1 - Fault Analysis:
Symmetrical Components and Unbalanced
Faults
2
Anlisis De Sistemas de Potencia
Symmetrical components
Negative sequence
Zero sequence
3
Anlisis De Sistemas de Potencia
Symmetrical components
4
Anlisis De Sistemas de Potencia
Symmetrical components
Va
One unbalanced
n-phase system is
equivalent to: Vb
Vc
n balanced n-phase
systems
Va1 Va2
Va0=Vb0=Vc0
Vb0 Vb2
Vc0
+ Vc1 +
Vb1 Vc2
Zero Positive Negative
Sequence (0) Sequence (1) Sequence (2)
5
Anlisis De Sistemas de Potencia
Symmetrical components
6
Anlisis De Sistemas de Potencia
Symmetrical components
aV1 a2 V 2
Vc V2
Va = V1
+ +
Vb
a2 V 1
aV2
aV1
aV2
V0 Va
V0
Vc
Vb V2
V0 V1
a2 V 1
a2 V 2
7
Anlisis De Sistemas de Potencia
Symmetrical components
8
Anlisis De Sistemas de Potencia
Symmetrical components
Or in matrix form:
I a 1 1 1 Ia0
I 1 a 2 a I a1
b
I c 1 a a I a 2
2
9
Anlisis De Sistemas de Potencia
Symmetrical components
I abc A I012
From the last expression it can be found that:
I012 A I abc
1
Where:
1 1 1
1
A 1 a a 2
1
3
1 a 2 a
10
Anlisis De Sistemas de Potencia
Symmetrical components
Vmn a Z aa Z ab Z ac I a
Vmn b Zba Zbb Zbc I b
Vmn c Z ca Z ab Z cc I c
11
Anlisis De Sistemas de Potencia
Symmetrical components
Z012
12
Anlisis De Sistemas de Potencia
Symmetrical components - Lines
Z S 0 2 Z M 0 Z S 2 Z M 2 Z S1 Z M 1
Z mn012 Z S1 Z M 1 Z S 0 Z M 0 Z S 2 2Z M 2
Z S 2 Z M 2 Z S1 2Z M 1 Z S 0 Z M 0
13
Anlisis De Sistemas de Potencia
Symmetrical components - Lines
1
ZS 0 Z aa Z bb Z cc
3
Z S1
1
3
Z aa aZ bb a 2 Z cc
Z S 2 Z aa a 2 Z bb aZ cc
1
3
and
1
Z M 0 Z bc Z ca Z ab
3
Z M 1 Z bc aZ ca a 2 Z ab
1
3
Z M 2 Z bc a 2 Z ca aZ ab
1
3
14
Anlisis De Sistemas de Potencia
Symmetrical components - Lines
Lets consider a three phase transposed line with one
single ground wire excited by a zero sequence source
Find zero
impedance
of this
system
(V0/I0)
15
Anlisis De Sistemas de Potencia
Loads
Saadat H. - 2011
16
Anlisis De Sistemas de Potencia
Zero sequence circuit of three-phase loads
I0 = 0
I0 = 0
I0 = 0
17
Anlisis De Sistemas de Potencia
Zero sequence circuit of three-phase loads
I0 = 0
I0 = 0
I0 = 0
Tleis N. - 2008
18
Anlisis De Sistemas de Potencia
Zero sequence circuit of three-phase loads
I0
I0
I0
Tleis N. - 2008
19
Anlisis De Sistemas de Potencia
Zero sequence circuit of three-phase loads
I0
I0
I0
I0
Tleis N. - 2008
20
Anlisis De Sistemas de Potencia
Zero sequence circuit of three-phase loads
Delta:
I0 I0 = 0
I0
I0 = 0
I0
I0 = 0
I0
Tleis N. - 2008
21
Anlisis De Sistemas de Potencia
Zero sequence circuit of three-phase loads
Delta:
I0 I0 = 0
I0
I0 = 0
I0
I0 = 0
I0
Tleis N. - 2008
22
Anlisis De Sistemas de Potencia
Sequence circuits of three-phase TRFs
23
Anlisis De Sistemas de Potencia
Sequence circuits of three-phase TRFs
Shatshat R. - 2010
24
Anlisis De Sistemas de Potencia
Zero Sequence circuits of three-phase TRFs
e) deltadelta;
25
Anlisis De Sistemas de Potencia
Sequence circuits of generators
For generators:
The sequence impedance matrix [Z012] is diagonal. No
coupling among sequences.
Only the direct component includes an voltage source.
Synchronous generators are built that way.
Sequences impedances are not equal. The zero
sequence impedance is usually substantially smaller.
j 0,05 pu
MVA Voltage X1 X2 X0
G1 100 11 kV 0,15 0,17 0,05
G2 100 11 kV 0,20 0,21 0,1
T1 100 11/220 kV 0,1 0,1 0,1
T2 100 11/220 kV 0,1 0,1 0,1
Line 100 220 kV 0,105 0,105 0,315
Shatshat R. - 2010 27
Anlisis De Sistemas de Potencia
Sequence Diagrams for Example
Shatshat R. - 2010
28
Anlisis De Sistemas de Potencia
Zero Sequence Diagrams for Example
j0,15
Shatshat R. - 2010
29
Anlisis De Sistemas de Potencia
Thevenin Equivalents
Shatshat R. - 2010
30
Anlisis De Sistemas de Potencia
Thevenin Equivalents
Shatshat R. - 2010
31
Anlisis De Sistemas de Potencia
Thevenin Equivalents
Shatshat R. - 2010
32
Anlisis De Sistemas de Potencia
Unbalanced Fault Analysis
33
Anlisis De Sistemas de Potencia
Single Line-to-Ground (SLG) Faults
With a SLG fault only one phase has non-zero fault current
it is assume that the fault phase is phase A.
Ignoring pre-fault currents, les find the SLG fault
voltage and current relationships:
Shatshat R. - 2010
34
Anlisis De Sistemas de Potencia
Single Line-to-Ground (SLG) Faults
35
Anlisis De Sistemas de Potencia
Single Line-to-Ground (SLG) Faults
36
Anlisis De Sistemas de Potencia
Single Line-to-Ground (SLG) Faults
37
Anlisis De Sistemas de Potencia
References
[1] Glover J., Sarma M. and Overbye T., Power System Analysis and Design. Fifth
Edition. Cengage. 2011.
[2] Saadat H., Power System Analysis. Third Edition, PSA Publishing 2010.
[3] Anderson P., Analysis of Faulted Power Systems. IEEE Press, 1973.
[4] Gmez-Exposito A. et al., Electric Energy Systems: Analysis And Operation.
Taylor & Francis Group, 2009.
[5] Tleis N., Power Systems Modelling and Fault Analysis: Theory and Practice.
Newnes. 2008.
[6] Gmez A., Sistemas Elctricos de Potencia: Problemas y Ejercicios Resueltos.
Prentice Hall 2003.
[7] Shatshat R., Lecture Notes ELEC-B7 - Power Systems Engineering. University
of Waterloo. 2010. Available at:
https://ece.uwaterloo.ca/~raelshat/COURSES_dr/eleb7/ELEB7.html
[7] Overbye T. and Baldick R. EE 369 Power System Analysis: Lecture 18 Fault
Analysis, 2012. Available at:
http://users.ece.utexas.edu/~baldick/classes/369/Lecture_18.ppt
[8] Conejo A. J., Anlisis de Sistemas Elctricos de Potencia Universidad de
Castilla La Mancha Course slides available at:
http://www.uclm.es/area/gsee/Archivos%20Pag-
web/docencia/aelect/04_UnbalancedFaultAnalysis_R3.pdf
38
Anlisis De Sistemas de Potencia
Comments
39
Anlisis De Sistemas de Potencia