PREDIMENSIONAMIENTO DE COLUMNAS POR GRAVED

(VIVIENDA)

Numero de Pisos: 02

Carga muerta (WD):

ALIGERADO Luz (m) = 5.00 20.00 H (cm) = 20.00 300.00


TABIQUERIA Tipo (*): solido Ancho (cm) = 15.00 Altura (m) = 2.60 741 330.00
ACABADOS 100.00
VIGAS 100.00
COLUMNAS 60.00
(*) Tipo de Ladrillo: SOLIDO / HUECO, Altura mayor de tabiqueria

Carga viva (WL):

COLEGIO 300.00
AZOTEA 100.00

Carga total (PU):

Peso total de cargas de gravedad que soporta la columna cada piso 1,756.00
Peso total de cargas de gravedad que soporta la columna 1 er Piso 1 er Piso 1,756.00
Peso total de cargas de gravedad que soporta la columna 2 er Piso 1,416.00
Peso total de cargas de gravedad por 02 Pisos 3,172.00
Resistencia del concreto en columna 210.00

GENERAL GENERAL (ESTRUCTURACION SIMETRICA)


D (cm)
Tipo de Area si b=D b (cm)
t n Pg bxD (calculado
columna tributaria (cm) (minimo)
)
C1 Interior 57.85 1.10 0.25 #DIV/0! #DIV/0! #DIV/0! 25 #DIV/0!

GENERAL (CASO CRITICO - TODA LA SUPERFICIE TECHADA)


D (cm)
Tipo de Area si b=D b (cm)
t n Pg bxD (calculado
columna tributaria (cm) (minimo)
)
C1 Esquinera 3.18 1.50 0.20 10086.96 360.25 18.98 25 35
C2 Lateral 6.36 1.25 0.25 20173.92 480.33 21.92 25 30
C4 Lateral 13.72 1.25 0.25 43519.84 1036.19 32.19 35 35
C5 Interior 12.81 1.10 0.25 40633.32 851.36 29.18 25 35
C6 Interior 7.60 1.10 0.25 24107.20 505.10 22.47 25 35
C3 Esquinera 3.18 1.50 0.20 10086.96 360.25 18.98 25 35
C7 Lateral 5.00 1.25 0.25 15860.00 377.62 19.43 25 25
C8 Interior 6.00 1.10 0.25 19032.00 398.77 19.97 35 25
PREDIMENSIONAMIENTO DE COLUMNAS POR GRAVED
(VIVIENDA)

Numero de Pisos: 02

Carga muerta (WD):

ALIGERADO Luz (m) = 5.00 20.00 H (cm) = 20.00 300.00


TABIQUERIA Tipo (*): solido Ancho (cm) = 15.00 Altura (m) = 2.60 741 330.00
ACABADOS 100.00
VIGAS 100.00
COLUMNAS 60.00
(*) Tipo de Ladrillo: SOLIDO / HUECO, Altura mayor de tabiqueria

Carga viva (WL):

COLEGIO 300.00
AZOTEA 100.00

Carga total (PU):

Peso total de cargas de gravedad que soporta la columna cada piso 1,756.00
Peso total de cargas de gravedad que soporta la columna 1 er Piso 1 er Piso 1,756.00
Peso total de cargas de gravedad que soporta la columna 2 er Piso 1,416.00
Peso total de cargas de gravedad por 02 Pisos 3,172.00
Resistencia del concreto en columna 210.00
IENTO DE COLUMNAS POR GRAVEDAD
(VIVIENDA)

Pisos

Kg/m2
Kg/m2
Kg/m2
Kg/m2
Kg/m2

kg/m2
kg/m2

Kg/m2
Kg/m2
Kg/m2
Kg/m2
Kg/cm2

GENERAL (ESTRUCTURACION SIMETRICA)


TIPOS
bxD Verifica

#DIV/0! #DIV/0! #DIV/0! C1

ASO CRITICO - TODA LA SUPERFICIE TECHADA)


TIPOS
bxD Verifica

875.00 OK !!! 25x35


750.00 OK !!! 25x30
1225.00 OK !!! 35x35
875.00 OK !!! 25x35
875.00 OK !!! 25x35
875.00 OK !!! 25x35
625.00 OK !!! 25x25
875.00 OK !!! 35x25
IENTO DE COLUMNAS POR GRAVEDAD
(VIVIENDA)

Pisos

Kg/m2
Kg/m2
Kg/m2
Kg/m2
Kg/m2

kg/m2
kg/m2

Kg/m2
Kg/m2
Kg/m2
Kg/m2
Kg/cm2
ANALISIS ESPECTRAL
(VIVIENDA)

Datos por Sismo:

DATOS
CATEGORIA DE EDIFICACION C
ZONA SISMICA 3
TIPO DE SUELO S2

COEFICIENTE DE REDUCCION DIRECCION X RX (*) Concreto Armado, Porticos


COEFICIENTE DE REDUCCION DIRECCION Y RY (*) Albaileria Armada o Confinada

TIPO DE ESTRUCTURA: REGULAR (1) / IRREGULAR (2) 1 FACTOR PARA ESCALAR R

ZUCS
S a ( X ,Y ) xg ( Aceleracin
R( X ,Y )
Espectro de Aceleracion Sisamica:
TP
C 2 .5 x ; C 2 .5 (C Factor de Ampl
T
Sax Say
T (s) C ZUCS/RX ZUCS/RY
Sa(x,y) = ZUCS/R

0.00 2.50 0.1500 0.4000 ESPECTRO DE SISMO NORMA E-030 20


0.20 2.50 0.1500 0.4000 0.45
0.40 2.50 0.1500 0.4000
0.40
0.45 2.50 0.1500 0.4000
0.50 2.50 0.1500 0.4000 0.35
0.55 2.50 0.1500 0.4000
0.30
0.60 2.50 0.1500 0.4000
0.65 2.31 0.1385 0.3692 0.25
0.70 2.14 0.1286 0.3429
0.20
0.75 2.00 0.1200 0.3200
0.80 1.88 0.1125 0.3000 0.15
0.85 1.76 0.1059 0.2824
0.10
0.90 1.67 0.1000 0.2667
0.95 1.58 0.0947 0.2526 0.05
1.00 1.50 0.0900 0.2400
0.00
1.05 1.43 0.0857 0.2286
0.00 0.50 1.00 1.50
1.10 1.36 0.0818 0.2182
1.15 1.30 0.0783 0.2087 PERIODO T (seg)
1.20 1.25 0.0750 0.2000
1.25 1.20 0.0720 0.1920
1.30 1.15 0.0692 0.1846
1.35 1.11 0.0667 0.1778
1.40 1.07 0.0643 0.1714
1.45 1.03 0.0621 0.1655
1.50 1.00 0.0600 0.1600
1.55 0.97 0.0581 0.1548
1.60 0.94 0.0563 0.1500
1.65 0.91 0.0545 0.1455
1.70 0.88 0.0529 0.1412
1.75 0.86 0.0514 0.1371
1.80 0.83 0.0500 0.1333
1.85 0.81 0.0486 0.1297
ANALISIS ESPECTRAL
(VIVIENDA)

Datos por Sismo:

DATOS
CATEGORIA DE EDIFICACION C
ZONA SISMICA 3
TIPO DE SUELO S2

COEFICIENTE DE REDUCCION DIRECCION X RX (*) Concreto Armado, Porticos


COEFICIENTE DE REDUCCION DIRECCION Y RY (*) Albaileria Armada o Confinada

1.90 0.79 0.0474 0.1263


1.95 0.77 0.0462 0.1231
2.00 0.75 0.0450 0.1200
2.05 0.73 0.0439 0.1171
2.10 0.71 0.0429 0.1143
2.15 0.70 0.0419 0.1116
2.20 0.68 0.0409 0.1091
2.25 0.67 0.0400 0.1067
2.30 0.65 0.0391 0.1043
2.35 0.64 0.0383 0.1021
2.40 0.63 0.0375 0.1000
2.45 0.61 0.0367 0.0980
2.50 0.60 0.0360 0.0960
ANALISIS ESPECTRAL
(VIVIENDA)

CALCULOS
U= 1.00
Z= 0.40
Tp (s) = 0.60
S= 1.20
Concreto Armado, Porticos RX = 8.00
Albaileria Armada o Confinada RY = 3.00

1.00 RX = 8.00
RY = 3.00

ZUCS
S a ( X ,Y ) xg ( Aceleracin Espectral )
R( X ,Y )
TP
C 2 .5 x ; C 2 .5 (C Factor de Amplificacin Ssmica)`
T
Sa(x,y) = ZUCS/R

ESPECTRO DE SISMO NORMA E-030 2003


0.45

0.40

0.35

0.30
SaX
SaY
0.25

0.20

0.15

0.10

0.05

0.00
0.00 0.50 1.00 1.50 2.00 2.50

PERIODO T (seg)
ANALISIS ESPECTRAL
(VIVIENDA)

CALCULOS
U= 1.00
Z= 0.40
Tp (s) = 0.60
S= 1.20
Concreto Armado, Porticos RX = 8.00
Albaileria Armada o Confinada RY = 3.00
COPIAR CELDAS EN ARCHIVO DE TEXTO PARA EXPORTAR
AL SAP O ETABS
PARA SISMO PARA SISMO
X-X Y-Y
0 0.15 0 0.4
0.2 0.15 0.2 0.4
0.4 0.15 0.4 0.4
0.45 0.15 0.45 0.4
0.5 0.15 0.5 0.4
0.55 0.15 0.55 0.4
0.6 0.15 0.6 0.4
0.65 0.138461538461538 0.65 0.369230769230769
0.7 0.128571428571429 0.7 0.342857142857143
0.75 0.12 0.75 0.32
0.8 0.1125 0.8 0.3
0.85 0.105882352941176 0.85 0.28235294117647
0.9 0.1 0.9 0.266666666666667
0.95 0.0947368421052631 0.95 0.252631578947368
1 0.09 1 0.24
1.05 0.0857142857142857 1.05 0.228571428571428
1.1 0.0818181818181818 1.1 0.218181818181818
1.15 0.0782608695652174 1.15 0.208695652173913
1.2 0.075 1.2 0.2
1.25 0.072 1.25 0.192
1.3 0.0692307692307692 1.3 0.184615384615384
1.35 0.0666666666666666 1.35 0.177777777777778
1.4 0.0642857142857142 1.4 0.171428571428571
1.45 0.0620689655172413 1.45 0.16551724137931
1.5 0.06 1.5 0.16
1.55 0.0580645161290322 1.55 0.154838709677419
1.6 0.05625 1.6 0.15
1.65 0.0545454545454545 1.65 0.145454545454545
1.7 0.0529411764705882 1.7 0.141176470588235
1.75 0.0514285714285714 1.75 0.137142857142857
1.8 0.05 1.8 0.133333333333333
1.85 0.0486486486486486 1.85 0.12972972972973
1.9 0.0473684210526315 1.9 0.126315789473684
1.95 0.0461538461538461 1.95 0.123076923076923
2 0.045 2 0.12
2.05 0.0439024390243902 2.05 0.117073170731707
2.1 0.0428571428571428 2.1 0.114285714285714
2.15 0.041860465116279 2.15 0.111627906976744
2.2 0.0409090909090909 2.2 0.109090909090909
2.25 0.04 2.25 0.106666666666667
2.3 0.0391304347826087 2.3 0.104347826086956
2.35 0.0382978723404255 2.35 0.102127659574468
2.4 0.0375 2.4 0.1
2.45 0.036734693877551 2.45 0.0979591836734694
2.5 0.036 2.5 0.096
t (cm) w (Kg/m2) Peso del tabique (Kg/m) Carga Equivalente (Kg/m2)
17 280 74 o menos 30
20 300 75 a 149 60
25 350 150 a 249 90
30 420 250 a 399 150
35 475 400 a 549 210
550 a 699 270
700 a 849 330
850 a 1000 390

USOS

SOBRECARGAS
ALTURA TOTAL
USO AMBIENTE S/C (Kg/m2)
Bibliotecas Sala de lectura 300
Sala de almacenaje 750
Escuelas Aulas y laboratorio 300
Talleres 350
Hospitales Cuartos 200
Sala de Operacin y laboratorio 300
Oficinas Ambientes Comunes 250
Sala de Archivos 500
Tiendas Corredores y Escaleras 500
Viviendas Corredores y Escaleras 200
Azoteas * Planas no utilizable 100

DEPARTAME GARAGES Y
NTO Y DEPOSITOS
TIENDAS
OFICINAS
250 500 1000
L/11 L/10 L/8
MATERIALES PESO (Kg/m3)
1.- AISLAMIENTO
Fibra de vidrio 300
Corcho 200
Poliuretano poliestireno 200
Fibrocemento 600
2.- ALBAILERIA DE
Adobe 1600
Unidades de albaileria solidas 1800
Unidades de albaileria huecas 1350
3.- CONCRETO SIMPLE DE
Grava 2300
Cascote de ladrillo 1800
Pomez 1600
Aadir 100 Kg/m3 al peso del
4.- CONCRETO ARMADO concreto simple
5.- ENLUCIDO O REVOQUE DE
Mortero de cemento 2000

Mortero de cal y cemento 1850


Mortero de cal 1700
Yeso 1000
6.- LIQUIDOS
Agua 1000
PARAMETROS

CATEGORIA EDIFICIO FACTOR U

A 1.5 Edificaciones Esenciales


B 1.3 Edificaciones Importantes
C 1.0 Edificaciones Comunes
D 0.6 Edificaciones Menores
(*) En estas edificaciones, a criterio del proyectista, se podr omitir el anlisis por fuerzas ssmicas,
pero deber proveerse de la resistencia y rigidez adecuadas para acciones laterales

ZONA SISMICA Z

1 0.15
2 0.30
3 0.40

TIPO DE SUELO TP (s) S

S1 0.4 1
S2 0.6 1.2
S3 0.9 1.4
S4 1.3 0.9

Caractersticas para hallar el periodo fundamental CT


1 35 Elementos resistentes en la direccin de los p
2 45 Elementos resistentes prticos, cajas de ascen
3 60 Elementos sismorresistentes por muros de cort

Zona contribuyente Relacin carga viva a carga


(metros cuadrados) 0.625 o menor
14.9 o menor 100%
15 - 29.9999 80%
30 - 44.9999 60%
45 - 59.9999 50%
60 ms 40%

R Coef Regular
R3 Acero, Arriostres en 6.000
R2 Acero, Arriostres Exc 6.500
R1 Acero, Porticos Duct 9.500
R8 Albaileria Armada o 3.000
R6 Concreto Armado, de 6.000
R5 Concreto Armado, Du 7.000
R4 Concreto Armado, Po 8.000
R9 Madera (Por Esfuerzo 7.000

Pgina 14
PARAMETROS

R7 Muros de Ductilidad 4.000

estado R
1 1.00 REGULAR
2 0.75 IRREGULAR

Pgina 15
PARAMETROS

Edificaciones Esenciales
Edificaciones Importantes
Edificaciones Comunes
Edificaciones Menores
zas ssmicas,

Roca o suelos muy rgidos


Suelos intermedios
Suelos flexibles o con estratos de gran espesor
Condiciones excepcionales

ntos resistentes en la direccin de los prticos


ntos resistentes prticos, cajas de ascensores y escaleras
ntos sismorresistentes por muros de corte

Relacin carga viva a carga muerta


1 2 ms
100% 100%
85% 85%
70% 75%
60% 70%
55% 65%

Pgina 16