Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
CXM/DXM Digital
Heat Pump Controllers
Table of Contents
CXM / DXM Control Features Comparison 2 Safety Features 10
Diagnostic Features 12
Part I - CXM Control 3 Unit Operation Description 12
CXM Overview 3 Special Application Notes 13
Physical Dimensions and Layout 3 Communications 14
Product Specification 3 Typical Schematic 16
Safety Features 5
Diagnostic Features 6 Part III - CXM/DXM Notes
Unit Operation Description 6 CXM/DXM Sensors 17
Typical Schematic 7 Thermostats 18
CXM and DXM Inputs and Outputs Reference 19
Part II - DXM Control 8 Troubleshooting Chart 20
DXM Overview 8 Functional Troubleshooting 21
Physical Dimensions and Layout 8 Performance Troubleshooting 22
Basic Control Features 9 Revisiom History 24
Field Selectable Inputs 9
CXM / DXM Electronic Control Features Comparison
Basic Features CXM CXM-Lon CXM-MPC DXM DXM-Lon DXM-MPC
High and Low Refrigerant Pressure Protection S S S S S S
Water Coil Freeze Protection S S S S S S
True 24VA Thermostat Signals S S S S S S
Thermostat Inputs Compatible with Triacs S S S S S S
Condensate Overflow Sensor S S S S S S
Anti-Short-Cyle Time Delay S S S S S S
Random Start S S S S S S
Alarm (selectable dry contact or 24VA) S S S S S S
Water Valve Relay S S S S S S
Water Valve Relay with Compressor Delay N/A N/A N/A S S S
Emergency Shutdown N/A DDC DDC S DDC DDC
Night Setback with Override N/A DDC DDC S DDC DDC
Outdoor Air Damper Control N/A N/A N/A S S S
Advanced Features
Intelligent Reset S S S S S S
High and Low Voltage Protection S S S S S S
Air Coil Freeze Protection S S S S S S
Freeze Setpoint Field Select (water, antifreeze) S S S S S S
Electric Heat Control Outputs S S S S S S
Boilerless Electric Heat Control N/A N/A N/A S S S
Intelligent Reversing Valve Operation N/A DDC DDC S S S
High/Low Fan Speed Outputs N/A N/A N/A S S S
Intelligent Fan Speed Control N/A N/A N/A S S S
Thermostat Type Select (Y,O or Y,W) N/A N/A N/A S N/A N/A
Reversing Valve Signal Select (O or B) N/A N/A N/A S N/A N/A
Dehumidistat Input N/A N/A N/A S S S
Reheat Dehumidification Control* N/A N/A N/A O O O
Multiple Units on One Thermostat/Wall Sensor N/A DDC DDC S DDC DDC
Service and Reliability Features
Service Test Mode S S S S S S
LED Fault and Status Lights S S S S S S
Fault Memory after Reset S S S S S S
Unit Performance Sentinel S S S S S S
Harness-Type Factory Wiring Connections S S S S S S
Fully Noise-Tested Design S S S S S S
CE Approval S S S S S S
Removable Low Voltage Connector N/A N/A N/A S S S
DDC / Energy Management Features
Echelon LonMark Compliant N/A S N/A N/A S N/A
BACNET Compliant N/A N/A S N/A N/A S
Johnson N2 Compliant N/A N/A S N/A N/A S
Modbus Compliant N/A N/A S N/A N/A S
Leaving Air and Water Temperature Sensor N/A S S N/A S S
Digital Wall Sensor N/A O O N/A O O
S = Standard O = Optional DDC = Feature can be provided by DDC System CXM-Lon = CXM with LonMark Module
DXM-Lon = DXM with LonMark Module CXM-MPC = CXM with MPC Module DXM-MPC = DXM with MPC Module
* = Check with your Factory Representative for model availability MPC = Multiple ProtoCol (BACNET, N2, Modbus)
BR BRG CCG CC
Comp
Off On
C Relay
Test
Factory Low
P2 Voltage Molex
1 HP connector for unit
R JW3 FP1 Low Temp HP harness
JW2 FP2 Low Temp LP
LP
FP1
FP1
Y 5.50
FP2
FP2
6.00 Y RV
Micro
RV
W CO
O 12 CO
G
R
Field Factory Low
C
Thermostat Status P3 Voltage Molex
AL1 JW1- AL2 Dry LED connector for
Connections 1 24Vdc
AL2 electric heat
A EH1 harness
P1 4 EH2
3/8 standoff
Alarm CO
Relay
17B0001N01
4 Mounting Screws:
1.50 3.50 #6 sheet metal screw
1 long
Field Selectable Inputs Air Coil Freeze Protection Limit Setting - Jumper 2 (JW2-
FP2 Low Temp) provides field selection of temperature limit
Test Mode - Test Mode allows the service personnel to setting for FP2 to be 30F or 10F.
check the operation of the control in a timely manner. By
momentarily shorting the test terminals, the CXM control Not Clipped=30F. Clipped=10F.
enters a 20 minute Test Mode period in which all time
delays are sped up 15 times. Upon entering Test Mode, the Alarm Relay Setting - Jumper 1 (JW1-AL2 Dry) provides
Status LED will flash a code representing the last fault. For field selection of Alarm Relay terminal AL2 to be jumpered
Diagnostic ease at the thermostat, the alarm relay will also to 24VAC or to be dry (no connection).
cycle during test mode. The Alarm relay will cycle on and off Not Clipped=AL2 connected to R. Clipped=AL2 dry
similar to the status LED to indicate a code representing the contacts (no connection).
last fault, at the thermostat.
DIP Switches
Note: Code 1 indicates there is no fault in memory; stated
differently, the control has not faulted since the last Note: In the following field configuration options, DIP
power-down to power-up sequence. switches should only be moved when power is removed from
the CXM control, to insure proper operation.
Test mode can be exited by shorting the test terminals for
3 seconds. DIP Switch 1: Unit Performance Sentinel Disable -
provides field selection to disable the UPS feature.
Test mode can also be entered and exited by cycling the G
input, 3 times within a 60 second time period. On = Enabled. Off = Disabled.
During Test mode, the control monitors to see if the FP1 and DIP Switch 2: Stage 2 Selection- provides selection of whether
FP2 thermistors are in the appropriate place. If the control is compressor has an on delay. If set to stage 2, the compressor
in Test mode, the control will lockout, with Code 9, after 30 will have a 3 second delay before energizing. Also, if set for
seconds if: stage 2, the alarm relay will NOT cycle during test mode.
a) the compressor is On in cooling mode and the FP1 sensor On = Stage 1 . Off = Stage 2
is colder than the FP2 sensor. Or, DIP Switch 3: - Not Used.
b) the compressor is On in heating mode and the FP2 sensor DIP Switch 4: DDC Output at EH2 - provides selection
is colder than the FP1 sensor. for DDC operation. If set to DDC Output at EH2, the EH2
Retry Mode - If the control is attempting a retry of a fault, terminal will continuously output the last fault code of the
the status LED will slow flash (slow flash=one flash every 2 controller. If set to EH2 normal, then the EH2 will operate
seconds) to indicate the control is in process of retrying. as standard electric heat output.
Note: In the following field configuration options, jumper On = EH2 Normal. Off = DDC Output at EH2.
wires should be clipped ONLY when power is removed
from the CXM control. NOTE: Some CXM controls only have a 2 position DIP
switch package. If this is the case, then this option can be
Water Coil Freeze Protection Limit Setting - Jumper 3 selected by clipping the jumper which is in position 4 of SW1:
(JW3-FP1 Low Temp) provides field selection of temperature
limit setting for FP1 to be 30F or 10F. Jumper not clipped = EH2 Normal. Jumper clipped = DDC
Output at EH2.
Not Clipped=30F. Clipped=10F.
DIP Switch 5: Factory Setting - Normal position is On. Do
not change selection unless instructed to do so by the Factory.
Table 1: LED & Alarm Relay Operations
Description of Operation LED Alarm Relay
Normal Mode On Open
Normal Mode with UPS Warning On Cycle (closed 5 sec., Open 25 sec.)
CXM is non-functional Off Open
Fault Retry Slow Flash Open
Lockout Fast Flash Closed
Over/Under Voltage Shutdown Slow Flash Open (Closed after 15 minutes)
Test Mode - No fault in memory Flashing Code 1 Cycling Code 1
Safety Features Water Coil Freeze Protection (FP1) - The control will
recognize an FP1 fault, during a compressor run cycle if:
The following safety features are provided to protect the
compressor, heat exchangers, wiring and other components a) the thermistor temperature is below the selected freeze
from damage caused by operation outside of design conditions. protection limit setting, AND
Anti-Short Cycle Protection- The control features a 5 minute b) the thermistor temperature is rising (getting warmer) at
anti-short cycle protection for the compressor. a rate LESS than 2F per 30 second time period. The
FP1 input is bypassed for the initial 120 seconds of a
Note: The 5 minute anti-short cycle also occurs at power up. compressor run cycle.
Random Start - The control features a 5-80 second random FP1 Lockout Code = 4
start upon power up.
Air Coil Freeze Protection (FP2) - The control will
Extended Compressor Operation Monitoring - If the recognize an FP2 fault, during a compressor run cycle if:
compressor relay has been on for 4 continuous hours, then
the control will automatically turn off the compressor relay a) the thermistor temperature is below the selected freeze
and wait the short cycle protection time. All appropriate protection limit setting, AND
safeties including the LP will be monitored during the off
time. If all operation is normal, then if the compressor b) the thermistor temperature is rising (getting warmer) at a
demand is still present, the control will turn the compressor rate LESS than 2F per 30 second time period.
back on. The FP2 input is bypassed for the initial 120 seconds of a
Fault Retry - In Fault Retry mode, the Status LED begins compressor run cycle.
slow flashing to signal that the control is trying to recover FP2 Lockout Code = 5
from a fault input. The CXM control will stage off the
outputs and then try again to satisfy the thermostat "Y" Condensate Overflow - The Condensate Overflow sensor
input call. Once the thermostat input calls are satisfied, must sense overflow levels for 30 continuous seconds to
the control will continue on as if no fault occurred. If 3 be recognized as a CO fault. Condensate Overflow will be
consecutive faults occur without satisfying the thermostat monitored during compressor run cycle.
"Y" input call, then the control will go to Lockout mode. The
last fault causing the lockout will be stored in memory and CO Lockout Code = 6
can be viewed by going into test mode. Over/Under Voltage Shutdown - An Over/Under Voltage
Note: If 1 Try is selected for FP1 and FP2, then there will condition exists when the control voltage is outside the
be no retries for FP1 and FP2 faults. The control will only range of 18VAC to 31.5VAC. Over/Under Voltage Shutdown
try one time for these faults. is self resetting in that if the voltage comes back within
range of 18.5VAC to 31VAC for at least 0.5 seconds, then
Lockout - In Lockout mode, the Status LED will begin fast normal operation is restored. This is not considered a fault or
flashing. The compressor relay is turned off immediately. lockout. If the CXM is in over/under voltage shutdown for
Lockout mode can be soft reset via the thermostat Y input 15 minutes, the alarm relay will close.
or can be hard reset via the disconnect. The last fault causing
the lockout will be stored in memory and can be viewed by Over/Under Voltage Shutdown Code = 7
going into test mode. Unit Performance Sentinel-UPS (patent pending) - The UPS
Lockout with Emergency Heat - While in Lockout mode, if feature warns when the heat pump is operating inefficiently.
W becomes active, then Emergency Heat mode will occur. A UPS condition exists when:
High Pressure Switch - When the High Pressure Switch a) in heating mode with compressor energized, if FP2 is
opens due to high refrigerant pressures, the Compressor relay greater than 125F for 30 continuous seconds, or
is de-energized immediately since the High Pressure Switch b) in cooling mode with compressor energized, if FP1 is
is in series with the compressor contactor coil. The High greater than 125F for 30 continuous seconds, OR FP2 is
Pressure Fault recognition is immediate as well. less than 40F for 30 continuous seconds.
High Pressure Lockout Code = 2 If a UPS condition occurs, the control will immediately go
Example: 2 quick flashes, 10 sec pause, 2 quick flashes, 10 to UPS warning. The status LED will remain on as if the
sec. pause, etc. control is in Normal mode. (see "LED and Alarm Relay
Operation Table" ). Outputs of the control, excluding LED
Low Pressure Switch - The Low Pressure Switch must be and Alarm Relay, will NOT be affected by UPS. The UPS
open and remain open for 30 continuous seconds during "on" condition cannot occur during a compressor off cycle.
cycle to be recognized as a Low Pressure fault. If the low During UPS warning, the alarm relay will cycle on and off.
pressure switch is open for 30 seconds prior to compressor The cycle rate will be On for 5 seconds, Off for 25 seconds,
power up it will be considered a low pressure (loss of charge) On for 5 seconds, Off for 25 seconds, etc.
fault. The Low Pressure Switch input is bypassed for the
initial 120 seconds of a compressor run cycle. Unit Performance Sentinel Warning Code = 8
Swapped FP1/FP2 Thermistors - During Test mode, the calls, the random start delay is omitted.
control monitors to see if the FP1 and FP2 thermistors are
in the appropriate place. If the control is in Test mode, the Heating Stage 2 - To enter Heating Stage 2 mode, W
control will lockout, with Code 9, after 30 seconds if: becomes active (Y already active). The G input must be active
or the W input is ignored. The Compressor relay remains on.
a) the compressor is On in cooling mode and the FP1 sensor EH1 is turned on immediately. With continuing Heating Stage
is colder than the FP2 sensor. Or, 2 demand, EH2 will turn on after 10 minutes. The EH2 will
not turn on (or will turn off if already on) if FP1 temperature
b) the compressor is On in heating mode and the FP2 sensor is greater than 45F and FP2 is greater than 110F.
is colder than the FP1 sensor.
Emergency Heat - In Emergency Heat mode, W becomes
Swapped FP1/FP2 Thermistor Code = 9. active while Y is not active. The G input must be active or
the W input is ignored. EH1 is turned on immediately. With
Diagnostic Features continuing Emergency Heat demand, EH2 will turn on after
The Status LED on the CXM control advises the serviceman 5 minutes. The FP1 and FP2 temperatures do not effect
of the current status of the CXM control. The status LED emergency heat operation.
can display either the current CXM mode or the last fault
memory if in test mode. See Table 1 for a complete listing of Engineering Guide Specifications
codes. If the Fault type is "Primary" (HP, LP, FP1, FP2, or
The following engineering guide specifications for the CXM
CO) then the Fault type will always be retained in memory
control should be a part of all product submittals.
(Primary faults will over write Secondary faults). If the Fault
type is "Secondary" (Over/Under Voltage, UPS or Swapped
FP1/FP2) then the Fault type will only be retained if there are CXM Control
no "Primary" faults in memory. The Secondary Fault types A microprocessor-based compressor controller (CXM)
will not "overwrite" the Primary fault memory. shall be provided to monitor and control unit operation.
The control shall provide compressor and electric heater
Unit Operation Description sequencing, high and low pressure monitoring, field
selectable water and air coil freeze protection sensing,
PowerUp - The unit will not operate until all the inputs
condensate overflow sensing, over/under voltage monitoring,
and safety controls are checked for normal conditions.
and unit performance sentinel. The control shall also
Note: The compressor will have a 5 minute anti-short
provide for water valve connection, a test mode, short cycle
cycle delay at power-up.
protection, random start-up, as well as fault LED, fault
Standby - In Standby mode, Y and W inputs are not active. memory, and intelligent fault retry.
Inputs O and G may be active. Compressor will be off.
The control shall employ a quick attach harness assembly for
Cooling - To enter Cooling mode, Y and O become low voltage connections to the CXM control board to aid in
active. The first time after power-up that there is a call for troubleshooting or replacement. An integral terminal block
compressor, the compressor will follow a 5 to 80 second with screw terminals shall be provided on the CXM control
random start delay. There will also be a 5 minute compressor for all field low voltage connections.
anti-short cycle protection time as well. After the random
start delay and the anti-short cycle delay, the compressor Table 1a: Fault Description Table
relay is energized. On all subsequent compressor calls, the
random start delay is omitted. Fault
Fault LED
Code
Fault Condition
No Fault In Memory 1 There has been no fault detected since the last
Heating Stage 1 - To enter Heating Stage 1 mode, Y power down/power up sequence
High Pressure Switch 2 HP Open Instantly
becomes active. The first time after power-up that there is LP open for 30 continuous seconds before or
Low Pressure Switch or LOC 3
a call for compressor, the compressor will follow a 5 to 80 during a call (bypassed for first 120 seconds)
FP1 below Temp limit for 30 continous seconds
second random start delay. There will also be a 5 minute Freeze Protection Coax - FP1 4
(bypassed for first 120 seconds of operation)
compressor anti-short cycle protection time as well. After Freeze Protection Air Coil - FP2 5
FP2 below Temp limit for 30 continous seconds
(bypassed for first 120 seconds of operation)
the random start delay and the anti-short cycle delay, the Condensate overflow 6
Sense overflow (grounded) for 30 continous
seconds
compressor relay is energized. On all subsequent compressor Over/Under Voltage Shutdown 7 (Autoreset) "R" power supply is <18VAC or >31.5VAC
5"
Sig
C
Sig
R
C
C
P1 Com
Y1 R P5 P4 Fan
FanEnable
Enable
Com2 Com1 (240Vac)
(240Vac)
Y2
W1 N.O.
O/W2
G Com
AL2
R Alarm
Relay JW4
AL2 Dry Micro Status 1
NSB HP
U2 HP
C
Test LP
ESD
7"
LP 6 1/2"
OVR Fault FP1
H P2 FP1
FP2 Factory low
A voltage molex
FP2
connection for
RV RV unit harness
Micro RV
Relay
U1 CO
12 CO
R
P7 Factory low
NO1
Test Jumpers voltage molex
NC1 1 24Vdc connection for
JW3 - FP1 Low Temp electric heat
COM harness
JW2 - FP2 Low Temp EH1
NO2 JW1 - LP Norm. Open 4 EH2
NC2 Acc1
P6
Facttory Use
S1 S2
1.62
5 5 1/2"
4 Mounting
Screws #6 sheet
metal screw 1 long
Basic Control Features Water Coil Freeze Protection Limit Setting - Jumper 3
Anti-short cycle protection (JW3-FP1 Low Temp) provides field selection of temperature
High and Low pressure cutouts limit setting for FP1 to be 30F or 10F.
High and Low voltage cutouts
Water Coil freeze protection Not Clipped=30F. Clipped=10F.
Air Coil freeze protection Air Coil Freeze Protection Limit Setting - Jumper 2 (JW2-
Random Start FP2 Low Temp) provides field selection of temperature limit
Status LED, Test LED, and Fault LED setting for FP2 to be 30F or 10F.
Reset Lockout at unit or disconnect
Intelligent Reset Not Clipped=30F. Clipped=10F.
Condensate Overflow sensor
Test Mode Alarm Relay Setting - Jumper 4 (JW4-AL2 Dry) provides
Electric Heat Outputs field selection of Alarm Relay terminal AL2 to be jumpered
Accessory Water Valve Connection to 24VAC or to be dry (no connection).
DIP 1.4: Thermostat Type (O/B) - provides selection of DIP Package #2 (S2)
Thermostat Type. Heat Pump Thermostats with O output on
with Cooling or B output on with Heating can be selected. DIP Package #2 is 8 position and provides the following
setup selections.
On=HP Stat with O output with Cooling. Off=HP Stat with B DIP 2.1: Accessory1 relay personality - provides selection of
output with Heating. Acc1 relay personality. See Table 2.
DIP 1.5: Dehumidification Mode - provides selection of DIP 2.2: Accessory1 relay personality - provides selection of
normal or dehumidification fan mode. In dehumidification Acc1 relay personality. See Table 2.
mode, the Fan Speed relay will remain off during Cooling DIP 2.3: Accessory1 relay personality - provides selection of
Stage 2. In normal mode, the Fan Speed relay will turn on Acc1 relay option. See Table 2.
during Cooling Stage 2. DIP 2.4: Accessory2 relay personality - provides selection of
Acc2 relay personality. See Table 3.
On=Normal fan mode. Off=Dehumidification mode. DIP 2.5: Accessory2 relay personality - provides selection
of Acc2 relay personality. See Table 3.
DIP 1.6: DDC Output at EH2 - DIP Switch 1.6 provides DIP 2.6: Accessory2 relay personality - provides selection of
selection for DDC operation. If set to DDC Output at EH2, Acc2 relay option. See Table 3.
the EH2 terminal will continuously output the last fault code
of the controller. If set to EH2 normal, then the EH2 will DIP 2.7: Auto Dehumidification Fan Mode or High Fan
operate as standard electric heat output. Mode - provides selection of Auto Dehumidification Fan
Mode or High Fan Mode. In Auto Dehumidification Mode,
On = EH2 Normal. Off = DDC Output at EH2. the Fan Speed relay will remain off during Cooling Stage 2
IF the H input is active. In High Fan Mode, the Fan Enable
DIP 1.7: Boilerless Operation - provides selection
and Fan Speed relays will turn on when the H input is active.
of Boilerless Operation. In Boilerless mode, only the
compressor is used for heating mode when FP1 is above the On=Auto Dehumidification Mode. Off=High Fan Mode.
temperature specified by the setting of DIP 1.8. If DIP 1.8
is set for 50F, then the compressor is used for heating as DIP Switch 2.8: Factory Setting - Normal position is On. Do
long as FP1 is above 50F. Below 50F, the compressor is not change selection unless instructed to do so by the Factory.
not used and the control goes into Emergency Heat mode,
staging on EH1 and EH2 to provide heating. If a thermal Safety Features
switch is being used in place of the FP1 thermistor, then only The following safety features are provided to protect the
the compressor will be used for heating mode when the FP1 compressor, heat exchangers, wiring and other components
terminals are closed. If the FP1 terminals are open, then the from damage caused by operation outside of design conditions.
compressor is not used and the control goes into Emergency
Heat mode. Anti-Short Cycle Protection - The control features a 5
minute anti-short cycle protection for the compressor.
On=normal. Off=Boilerless operation.
Note: The 5 minute anti-short cycle also occurs at power up.
DIP 1.8: Boilerless Changeover Temperature - provides
selection of Boilerless changeover temperature setpoint. Random Start - The control features a 5-80 second random
On=50F. Off=40F. start upon power up. The random start delay will be present
after a control power up and after returning from Night
Setback or Emergency Shutdown modes.
Note: If 1 Try is selected for FP1 and FP2, then there will Condensate Overflow - The Condensate Overflow sensor
be no retries for FP1 and FP2 faults. The control will only must sense overflow levels for 30 continuous seconds to
try one time for these faults. be recognized as a CO fault. Condensate Overflow will be
monitored at all times. The Fault LED will immediately begin
Lockout - In Lockout mode, the Status LED will begin fast flashing Code 6 when a Condensate Overflow Fault occurs.
flashing. The Fault LED will be flashing a code representing Condensate overflow will be monitored during compressor
the last fault, which occurred that caused the lockout. The run cycle.
compressor relay is turned off immediately. Lockout mode
can be soft reset via the thermostat by removing the call for CO Lockout Code = 6
compressor, or can be hard reset via the disconnect. The last
fault causing the lockout will be stored in memory and is Over/Under Voltage Shutdown - An Over/Under Voltage
displayed by the Fault LED. condition exists when the control voltage is outside the
range of 18VAC to 31.5VAC. Over/Under Voltage Shutdown
Lockout with Emergency Heat - If the DXM is configured is self-resetting in that if the voltage comes back within
for Heat Pump thermostat mode (see DIP 1.3), the DXM range of 18.5VAC to 31VAC for at least 0.5 seconds, then
is in Lockout mode, and the W input becomes active, then normal operation is restored. This is not considered a fault or
Emergency Heat mode will occur during Lockout. lockout. If the DXM is in over/under voltage shutdown for
High Pressure Switch - When the High Pressure Switch 15 minutes, the alarm relay will close.
opens due to high refrigerant pressures, the Compressor relay
is de-energized immediately since the High Pressure Switch Over/Under Voltage Shutdown Code = 7
is in series with the compressor contactor coil. The High Unit Performance Sentinel-UPS (patent pending) -
Pressure Fault recognition is immediate as well. The Fault The UPS feature warns when the heat pump is operating
LED will immediately begin flashing Code 2 when a High inefficiently. A UPS condition exists when:
Pressure Fault occurs.
a) In heating mode with compressor energized, if FP2 is
High Pressure Lockout Code = 2 greater than 125F for 30 continuous seconds, or
Example: 2 quick flashes, 10-sec pause, 2 quick flashes, 10-
b) In cooling mode with compressor energized, if FP1 is
sec. pause, etc.
greater than 125F for 30 continuous seconds, OR FP2 is
Low Pressure Switch - The Low Pressure Switch must be less than 40F for 30 continuous seconds.
open and remain open for 30 continuous seconds during a
compressor on cycle to be recognized as a Low Pressure If a UPS condition occurs, the control will immediately go
fault. If the low pressure switch is open for 30 seconds prior to UPS warning. The status LED will remain on as if the
to compressor power up it will be considered a low pressure control is in Normal mode. (see "LED and Alarm Relay
(loss of charge) fault. The Low Pressure Switch input is Operation Table"). Outputs of the control, excluding Fault
bypassed for the initial 120 seconds of a compressor run LED and Alarm Relay, will NOT be affected by UPS. The
cycle. The Fault LED will immediately begin flashing Code UPS condition cannot occur during a compressor off cycle.
3 when a Low Pressure Fault occurs. During UPS warning, the Alarm Relay will cycle on and off.
The cycle rate will be On for 5 seconds, Off for 25 seconds,
Low Pressure Lockout Code = 3 On for 5 seconds, Off for 25 seconds, etc
Water Coil Freeze Protection (FP1) -The control will Unit Performance Sentinel Warning Code = 8
recognize an FP1 fault, during a compressor run cycle if:
Swapped FP1/FP2 Thermistors - During Test mode, the
a) the thermistor temperature is below the selected freeze control monitors to see if the FP1 and FP2 thermistors are
protection limit setting, AND in the appropriate place. If the control is in Test mode, the
control will lockout, with Code 9, after 30 seconds if:
b) the thermistor temperature is rising (getting warmer) at a
rate LESS than 2F per 30 second time period. a) the compressor is On in cooling mode and the FP1 sensor
is colder than the FP2 sensor. Or,
The FP1 input is bypassed for the initial 120 seconds of a
compressor run cycle. The Fault LED will immediately begin b) the compressor is On in heating mode and the FP2 sensor
flashing Code 4 when a FP1 Fault occurs. is colder than the FP1 sensor.
FP1 Lockout Code = 4 Swapped FP1/FP2 Thermistor Code = 9.
Air Coil Freeze Protection (FP2) - The control will ESD The ESD (Emergency Shut Down) mode is utilized
recognize an FP2 fault, during a compressor run cycle if: when the ERV (Energy Recovery Ventilator) option is
applied to an RE series rooftop unit to indicate an ERV fault.
a) the thermistor temperature is below the selected freeze A contact closure at the ERV unit will connect common to
protection limit setting, AND the ESD terminal, which will shut down the rooftop/ERV
b) the thermistor temperature is rising (getting warmer) at a units. The green status light will flash code 3 when the unit
rate LESS than 2F per 30 second time period. is in ESD mode. The ESD mode can also be enabled from an
external common signal to terminal ESD (see Thermostat
The FP2 input is bypassed for the initial 120 seconds of a Inputs section for details).
compressor run cycle. The Fault LED will immediately
begin flashing Code 5 when a FP2 Fault occurs. ESD mode = code 3 (green status LED)
Notes:
a)"Flashing Appropriate Code" means that the Fault LED will b) Codes will be displayed with a 10 second Fault LED off period.
ALWAYS flash a code representing the LAST fault in memory. If c) Slow flash will be 1 flash per every 2 seconds.
there is no fault in memory, the Fault LED will flash code 1. d) Fast flash will be 2 flash per every 1 second.
e) On pulse 1/3 sec.; off pulse 1/3 sec.
Emergency Heat Mechanical Night Set Back - When the NSB input is
In Emergency Heat mode, the Fan Enable and Fan Speed connected to Ground C, all thermostat inputs (G, Y1, Y2,
relays are turned on. EH1 is turned on immediately. With W1, and O/W2) are ignored. A thermostat setback Heating
continuing Emergency Heat demand, EH2 will turn on after call can then be connected to the OVR input. If the OVR
5 minutes. EH1 and EH2 are turned off immediately when input becomes active, then the DXM will enter NLL Staged
the Emergency Heat demand is removed. The Fan Enable Heating mode. NLL Staged Heating Mode would then
and Fan Speed relays will turn off after a 60-second delay. provide heating during the NSB period.
The control reverts to Standby mode. During Emergency Water Valve/Slow Opening - If an Accessory relay is
Heat mode, EH1, EH2, Fan Enable and Fan Speed will be on configured for Water Valve/Slow Opening, the Accessory
if the G input is not active. relay will turn on 60 seconds prior to the Compressor Relay
Cooling Stage 1 turning on.
In Cooling Stage 1 mode, the Fan Enable, Compressor, Outside Air Damper-If an Accessory relay is configured for
and RV relays are turned on immediately. If configured as OAD, the Accessory relay will normally turn be on any time the
Stage 2 (DIP1.2=off), then the compressor and fan will not Fan Enable relay is on. But, following a return from NSB (NSB
turn on until there is Stage 2 demand. The Fan Enable and input no longer connected to Ground C) to Normal Mode,
Compressor relays are turned off immediately when the the Accessory relay will not turn on for 30 minutes even if the
Cooling Stage 1 demand is removed. The control reverts Fan Enable relay is on. After this 30-minute timer expires, the
to Standby mode. The RV relay remains on until there is a Accessory relay will turn on if the Fan Enable relay is on.
Heating demand. If there is a Master/Slave situation or a
Dual Compressor situation, all Compressor relays and related Thermostat Inputs
functions will track with their associated DIP1.2. Table 5 shows the resulting demand from differing
Cooling Stage 2 combinations of inputs.
In Cooling Stage 2 mode, the Fan Enable, Compressor, Y1 - Y1 is the input for compressor stage 1 if DIP1.3=on.
and RV relays remain on. The Fan Speed relay is turned on Y1 is the input for Cooling Stage 1 if DIP1.3=off.
immediately (see DIP1.5). The Fan Speed relay is turned off
immediately when the Cooling Stage 2 demand is removed. Y2 - Y2 is the input for compressor stage 2 if DIP1.3=on. Y2
The control reverts to Cooling Stage 1 mode. If there is a is the input for Cooling Stage 2 if DIP1.3=off.
Master/Slave situation or a Dual Compressor situation, all W1 - If Y1 and Y2 are active and DIP1.3=on, then W1 is
Compressor relays and related functions will track with their the input for Heating Stage 3. If Y1 and Y2 are not active
associated DIP1.2. and DIP1.3=on, then W1 is the input for Emergency Heat. If
Night Low Limit (NLL) Staged Heating DIP1.3=off, then W1 is the input for Heating Stage 1.
In NLL Staged Heating mode, the OVR input becomes active O/W2 - O/W2 is the input for Reversing Valve relay if
and is recognized as a call for Heating (OVR is an alternate DIP1.3=on and DIP1.4=on. O/W2 is the input for Heating
means of calling for Heating mode). In NLL Staged Heating Stage 2 if DIP1.3=off. O/W2 is the input for Heat Mode
mode, the control will immediately go into Heating Stage if DIP1.3=on and DIP1.4=off; this means that the thermostat
1 mode With an additional 30 minutes of NLL demand, the outputs a B call when in Heating mode and does NOT have
control will go into Heating Stage 2 mode. With another an O output. The DXM control will employ Smart RV
additional 30 minutes of NLL demand, the control will go control. This ensures that the RV will only switch positions if
into Heating Stage 3 mode. the thermostat has called for a heating/cooling mode change.
G - G is the input for Fan Enable relay.
Special DXM Application Notes
Generally the following applications are based upon NSB and Override - NSB is the input for Night Setback
configuring the accessory relays. mode. When Digital NSB is selected via the Accessory relays
DIPswitch inputs and the NSB input is connected to Ground
Cycle with Fan - If Accessory relay 1 is configured to cycle C, then the appropriately configured Accessory relay is
with fan, Accessory relay 1 will be on any time the Fan turned on to signal the digital thermostat to go to Night Setback
Enable relay is on. Setpoints. Stated differently, when configured for Digital NSB
mode, the Accessory relay directly tracks the NSB input.
Cycle with Compressor - If Accessory relay 2 is configured
to cycle with compressor, Accessory relay 2 will be on any When Digital NSB is NOT selected via the Accessory
time the Compressor relay is on. relays DIPswitch inputs and the NSB input is connected to
Ground C, then Y1, Y2, W1 and O/W2 and G are ignored.
Digital Night Setback - If an Accessory relay is configured During this time period, if OVR is momentarily connected
for Digital NSB, the Accessory relay will be on any time the to 24VAC, then Y1, Y2, W1 and O/W2 and G are once again
NSB input is connected to Ground C. monitored for 2 hours. After the 2 hour Override period, the
Note: If there are no Accessory relays configured DXM reverts back to ignoring Y1, Y2, W1 and O/W2 and
for Digital NSB, then the NSB and OVR inputs are G, assuming the NSB input is still connected to Ground C.
automatically configured for mechanical operation. There will be a random start timer when coming back from
See Mechanical NSB operation below. NSB mode.
Note: The maximum number of DXM controls with daisy- Other Outputs
chained "NSB" terminals is 75. Also, the maximum total
wire resistance of the "NSB" wiring is 500 Ohms. Table 12 displays input and output signals.
ESD - ESD is the input for Emergency Shutdown mode. Electric Heat
When the ESD input is connected to Ground C, all inputs Outputs EH1 and EH2 turn on whenever the DXM control is
are ignored and all outputs are turned off. There will be a in the following modes: Heating Stage 3, Emergency Heat,
random start timer when coming back from ESD. and boilerless operation.
Note: The maximum number of DXM controls with Status LED
daisy-chained "ESD" terminals is 75. Also, the maximum
total wire resistance of the "ESD" wiring is 500 Ohms. The Status LED is green. The Status LED indicates what
mode the DXM control is in. See Table 4: LED and Alarm
OVR - OVR is the input for Night Setback Override or Relay Operation.
Night Low Limit Staged Heating input (NLL). When Digital
NSB is NOT selected via the Accessory relays DIP switch Test LED
inputs and NSB is connected to Ground C, then if OVR is
momentarily connected to 24VAC (minimum 1 second) then The Test LED is yellow. The Test LED will be on any time
the OVR input is recognized as a Night Setback Override the control is in Test mode. See Table 4: LED and Alarm
signal and the DXM control reverts from Night Setback and Relay Operation.
begins monitoring thermostat inputs for heating and cooling
calls for a 2 hour override period. If NSB is connected to Fault LED
ground "C", then if OVR is continuously connected to 24V The Fault LED is red. The Fault LED ALWAYS flashes the
AC, then the OVR input is recognized as a call for NLL corresponding code for the last fault that has occurred. If
staged heating and the control enters NLL staged heating. there is no fault in memory, then the fault LED will flash
H - The H input function is determined by the setting Code 1. If the Fault type is Primary (HP, LP, FP1, FP2, or
of DIP2.7. If DIP2.7=on then the H input is defined as CO) then the Fault type will always be retained in memory
Automatic Dehumidification Mode and is used as an (Primary faults will over write Secondary faults). If the Fault
automatic counterpart to DIP1.5, meaning if H is connected type is Secondary (Over/Under Voltage, UPS or Swapped
to 24VAC then the Fan Speed Relay will not turn on during FP1/FP2) then the Fault type will only be retained if there are
Cooling Stage 2. If H is not connected to 24VAC then the Fan no Primary faults in memory. The Secondary Fault types
Speed Relay will turn on during Cooling Stage 2. will not overwrite the Primary fault memory. See Table 4:
LED and Alarm Relay Operation.
If DIP2.7=off then the H input is defined as High Speed Fan
input and is used as an input to call for High Speed Fan. If the Communications
control is in normal operating modes such as Standby, Cooling
or Heating AND the H input is connected to 24VAC, then the There are two communications ports (Com1 and Com2) which
Fan Enable and Fan Speed relays will be on at all times (this provide robust communications to external DXM control
operation is very similar to the G/Fan Enable operation). boards via a simple noise resistant low speed protocol. Wiring
to Com1 and Com2 does NOT require the use of shielded
Table 5: Thermostat Inputs with resulting demands wiring for operation; standard thermostat wire can be used.
Com1
Tstat Inputs Dip Switch
Stat (HP/HC) Stat Resulting
Com1 is used to communicate thermostat and
G Y1 Y2 W1 O/W2 external calls to other DXM Master/Slave
Ty p e ( O / B ) Ty p e Demand #1
Dip 1.3 Dip 1.4 controls. In this configuration, up to 3 heat
- - Standby/Off pumps can be controlled by one thermostat.
- x x HP O C1 Note: Each heat pump could potentially be
- x HP B C1 a Dual Compressor unit thus there could
- x HC - C1 be up to 6 DXM controls being controlled
- - x x HP O C2
- - x HP B C2
by one thermostat. However, only 1 DXM
- - x HC - C2 control in each heat pump will be daisy-
- x HP O H1 chained on Com1. See schematic on page 16.
- x x HP B H1
The Master DXM control is defined as the
- - x HP O H2 DXM control, which is directly connected
- - x x HP B H2 to the wall-mounted thermostat, time clock,
fire alarm, and humidistat. The Master DXM
- x - x HP O H3
- x - x x HP B H3
communicates to the Slave DXM typical
signals such as: Y1, Y2, W1, O/W2, G, NSB,
ESD, OVR, and H. The Slave DXM controls
- - - x x HP O Invalid should have no direct connections to any
- x - x - HC - Invalid exterior devices such as thermostats, time
- x - - x HC - Invalid clocks, fire alarms, humidistats, etc
- - x x - HC - Invalid
- - x - x HC - Invalid
- x x x HP B Invalid
Table 6: System Inputs with the resulting demand. Table 6 describes demand changes with differing system input
(ESD, NSB, OVR) and DIP input settings. Resulting Demand #1 is derived from Table 4.
Resulting Demand #1 System Inputs NSB Type Resulting Demand #2
(From Table 4) ESD NSB OVR (After ESD, NSB)
- x - - - ESD
Invalid - - - - Invalid
All (excluding Invalid) - All (excluding Invalid)
All (excluding Invalid) M - All (excluding Invalid)
C1, C2 x - Invalid
Off, F, H1, H2, or H3 x - NLL Staged Heating
EH x - EH
All (excluding Invalid) x Mechanical Standby/Off
All for 2 hrs and then revert to
All (excluding Invalid) x M Mechanical
Standby/Off (excluding Invalid)
C1, C2 x x Mechanical Invalid
Off, F, H1, H2, or H3 x x Mechanical NLL Staged Heating
EH x x Mechanical EH
All (excluding Invalid) x Digital All (excluding Invalid)
All (excluding Invalid) x M Digital All (excluding Invalid)
C1, C2 x x Digital Invalid
Off, F, H1, H2, or H3 x x Digital NLL Staged Heating
EH x x Digital EH
"M" is momentary input
"X" is continuous input
Table 7: "H" input with resulting demand modes. Table 7 describes demand changes with "H" input and DIP 2.1-2.3,
and 2.7 settings. Resulting Demand #2 is derived from Table 5.
Only the impurities from the drain pan and coil dust or
dirt create the conductance. A second ground wire with
appropriate terminal to the drain pan can be used with the
control to replace the air coil ground path. The condensate Chart 2: Thermistor Nominal Resistance
sensor can also essentially be any open contact that closes 90.0
upon a fault condition. 80.0
70.0
Thermistor Temperature Sensors-
60.0
Resistance (kOhm)
The thermistor is available in the following configurations
shown in Table 8. The thermistor is an NTC (negative 50.0
temperature coefficient) type. The sensor has a 1% tolerance
40.0
and follows the Table 8 and Chart 2 shown. Table 9 shows
the nominal resistance at any given temperature and can 30.0
be used for field service reference. The sensor will use a
minimum of 24 awg wire and be epoxy embedded in the 20.0
beryllium copper clip 10.0
. 0.0
0.0 20.0 40.0 60.0 80.0 100.0 120.0 140.0
Temperature (degF)
Sensor Inputs Y1
Y2
I
I
Connect to thermostat - Y1 output call for compressor stage 1
Connect to thermostat - Y2 output call for compressor stage 2
W1 I Connect to thermostat - W1 output call for Htg 3 or Emerg Ht
All sensor inputs are 'paired wires' connecting each O/W2 I Connect to thermostat - 0 output call for reversing valve with cooling
G I Connect to thermostat - G output call for fan
component with the board. Therefore continuity on AL1 O Connect to thermostat fault light - 24VAC or dry alarm
AL2 O Alarm Relay 24VAC or dry
pressure switches, and the condensate switch can be A O Output for water solenoid valve - paralleled with compressor contactor coil
Fan Enable O Fan enable relay
checked at the board connector. Fan Speed O Fan speed relay
CC O Connection for compressor contactor
The thermistor resistance should be measured with the CCG O Compressor contactor common connection
HP I High Pressure Switch input terminals
connector removed so that only the impedance of the LP I Low Pressure Switch input terminals
FP1 I Water Coil Freeze Protection Thermistor Input
thermistor is measured. If desired this reading can be FP2 I Air Coil Freeze Protection Thermistor Input
compared to the chart shown in the thermistor section RV
CO
O
I
Reversing Valve Output Terminals - direct connect from "O"
Condensate overflow input terminals
of this manual based upon the actual temperature of 24VDC
EH1
O
O
24 VDC supply to electric heat module
Output terminal for stage 1 electric heat
the thermistor clip. An ice bath can be used to check EH2 O Output terminal for stage 2 electric heat
NSB I Night Setback input
calibration of a thermistor if needed. OVR I Night Setback Over Ride Input
ESD I Emergency Shutdown Input
The compressor relay is 24VAC and can be verified using Test Mode
a voltmeter. The fan signal is passed through the board Test mode can be entered for 20 minutes by shorting the
to the external fan relay. The alarm relay can either be test pins. For Diagnostic ease at the thermostat, the alarm
24VAC as shipped or dry contacts (measure continuity relay will also cycle during test mode. The Alarm relay
during fault) for use with DDC by clipping the J1 jumper. will cycle on and off similar to the fault LED to indicate
Electric heat outputs are 24VDC and require a voltmeter
a code representing the last fault, at the thermostat. Test
set for DC to verify operation. When troubleshooting,
mode can also be entered and exited by cycling the G
measure from 24VDC terminal to EH1 or EH2 terminals.
input, 3 times within a 60 second time period.
See the I/O Reference table below.
DXM Outputs
The compressor relay is 24VAC and can be verified using
a voltmeter. The alarm relay can either be 24VAC as
shipped or dry contacts (measure continuity during fault)
for use with DDC by clipping the J4 jumper. Electric heat
outputs are 24VDC and require a voltmeter set for DC to
verify operation. When troubleshooting, measure from
24VDC terminal to EH1 or EH2 terminals. See the I/O
Reference table below.
Troubleshooting Chart
Use the following troubleshooting flow chart to find appropriate troubleshooting strategies on the following pages for the
CXM/DXM control and most water source heat pump applications.
Start
CXM / DXM Functional
Troubleshooting Chart
Did Unit No Check Main
Attempt to power (see power
Start? problems)
Yes
Did Unit Yes
Check fault LED code No fault
Lockout at
on control board shown
Start-up?
No
See "Unit Yes See See FP1
Unit Short See HP Replace
short LP/LOC Fault
Cycles? Fault CXM/ DXM
cycles" Fault
No
Unit is OK!
"See Performance
Troubleshooting" for
further help
Functional Troubleshooting
Fault Htg Clg Possible Cause Solution
Main power Problems X X Green Status LED Off Check Line Voltage circuit breaker and disconnect
Check for line voltage between L1 and L2 on the contactor
Check for 24VAC between R and C on DXM
Check primary/secondary voltage on transformer
HP Fault-Code 2 X Reduced or no water flow Check pump operation or valve operation/setting
High pressure in cooling Check water flow adjust to proper flow rate
X Water Temperature out of range in
Bring water temp within design parameters
cooling
X Reduced or no Air flow Check for dirty air filter and clean or replace
in heating Check fan motor operation and airflow restrictions
Dirty Air Coil- construction dust etc.
X Water Temperature out of range Bring water temp within design parameters
Performance Troubleshooting
Symptom Htg Clg Possible Cause Solution
Insufficient capacity/ X X Dirty Filter Replace or clean
Not cooling or heating X Reduced or no Air flow Check for dirty air filter and clean or replace
properly in heating Check fan motor operation and airflow restrictions
Too high of external static. Check static vs blower table
X Reduced or no Air flow Check for dirty air filter and clean or replace
in cooling Check fan motor operation and airflow restrictions
Too high of external static. Check static vs blower table
Check supply and return air temperatures at the unit and at
X X Leaky duct work distant duct registers if significantly different, duct leaks
are present
X X Low refrigerant charge Check superheat and subcooling per chart
X X Restricted metering device Check superheat and subcooling per chart. Replace.
X Defective Reversing Valve Perform RV touch test
X X Thermostat improperly located Check location and for air drafts behind stat
Recheck loads & sizing check sensible clg load and heat
X X Unit undersized
pump capacity
X X Scaling in water heat exchanger Perform Scaling check and clean if necessary
X X Inlet Water too Hot or Cold Check load, loop sizing, loop backfill, ground moisture.
High Head Pressure X Reduced or no Air flow Check for dirty air filter and clean or replace
in heating Check fan motor operation and airflow restrictions
X Water Temperature out of range Bring water temp within design parameters
X Reduced Air flow Check for dirty air filter and clean or replace
in cooling Check fan motor operation and airflow restrictions
Too high of external static. Check static vs blower table
Too much cold vent air? Bring entering air temp within
X Air Temperature out of range
design parameters
X X Insufficient charge Check for refrigerant leaks
*97B0003N08*
97B0003N08
The manufacturer works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed
without notice and may not be as described herein. Please contact the manufacturer's Customer Service Department at 1-405-745-6000 for specific information
on the current design and specifications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain
between the parties, but are merely the manufacturer's opinion or commendation of its products.