1 - Fault Analysis:
Symmetrical Components and Unbalanced
Faults

JORGE FERNANDO GUTIRREZ GMEZ



Anlisis De Sistemas De Potencia
Analysis of Unsymmetrical Systems

Except for the balanced three-phase fault, faults result in


an unbalanced system:
The most common unsymmetrical faults are:

Single line-to-ground (SLG)

Line-to-line faults (LL)

Double line-to-ground (DLG)

System is only unbalanced at point of fault!

The easiest method to analyze unbalanced system


operation due to faults is through the use of
symmetrical components

2
Anlisis De Sistemas de Potencia
Symmetrical components

The key idea of symmetrical component analysis is to


decompose the system into three sequence networks.
The networks are then coupled only at the point of the
unbalance (i.e., the fault)
The three sequence networks are known as:
Positive sequence (this is the one weve been using)

Negative sequence

Zero sequence

3
Anlisis De Sistemas de Potencia
Symmetrical components

Symmetrical components: first proposed for power


system analysis by C.L. Fortescue in a classic paper
devoted to consideration of the general N-phase case
(1918)

A system with an unbalanced set of n phasors may


be resolved into n-1 balanced n-phase systems of
different phase sequence and one zero-phase
system

4
Anlisis De Sistemas de Potencia
Symmetrical components
Va
One unbalanced
n-phase system is
equivalent to: Vb

Vc

n balanced n-phase
systems

Va1 Va2
Va0=Vb0=Vc0
Vb0 Vb2
Vc0
+ Vc1 +

Vb1 Vc2
Zero Positive Negative
Sequence (0) Sequence (1) Sequence (2)
5
Anlisis De Sistemas de Potencia
Symmetrical components

Defining the complex operator (a) which causes a


counterclockwise rotation of 120:

a= 1120= -0,5 +j0,866

a2= 1 -120= -0,5 -j0,866

a3= 1 360= 1+j0,0

6
Anlisis De Sistemas de Potencia
Symmetrical components
aV1 a2 V 2
Vc V2
Va = V1
+ +
Vb
a2 V 1
aV2

aV1
aV2
V0 Va
V0
Vc
Vb V2
V0 V1
a2 V 1
a2 V 2

7
Anlisis De Sistemas de Potencia
Symmetrical components

Consider the three phase unbalanced currents: Ia, Ib, Ic.


Using Fortescue definition they are equivalent to:

Ia= Ia0 + Ia1 + Ia2

Ib= Ib0 + Ib1 + Ib2

Ic= Ic0 + Ic1 + Ic2

8
Anlisis De Sistemas de Potencia
Symmetrical components

It is possible to rewrite all phasors in terms of phase a


using the complex operator a:
Ia= Ia0 + Ia1 + Ia2

Ib= Ia0 + a2Ia1 + aIa2

Ic= Ia0 + aIa1 + a2Ia2

Or in matrix form:

I a 1 1 1 Ia0
I 1 a 2 a I a1
b
I c 1 a a I a 2
2

9
Anlisis De Sistemas de Potencia
Symmetrical components

In a more compact way, it can be written as:

I abc A I012
From the last expression it can be found that:

I012 A I abc
1

Where:
1 1 1
1
A 1 a a 2
1

3
1 a 2 a
10
Anlisis De Sistemas de Potencia
Symmetrical components

Sequence Components For Unbalanced Network Impedances

Vmn a Z aa Z ab Z ac I a

Vmn b Zba Zbb Zbc I b
Vmn c Z ca Z ab Z cc I c

11
Anlisis De Sistemas de Potencia
Symmetrical components

Replacing voltages and currents in terms of Fortescue


matrix:

A Vmn 012 Zabc A I012

Vmn 012 A Zabc A I012


1

Z012

12
Anlisis De Sistemas de Potencia
Symmetrical components - Lines

Sequence Components For Unbalanced Network Impedances

Z S 0 2 Z M 0 Z S 2 Z M 2 Z S1 Z M 1

Z mn012 Z S1 Z M 1 Z S 0 Z M 0 Z S 2 2Z M 2
Z S 2 Z M 2 Z S1 2Z M 1 Z S 0 Z M 0
13
Anlisis De Sistemas de Potencia
Symmetrical components - Lines

1
ZS 0 Z aa Z bb Z cc
3
Z S1
1
3
Z aa aZ bb a 2 Z cc

Z S 2 Z aa a 2 Z bb aZ cc
1
3
and
1
Z M 0 Z bc Z ca Z ab
3
Z M 1 Z bc aZ ca a 2 Z ab
1
3
Z M 2 Z bc a 2 Z ca aZ ab
1
3
14
Anlisis De Sistemas de Potencia
Symmetrical components - Lines
Lets consider a three phase transposed line with one
single ground wire excited by a zero sequence source

Find zero
impedance
of this
system
(V0/I0)

What can be concluded


from this result?

15
Anlisis De Sistemas de Potencia
Loads

Write the phase-domain line to neutral voltages and


find the sequence-domain equations

Saadat H. - 2011
16
Anlisis De Sistemas de Potencia
Zero sequence circuit of three-phase loads

Star with isolated neutral:

I0 = 0

I0 = 0

I0 = 0

17
Anlisis De Sistemas de Potencia
Zero sequence circuit of three-phase loads

Star with isolated neutral:

I0 = 0

I0 = 0

I0 = 0

Tleis N. - 2008
18
Anlisis De Sistemas de Potencia
Zero sequence circuit of three-phase loads

Star with solidly earthed neutral:

I0

I0

I0

Tleis N. - 2008
19
Anlisis De Sistemas de Potencia
Zero sequence circuit of three-phase loads

Star with solidly earthed neutral:

I0

I0

I0

I0

Tleis N. - 2008
20
Anlisis De Sistemas de Potencia
Zero sequence circuit of three-phase loads

Delta:

I0 I0 = 0

I0
I0 = 0
I0

I0 = 0

I0

Tleis N. - 2008
21
Anlisis De Sistemas de Potencia
Zero sequence circuit of three-phase loads

Delta:
I0 I0 = 0

I0
I0 = 0
I0

I0 = 0

I0

Tleis N. - 2008
22
Anlisis De Sistemas de Potencia
Sequence circuits of three-phase TRFs

The positive and negative sequence diagrams for


transformers are similar to those for three-phase loads.

23
Anlisis De Sistemas de Potencia
Sequence circuits of three-phase TRFs

The zero sequence network depends upon both how the


transformer is grounded and its type of connection. The
easiest to understand is a double grounded wye-wye

Shatshat R. - 2010
24
Anlisis De Sistemas de Potencia
Zero Sequence circuits of three-phase TRFs

Analyze the following connections:


a) starstar with isolated neutrals;

b) star with solidly earthed neutral star isolated


neutral;
c) star solidly earthed star neutral earthing
impedance;
d) star isolated neutral delta;

e) deltadelta;

f) star neutral earthing impedance delta

g) deltastar neutral earthing impedance

25
Anlisis De Sistemas de Potencia
Sequence circuits of generators
For generators:
The sequence impedance matrix [Z012] is diagonal. No
coupling among sequences.
Only the direct component includes an voltage source.
Synchronous generators are built that way.
Sequences impedances are not equal. The zero
sequence impedance is usually substantially smaller.

The value of Zn depends


on whether the generator
is grounded or not.
Shatshat R. - 2010
26
Anlisis De Sistemas de Potencia
Unbalanced Fault Analysis
The first step in the analysis of unbalanced faults is to
assemble the three sequence networks.
Consider the following example:

j 0,05 pu

MVA Voltage X1 X2 X0
G1 100 11 kV 0,15 0,17 0,05
G2 100 11 kV 0,20 0,21 0,1
T1 100 11/220 kV 0,1 0,1 0,1
T2 100 11/220 kV 0,1 0,1 0,1
Line 100 220 kV 0,105 0,105 0,315
Shatshat R. - 2010 27
Anlisis De Sistemas de Potencia
Sequence Diagrams for Example

Positive Sequence Network:


j0,15 j0,1 j0,105 j0,1 j0,2

Negative Sequence Network

j0,17 j0,1 j0,105 j0,1 j0,21

Shatshat R. - 2010
28
Anlisis De Sistemas de Potencia
Zero Sequence Diagrams for Example

Zero sequence network:

j0,05 j0,1 j0,315 j0,1 j0,1

j0,15

Shatshat R. - 2010
29
Anlisis De Sistemas de Potencia
Thevenin Equivalents

Second is to calculate the Thevenin equivalents as seen


from the fault location. In this example the fault is at the
terminal of the right machine so the Thevenin equivalents
are:

Shatshat R. - 2010
30
Anlisis De Sistemas de Potencia
Thevenin Equivalents

Second is to calculate the Thevenin equivalents as seen


from the fault location. In this example the fault is at the
terminal of the right machine so the Thevenin equivalents
are:

Shatshat R. - 2010
31
Anlisis De Sistemas de Potencia
Thevenin Equivalents

Second is to calculate the Thevenin equivalents as seen


from the fault location. In this example the fault is at the
terminal of the right machine so the Thevenin equivalents
are:

Shatshat R. - 2010
32
Anlisis De Sistemas de Potencia
Unbalanced Fault Analysis

Unbalanced faults unbalance the network, but only at the


fault location. This causes a coupling of the sequence
networks. How the sequence networks are coupled
depends upon the fault type.
It is necessary to derive these relationships for several
common faults.

33
Anlisis De Sistemas de Potencia
Single Line-to-Ground (SLG) Faults

With a SLG fault only one phase has non-zero fault current
it is assume that the fault phase is phase A.
Ignoring pre-fault currents, les find the SLG fault
voltage and current relationships:

Shatshat R. - 2010
34
Anlisis De Sistemas de Potencia
Single Line-to-Ground (SLG) Faults

The only way that these two constraint can be satisfied is


by coupling the sequence networks in series:

35
Anlisis De Sistemas de Potencia
Single Line-to-Ground (SLG) Faults

The only way that these two constraint can be satisfied is


by coupling the sequence networks in series:

36
Anlisis De Sistemas de Potencia
Single Line-to-Ground (SLG) Faults

The only way that these two constraint can be satisfied is


by coupling the sequence networks in series:

37
Anlisis De Sistemas de Potencia
References
[1] Glover J., Sarma M. and Overbye T., Power System Analysis and Design. Fifth
Edition. Cengage. 2011.
[2] Saadat H., Power System Analysis. Third Edition, PSA Publishing 2010.
[3] Anderson P., Analysis of Faulted Power Systems. IEEE Press, 1973.
[4] Gmez-Exposito A. et al., Electric Energy Systems: Analysis And Operation.
Taylor & Francis Group, 2009.
[5] Tleis N., Power Systems Modelling and Fault Analysis: Theory and Practice.
Newnes. 2008.
[6] Gmez A., Sistemas Elctricos de Potencia: Problemas y Ejercicios Resueltos.
Prentice Hall 2003.
[7] Shatshat R., Lecture Notes ELEC-B7 - Power Systems Engineering. University
of Waterloo. 2010. Available at:
https://ece.uwaterloo.ca/~raelshat/COURSES_dr/eleb7/ELEB7.html
[7] Overbye T. and Baldick R. EE 369 Power System Analysis: Lecture 18 Fault
Analysis, 2012. Available at:
http://users.ece.utexas.edu/~baldick/classes/369/Lecture_18.ppt
[8] Conejo A. J., Anlisis de Sistemas Elctricos de Potencia Universidad de
Castilla La Mancha Course slides available at:
http://www.uclm.es/area/gsee/Archivos%20Pag-
web/docencia/aelect/04_UnbalancedFaultAnalysis_R3.pdf
38
Anlisis De Sistemas de Potencia
Comments

39
Anlisis De Sistemas de Potencia

Potrebbero piacerti anche