ENCLOSURE 0411 SIKA waterproofing external and tanking

0411 SIKA WATERPROOFING EXTERNAL AND TANKING

1 GENERAL

.1.1 RESPONSIBILITIES
General
Requirement: Provide SIKA roof and deck waterproofing systems to substrates, as documented, which
are:
- Waterproof under five minutes duration rainfall intensity, which has an average recurrence interval of
100 years.
- Graded to falls to dispose of stormwater without ponding above the depth of lapped seams.
- Able to accommodate anticipated building movements.
- Able to accommodate its own shrinkage over the warranty life of the waterproofing system.
.1.2 COMPANY CONTACTS
Sika Technical contacts
Web link: www.sika.com.au
.1.3 CROSS REFERENCES
General
Requirement: Conform to the following worksection(s):
- General requirements.
[complete/delete]
.1.4 STANDARDS
Membrane materials
Standard: To AS 4654.1.
Membrane design and installation
Standard: To AS 4654.2.
Stormwater drainage
Standard: To AS/NZS 3500.3.
.1.5 MANUFACTURER'S DOCUMENTS
Technical manuals
Technical data: www.sika.com.au/cmc/Waterproofing.htm
.1.6 INTERPRETATION
Definitions
General: For the purposes of this worksection the definitions given in AS 4654.1 and AS 4654.2 and
the following apply:
- Bitumen: A viscous material from the distillation of crude oil comprising complex hydrocarbons,
which is soluble in carbon disulphide, softens when it is heated, is waterproof and has good powers
of adhesion. It is produced as a refined by-product of oil.
. SBS bitumen: Bitumen modified with Styrene Butadiene Styrene, a thermoplastic rubber that
undergoes a phase inversion at elevated temperature and converts to an elastomeric material.
The membrane is reinforced with fibreglass or non-woven polyester (NWP).
- Bond breakers: A system preventing a membrane bonding to the substrate, bedding or lining.
- Double detail joint: A joint formed by turning up and bonding the horizontal membrane to a vertical
substrate and adding an overflashing of membrane material bonded to the vertical substrate and
folded over and bonded to the horizontal membrane. In certain situations the double detail can be
achieved by bonding an angle profile of membrane material to the junction prior to laying the
membrane
- Elastomer: A polymer having elastic properties similar to rubber.
- Membranes: Impervious barriers to liquid water.
NATSPEC (Oct 13) 1 [insert date]
ENCLOSURE 0411 SIKA waterproofing external and tanking

- Membrane systems: Combinations of membranes, flashings, drainage and accessories which form
waterproof barriers and which may be:
. Loose-laid.
. Bonded to substrates fully or partially.
. Fixed mechanically to substrates.
. Protected either by ballast or an external insulation, also known as inverted membrane roof
assembly (IRMA), or by both.
. Trafficable, which may be for maintenance, pedestrians or vehicles.
- Plasticised PVC: Rigid PVC made flexible with plasticisers to form a plastic sheet membrane (vinyl).
- Polyurethane liquid applied: Solvent based formulations which moisture cure to form an elastic
rubber membrane.
- Slip sheet: A sheet used to isolate the membrane system from the supporting substrate or from the
topping or mortar bedding above. The most common material is polyethylene sheeting.
- Substrates: The surfaces on which membrane systems are laid.
- XPS: Extruded polystyrene.
.1.7 INSPECTION
Notice
Inspection: Give notice so that inspection may be made of the following:
- Substrate preparation completed.
- Secondary layers preparation completed.
- Before membranes are covered up or concealed.
- Underflashings complete before installation of overflashings.
- After flood testing.
.1.8 SUBMISSIONS
Applicators
Requirement: All work to be completed by a Sika approved applicator.
Documents: Submit evidence of accreditation from Sika Australia.
Execution records
Placing records: Photographically record the application of membranes and label with the following
information:
- Date.
- Portion of work.
- Substrate preparation.
Products documentation
Documents: Submit Sikas technical data sheets and material safety data sheets.
Samples
Requirement: Submit 300 x 300 mm samples of each type of membrane including the finish of the
visible surface.
Shop drawings
Requirement: Submit shop drawings showing the following:
- Junctions with vertical surfaces.
- Drainage details.
- Control joints.
- Flashings.
- Penetrations.
- Corners.
- Terminations and connections.
- Membrane layers.
- Insulation and protection.

NATSPEC (Oct 13) 2 [insert date]


ENCLOSURE 0411 SIKA waterproofing external and tanking

Substrate acceptance
Applicator or installer: Submit the applicators or installers certification of the acceptability of the
substrate.
Timing: Before commencing application or installation.
Warranty
Warranty type: Interlocking with the applicator or installer.
Extent: [complete/delete]
Sika product: [complete/delete]

2 PRODUCTS

.2.1 GENERAL
Product substitution
Other external waterproofing and tanking: Conform to PRODUCTS, GENERAL, Substitutions in
the General requirements worksection.
.2.2 MARKING
Identification
General: Deliver materials to the site in Sikas original sealed containers or packaging legibly marked
to show the following:
- Manufacturers identification.
- Product brand name.
- Product type.
- Quantity.
- Product reference code and batch number.
- Date of manufacture.
- Material composition and characteristics such as volatility, flash point, light fastness, colour and
pattern. Provide technical data sheets if not shown on labels.
- Handling and installation instructions.
- Material safety data sheets. (Available online).
.2.3 SINGLE LAYER PVC SHEET MEMBRANES
SarnafilS327 L
Description: Polyester scrim reinforced, multi layer, synthetic roof waterproofing membrane based on
premium quality PVC for mechanically fixed roofing systems.
Sarnafil G 476
Description: Glass fibre reinforced, multi layer, synthetic roof waterproofing membrane based on
premium quality PVC. Non UV stable for below ground applications.
Sarnafil G 410 L
Description: Glass fibre reinforced, multi layer, synthetic roof waterproofing membrane based on
premium quality PVC.
Sarnafil G 410 L Felt 200 g
Description: Glass fibre reinforced, multi layer, felt backed synthetic roof waterproofing membrane
based on premium quality PVC.
Sarnafil F 610
Description: Dual layer, homogenous roof waterproofing membrane based on premium quality PVC.
For detailing.
Sarnafil F 610 Felt 130 g
Description: Dual layer, felt backed homogenous roof waterproofing membrane based on premium
quality PVC.
.2.4 LIQUID APPLIED MEMBRANES
Sikafloor-400N Elastic
Description: UV-resistant, highly elastic, moisture curing polyurethane waterproofing membrane.

NATSPEC (Oct 13) 3 [insert date]


ENCLOSURE 0411 SIKA waterproofing external and tanking

Data sheet: Sikafloor-400N Elastic


SikaTite-PUD Plus
Description: One-component, water-based polyurethane modified waterproofing membrane.
VOC: 2.5 g/Litre.
SikaTite Primer
Description: Single component acrylic emulsion primer for use with SikaTite PUD Plus.
Data sheet: SikaTite Primer
VOC: 0.35 g/Litre.
Sikafloor-156
Description: Solvent free, low viscosity high performance epoxy primer.
Data sheet: Sikafloor-156
VOC: 24 g/Litre.
Sika Thinner C
Description: 10% thinner used to dilute Sikafloor-400N elastic for the purpose.
Data sheet: Reference made to product use through other Technical Data Sheets when required.
.2.5 ACCESSORIES
Sarnametal sheet
Description: 0.6 mm thick galvanized steel sheet steel with a paint finish on one face and a Sarnafil G
410-12 PVC membrane laminated to the other.
Sarnafil S-Termination Bar III
Description: 2 x 35 mm aluminium alloy strip with one side bending edge. 6.5 mm diameter fixing holes
at 100 mm centres.
Sarnafil S-U Bar
Description: Perimeter fixation bar comprised of a 25 x 6 x 1 mm thick galvanized metal strip with
reinforced bending edges. 7.5 mm diameter fixing holes at 50 mm centres.
Sarnafil Dcor Profile
Description: PVC extrusion for fixing to roof membranes for decorative purposes.
Sarnafil Stainless Steel Rainwater Outlet
Description: Stainless steel outlet combined with a Sarnametal flange with a PVC membrane attached.
Sarnafil Stainless steel Leaf Guard
Description: Mechanically fixed guard for tops of SS Rainwater Outlets to prevent leaf debris entering
drainage inlets.
Sarnafil Walkway pad
Description: 600 x 600 x 7 mm thick walkway pad with herringbone pattern on walking surface.
.2.6 THERMAL INSULATION
Rockwool
Description: 100 mm thick 175 kg/m density rockwool sheets.
Extruded polystyrene
Description: 25 mm thick 32 kg/m density extruded polystyrene sheets.
.2.7 PROTECTION BOARD
Protection board
Description: Hollow twin wall plastic board manufactured from lightweight extruded polypropylene.
.2.8 SLIP SHEETS
Polyethylene
Description: 1 layer of 300 m thick polyethylene sheet.
Geotextile
Description: 1 layer of 130 g/m geotextile sheet.

NATSPEC (Oct 13) 4 [insert date]


ENCLOSURE 0411 SIKA waterproofing external and tanking

.2.9 DRAINAGE CELL PANELS


General
Drainage system: Provide modular cell panels for drainage, protection or both, complete with filter
fabric.
Application: [complete/delete]
Membrane protection: Required.
Planter bases
Cell panels: Polypropylene (PP) injection moulded.
Panel thickness: [complete/delete]
Filter fabric: 130 gm geotextile fabric.
Landscaped areas
Cell panels: Polypropylene (PP) injection moulded with factory applied filter fabric.
.2.10 FASTENERS
Sarnafil Fastener SB Series
Description: 6.3 mm diameter case hardened carbon steel self-drilling screws with an E-coating
(Electroplated).
Sarnafil Washer IF/IG-C
Description: 82 x 40 mm washer with a 6.3 mm diameter hole, fabricated from 1 mm thick galvanized
metal plate, and for use with Sarnafil BD Series Fasteners.
Sarnafil Washer KTL
Description: 82 x 40 mm washer with a 7.5 mm diameter hole, fabricated from 1 mm thick galvanized
metal plate, and for use with Sarnafil BD Series Fasteners. Incorporates 8 No. stamp-formed barbs.
Sarnafil Thermal Insulation Washer
Description: 70 x 70 mm washer with a 7.5 mm diameter hole, fabricated from 1 mm thick galvanized
metal plate, and for use with Sarnafil BD Series Fasteners.
Sarnafil S-Welding Cord
Description: Hot air weldable PVC cord.
.2.11 ADHESIVES
Sarnacol 808
Description: Solvent based adhesive.
Sarnacol 606
Description: Polyurethane based adhesive.
Sarnacol 2142S
Description: Polyurethane based adhesive.
.2.12 SEALANTS
Sikaflex-PRO
Description: High performance polyurethane joint sealant.
Data sheet: Sikaflex-PRO
VOC: 47 g/Litre.
Colour: [complete/delete]
Sikaflex-11FC
Description: One component polyurethane sealant/adhesive.
Data sheet: Sikaflex-11FC
VOC: 62.5 g/Litre.
Colour: [complete/delete]

NATSPEC (Oct 13) 5 [insert date]


ENCLOSURE 0411 SIKA waterproofing external and tanking

3 EXECUTION

.3.1 PREPARATION
General
Substrates: Prepare substrates as follows:
- Fill all cracks in substrates wider than 1.5 mm with a filler compatible with the membrane system.
- Fill voids and hollows in concrete substrates with a concrete mix not stronger than the substrate.
- Remove projections.
- Round off sharp edges.
- Remove deleterious and loose material.
- Remove all traces of a concrete curing compound if used.
- Leave the surface free of contaminants, clean and dust free.
Moisture content
Concrete substrates: Cure for > 21 days.
Moisture content: Verify that the moisture content of the substrate is compatible with the water vapour
transmission rate of the membrane system by testing to AS 1884 Appendix A.
Test type: select from the following:
- Hygrometer test: Seal a hygrometer to the substrate for > 16 hours and measure the relative
humidity of the air between the instrument and the slab.
Falls
Verify that falls in substrates are > 1.5%.
Joints and fillets
Internal corners: [complete/delete]
- PVC membrane: Double detail with non felt backed PVC membrane.
- Liquid applied membrane: Provide 45 fillets 10 x 10 mm with Sikaflex-11FC or Sikaflex-PRO
sealant.
External corners: Round or arris edges.
Control joints: Prepare all substrate joints to suit the membrane system.
Priming for liquid applied systems
SikaTite PUD Plus: Prime substrates with SikaTite Primer for adhesion of membrane systems. Prime
any metal surfaces with a zinc chromate etch primer before application.
Sikafloor-400N Elastic: Prime substrates with Sikafloor-400N diluted with 10% Sika Thinner C and
applied at a rate of 0.4 kg/m.
.3.2 APPLICATION
Protection during installation
General: Protect membrane from damage during installation and for the period after installation where
there is an applied finish such as backfill, topping insulation or other construction activity that may
damage the membrane.
Drains
General: Prevent water from tracking under the membranes at drainage locations.
Drains and cages: Provide removable grates or cages, to prevent blockage from debris. If the finished
surface is above the level of the membrane provide a slotted extension piece to bring the grate up to
the level of the finished surface.
Overflows: Apply a bond breaker to the perimeter of the overflow outlet at its junction with the surface
to which the membrane will be fixed. Turn the membranes into the overflow to prevent water from
tracking behind the membrane.
Sheet joints
PVC sheet membranes:
- Side laps: 80 mm comprised of 40 mm heat welding zone and 40 mm fastener zone (for
mechanically fixed systems).
- End laps: 100 mm. Stagger end lap joints.

NATSPEC (Oct 13) 6 [insert date]


ENCLOSURE 0411 SIKA waterproofing external and tanking

- Method: Heat welded. Ensure welding surfaces are clean and dry. Clean dirty surfaces with a damp
cloth.
Control of movement
General: Provide control joints located over control joints in the substructure.
Fillets and bond breakers: Size to allow the membrane to accommodate the movement.
Bonded membranes: Carry control joints in the substrate through to and into the surface finish.
Backing rod: [complete/delete]
Sealant: [complete/delete]
Joint backing gutter: [complete/delete]
Control joint covers: Install after fixing hobs and membranes.
Membrane terminations
Membrane upturns: Provide upturns above the maximum water level expected from the exposure
conditions of rainfall intensity and wind.
- Height: To AS 4654.2 Appendix A.
- Anchoring: Secure sheet membranes along the top edge.
- Edge protection: Protect edges of the membrane.
Vertical upward terminations - Angle edge protection method:
- Trim: 20 x 25 mm aluminium angle.
- Fixing: Set angle in saw cut to the masonry wall or upstand and fix in Sikaflex-PRO or Sikaflex-
11FC sealant, with the down leg covering the membrane upstand.
Vertical upward terminations - Z section edge protection method:
- Trim: 20 x 10 x 20 mm x 1.6 mm aluminium Z.
- Fixing: Mechanically fix and seal to substrate.
Waterproofing above terminations: Waterproof the structure above the termination to prevent moisture
entry behind the membrane using cavity flashings, capping, waterproof membranes or waterproof
coatings. Contact Sika technical department for additional information.
Vertical downward terminations: [complete/delete]
Horizontal terminations: Do not provide. Use vertical terminations.
Internal roof outlets
Installation: Cast rainwater outlets into the roof slab, set 4 mm below the substrate to allow for a
membrane downturn without localised puddling, with a removable grating and leaf guard. Seal the
membrane onto the section of PVC membrane prefixed to the outlet flange.
Membrane vertical penetrations
Pipes, balustrades, ducts, and vents: Provide separate sleeves for all pipes, ducts, and vents and
have them fixed to the substrate.
Membrane horizontal penetrations
Sleeves: Protect rigid PVC conduits and pipes with a sleeve of SBS bitumen in order to seal to the
membrane without burning the PVC. Do not use high density polyethylene (HDPE) or polypropylene
(PP) pipes or flexible PVC conduit.
Membrane at balcony doors and windows
Requirement: Install membrane before the fixing of door or window frames.
Membrane upturn:
- Sheltered areas: 40 mm above the finished external floor surface or overflow level, whichever is the
higher.
- Exposed areas: 150 mm upturn from the finished external floor level or overflow level, whichever is
the higher.
Hobless and flush thresholds: Install membrane before the fixing of door or window frames with a
continuous grated drain abutting the external face of the door or window sill.
Membrane around skylights and hatches
Requirement: Install membranes to upstands before the installation of the skylight or hatch.
Upstand height above roof surface: [complete/delete]
Membrane at parapets

NATSPEC (Oct 13) 7 [insert date]


ENCLOSURE 0411 SIKA waterproofing external and tanking

Requirement: Terminate membrane upstands under parapet flashing or capping giving 75 mm overlap.
Do not top fix parapet cappings. Seal heads of fasteners against capping.
Membrane at gutters
Requirement: Terminate membrane over a corrosion resistant metal angle fixed to the gutter support
substrate with the vertical leg of the angle turned down into the gutter at least 35 mm.
Membrane at post supports
Post supports fixed before/after membrane: [complete/delete]
Membrane to planter boxes
Membrane: Extend root-resistant membrane at least 100 mm vertically above the soil fill level and
secure.
Drainage: Grade the base of the planter to adequately sized drainage outlets and terminate the
membrane in the outlets.
Drainage riser: Install a riser with drainage slots that extend from the membrane level to the top of the
drainage cell. Extend the riser above the soil fill level and finish with a screw cap to provide access for
drain clearing.
Protection board: Provide protection board to the full extent of the membrane including areas between
soil level and the underside of flashings and cappings.
Drainage cell: Provide geo-filter fabric wrapped drainage cell to the base of the planter and turn geo-
filter fabric up drainage riser at least 100 mm above drainage slots.
Cappings and flashings: Provide capping to the tops of planter walls to protect the membrane. Extend
the capping to overlap the top of the protection board on the inside face of the planter wall. Where
planter walls abut other walls, provide a flashing over the top of the membrane.
Overlaying finishes on membranes
Compatibility: If a membrane is to be overlayed with another system such as tiles, pavers, ballast,
insulation or soil, provide an overlaying system that is compatible with and will not cause damage to
the membrane.
Bonded or partially bonded systems: If the topping or bedding mortar requires to be bonded to the
membrane, provide sufficient control joints in the topping or bedding mortar to reduce the movement
over the membrane.
Slip sheet: If the topping or bedding mortar is structurally sufficient not to require bonding to the
substrate, lay a double slip sheet over the membrane to separate it from the topping or bedding
mortar.
Paint coatings: If maintenance pathways are indicated by a paving paint, use a paving paint which is
compatible with the membrane.
Membrane protection boards:
Installation: [complete/delete]
Location: [complete/delete]
Fixing: [complete/delete]
.3.3 FLOOD TEST
General
Application: Perform a flood test before the installation of surface finishes.
Set-up:
- Measure for dryness the wall/floor junction of adjacent spaces and of the slab soffit below using
electrical resistance testing to AS 1884 Appendix A.
- Record the result for each area.
- Dam the access openings and seal drainage outlets to allow 50 mm water level but no higher than
25 mm below the weir level of the perimeter flashings.
- Provide temporary overflows of the same capacity as the roof outlets to maintain the flood level.
- Fill space with clean water and leave overnight.
Evaluation:
- Make a visual inspection of the wall/floor junction of adjacent spaces and of the slab soffit below for
obvious water or moisture.

NATSPEC (Oct 13) 8 [insert date]


ENCLOSURE 0411 SIKA waterproofing external and tanking

- Test the same areas for dryness using a moisture meter, and compare the results to the
measurements taken before flooding.
Compliance:
- Evidence of water from the visual test: Failure.
- No visual evidence of water: Proceed with the moisture meter test.
- Increase in test results before and after flooding: Failure.
Records: Submit records of all flood tests.
.3.4 COMPLETION
Protection
General: Keep traffic off membrane surfaces until bonding has set or for 24 hours after laying,
whichever period is the longer.
Reinstatement: Repair or replace faulty or damaged work. If the work cannot be repaired satisfactorily,
replace the whole area affected.
Warranties
Waterproofing: Cover materials and workmanship in the terms of the warranty in the form of
interlocking warranties from Sika and the applicator.
- Form: Against failure of materials and execution under normal environment and use conditions.
- Period: Extend the warranty period to 15 years for balconies, ground floor slabs, concrete roofs and
projecting concrete hoods; 15 years for tanking to basement and lift pit walls; and 15 years for
planters.

4 SELECTIONS

.4.1 SCHEDULES
Requirements schedule
Property A B C
Traffic
Nature of traffic
Overlaying finish
Root resistance

Single layer PVC sheet system schedule


Property A B C
Sika system
Method of fixing to substrate
Membrane for detail work
Perimeter fixation Sarnafil S-U Bar
fixed to
substrate with
Sarnafil BD
Series
fasteners. Bond
outside edge of
S-U Bar to
membrane with
Sarnafil S-
Welding Cord.
Accessories
Fasteners
Adhesives

NATSPEC (Oct 13) 9 [insert date]


ENCLOSURE 0411 SIKA waterproofing external and tanking

Property A B C
Sealant
Sealant colour
Thermal insulation
Membrane protection: Horizontal applications
Membrane protection: Tanking (vertical)
Drainage cell
Slip sheet
Surface protection/finish

Liquid applied membrane system schedule


Property A B C
Sika system
Material type Polyurethane
Method of application
Prime coat
1st coat
2nd coat
Anti-slip surface Quartz sand
applied at a rate
of 3 5 kg/m
3rd coat
Dry film thickness (total) ( mm)
Accessories
Sealant
Sealant colour
Thermal insulation
Membrane protection: Horizontal applications
Membrane protection: Tanking (vertical)
Drainage cell
Slip sheet
Surface protection/finish

NATSPEC (Oct 13) 10 [insert date]