TECHNICAL MANUAL
Hollowcore Floor Planks, as a structural unit: Hollowcore Floor Planks, as a floor system, provide:
Are lightweight and efficient Are durable Required fire ratings Accommodation of services
Allow design flexibility Allow long spans Sound insulation Flexible ceiling options
Have high load capacity Complete package (manufacture, delivery and installation)
FLOORING
TECHNICAL MANUAL
CONTENTS
1 Introduction 2
2 Design Approach 3
3 Pre-planning 4
4 Preliminary Design 5
5 Final Design 8
6 Construction 16
7 Guide Specification 22
8 Bibliography 24
9 Sample Calculation 25
2
Support and joint details.
2 DESIGN APPROACH
Product drawings showing plank details
including dimensions and the location of lifting
The design of a hollowcore floor is usually and fixing inserts.
undertaken in two stages:
The erection procedure.
Preliminary Design The general layout, the
The structural design of the planks may be
overall dimensions of the planks and the typical
provided by either party, depending on the
details are selected to suit the building
contractual arrangements:
requirements, and
If carried out by the Structural Engineer, the
Final Design The details of the planks such as
manufacturer supplies design properties unique
strand patterns, connections, embedded items
to his product, such as section properties,
are decided and the shop drawings produced.
normal concrete strengths, strand patterns.
It is normal for the manufacturer to participate in
If carried out by the manufacturer all design
the design process with the project management
team as well as providing advice on costing. The documentation is provided to the Structural
capacity to participate varies with each Engineer who checks that the design meets the
manufacturer and from job to job. The project requirements in all respects.
responsibilities are generally divided as follows.
The project management team, which includes the
Architect and Structural Engineer, usually provides
the following:
The general arrangement drawings showing the
floor plan layout, building dimensions and
general structure and support methods.
The project specification.
The codes and particular building regulations
governing the project.
The vertical and horizontal loadings on the floor.
The required fire resistance levels.
The noise insulation requirements.
The vibration characteristics if required.
Any deflection restrictions.
Forces arising from structural frame actions.
Checking and acceptance of the design
calculations when the manufacturer carries
these out.
Overall responsibility for the structural design of
all elements in the project including the
integration of the hollowcore planks into the
structure.
The manufacturer usually provides the following:
Detailed specification for the manufacture of the
planks using proprietary equipment.
The detailed design of the hollowcore planks as
agreed.
Detailed layout drawings locating each plank
type in the structure.
3
Connections
3 PRE-PLANNING
The type and details of the connections between
hollowcore floor planks and supporting beams or
In planning a structure considerable benefits are walls should be chosen in consultation with a
achieved by establishing a framing layout to suit manufacturer. Refer to Figures 16, 17, and 18 for
the hollowcore module and span capability, rather examples of connections that have been developed
than substituting hollowcore for a traditional insitu for typical situations.
concrete layout. The most economical grid in a
framed structure maximises the span of the
hollowcore and minimises the span of the support Tolerances
beams. Most buildings have at least one short grid Construction tolerances must be allowed for in
(usually 7.2 to 8.4 m) which can be used as the developing a plan layout. Tolerance in plank length
beam span and then the span of the planks follow. is absorbed by allowing a gap at the end of the
The primary consideration in developing a framing plank and specifying the minimum length of
plan is the span length. For a given loading, fire bearing. A clearance gap is also required along the
rating and exposure classification, the span length side of a plank that abuts a wall or beam to allow
and the plank thickness can be optimised using a for an accumulation of width tolerances. Small
manufacturers published load tables as a guide. increases in floor width can be accommodated by
increasing joint width with the use of a strip of
It is strongly recommended that a manufacturer be former to bridge the base of the joint during
consulted during the preliminary stages of a grouting, Figure 15.
project so that advice can be provided on the most
cost-effective and practical design.
Camber and Topping
Plank Length
The planks are cut to the length required for their
location in the floor-plan. The ends can be cut to
an angle to suit skew layouts.
4
4 PRELIMINARY DESIGN
(building regulations)
Exposure classifications and durability
5
150-mm PLANK WITHOUT TOPPING 150-mm PLANK WITH 60-mm TOPPING
14
13
12
11
10
9
8
7
6
5
LIVE LOAD (kPa)
4
3
2
L/D = 40 L/D = 40
1
0
0 1 2 3 4 5 6 7 8 9 10 11 12 0 1 2 3 4 5 6 7 8 9 10 11 12
SPAN (m) SPAN (m)
14
13
12
11
10
9
8
7
6
5
LIVE LOAD (kPa)
4
3
2
L/D = 40 L/D = 40
1
0
0 1 2 3 4 5 6 7 8 9 10 11 12 0 1 2 3 4 5 6 7 8 9 10 11 12
SPAN (m) SPAN (m)
14
13
12
11
10
9
8
7
6
5
LIVE LOAD (kPa)
4
3
2
L/D = 40 L/D = 40
1
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
SPAN (m) SPAN (m)
6
300-mm PLANK WITHOUT TOPPING 300-mm PLANK WITH 80-mm TOPPING
14
13
12
11
10
9
8
7
6
5
LIVE LOAD (kPa)
4
3
2
L/D = 40 L/D = 40
1
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
SPAN (m) SPAN (m)
14
13
12
11
10
9
8
7
6
5
LIVE LOAD (kPa)
4
3
2
L/D = 40 L/D = 40
1
0
0 2 4 6 8 10 12 14 16 18 20 0 2 4 6 8 10 12 14 16 18 20
SPAN (m) SPAN (m)
14
13
12
11
10
9
8
7
6
5
LIVE LOAD (kPa)
4
3
2
L/D = 40 L/D = 40
1
0
0 2 4 6 8 10 12 14 16 18 20 0 2 4 6 8 10 12 14 16 18 20
SPAN (m) SPAN (m)
7
5.3 Flexural Strength
5 FINAL DESIGN
The design ultimate bending strength of the section is
calculated in accordance with Clause 8.1 of AS 3600.
5.1 General The design strength Mu may be calculated using the
The detailed design of a hollowcore plank follows rectangular stress block for compression taking into
the normal procedure for a prestressed member account any area reduction due to the presence of
(see Sample Calculation Chapter 9). The plank is cores. The maximum stress in the strands at ultimate
checked for design ultimate strength in bending, may be determined by either strain compatibility or by
shear and at transfer, and at service load for crack the approximate formula in Clause 8.1.5. of AS 3600.
control, camber at time of erection and deflection. The capacity reduction factor, , is 0.8. The strand
For the standard conditions of uniformly distributed length to develop the prestress by bond is 60 strand
live load, the manufacturer's load tables take into diameters. The bond length to develop the stress at
account these design criteria and show the load ultimate flexure is approximately 150 diameters.
capacity based on the governing criteria. For non-
To ensure a ductile failure, upper and lower limits are
uniform load cases or non-standard conditions
placed on the area of prestressing steel. A minimum
separate calculations are required. The design
area of steel has to be provided so that the ultimate
steps are outlined in the following sections.
capacity of the section is not less than 1.2 times the
cracking moment. This ensures that when the section
5.2 Section Availability cracks the strand will not simultaneously fail. The
maximum quantity of prestress steel is controlled by the
Each hollowcore manufacturer has a standard set
requirement that the neutral axis depth does not
of cross-sections that can be produced by their
exceed 0.4 times the effective depth of the section. In
machine. Depths vary from 150 to 400 mm. The
practice over-reinforced hollowcore sections are
core configuration makes each system unique,
precluded by the number of strands that can be bonded
actual depths vary between manufacturers and not
between the cores. The compression zone of
all are available in each system.
composite sections is usually above the core zone of
Hollowcore manufacturers prepare and distribute the plank.
product literature that includes section properties
and capacities and load span tables for their
5.4 Shear Strength
product range. These are calculated for the
particular planks, strand configuration and effective Hollowcore planks are designed for shear in
depth of the section with concrete cover to meet accordance with Clause 8.2 of AS 3600. Stirrups
designated fire rating and exposure classifications. cannot be provided in hollowcore planks and the
capacity of the section is controlled by concrete
For the purpose of this Manual, typical section
strength. The capacity in both flexure-shear cracking
plank capacity charts are provided as an aid for
and web cracking is calculated and the lesser value
preliminary sizing and to illustrate the procedures
taken as Vuc where = 0.7. Negative moments can
for a detailed final design. In practice, the amount
of prestress is varied to suit the load within each reduce the shear capacity by causing premature
plank size. Top strands are required in 350-mm cracking in the web. Precautions need to be taken in the
and 400-mm deep sections (3 x 12.7-mm dia.) to design to ensure that this does not happen, see
control the stress distribution. Concrete strengths Clause 5.9 Continuity.
range from 40 to 65 MPa and topping strength is The shear capacity of given plank sizes varies between
usually 32 or 40 MPa. manufacturers due to different void configurations.
For convenience, the load-span graphs (Figures 2 These affect the web width at the neutral axis where
to 7) are presented in terms of the allowable shear stress is a maximum. The load capacity charts in
superimposed distributed live load applied to a this Manual assume that shear is not critical for the load
simply-supported span. Where added dead loads ranges shown, this may not be the case for all types of
or concentrated loads are applied to the floor, cross-section, particularly those with large circular voids
these can be converted to equivalent uniform live and needs to be checked with the individual
loads for a preliminary design. Refer Figures 8 manufacturer.
to 11. In addition to the check for vertical shear, the
longitudinal shear strength of a composite section must
be checked at the interface between the plank and the
insitu topping in accordance with Clause 8.4, AS 3600.
When the surface texture at the top of the plank is
as-screeded by the machine, a shear plane coefficient
of 0.2 may be used in the calculation and 0.4 when the
surface is intentionally roughened or wire brushed.
8
5.5 Transfer Stress The camber at erection due to prestress can be
estimated using a creep factor of 1.7 to 2.0 times
When the strands are cut and apply the prestress
the initial camber.
force to the concrete, only the self-weight of the
plank acts to counter the upward bending moment Deflection results from the applied loads. If the
due to eccentricity. The strength of the section section is uncracked the deflection depends on the
should be checked for crushing or cracking of the stiffness of the gross concrete section and is
concrete. Although Clause 8.1.4 of AS 3600 independent of the amount of prestressing. Usually
specifies a maximum compressive stress in the hollowcore planks are designed to be uncracked
concrete at release of 0.5 times the cylinder under service loads so the gross moment of inertia
strength, a factor of 0.6 has been found to be may be used, otherwise the effective moment of
satisfactory. In practice this limiting stress is met by inertia of the cracked section must be taken into
choosing the release strength of the concrete. The account.
tensile stress in the section at release is not
Camber and deflection change with time due to
critical for the strand patterns normally used.
concrete creep, loss of prestress and other long-
term factors such as climate. A long-term load in
5.6 Crack Control excess of the load balanced by the prestress
causes the plank to creep downwards.
Flexural cracking in a prestressed slab may be
controlled by limiting the tensile stress in Composite action with a topping results in a stiffer
accordance with the provisions of Clause 9.4.2. of section. The deflection of interest is the movement
AS 3600. As the strands in hollowcore planks are from the as-cast level of the topping resulting from
fully bonded, a calculated flexural tensile stress the long-term effect of the sustained load and the
under short-term service loads up to 0.5fc may instantaneous effect of the short-term load.
be used in the design. This means that the section Limiting values for these deflections are specified
is effectively uncracked at normal service loads. in AS 3600, Table 2.4.2. As an aid to estimating
deflection, long-term multiplication factors are
Alternatively, the more general provision for partial given in reference 4, Chapter 8 and are used in
prestressing may be adopted whereby the the Sample Calculation, Chapter 9.
increment in strand stress is limited to 150 MPa as
the load increases from the decompression value
to the short-term service load. 5.8 Load Distribution
Hollowcore floor planks are usually designed as
5.7 Camber and Deflection simple, one-way-spanning slabs. Floors are often
subject to non-uniform loads such as line loads,
Camber is the upward deflection of a prestressed concentrated loads or loads at openings. The
member and results from the prestressing force shear/torsion interaction between planks with
being eccentric to the centre-of-gravity of the properly-filled side joints and lateral restraint
section. It is therefore determined by the design against spreading, allows these concentrations to
loading and span for a given depth of plank and be shared by several planks.
should not be specified as a limiting value.
Unloaded planks tend to creep upwards when the This ability to distribute loads has been
self-weight of the plank is insufficient to balance demonstrated by full scale testing and explained
the prestress. To avoid unnecessarily-high by a combination of shear stresses induced in the
cambers, it is important not to over-specify the grouted keyways and by transverse bending in the
design loading or arbitrarily increase the prestress. planks. For design purposes, an effective load-
resisting width can be used to calculate design
When the design live load is high, the resulting bending moments and shears. This effective width
camber can be reduced by using additional top depends upon the span.
strand to give a less triangular stress distribution
over the cross-section. A simple linear distribution is shown in Figure 8.
The FIP method (see Item 3, Chapter 8) is a more
The initial camber is calculated from the formulae detailed approach and is shown in Figures 9, 10
for elastic deflection due to the prestressing and 11 for both point and line loads. Load sharing
moment and the self-weight using appropriate decreases near an edge or large opening and a
values for the prestressing force and the modulus conservative approach must be taken to re-
of elasticity at release. As these are known with distribution in these regions, particularly for large
reasonable accuracy the elastic deflection can be edge loads on long spans. When in doubt a finite
predicted fairly well. However, time-dependent element analysis can be carried out for more
camber and deflection calculations are only insight into the distribution between the units.
estimates.
9
Face of
L /4 support L /4
Effective
Effective width (L /2)
1200-mm width (L /4)
units
L /2 L /2 L
Grouted joints
Effective width Effective
(Interpolate) width
(Interpolate)
L /4 Face of L /4
support
100 100
1200-wide 1200 units P
units Linear loading
1 2 3 2 1
90
90 1 2 3 2 1 x
Linear loading 16 = L/x P
80 80
3 2 1
10 L
70 70
6
60 60
50 50 2
Proportion of Loading on 1200-mm-wide Unit (%)
Proportion of Loading on 1200-mm-wide Unit (%)
3
40 40
3
30 2 30
3 L/x
1 2 2
20 2 20 16
1
10 10 1
L/x
2
0 6 10 16
0
3 4 5 6 7 8 9 10 11 12 13 14 3 4 5 6 7 8 9 10 11 12 13 14
Span (m)
Span (m)
10
100 Limited continuity can be achieved by placing
P 1200-mm-wide units reinforcement in the topping concrete at supports.
1 2 3 4 5 Continuity should only used where there is a clear
90 advantage to the structure to do so, and then, only in
x = 0.5 L
composite construction. The cost per kN of force
P
80 supplied by prestressing strand is about a third that
of reinforcement. Thus, it is uneconomical to use
L ordinary reinforcement as negative-moment steel to
70 replace positive-moment strand steel.
Continuity can be used to achieve a higher fire-rating
60 for a given cover to the strand; this is useful when it
is not possible, or inadvisable, to raise the strand
any higher in the cross-section. Continuity is also
50
useful for increasing the robustness of a structure to
Proportion of Loading on 1200-mm-wide Unit (%)
11
Verify maximum dimension with designer Verify maximum dimension with designer
Allow for
Bearing strip Bearing wall beyond
camber
Non-bearing wall
12
L1 Tie bar Insitu concrete
B x 20 kN/m 70 kN
2
B
L1 + L2 L1
A x 20 kN/m 70 kN
2 Hollowcore plank
with cores opened
70 kN 70 kN
Precast support
A beam with
L2 projecting ties
C C 20 kN/m typical SECTION AA
Hollowcore plank
L1 with cores opened
B x 20 kN/m 70 kN
2 Precast support
beam with
anchored ferrule
B
70 kN SECTION BB
70 kN L1 + L2 L1
A x 20 kN/m 70 kN
2
Insitu concrete Tie bar
70 kN 70 kN
L2
70 kN 20 kN/m typical 70 kN
Hollowcore plank
L2 with cores opened
x 20 kN/m 70 kN
2 Precast support
beam with
anchored ferrule
TRANSVERSE EDGE-BEAMS ONLY SECTION CC
13
5.13 Fire Rating The effective thickness of a hollowcore plank is
taken as the nett cross-sectional area divided by
The fire rating or fire resistance level (FRL) of a
its width. If the effective thickness is not sufficient
floor is specified in the building codes as the
to achieve the required fire rating, this can be
period in minutes during which the floor must
increased by providing fewer cores, a concrete
retain its structural adequacy, integrity and
topping or an insulating layer to the soffit.
insulation when subjected to the standard fire test
and is expressed as 180/90/90 for example (ie 180 As the size and spacing of the cores vary with the
minutes structural adequacy/90 minutes particular machine there are some small
integrity/90 minutes insulation). differences in the deemed-to-comply fire resistance
levels of the planks provided by different
The FRL is normally varied by changing the cover
manufacturers. In practice these differences tend
to the strands and perhaps adding topping to the
to be significant only for the higher fire ratings and
floor. This is effective up to a fire resistance period
for planks that are not topped.
of 180 minutes. Beyond that it is usually necessary
to vary the number of cores or increase the soffit Grouted joints of untopped planks have been
thickness or insulate the soffit. Fire protection must shown by fire tests to provide a fire resistance
be maintained at penetrations through cores. This level at least equal to that of the plank section.
can be achieved by back-filling them with concrete However, untopped planks should generally be
for the requisite length. restricted to lower fire resistance levels unless
adequate restraint or tie reinforcement at the ends
The Concrete Structures Code, AS 3600, specifies
of the planks can be provided to stop spreading.
that fire resistance be met either by testing or
calculation or by proportioning members to comply If the required cover to the strand results in an
with certain rules. In practice the deemed-to- inefficient design for the specified load capacity,
comply rules are adopted as a convenient method the cover can be reduced by applying an
of compliance. Two criteria must be satisfied. appropriate thickness of insulating material to the
soffit. Continuity can also be used to increase the
Insulation requires a minimum effective
structural adequacy for a given cover. The
thickness of concrete and a minimum thickness requirement (AS 3600, Clause 5.5.3) is that the
of concrete between adjacent cores and floor is structurally-continuous at one end under
between a core and the exposed surface. the superimposed loads. Note that it is more
Structural adequacy requires a minimum economical to provide the required cover and use
concrete cover to the strand. simply-supported members.
14
5.14 Sound Insulation 5.15 Durability
Hollowcore floor planks provide a high level of Hollowcore planks are cast using concrete with a
acoustical insulation to airborne sound low water-cement ratio and high strength, typically
transmission and are similar to solid concrete in excess of 40 MPa. This concrete is inherently
slabs in the transmission of impact noise. The durable and protects the strands provided that the
parameter which is used to measure the resistance thickness of cover is appropriate to the degree of
of a wall or floor to airborne sound transmission is
exposure.
the Rw rating. Rw stands for Sound Reduction
Index and is a single-number measure of the The Concrete Structures Code, AS 3600, provides
sound transmission loss of air-borne sound a classification of typical exposure conditions to
through the component. The larger the value of Rw cover the range from an internal enclosed
the greater the sound insulation. A negative environment to exterior environment with exposure
adjustment factor Ctr is added to the Rw value to conditions of different degrees of severity. Typical
compensate for low frequency sounds in the
values are shown in Table 2.
environment, such as traffic noise.
Building codes specify minimum values of sound For very severe conditions of exposure protective
insulation for floors and walls separating different coatings may be used to reduce the ingress of
occupancies in residential buildings. A floor corrosive agents. Further guidance on design for
separating dwellings must have an Rw + Ctr not durability may be obtained from the Commentary
less than 50 dB. A 150-mm deep plank with 60 mm on AS 3600.
of topping meets this requirement.
Impact noise is conducted easily through building Table 2 Required Concrete Cover for
materials and can travel great distances. The Various Exposure Classifications
Normalised Impact Sound Pressure Level
(Ln,w + C1) is a single-figure rating of the overall Class- Typical Concrete cover (mm)
impact sound insulation performance of a floor- ification exposure conditions for 40 MPa concrete
ceiling assembly. It is to be 62 dB or greater for Al Enclosed within building or
floors between dwellings. exterior inland non-industrial,
Impact noises are very dependent on the floor arid zone 20
surface and it is best to arrest the sound at the A2 Exterior inland non-industrial,
impact point. Hollowcore floors, in combination with temperate zone 20
resilient materials, are effective at this. Carpet on a
resilient underlay provides the best insulation. B1 Exterior 150 km from coast
Overlays such as rubber and vinyl are less and inland industrial, any zone 30
effective. Hard surface areas, such as tiling, B2 Exterior 01 km from coast,
require the working surface to be resiliently- any zone 45
supported on the hollowcore plank to achieve the
required impact rating. All these are normal
construction techniques.
15
A connection should not unnecessarily restrain
6 CONSTRUCTION DETAILS volume change movements that occur in precast
concrete. Movement joints should be provided at
6.1 Connections regular intervals in the structure, usually at every
third span longitudinally. If these movements are
The connection details at a support must not only restrained, significant axial forces can develop in
transfer load but also contribute to the monolithic the planks, reducing shear capacity in particular.
behaviour of the entire structure. Tie arrangements
in the longitudinal and transverse directions should The length of compression bearing required to
provide the required diaphragm action, transverse adequately support a plank is a function of the
distribution of vertical loads, differential reinforcing detail across a joint and the
settlements and restrained deformations. The construction tolerances of the members coming
detailing of the connection is usually at the together at the support. Detailing of the bearing
discretion of the Manufacturer as he is familiar with length should allow for realistic tolerances and
the economical arrangements to suit his product. provide adequate clearances for erection and
Any special forces to be taken into account, such concreting of reinforcement details. The bearing
as those due to frame action, should be specified lengths set out in Table 3 are for planks in simple
by the Structural Engineer for the project. The bearing. A generally-accepted absolute minimum
Manufacturer details the planks to include all the to support any size plank in bearing is 50 mm.
items that are cast into or supplied with the planks. Tolerances for the dimensions of planks, as
Any other items necessary to complete the supplied, are set out in Chapter 7 Guide
connection are supplied by the Building Contractor. Specification.
The bearing strip shown in Figures 16 and 17,
6.2 Bearing Support must be specified by the designer if the plank is
not to sit directly on its support. A concrete bearing
Typical connection and support details are shown surface is often provided with an elastomer strip
in Figures 15 to 17. Hollowcore units are normally set back at the edge. These strips are usually 2 or
designed to be simply-supported and the 3 mm thick. Planks supported on masonry walls
connections at the supports should be detailed require a bearing strip or slip joints to separate the
accordingly, taking into account the requirement for different materials and to prevent cracking or
overall structural integrity. Unintended restraining spalling of the brickwork. Rendered walls and
effects at the supports by stiff structural elements cornices should be detailed to permit some
such as cross-walls may need to be considered. movement in the floor planks.
Continuity reinforcement in topping over the
supports must have sufficient cover, allowing for
transverse steel and laps.
16
Tie as required Topping with
Topping with any moment restraint reinforcement as required
reinforcement as required
EXTERNAL MASONRY CAVITY WALL DETAIL INTERNAL MASONRY LOADBEARING WALL DETAIL
Precast or insitu concrete edge beam Precast beam with core Precast column with
holes for column bars projecting bars
EXTERNAL CONCRETE BEAM DETAIL
* For recommended bearing lengths, see Table 3 (50 mm absolute minimum) INTERNAL CONCRETE BEAM/COLUMN INTERSECTION DETAIL
17
N20 dowel at 6001200 centres, typical
Topping with reinforcement N20 dowel or studs at
N12 hairpin tie in core breakout, typical as required 3001200 centres, typical
Topping with reinforcement as required
3-mm neoprene
Hollowcore floor plank with dam in cores Hollowcore floor plank
bearing pads, typical*
with dam in cores
3-mm neoprene bearing pad, typical* NOTE: If unrestrained against
rotation, beam may require
Steel edge beam NOTE: May require propping Steel support beam propping if loaded on one
until connection reaches strength
side during erection
EXTERNAL STEEL BEAM DETAIL INTERNAL STEEL BEAM DETAIL
Hollowcore floor plank with dam in cores Hollowcore floor plank 3-mm neoprene
3-mm neoprene bearing pad, typical,* with dam in cores bearing pads, typical*
on steel shelf angle fixed to wall Steel beam with continuous NOTE: If unrestrained against
rotation, beam may require
Precast or insitu concrete wall angles welded to web (difficult
propping if loaded on one
to erect if same detail each end) side during erection
EXTERNAL STEEL SHELF ANGLE DETAIL INTERNAL SHELF ANGLE ON STEEL BEAM DETAIL
Hollowcore floor plank with dam in cores Hollowcore floor plank 3-mm neoprene
with dam in cores bearing pads, typical*
3-mm neoprene bearing pad, typical*
NOTE: Lintel may require
Channel-and-plate lintel over opening Steel angles back-to-back propping if loaded on one
or steel tee section side during erection
18
6.3 Insitu Connection 6.4 Steel Support Beams
A connection type, which does not require a direct Steel support beams may be designed for
bearing or corbel support for the plank, is shown in composite action with the plank and topping
Figure 18. An insitu reinforced concrete interface (Figure 17) by providing for shear transfer at the
transfers moment and shear between the topped interface. If the overall depth of construction is
plank and the supporting wall panel. During critical, support angles may be welded to the web,
construction a temporary angle is bolted to the wall thus reducing the floor height. Note that clearances
to support the plank and topping until the are needed between the planks and beam for
connection gains strength. The projects in which satisfactory erection and this arrangement should
this type of support has been used, along with the not be used at both ends without careful
results of test programmes and advice on design, consideration of the installation sequence. Bolted
are available from manufacturers. splices in steel beams should be detailed so that
they do not interfere with the bearing of the planks.
6.7 Ties
Structural integrity ties may be required in both
longitudinal and transverse directions. These may
SECTION AA be reinforcement or strand grouted into keyways or
joints at the ends of planks. Connection to the
Figure 18 Insitu Connection Detail structure is usually by cast-in inserts. Care is
needed in setting out the planks to ensure that the
keyways line up with adjacent spans, projecting
bars or ferrule locations.
19
6.8 Penetrations
Penetrations and block-outs in planks should not
cut through the strand unless this has been
allowed for in the design, Figure 19. Any coring on
site should be restricted to defined parts of
members. Where large penetrations are required
full-width headers (Figure 20) may be used to
support the end of a plank and transfer the load to
adjacent planks. These planks must be designed
for the additional load.
Suitable
A locations
600 maximum
Core holes may without use of
be cut on-site header beam
A A
Hangers
20
6.9 Hangers 6.10 Waterproofing
Fixings and support hangers (Figure 21) should Hollowcore decks which are open to the weather
be installed strictly in accordance with the can be made waterproof in the usual ways. These
suppliers directions. Where heavy loads are to be include:
supported, through-bolts to a distribution plate or
Post-tensioning a topping of minimum 100-mm
beam may be required. These are required to be
in accordance with the design engineers thickness
specification. Using a proprietary waterproofing admixture
which is capable of sealing cracks to 0.4-mm
width. The Suppliers recommendation must be
strictly followed
Membranes.
In each case, only careful construction practice will
ensure a satisfactory result.
21
Scope
7 GUIDE SPECIFICATION
This guide specification covers the manufacture
and erection of hollowcore floor planks produced
This guide specification is intended to be used in by an approved manufacturer.
the preparation of the specification for a particular
project. It should be checked for compatibility with
Design
the particular job requirements by deleting any
provisions that do not apply and adding special Planks shall be designed in accordance with
provisions needed. AS 3600, except where industry practice provides
a proven alternative method.
The manufacturer shall prepare and submit shop
drawings for approval of the general arrangement
of the planks, adequacy and dimensions prior to
manufacture. Shop drawings shall show the
location of all planks with all major openings
detailed. Shop drawings detailing each unit, cast-in
inserts and its strand configuration shall be
submitted to the building contractor for approval.
The design of the structure, including checking the
adequacy of the hollowcore planks for their
intended use in the structure, shall be the
responsibility of the Structural Engineer for the
project.
Materials
Cement shall comply with AS 3972 and
supplementary cementitious materials with
AS 3582 parts 1 and 2. Aggregates shall comply
with AS 2758.1. Chemical admixtures shall comply
with AS 1478.1.
Prestressing steel shall be stress-relieved low-
relaxation strand complying with AS 1311. Strand
shall be clean and free of deleterious substances
at the time of concreting.
Concrete shall have a minimum characteristic
28-day strength of 40 MPa and shall conform to
the requirements of AS 3600. Concrete strength at
release of prestress shall be a minimum of 25 MPa
or as required by the structural drawings.
Topping concrete shall have a minimum
characteristic 28-day strength of 32 MPa or as
shown on the drawings. If topping concrete is used
to grout the keyways, the maximum aggregate size
shall be 14 mm.
22
Manufacture Bearing strips shall be accurately set where
required. Place any reinforcement required by the
Hollowcore floor planks shall be cast on a long-line
drawings. Keyways shall be filled and compacted
bed by an approved machine and mechanically
with a 3:1 sand-cement grout mix or by the topping
compacted. The top surface shall be finished as
concrete using a maximum aggregate size of
cast by the machine or intentionally-roughened to
14 mm. Voids at plank ends shall be sealed to
achieve the specified bond characteristics of the
prevent penetration of topping into the cores by
topping or other finish applied after erection.
more than 50 mm. It should not be more than the
The underside finish shall be as cast against the support length without considering the implications
bed in accordance with good industry practice. on the shear capacity.
Some surface voids and colour variations shall be
acceptable in accordance with the sample agreed
Attachments and Penetrations
prior to casting.
Attachments and fixings to the hollowcore planks
shall be in accordance with the approved details
Tolerances
only and shall not impair or reduce the strength of
Floor planks shall be supplied in accordance with the floor planks.
the following tolerances.
Penetrations and chases to the hollowcore planks
Length + 10 mm - 10 mm shall be in accordance with details approved by the
Structural Engineer and agreed by the
Width + 3 mm - 6 mm
Manufacturer.
Thickness + 3 mm - 3 mm
Squareness of end + 6 mm - 6 mm Insitu Topping
Wind 10 mm per 3000 mm The Building Contractor shall provide a well-
compacted insitu structural concrete topping to the
Location of ferrules + 20 mm - 20 mm
floor planks as detailed on the drawings.
Location of strand + 3 mm - 3 mm Reinforcement is to be placed in accordance with
structural details. The plank surface shall be clean
Differential camber and free of loose material and surface-moist
adjacent units 2 mm/m span but not (saturated surface-dry) immediately prior to placing
greater than 15 mm the topping. Finish and cure the topping so that
plastic shrinkage cracks are controlled to
Delivery and Handling acceptable levels. Construction joints in the
topping shall be located as shown on the drawings.
Hollowcore floor planks shall be lifted and
supported during manufacture, storage, transport
and erection operations at the nominated lifting Inspection and Acceptance
positions only. The manufacturer shall provide access to its
production facilities for inspection of work in
Erection progress by the Structural Engineer to verify
conformity of the product with the project
The Building Contractor shall be responsible for specifications.
providing true and level bearing surfaces for the
support of the hollowcore planks. Temporary
shoring and bracing shall also be provided as
necessary to ensure the stability of the structure
during erection. The hollowcore planks shall be
installed by a competent erection contractor.
Where the manufacturer also erects the planks,
the Building Contractor shall be responsible for
providing suitable access at the site to enable
trucks and cranes to operate under their own
power.
23
8 BIBLIOGRAPHY
24
1.2 Design Values
9 SAMPLE CALCULATION
Load factors
Ultimate load combination Ed.dst = [1.2G, 1.5Q]
A hollowcore plank floor is required to span 8 m Moment strength reduction factor m = 0.8
between centreline of bearings and carry a live Shear strength reduction factor v = 0.7
load of 3 kPa plus a superimposed dead load of Short term combination factor s = 0.7
1.5 kPa. It will have an insitu screed of 60 mm
Long term combination factor l = 0.4
thickness forming a composite section. The strands
are located at 40 mm from the soffit. Bearing Working loads
length is 80 mm at each end. Plank mass Whc = 3.8 kN/m
AS 36002001 Concrete structures and Topping mass Wscreed = 1.8 kN/m
AS 11702002 Structural design actions are the Live load Wll = 3.6 kN/m
relevant standards. Superimposed dead load Wsdl = 1.8 kN/m
Ultimate loads
1 TRIAL SECTION Plank mass W*hc = 3.8 x 1.2 = 4.56 kN/m
Choose a 200 deep hollowcore section with 60 mm Topping mass W*screed = 1.8 x 1.2 = 2.16 kN/m
of structural topping, from the load-span charts Live load W*ll = 3.6 x 1.5 = 5.4 kN/m
(Figure 3). Span/depth ratio is 31 and thus Superimposed
vibration response will be satisfactory. dead load W*sdl = 1.8 x 1.2 = 2.16 kN/m
Composite section
Distance to Neutral axis Ybcomp = 138.8 mm
Moment of Inertia Icomp = 1479 x 106 mm4
Bottom section modulus Zbcomp = 10.66 x 103 mm3
Shear area moment for
bottom flange Qbfcomp = 7.2 x 106 mm3
Concrete Properties
Plank strength at release fchci = 25 MPa
Elastic modulus at release Ehci = 25,250 MPa
Plank characteristic strength fchc = 40 MPa
Elastic modulus at 28days Ehc = 31,900 MPa
In-situ screed strength fc.screed = 32 MPa
In-situ elastic modulus Escreed = 28,500 MPa
Concrete density concrete = 2,500 kg/m3
Other Variables
Span Ls = 8.0 m
Bearing length Lbrg = 80 mm
Overhang past bearing Lohang = 0 mm
25
2 SECTION ANALYSIS 2.2 Prestress on the Precast Cross-Section
In the following calculations the stress due to
2.1 Number of Strands
prestress or bending at a particular level above the
Assuming 9.3-mm diameter strand at 35 mm cover,
bottom (soffit) of the cross-section is often
the effective depth (dp) of the composite section is
required. The generic equations used are as
260 - 40 = 220 mm. follows.
The area of prestressing steel can be estimated as For computing the stress due a bending moment, M:
follows. The product of the -factor, lever arm
(Y - Yb)
factor (j) and stress in the strand at ultimate is =M
generally about 1200 to 1250 MPa. Taking a value I
of 1200: Where Yb is the distance from the soffit to the
M* neutral axis of the precast or composite section
Ap = = 432 mm2
1200 dp and I is the corresponding moment of inertia.
Select an integer number, Np, of strands of For computing the stress in the precast section
suitable size. Strand diameters available are 9.3, due to a prestress force, P, at an eccentricity, e,
12.7 and, less commonly, 15.2 mm. Using 9.3 mm from the precast neutral axis:
diameter super strand: P P e(Y - Ybhc)
= +
Ap Ahc Ihc
Np = = 7.9
54.7 mm2 Where the eccentricity, e, is the distance from
Allow some margin strand centreline to the precast neutral axis and Y
Say, Np = 9 is the distance from the soffit to the level at which
Then, Ap = 492.3 mm2 the stress is required The section properties are as
defined in item 1.1 above. The section modulus, Z,
Adopt 9 off 9.3 mm dia. strand with an ultimate at the top or bottom fibre is the moment of inertia,
stress, fp, of 1860 MPa. I, divided by the distance to the neutral axis.
Compression stress is taken as positive.
The jacking load of strand usually lies in the range
65% to 80% of ultimate stress, with 70% as a Check that the bottom fibre stress gives a
typical value. Prestress loss occurs with time and reasonable ratio to release strength (say, about
ranges from 18 to 25%, experience suggests to 0.6) and calculate the residual prestress at the
allow 11% at release and 22% total with this critical section for flexure for later use. The top
amount of prestress until checked. fibre stress at release can also be checked at the
prestress development length from the end of the
For typical loss calculations, see Chapter 6 of plank. It includes some self-weight stress and may
Bibliography Item 1. be tensile. It is usually not critical for the amount
Pj = (70% fp)Ap = 641 kN and eccentricity of prestress used in hollowcore
planks.
Pi = 89% Pj = 570.5 kN
The strand eccentricity, e, for the precast section is
Pf = 78% Pi = 445 kN 99.8 - 40 = 59.8 mm.
Pi Pi e
bpi = + = 8.7 MPa
Ahc Zbhc
Pf Pf e
bphc = + = 6.8 MPa
Ahc Zbhc
26
2.3 Flexural Capacity of Composite Section Check that the maximum flexural tensile stress
The flexural capacity can be determined by under short-term service loading does not exceed
standard formulae for a rectangular section 0.5fc . Values for the short-term factor, s, are
provided the neutral axis is above the zone of the given in AS 1170.0. For office loading s = 0.7.
cores. The rectangular stress block factor, g, and
the stress in the strand at ultimate moment, st, ft = 0.5 fchc = 3.2 MPa
are calculated in accordance with AS 3600
Clause 8.1. The equations for ku and Mu can be The net bottom fibre stress in the precast after
topping is:
found in standard concrete texts, see Chapter 7 of
Bibliography Item 13. Mhc Mscreed
bhc = bphc - - = 0.37 MPa
The concrete strength in the calculation is that of Zbhc Zbhc
compression
the insitu topping for a composite section. The
value of fp is the appropriate ultimate strength for The bottom fibre stress at service load is:
the strand diameter. The effective depth of the Msdl Mll
bcomp = bhc - - s = -2.9 MP
composite section is 220 mm. Zbcomp Zbcomp
tension
= 0.85 - 0.007(fc.screed - 28) = 0.822
< allowable ft OK
k1 = 0.4
Ap fp
k2 = = 0.108
Bhc dp fc.screed
k1 k2
st = fp 1 - = 1761.9 MPa
Ap st
ku = = 0.147
0.85 fc.screed dp Bhc
Mu = m Mu = 143.4 kNm
> M* OK
The ultimate moment capacity of the section must
exceed its cracking moment by a margin of 1.2
(AS 3600, Clause 8.1). The cracking moment of a
composite section is affected by the mass of the
insitu screed since it is carried on the precast
section alone and reduces the bottom fibre
prestress. However the composite action also
increases the section properties. Thus at mid-span,
where the cracking moment is a minimum:
Mhc + Mscreed
Mcr = bphc + 0.6fchc - Zbcomp + Mhc + Mscreed = 89 kNm
Zbhc
Mu
= 2.02 > 1.2 OK
Mcr
27
2.4 Shear 2.5 Flexure-shear
The requirements of AS 3600, Clause 8.2, for The flexure-shear capacity at a cross-section must
flexure-shear must be met at all sections of the be calculated at several locations along the span
plank. This capacity can be calculated directly. The to locate the critical section. For a UDL the shear
provisions for web-shear (principal tension capacity equation in AS 3600, Clause 8.2, is a
cracking) only apply to cross-sections uncracked in descending curve from the support to mid-span.
flexure. The calculation for web-shear capacity is The minimum difference between the capacity and
more involved except at the neutral axis. Refer to a the shear force at a section occurs at about
standard text for derivation of the formulae, such quarter span where shear is significant and
as Chapter 12 of Bibliography Item 13. bending moment is reasonably high.
At sections uncracked in flexure, the criteria used Check the capacity at quarter span.
below is that both the flexure-shear must be less The un-factored plank and topping dead loads act
than the calculated capacity and the maximum on the precast plank section, reducing the effective
principal tension must be less than the allowable prestress in the composite section, this moment is:
value in AS 3600, Clause 8.2. The section cannot Ls
be reinforced for shear so it is not necessary to x= = 2.0 m
know the actual web-shear capacity. 4
28
2.6 Web-shear The section is uncracked, hence web-shear
The principal tension under the design loading at a provisions apply.
cross-section is limited to 0.33fchc by AS 3600, Y = 85 mm
Clause 8.2. It is not obvious where the maximum
value will occur and a number of locations in the Direct stress at this location is:
section will require examination. These include the Px Y - Ybhc Y - Ybhc Y - Ybcomp
minimum web width, the neutral axis and the x = - Px e + M*xhc + M*x
bottom web-flange junction. The latter only applies Ahc Ihc Ihc Icomp
to planks with non-circular voids. At positions other = 1.29 MPa
than the neutral axis there will be flexural stress on compression
the cross-section due to superimposed loads in
bv = bwhc
addition to the self weight and prestress.
The critical section for web-shear is likely to be at V*x Qbfcomp
s = = 0.6 MPa
dp from the support. In a hollowcore plank this Icomp bv
section will almost always be within the
development length of the strand where shear is at x 2 x
px = + s2 - = 0.24 MPa
a maximum and the prestress will be less than the 2 2
full amount. tension
< p OK
Check intersection of web and bottom flange.
As an example, check the intersection of web and The web width, bv, is the total width across the
bottom flange at a section located at the effective plank at the level being considered, in this case
below the flange fillet. Q is the first moment about
depth from the support. There are corner fillets the neutral axis of the cross-section area below
commencing at 85 mm from the soffit. that level. Note that compressive direct stress is
positive in the above equations. The flexure-shear
The development length of a strand is 60 capacity must also be checked.
diameters. The available prestress development
length, Ld, from the end of the plank to the section
includes the bearing length and any overhang 2.7 Interface shear
beyond the bearing. Check the interface shear (AS 3600, Clause 8.4)
between the topping and the plank, using the
Ld = dp + Lbrg + Lohang = 300 mm appropriate surface roughness, in this case
60 strand diameters assume a smooth machine-screeded surface.
The first 10% of the total development length is 5 = 0.2
assumed to be unstressed (AS 3600, Clause 13.3).
Thus the prestress force at a section within the fct = 0.4 fc.screed = 2.3 MPa
development length is:
Ld - 0.1(60 db) Vuf = v 5 Bhc dp fct = 83.6 kN
Px = Pf = 216.4 kN > V* OK
0.9(60db)
The maximum allowable principal tension is:
(W*hc + W*sdl) x
M*xhc = (Ls - x) = 6.7 kNm
2
(W*ll + W*sdl) x
M*x = (Ls - x) = 7.6 kNm
2
29
2.8 Deflection The long-term service load deflection of the datum
Calculate the deflection of the plank at installation top screed surface has only the long-term
and under long-term service load using the components of the multipliers for the prestress,
deflection multipliers from Table 3 in Bibliography plank mass and topping mass in the deflection
Item 12 (reproduced below). The insitu topping calculation. Therefore the elastic deflection
provides a level surface initially and is the datum component must be subtracted from the multipliers
from which subsequent deflections are measured. in the Table (below), e.g. for ps the long-term
Downward deflection is negative in these component of the multiplier for a composite unit is
calculations. 2.2 -1 = 1.2. Values for the long-term load factor,
The hog due to prestress at release is: l, are given in AS 1170.0. For office loading
l = 0.4.
Pi e Ls2
ps = = 15.6 mm top.surface = (1.2 ps + 1.4 hc + 1.3 screed) +
8Ehci Ihc 3.0 sdl + 3.0 l ll
The self-weight deflection is: = - 15.3 mm
-5 Wscreed Ls4
screed = = - 4.3 mm
384 Ehc Ihc
-5 Wsdl Ls4
sdl = = - 2.3 mm
384 Escreed Icomp
-5 Wll Ls4
ll = = - 4.5 mm
384 Escreed Icomp
Suggested Multipliers for Estimating Long-term Cambers and Deflections for Typical Elements
[Based on Table 3 in Bibliography Item 12]
Composite topping
Stage Component Application Without With
Erection Deflection (downward) Elastic deflection due to element mass at release of prestress 1.85 1.85
Erection Camber (upward) Elastic camber due to prestress at time of release of prestress 1.80 1.80
Final Deflection (downward) Elastic deflection due to element mass at release of prestress 2.70 2.40
Final Camber (upward) Elastic camber due to prestress at time of release of prestress 2.45 2.20
Final Deflection (downward) Elastic deflection due only to superimposed dead load or to
long-term live load 3.00 3.00
Final Deflection (downward) Elastic deflection caused by the composite topping 2.30
30
Core break-outs are
used to grout in
integrity ties, see
Figure 13 (page 13)