insulated Duct
Kingspan Kooltherm FM Duct Insulation has been developed
to provide premium performance with regards to insulation Support Inserts
efficiency, fire resistance, smoke emissions, compressive Duct Support Inserts can be fabricated on site from Kingspan
strength and cost. Kooltherm FM Duct Insulation. They can withstand the loads
imposed by HVAC / building services ductwork at locations
Kingspan Kooltherm FM Duct Insulation where ductwork supports and hangers are installed.

Kingspan Kooltherm FM Duct Insulation


comprises a fibre-free rigid thermoset
phenolic insulation core, faced on one
side (external face) with a 25.4 micron /
1 mil aluminium vapour barrier foil, and faced on the other side
(internal face) with a glass tissue based facing. Both facings are
autohesively bonded to the insulation core during manufacture.

The insulation core is manufactured with a blowing agent that


has zero Ozone Depletion Potential (ODP) and low Global
Warming Potential (GWP).

Kingspan Kooltherm FM Duct Insulation has a 90% (or greater) Kingspan Kooltherm FM Pipe Insulation
installed on curved surfaces < 80 mm / 3
closed cell structure and a compressive strength that typically
exceeds 100 kPa / 14.5 psi at 10% compression. The product
can be Vgrooved through its internal face to accommodate
the surface curvature of circular and flat oval ductwork with an
outside diameter (O.D.) of 80 mm / 3 or greater*. Kingspan
Kooltherm FM Pipe Insulation should be used on curved
surfaces with an outside diameter <80 mm.

The rigid nature of Kingspan Kooltherm FM Duct Insulation


enables the specified thickness of insulation to be maintained Steel channel
& threaded rod
at the corners of ductwork, and at locations where HVAC / support system
building services equipment is specified. Nonrigid glass and
rock mineral fibre duct wrap products, on the other hand,
risk being overstretched and compressed in these locations,
Flat oval duct
potentially leading to a reduction in thermal performance. Kingspan Kooltherm FM Flat Insulated
Duct Support Insert installed to extend
50 mm / 2 either side of support
2
There are two different types of Insulated Duct Support Inserts: Kingspan Kooltherm FM Insulated Duct Support Inserts
enable a more consistent run of ductwork insulation, by
l Kingspan Kooltherm FM Flat Insulated Duct Support
allowing specified insulation levels to be maintained at
Inserts; and
ductwork support and hanger locations.
l Kingspan Kooltherm FM Circular Insulated Duct Support
Inserts. Interruptions in insulation continuity, by materials with
significantly worse thermal conductivities, or no insulation at all,
Kingspan Kooltherm FM Flat Insulated Duct Support Inserts are
can result in thermal bridging (sometimes referred to as cold
strips of flat rectangular Kingspan Kooltherm FM Duct
bridging). This can reduce the efficacy of the insulation through
Insulation. They are used with rectangular and flat oval ductwork.
consequential heat losses / gains. The use of noninsulated
Kingspan Kooltherm FM Circular Insulated Duct Support duct support inserts can result in up to 5% of the total area of a
Inserts are strips of V-grooved / slotted Kingspan Kooltherm ductwork system being seriously under-insulated.
FM Duct Insulation. They can be used with circular ductwork
Kingspan Kooltherm FM Duct Insulation and Kingspan
that has an outside diameter (O.D.) of 80 mm / 3 or greater*.
Kooltherm FM Insulated Duct Support Inserts, where
They cannot, however, be used to support the compressive
appropriately taped and sealed, can facilitate the creation of a
loads imposed by pipework carrying water or other liquids and
continuous and fully sealed vapour barrier. This is particularly
should not be used in such applications.
important for ductwork operating at below ambient
temperatures, or in high relative humidity environments and
could be considered good practice.
*For curved surfaces with an O.D. less than 80 mm / 3, it is recommended that Kingspan
Kooltherm FM Pipe Insulation and Kingspan Kooltherm FM Insulated Pipe Support Inserts
Kingspan Kooltherm FM Duct Insulation are used. Information on Kingspan Kooltherm FM Pipe Insulation and Kingspan Kooltherm
installed on flat surfaces such that the FM Insulared Pipe Support Inserts, and their FM approval, can be requested from the Kingspan
insulation fixed to the top & bottom, Insulation marketing department. See rear cover for details.
overlaps the insulation fixed to the sides

Highstrength contact adhesive


applied in accordance with
manufacturer recommendations

Selfadhesive aluminium foil vapour barrier tape


securely applied in a smooth & wrinklefree manner
Mechanical fixing firmly to extend 25 mm / 1 either side of joints, seams,
attached to duct wall exposed insulation edges, insulation terminations, pin
Rectangular duct punctures, retaining washers and other protrusions

Kingspan Kooltherm FM Circular Insulated Duct Support


Hanger bracket Insert installed on circular ductwork 80 mm / 3 & to
extend 50 mm / 2 either side of support

Kingspan Kooltherm Circular duct


Insulated Pipe Support
Insert installed on circular
ductwork < 80 mm / 3

Kingspan Kooltherm FM Duct Insulation Vgrooved


through its internal face to accommodate curved
surfaces 80 mm / 3 Figure 1: Fixing Details

3
Design Considerations
Environmental Impact & Responsible
Sourcing Fire Performance
Green Guide Rating Properties
An Ecoprofile, certified by BRE (Building Research Establishment) Kingspan Kooltherm FM Duct Insulation is characterised, by
Certification to the 2008 BRE Environmental Profiles FM Approvals, member of the FM Global Group, as low fire
Methodology, has been created for Kingspan Kooltherm FM hazard, which does not require automatic sprinkler protection.
Duct Insulation produced at Kingspan Insulations Pembridge, UK,
The insulation core of Kingspan Kooltherm FM Duct Insulation
manufacturing facility. BRE has assigned the product a 2008
is a rigid thermoset material and, unlike thermoplastic materials,
Green Guide Summary Rating of A+, the best possible rating.
it does not melt, drip or produce flaming droplets. Its intricately
Responsible Sourcing crosslinked structure makes it difficult to ignite and, when
Kingspan Kooltherm FM Duct Insulation produced at subjected to fire, its outer surface forms a strong carbonaceous
Kingspan Insulations Pembridge and Selby manufacturing layer that limits heat generation and retards further flame
facilities, is certified to BES 6001 Excellent. spread. Furthermore, there is an almost complete absence of
NB The above information is correct at the time of writing. Please confirm at the point of need smoke when subjected to a flame source.
by contacting the Kingspan Insulation Technical Service Department (see rear cover), from
which copies of Kingspan Insulations and its suppliers BES 6001 certificates can be obtained, In addition, the insulation core has a resistance to burning and
along with confirmation of Kingspan Insulations products Green Guide Ratings.
spread of flame far superior to that of flexible elastomeric foam
(FEF), rigid polyurethane (PUR) and rigid polyisocyanurate (PIR)
Sustainability & Responsibility
insulants.
Kingspan Insulation has a longterm commitment to sustainability
and responsibility: as a manufacturer and supplier of insulation Kingspan Kooltherm FM Duct Insulation, when subjected to
products; as an employer; and as a substantial landholder. the fire and smoke tests of the standards specified in Table 2,
has achieved the results shown.
Further information can be found at:
www.kingspaninsulation.com/sustainabilityandresponsibility. Standard Result
ASTM E 84: 2008 Flame spread / smoke
Standards & Approvals (Test for Surface Burning developed indices:
Characteristics of Building < 25/50
Kingspan Kooltherm FM Duct Insulation is manufactured
Materials)
under a management system certified to ISO 9001: 2008 EN ISO 56592: 2006 Maximum specific optical density
(Quality management systems. Requirements), ISO 14001: (Plastics Smoke generation of smoke (mean):
2004 (Environmental Management Systems. Requirements) Part 2: Determination of In presence of pilot flame:
optical density by a single 0 (25 kW/m2)
and BS OHSAS 18001: 2007 (Health and
Chamber test) 6 (50 kW/m2)
Safety Management Systems. Requirements). In absence of pilot flame:
Kingspan Kooltherm FM Duct Insulation is approved for use 0 (25 kW/m2)
9 (50 kW/m2)
by the Dubai Central Laboratory, and the State of Qatar Ministry
of Interior General Admin of Civil Defense. UBC 263: 1997 Pass
(Uniform Building Code
Standard: Room Fire Test
Method for Interior of Foam
Plastic Systems)
Table 1: Results of Fire & Smoke Test Standards Achieved by Kingspan
Kooltherm FM Duct Insulation

Classification
Kingspan Kooltherm FM Duct Insulation, and its rigid
thermoset insulation core, are Class 0, as defined by the
Building Regulations in England.

4
Thermal Properties
Thermal Conductivity
The aged thermal conductivity (kvalue / value) of Kingspan
Kooltherm FM Duct Insulation is 0.021 W/mK at 1025C /
0.146 Btuin/ftinF at 10-25C / 50-77F mean (ASTM
C 518 Standard Test Method for SteadyState Thermal
Transmission Properties by Means of the Heat Flow Meter
Apparatus).

The low thermal conductivity of Kingspan Kooltherm FM Duct


Insulation makes it the most thermally efficient, and hence the
thinnest, insulation product commonly used to insulate
ductwork in HVAC / building services applications.

Thin insulation can contribute towards space savings. This can


be particularly useful where space is often at a premium, e.g.
Compliance
service runs, raised floors and prefabricated modules.
Kingspan Kooltherm FM Duct Insulation meets the flame
Increased space can facilitate installation, cleaning and
spread and smoke developed requirements for duct insulation,
maintenance operations in confined areas. Furthermore, thinner
as defined by NFPA (National Fire Protection Assembly) 90A
insulation can result in a reduction in surface area and therefore
(Standard for the Installation of Air-conditioning & Ventilating
savings in finishing materials.
Systems), and 90B (Standard for the Installation of Warm Air
Heating & Air-conditioning Systems). Thermal Resistance
The installed and outofpackage material thermal resistances
Kingspan Kooltherm FM Duct Insulation exceeds the flame
(R-values), of the different thicknesses of Kingspan Kooltherm
spread and smoke developed requirements for duct insulation,
FM Duct Insulation (calculated by dividing its thickness by its
and foam plastic insulation (including that used as interior trim in
thermal conductivity), are shown in Table 3.
plenums), as defined by the IMC (International Mechanical
Codes), IBC (International Building Codes) and IRC (International Thickness R-value
Residential Codes) of the ICC (International Code Council). 20 mm / /
51 64 0.95 mK/W / 5.4 fthrF/Btu
25 mm / 1 1.21 mK/W / 6.8 fthrF/Btu
FM Certification 30 mm / 1 3/16 1.44 mK/W / 8.1 fthrF/Btu
40 mm / 1 37/64 1.89 mK/W / 10.8 fthrF/Btu
Kingspan Kooltherm FM Duct Insulation is certified, by FM
50 mm / 1 31/32 2.38 mK/W / 13.5 fthrF/Btu
Approvals, to Factory Mutual Research Approval Standard
Table 2: Installed & OutofPackage Rvalues of the Different Thicknesses of
Pipe Insulation Class Number 4924 March Kingspan Kooltherm FM Duct Insulation
1973, when manufactured and installed in
Compliance
accordance with the conditions defined by
Kingspan Kooltherm FM Duct Insulation is available in
the approval.
thicknesses that meet or exceed the insulation thickness
This certification is valid for thermal insulation produced at requirements of BS 5422: 2009 (Method for specifying thermal
Kingspan Insulations Pembridge, UK, manufacturing facility. It insulating materials for pipes, tanks, vessels, ductwork &
allows Kingspan Kooltherm FM Duct Insulation to be installed equipment operating within the temperature range 40C
in single or multiple arrays, in thicknesses up to 90 mm / 3 1/2, to +700C).
on rectangular, circular and flat oval ductwork, operating at
Kingspan Kooltherm FM Duct Insulation is available in
temperatures not exceeding 104C / 220F*, in HVAC / building
thicknesses that meet or exceed the minimum duct insulation R
services applications.
value requirements of: ANSI/ASHRAE/IESNA 90.1: 2004, 2007,
Further details of the FM Approval listing for Kingspan Kooltherm 2010 & 2013 (American National Standards Institute / American
FM Duct Insulation are published on the FM Global website at: Society of Heating, Refrigerating & AirConditioning Engineers/
www.approvalguide.com under the Building Materials division. Illuminating Engineering Society of North America Energy
To view the listing, click on the category Pipe and Duct Insulation Standard for Buildings except LowRise Residential Buildings),
(FM Approval Class Number 4924) and select Pipe and Duct for heating and cooling supply and return ducts; and ICC: IECC
Insulation. (International Code Council: International Energy Conservation
*Although the approval allows Kingspan Kooltherm FM Duct Insulation to be used on Codes), for supply and return air ducts and plenums.
ductwork operating at temperatures up to 104C / 220F, the upper limit should not exceed
80C / 176F.

5
Sitework

Introduction
In addition to the information given in this section, it is l The insulation must be securely fixed to the substrate with a
recommended that reference is also made to BS 5970: 2012 compatible high-strength contact adhesive, which must be
(Thermal insulation of pipework, ductwork, associated applied in accordance with the manufacturers recommendations.
equipment and other industrial installations in the temperature For suitable adhesives, please contact the Kingspan Insulation
range of 100C to +870C Code of practice). HVAC Technical Service Department (see rear cover).
l Insulation fixed to circular ductwork must be additionally
Installation supported with banding (preferably aluminium) and matching
l Care should be taken when handling and transporting seals. The banding must be no less than 15 mm / 1/2 wide
insulation products to prevent physical damage. and should be applied circumferentially at 350 mm / 13 3/4
l The insulation should only be installed after all testing of the centres.
ductwork system has been completed. l It may also be necessary to further secure the insulation in
l In addition to the surfaces of ductwork, plenums and place on rectangular ductwork, with compatible mechanical
associated HVAC equipment flanged joints, stiffeners, fixings. This will be dependent upon: the substrate material;
fasteners and connections must also be effectively insulated the pressure rating, operating temperatures, size and
in order to reduce heat loss, heat gain and / or to control orientation of the duct and duct wall; and the degree of
condensation. vibration to which the duct is subjected during operation.
l Mechanical fixings, if used, must be corrosion resistant,
l To facilitate inspection, testing, adjustment, balancing,
maintenance and cleaning, a removable and fully vapour capable of sustaining the calculated tensile dead load
sealed piece of insulation, of sufficient size, must be perpendicular to the duct wall, and securely fixed so that
provided at access door locations, if the door is not they do not detach from the duct during its service life.
already preinsulated. l Mechanical fixings should be positioned so that they are
l Insulation must not be installed at locations where the neatly and evenly distributed under each piece of insulation.
ductwork penetrates fire resistance rated walls, partitions, They should be located no less than 50 mm / 2, and no
floors and ceilingfloor assemblies. Consideration should be greater than 150 mm / 6, from insulation edges and corners.
given to current building regulations, codes all standards
with regard to the requirements for, and provision of, fire Vapour Barrier
stops. l The vapour barrier over the insulation should be continuous
l Before being insulated, surfaces must be made clean, dry and fully sealed.
and free from grease, dust, dirt, loose rust, scale and all l A high strength selfadhesive aluminium foil vapour barrier
other foreign matter. tape should be applied to all discontinuities in the vapour
l The insulation should be installed to achieve a close fit barrier. This includes those between insulated duct support
between the insulation and substrate, as well as between inserts and abutting duct insulation, joints, seams, exposed
insulation joints. insulation edges, insulation terminations, pin punctures,
retaining washers and other protrusions.
l The ingress of moisture, or other foreign matter, either into
the insulation or between the insulation and substrate, l The self-adhesive vapour barrier tape should be applied in a
should be prevented during installation. smooth and wrinklefree manner. It should extend no less
than 25 mm / 1 either side of joints, seams, insulation
l When insulating rectangular ductwork, the thickness of
edges and terminations, as well as in all directions of pin
insulation that has been specified should be maintained at
punctures, retaining washers and other protrusions.
all four corners of the duct.
l To ensure successful adhesion, all surfaces to receive self
l On horizontally orientated ducts, the insulation fixed to the
adhesive vapour barrier tape should be made clean, dry and
top and bottom should overlap the insulation that is fixed to
free from grease, dust, dirt and all other foreign matter prior
the sides (see Figure 1 on pages 23 of this document).
to application. If required, surfaces may be primed with a
l Insulated duct support inserts should be of the same
thin coat of compatible highstrength contact adhesive.
thickness as that of the adjacent duct insulation. In order to
A gentle pressure may also be exerted using a soft spatula
facilitate the straightforward application of selfadhesive
tool, whilst applying the tape.
vapour barrier tape, they should be installed to extend no
less than 50 mm / 2 either side of the support.

6
Protection & Finishes General
l The factoryapplied aluminium foil vapour barrier facing is Cutting
normally the standard finish for concealed indoor areas, l Manual cutting of the insulation boards should be carried
e.g. ceiling voids, floor voids, modules and risers. out either by using a fine toothed saw, or by scoring with a
l Although the factoryapplied aluminium foil vapour barrier sharp knife, snapping the board over a straight edge and
facing is normally the standard finish for opentoview then cutting the facing on the other side.
indoor applications, an additional cosmetic finish, e.g. paint l Ensure accurate trimming to achieve closebutting joints
may be provided. Consideration should, however, be given and continuity of insulation.
to any effect that it might have on the thermal and fire l Automated computer aided cutting may be carried out
performance of the finish ductwork.
using CNC blade / router machinery.
l If located indoors 2 m / 66 above finished floor level, or
Availability
at risk of being subjected to mechanical or physical abuse,
l Kingspan Kooltherm FM Duct Insulation is available
e.g. in plant rooms, boiler houses, service areas or publicly
accessible areas, an additional protective finish should through specialist insulation distributors and selected
be applied over the insulation. Suitable finishes include: Delivery Partners. For details, please contact Kingspan
aluminium or stainless steel sheet; aluminiumzinc alloy Insulation (see rear cover).
coated steel sheet; heavyduty, self-adhesive laminate; Packaging & Storage
synthetic elastomeric jacketing, systems; reinforcing glass / l The polyethylene packaging of Kingspan Insulation
synthetic cloth embedded between two coats of products, which is recyclable, should not be considered
appropriate coating; or glass reinforced polyester / epoxy adequate for outdoor protection.
(GRP / GRE) cladding systems (all applied in accordance
l Insulation materials should be adequately protected from
with the manufacturers recommendations and the projects
the weather, humidity, abrasive matter, contaminants and
specification requirements).
all other foreign matter.
l If located outdoors, the insulation must be adequately
l Ideally, products should be stored inside a building. If,
protected with an additional weatherproof and water /
however, outside storage cannot be avoided, they should
vapour tight finish that shields against the effects of wind,
be stored in a dry atmosphere, clear of the ground, out of
sunlight and birds. The finish must also be capable of
direct sunlight and covered with an opaque and
providing suitable protection if at risk of being subjected to
weatherproof material. Products that have been allowed
mechanical or physical abuse. Suitable finishes include:
aluminium or stainless steel sheet; aluminiumzinc alloy to get wet should not be used.
coated steel sheet; heavyduty, self-adhesive laminate; l Insulation products should be maintained in good condition
synthetic elastomeric jacketing, systems; reinforcing glass / throughout the duration of the works and should not be
synthetic cloth embedded, between two coats of unpacked onsite until required for immediate use. They
appropriate coating; or UV resistant glass reinforced should be returned to storage at the end of each workday.
polyester / epoxy (GRP / GRE) cladding systems (all applied
Health & Safety
in accordance with the manufacturers recommendations
l Kingspan Kooltherm FM Duct Insulation is chemically inert
and the projects specification requirements).
and safe to use.
l If installing an additional finish over the standard factory
l A Safety Information Data Sheet is available from the
applied aluminium foil vapour barrier facing, extreme care
Kingspan Insulation website
must be taken to preserve the integrity of the vapour barrier
www.kingspaninsulation.com
at all times.
NB The reflective surfaces on this product is designed to enhance its thermal performance.
As such, they will reflect light as well as heat, including ultraviolet (UV) light. Therefore, if the
Identification of Services product is being installed during very bright or sunny weather, it is advisable to wear UV
protective sunglasses or goggles, and if the skin is exposed for a significant period of time, to
l Both insulated and noninsulated services should be clearly protect the bare skin with a UV block sun cream. The reflective facing used on this product can
be slippery underfoot when wet. Therefore, it is recommended that any excess material should
identifiable. be contained to avoid a slip hazard. Warning do not stand on or otherwise support your
weight on these products.
l The identification system should preferably be in accordance
with the requirements of the authority having jurisdiction, but
should always be approved by the engineer.
l The identification system and its method of application
should be compatible with the finish. They should also
be suitable for the operating and ambient conditions.

7
Kingspan Insulation LLC reserves the right to amend product specifications without prior notice. Product thicknesses shown in this document should not be taken as being available exstock and
advice should be sought directly from Kingspan Insulation LLC. The information, technical details and fixing instructions etc. included in this literature are given in good faith and apply to uses described
herein. Recommendations for use should be verified as to the suitability and compliance with actual requirements, specifications and any applicable codes, laws and regulations. For other applications
or conditions of use, contact Kingspan Insulation LLC. Advice should be sought for uses of Kingspan Insulation products that are not specifically described herein. The fire tests referenced in this
literature and the assigned results are not intended to reflect hazards presented by the materials and products described herein under actual fire conditions. Please check that your copy of the literature
is current by visiting www.kingspaninsulation.com.

Kingspan Insulation LLC


P.O. Box 113826, Dubai Investment Park 2, Dubai, U.A.E.
Tel: +971 4 889 1000 Fax: +971 4 883 8515
info@kingspaninsulation.ae
www.kingspaninsulation.com

Countries comprise: all of Africa except South Africa and Lesotho; South and Central America except Mexico; the Caribbean; the Middle East and Asia as far north and east (and including) Turkey,
Georgia, Azerbaijan, Kazakhstan, Kyrgyzstan, Afghanistan, Pakistan, India, Nepal, Bhutan and Bangladesh.
TM
Kingspan, Kooltherm and the Lion Device are Trademarks of the Kingspan Group plc.

Potrebbero piacerti anche