Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
In setting out a cable route, numbers of angles and bends should be kept to a minimum for ease
in pulling. Recommended limits on pulling tensions are given below:
0.12xD Newtons (kN), where D = the overall diameter of the cable (mm) subject to a maximum
of:
Steel tape armoured cables are not suitable for stocking grip because of a tendency for the
steel tape to unravel. In this case the best procedure is to strip the armour and apply a
stocking over the next layer, or to attach a pulling eye to the conductor.
On Armour:
Caution:
Installers are advised to review actual pulling tensions, taking into account the maximum
sidewall pressures, cable minimum bending radius and other installations restrictions.
Pulling different conductor sizes at the same time is not recommended if the conductor
size or other cable characteristics are significantly different.