SITE INSPECTION AND TEST RECORD

Description: Order no.:


110/33 KV TRF DIFFERENTIAL, STABILITY TEST 13092
Customer: End Client:
DELTA N.G-WNR
Site: PAGE
MODON-2 110/33/13.8 S/S TRANSFORMER-4 1 of 7

TRANSFORMER No. 4

TRANSFORMER DATA
TRANF.TYPE HYOSUNG SERIAL NO. 10017746-0002
RATING 83.64/ 104.55 MVA TRANF.DIFF RELAY TYPE SIEMENS-7UT61
WINDING VECTOR GROP YNyn0+d1 HV CT RATIO 1000 /1 CLASS 5P30
IMPEDANCE % TAP1 : 19.84 % LV CT RATIO 2500/1CLASS5P20
TAP11 : 18.95%
TAP27 : 18.40 %
NO.OF TAPS 21 HV NEUTRAL CT RATIO 1000/1 CLASS X
RATIO (KV) TAP1 :121/33 KV LV NEUTRAL CT RATIO 2500/1CLASS X
TAP9 : 107.250/33 KV
TAP21 : 93.500/33 KV
RATED CURRENT(A) HV . 439/549 A HV CT RATIO 1000/1 CLASS 5P30
LV . 1400/1750 A

INJECTION AT L.V SIDE OF TRANSFORMER , SHORT AT H.V SIDE OF TRANSFORMER

APPLIDE VOLTAGE = 380 V


Tested: Witnessed : Consultant:
ENGR.: HEGAZY ABDALLAH ENG: MAHMOUD ALI ENG:
sign sign sign

Date : 9/12/2015 Date: 9/12/2015 Date : 9/12/2015


SITE INSPECTION AND TEST RECORD
Description: Order no.:
110/33 KV TRF DIFFERENTIAL, STABILITY TEST 13092
Customer: End Client:
DELTA N.G-WNR
Site: PAGE
MODON-2 110/33/13.8 S/S TRANSFORMER-4 2 of 7

1- TRANSFORMER DIFFERENTIAL STABILITY

PHASE H.V SIDE L.V SIDE EXTERNAL FAULT


TAP

I PRI. (A) I SEC (m A) I PRI.( A) I SEC (m A) Id(I/In) IR(I/In)


1 28 28.1 95 39 0 0.10
0
R 9 32 31.9 100 40.7 0.11

21 39 38.6 110 42.1 0 0.13


0
1 28 28 95 39.1 0.10
0
Y 9 32 32.1 100 41.2 0.11

21 39 38.2 110 42.2 0 0.13


0
1 28 28.5 95 39.7 0.10
0
B 9 32 32.4 100 41.7 0.11
0
21 39 39.1 110 43 0.13
2-TRANSFORMER DIFFERENTIAL SENESTIVITY AT TAP 9

H.V SIDE REVERSED


MEASURED VALUE R Y B I SEC (m A)
Tested: Witnessed : Consultant:
ENGR.: HEGAZY ABDALLAH ENG: MAHMOUD ALI ENG:
sign sign sign

Date : 9/12/2015 Date: 9/12/2015 Date : 9/12/2015


SITE INSPECTION AND TEST RECORD
Description: Order no.:
110/33 KV TRF DIFFERENTIAL, STABILITY TEST 13092
Customer: End Client:
DELTA N.G-WNR
Site: PAGE
MODON-2 110/33/13.8 S/S TRANSFORMER-4 3 of 7

I (H.V) (A) 32 32 32 32
I (L.V) (A) 100 100 100 40.7
R
I DIFFRENTIAL 0.11 0 0 ------
I RESTRAIN 0.11 0.11 0.11 --------
I (H.V) (A) 32 32 32 32.3
I (L.V) (A) 100 100 100 41.1
Y
I DIFFRENTIAL 0 0.11 0 -------

I RESTRAIN 0.11 0.11 0.11 --------

I (H.V) (A) 32 32 32 32.1


B
100 100 100
I (L.V) (A) 41.3

I DIFFRENTIAL 0 0 0.11 --------


I RESTRAIN 0.11 0.11 0.11 --------

3- TRANSFORMER HV REF STABILITY

INJECTED CURRENT = 31 A SR SETTING = 451.9 OHM

EXPECTED VOLTAGE ACRROSS SR = 0 V


Tested: Witnessed : Consultant:
ENGR.: HEGAZY ABDALLAH ENG: MAHMOUD ALI ENG:
sign sign sign

Date : 9/12/2015 Date: 9/12/2015 Date : 9/12/2015


SITE INSPECTION AND TEST RECORD
Description: Order no.:
110/33 KV TRF DIFFERENTIAL, STABILITY TEST 13092
Customer: End Client:
DELTA N.G-WNR
Site: PAGE
MODON-2 110/33/13.8 S/S TRANSFORMER-4 4 of 7

RELAY
PHASE MEASURED CURRENT(I ma) CURREN
Y
(A)
X1B(1:3) X1B(6:8) Isum I METRO I SR V SR
CELL
(mA) (mA) (V)
R 31.4 31.3 0 0 0 0 0

31.7 31.8 0 0 0 0 0
Y
31.2 31.1 0 0 0 0 0
B

4-TRANSFORMER HV REF SENSTIVITY

INJECTED CURRENT = 31 A SR SETTING = 451.9 OHM

EXPECTED VOLTAGE ACRROSS SR= I sr * 451.9 = 27 V


Tested: Witnessed : Consultant:
ENGR.: HEGAZY ABDALLAH ENG: MAHMOUD ALI ENG:
sign sign sign

Date : 9/12/2015 Date: 9/12/2015 Date : 9/12/2015


SITE INSPECTION AND TEST RECORD
Description: Order no.:
110/33 KV TRF DIFFERENTIAL, STABILITY TEST 13092
Customer: End Client:
DELTA N.G-WNR
Site: PAGE
MODON-2 110/33/13.8 S/S TRANSFORMER-4 5 of 7

RELAY
PHASE MEASURED CURRENT(I mA) CURREN
Y

X1B(1:3) X1B(6:8) Isum I METRO I SR V SR


CELL
(mA) (mA) (V)
R 31.3 31.2 62.6 0 59.1 26.9 59

31.6 31.5 63.3 0 59 26.2 58


Y
30.9 31.2 62.1 0 58.9 26 58
B

5-TRANSFORMER LV REF SENESTIVITY

INJECTED CURRENT = 100 A SR SETTING = 1005 OHM

EXPECTED VOLTAGE ACRROSS SR= I sr * 1005 = 0 V


Tested: Witnessed : Consultant:
ENGR.: HEGAZY ABDALLAH ENG: MAHMOUD ALI ENG:
sign sign sign

Date : 9/12/2015 Date: 9/12/2015 Date : 9/12/2015


SITE INSPECTION AND TEST RECORD
Description: Order no.:
110/33 KV TRF DIFFERENTIAL, STABILITY TEST 13092
Customer: End Client:
DELTA N.G-WNR
Site: PAGE
MODON-2 110/33/13.8 S/S TRANSFORMER-4 6 of 7

RELAY
PHASE MEASURED CURRENT(I ma) CURREN
Y

X1C(1:3) X1C(6:8) Isum I METRO I SR V SR


CELL
(mA) (mA) (V)
R 40.5 40.8 0 0 0 0 0

40.6 40.8 0 0 0 0 0
Y
40.7 40.3 0 0 0 0 0
B

6-TRANSFORMER HV REF SENESTIVITY

INJECTED CURRENT = 100 A SR SETTING = 1005 OHM

EXPECTED VOLTAGE ACRROSS SR = I sr * 1005 = 80 V


Tested: Witnessed : Consultant:
ENGR.: HEGAZY ABDALLAH ENG: MAHMOUD ALI ENG:
sign sign sign

Date : 9/12/2015 Date: 9/12/2015 Date : 9/12/2015


SITE INSPECTION AND TEST RECORD
Description: Order no.:
110/33 KV TRF DIFFERENTIAL, STABILITY TEST 13092
Customer: End Client:
DELTA N.G-WNR
Site: PAGE
MODON-2 110/33/13.8 S/S TRANSFORMER-4 7 of 7

RELAY
PHASE MEASURED CURRENT(I ma) CURREN
X1C(1:3) X1C(6:8) Isum I METRO I SR V SR Y
(mA) CELL
(mA) (V) (A)
R 40.4 40.3 81.1 0 78.3 77.8 190

40.5 40.7 81.7 0 77.1 77.8 190


Y
40.5 40.3 81.1 0 76.9 76.1 190
B

Tested: Witnessed : Consultant:


ENGR.: HEGAZY ABDALLAH ENG: MAHMOUD ALI ENG:
sign sign sign

Date : 9/12/2015 Date: 9/12/2015 Date : 9/12/2015