Insert a template
1) Open your project from CAP 540, insert a new terminal REL 511
*2.3 in line_bay, start CAP 531.
2) Insert the template TRAINING
3) Communicate with the terminal and run Upload Options
4) You will get an error list
5) By double clicking on each error of the list and fix the error.
After you have fixed one error, run Make / Update version
(this will refresh the error list).
6) When the error list is empty you can continue, otherwise go
back to step 5)
7) Run Function Selector / Uploaded Data
8) You will get an error list, this time related to I/O cards.
9) Fix the errors by double clicking on each one. After you have
fixed one error, run Make / Update version (this will refresh
ABB Automation Technology
10) When the error list is empty you can continue, otherwise go
back to step 9)
Products AB
Exercise 3
This could create problems in the configuration and you have to take
SA.T.Training CAP540 061100 - 5
care about the signals that maybe were used in the original template.
Products AB
WHAT HAVE YOU DONE?
Impedance protections had single phase signals. Since the terminal has
three phase trip, also impedance protections are missing the single
phase information.
TEF function used in the template was not included in the terminal.
- This can create problems in the configuration and you have to take
care about the signals that maybe were used in the original template.
For instance in this case:
In the template one BIO card was foreseen, but in the terminal
one BIM and one BOM are installed.
ABB Automation Technology
SA.T.Training CAP540 061100 - 8
Products AB
WHAT HAVE YOU DONE?
- You had to delete the BIO function block and replace it with the
BIO and BOM.
OUTPUTS
WHAT HAVE YOU DONE?
INPUTS
ABB Automation Technology
Products AB
SA.T.Training CAP540 061100 - 11
OUTPUTS
WHAT HAVE YOU DONE?
INPUTS
WHAT HAVE YOU DONE?
INPUTS
ABB Automation Technology
SA.T.Training CAP540 061100 - 12
You had also to configure the slot position of the BIO and BIM
Products AB
function blocks.
WHAT HAVE YOU DONE?
COMPILE
The command compile generated an error list.
When you have fixed all the errors related to UPLOAD OPTIONS and
FUNCTION SELECTOR you have fixed all the errors related to
functions and cards which are not present or are different in your
configuration.
Errors detected by the compiler are configuration errors I.e. inputs in
function blocks not connected to any signal, variables not
defined because they had origin from function blocks which have
been deleted etc.
EXAMPLE CONFIGURATION
Together with CAP 540 you get a set of Example Configurations for
all REx 5xx terminals, in form of templates.
The configurations contain all the functions which can be
included in the terminal, and mainly it is easy to adapt an example
configuration from ABB Automation Products to your terminal,
because you have to delete some functions and not add them.
The job to carry out is the same as the previous exercise.