1. Specification
Indoor unit type Ceilling Cassette - 4way

Model ATNH243PLAE[LCN246HV]

Decoration panel PT-UMC


Power Supply /V/Hz 1 / 208-230 / 60
Cooling Capacity kW 6.74
Btu/h 23,000
Heating Capacity kW 7.33
Btu/h 25,000
Current Nominal running current A 10.4
Fan Motor Type BLDC
Fan Type Turbo Fan
Motor Output x Number of Unit 60 x 1
Air Flow Rate(H/M/L) CMM 18 / 16 / 14
cfm 636/565/494
External Static Pressure mmAq -
Capacitor F/Vac 220 / 450
Drive Direct Drive
Coil Row x Column x FPI 2R x 8C x 19
Dimensions Body mm(inch) 840 x 204 x 840 (33 x 8 x 33)
(WxHxD) Decorative Panel mm(inch) 950 x 37 x 950(37 3/8 x 1 15/32 x 37 3/8)
Weight Body kg(lbs) 21(46.3)
Decorative Panel kg(lbs) 5(11.02)
Air Filter Long life filter
Sound Level (H/M/L) dB(A)+3 39 / 37 / 34
Piping Liquid mm(inch) 9.52 (3/8)
Connections Gas mm(inch) 15.88 (5/8)
Drain(OD/ID) mm(inch) 32/25
Dehumidification Rate l/h 2.1
Safety devices Fuse, Thermal protector for fan motor
Temperature Sensor Thermistor
Referigerant R410A
Referigerant Control EEV(Outdoor Unit)
Connectable outdoor unit LUU246HV
Power and transmission interunit cable No. x AWG 4 x 18

Note : Conversion Formula


1. Capacities are based on the following conditions: Btuh = kW 3,412
Cooling: - Indoor Temperature 27C(80.6F) DB /19C(66.2F) WB
cfm = CMM 35.3
- Outdoor Temperature 35C(95F) DB /24C(75.2F) WB
Heating: - Indoor Temperature 20C(68F) DB / 15C(59F) WB
- Outdoor Temperature 7C(44.6F) DB / 6C(42.8F) WB
Piping Length - Interconnecting Piping Length 7.5m(24.6ft)
- Level Difference of Zero.
2. Without optional accessories(i.e. Plasma kit, elevation grille etc.) and with maximum airvolume (Cassette type is using PQRCUS0)
3. Wiring cable size must comply with the applicable local and national code.

Copyright 2010 LG Electronics. Inc. All right reserved. -2-


LGE Internal Use Only
Only for training and service purposes
2. Piping Diagrams

Heat Exchanger : Cooling


Th3
Th2 Th2 : Heating

Turbo Fan

Indoor Unit
Th1

LOC. Description PCB Connector


Th1 Thermistor for inlet air temperature CN_ROOM
Th2 Thermistor for EVA. in temperature CN_PIPE/IN
Th3 Thermistor for EVA. out temperature CN_PIPE/OUT

[Unit:mm(inch)]
Model Gas Liquid
ATNH243PLAE[LCN246HV] 15.88(5/8) 9.52(3/8)

Copyright 2010 LG Electronics. Inc. All right reserved. -3-


LGE Internal Use Only
Only for training and service purposes
3. Wiring Diagrams

SW01
CN_OPTION

CN_MOTOR CN_FLOAT CN_DISPLAY

CN_ROOM

CN_PIPE/IN

CN_PIPE/OUT

CN_D/PUMP
CN_VANE2 CN_VANE1 CN_REMO

CN_POWER

Copyright 2010 LG Electronics. Inc. All right reserved. -4-


LGE Internal Use Only
Only for training and service purposes
4. Exploded View
Indoor Unit

130411
158591

131410

148000

131400B
130911C
354211
130911A

148000
352118

W49810

552111 W48300B 131400D


W48310
249310 346810
352150
249951

263230B
359012
263230C W6640
W4056
267110

W3110

330871B 268711B
330871A

W50060 W0FZZ

349480 268711D
268711E

567480A
135500

* 268711D is LGELAP only

Note) * Please ensure GCSC since the replacement parts may be changed depending upon the buyer's request.
Please check the correct parts in View RPL(Replacement Part List) on GCSC.
(GCSC Website http://biz.Lgservice.com,)

Copyright 2010 LG Electronics. Inc. All right reserved. -5-


LGE Internal Use Only
Only for training and service purposes
Front Panel

146811

147581

145200

135500

159830

135303

135800

Copyright 2010 LG Electronics. Inc. All right reserved. -6-


LGE Internal Use Only
Only for training and service purposes
P/NO : MFL62129309 MAY, 2010