1.0 OBJETIVO
3.1 LOS CONDUCTORES A EMPLEAR PARA BAJA TENSION SERAN DE COBRE SUAVE,
AISLAMIENTO VINANEL 2000 TIPO THHW-LS, TENSION DE OPERACIN 600 V,
TEMPERATURA MAXIMA EN EL CONDUCTOR: AMBIENTE SECO Y HUMEDO 90 C
MEMORIA TECNICA.
PROYECTO ELECTRICOS INDUSTRIALES Y COMERCIALES
A = 2 x 1.7320 x In x L
V x %e
DATOS:
CIRCUITO:
TENSION 220 V
No. FASES 3F
F.P. 0.9
MEMORIA TECNICA.
PROYECTO ELECTRICOS INDUSTRIALES Y COMERCIALES
= 593.80 AMP.
EL CABLE CON AISLAMIENTO THHW LS DE 400 KCM CONDUCE 615 AMP EN TUBO A 90,
APLICANDO UN FACTOR POR TEMPERATURA FT = 1 POR LO QUE SE PROPONE 1
CONDUCTOR POR FASE, UN CIRCUITO POR TUBO QUEDANDO:
QUEDANDO
e% = 2 3 L I
V x S
I = 593.8 AMP.
L = 15 M
S= 2 x 1.732 x 593.8 x 15
220 x 202.7
= 0.69 %
MEMORIA TECNICA.
PROYECTO ELECTRICOS INDUSTRIALES Y COMERCIALES
DATOS:
CIRCUITO:
TENSION 220 V
No. FASES 3F
F.P. 0.9
= 173.67 AMP.
EL CABLE CON AISLAMIENTO THHW LS DE 3/0 AWG CONDUCE 225 AMP EN TUBO A 90,
APLICANDO UN FACTOR POR TEMPERATURA FT = 1 POR LO QUE SE PROPONE 1
CONDUCTOR POR FASE, UN CIRCUITO POR TUBO QUEDANDO:
QUEDANDO
MEMORIA TECNICA.
PROYECTO ELECTRICOS INDUSTRIALES Y COMERCIALES
2
A CUATRO CABLES = 203.58 x 4 = 814.33 mm
2 2
A TUBO = Pi x ( 51 ) = 2042.83 mm
4
2 2
FACTOR DE RELLENO 40% = 817 mm > 814.33 mm
e% = 2 3 L I
V x S
I = 173.67 AMP.
L = 70 M
S= 2 x 1.732 x 173.67 x 70
220 x 75.01
= 2.55 %
DATOS:
CIRCUITO:
MEMORIA TECNICA.
PROYECTO ELECTRICOS INDUSTRIALES Y COMERCIALES
TENSION 220 V
No. FASES 3F
F.P. 0.9
= 181.47 AMP.
EL CABLE CON AISLAMIENTO THHW LS DEL No. 3/0 CONDUCE 225 AMP EN TUBO A 90,
APLICANDO UN FACTOR POR TEMPERATURA FT = 1 POR LO QUE SE PROPONE 1
CONDUCTOR POR FASE, UN CIRCUITO POR TUBO QUEDANDO:
QUEDANDO
4
2
A CUATRO CABLES = 203.58 x 4 = 814.33 mm
2 2
A TUBO = Pi x ( 51 ) = 2042.83 mm
MEMORIA TECNICA.
PROYECTO ELECTRICOS INDUSTRIALES Y COMERCIALES
2 2
FACTOR DE RELLENO 40% = 817.13 mm > 814.33 mm
e% = 2 3 L I
V x S
I = 181.47 AMP.
L = 50 M
S= 2 x 1.732 x 181.47 x 50
220 x 85.01
= 1.68 %
DATOS:
CIRCUITO:
TENSION 220 V
No. FASES 3F
F.P. 0.9
MEMORIA TECNICA.
PROYECTO ELECTRICOS INDUSTRIALES Y COMERCIALES
= 317.48 AMP.
EL CABLE CON AISLAMIENTO THHW LS DE 350 KCM CONDUCE 350 AMP EN TUBO A 90,
APLICANDO UN FACTOR POR TEMPERATURA FT = 1 POR LO QUE SE PROPONE 1
CONDUCTOR POR FASE, UN CIRCUITO POR TUBO QUEDANDO:
QUEDANDO
4
2
A CUATRO CABLES = 387.07 x 4 = 1548.31 mm
2 2
A TUBO = Pi x ( 76 ) = 4536.47 mm
4
2 2
FACTOR DE RELLENO 40% = 1814.59 mm > 1548.31 mm
MEMORIA TECNICA.
PROYECTO ELECTRICOS INDUSTRIALES Y COMERCIALES
e% = 2 3 L I
V x S
I = 317.48 AMP.
L = 40 M
S= 2 x 1.732 x 317.48 x 40
220 x 177.3
= 1.13 %
DATOS:
CIRCUITO: LG
TENSION 220 V
No. FASES 3F
F.P. 0.9
= 291.94 AMP.
MEMORIA TECNICA.
PROYECTO ELECTRICOS INDUSTRIALES Y COMERCIALES
EL CABLE CON AISLAMIENTO THHW LS DE 3/0 AWG CONDUCE 225 AMP EN TUBO A 90,
APLICANDO UN FACTOR POR TEMPERATURA FT = 1 POR LO QUE SE PROPONE 1
CONDUCTOR POR FASE, UN CIRCUITO POR TUBO QUEDANDO:
QUEDANDO
e% = 2 3 L I
V x S
I = 291.94 AMP.
L = 15 M
S= 2 x 1.732 x 291.94 x 15
220 x 85.01
= 0.81 %
MEMORIA TECNICA.
PROYECTO ELECTRICOS INDUSTRIALES Y COMERCIALES
1.0 OBJETIVO
3.1 LOS CONDUCTORES A EMPLEAR PARA BAJA TENSION SERAN DE COBRE SUAVE,
AISLAMIENTO VINANEL 2000 TIPO THHW-LS, TENSION DE OPERACIN 600 V,
TEMPERATURA MAXIMA EN EL CONDUCTOR: AMBIENTE SECO Y HUMEDO 90 C
MEMORIA TECNICA.
PROYECTO ELECTRICOS INDUSTRIALES Y COMERCIALES
A = 2 x 1.7320 x In x L
V x %e
DATOS:
CIRCUITO: L1
TENSION 220 V
No. FASES 3F
F.P. 0.9
MEMORIA TECNICA.
PROYECTO ELECTRICOS INDUSTRIALES Y COMERCIALES
= 569.28 AMP.
EL CABLE CON AISLAMIENTO THHW LS DE 400 KCM CONDUCE 615 AMP EN TUBO A 90,
APLICANDO UN FACTOR POR TEMPERATURA FT = 1 POR LO QUE SE PROPONE 1
CONDUCTOR POR FASE, UN CIRCUITO POR TUBO QUEDANDO:
QUEDANDO
e% = 2 3 L I
V x S
I = 569.28 AMP.
L = 15 M
S= 2 x 1.732 x 569.28 x 15
220 x 202.7
= 0.66 %
MEMORIA TECNICA.
PROYECTO ELECTRICOS INDUSTRIALES Y COMERCIALES
6.2 TABLERO E 1:
DATOS:
CIRCUITO: L2
TENSION 220 V
No. FASES 3F
F.P. 0.9
= 333.37 AMP.
EL CABLE CON AISLAMIENTO THHW LS DE 600 KCM CONDUCE 475 AMP EN TUBO A 90,
APLICANDO UN FACTOR POR TEMPERATURA FT = 1 POR LO QUE SE PROPONE 1
CONDUCTOR POR FASE, UN CIRCUITO POR TUBO QUEDANDO:
QUEDANDO
MEMORIA TECNICA.
PROYECTO ELECTRICOS INDUSTRIALES Y COMERCIALES
2
A CUATRO CABLES = 642.43 x 4 = 2569.72 mm
2 2
A TUBO = Pi x ( 102 ) = 8171.30 mm
4
2 2
FACTOR DE RELLENO 40% = 3268.52 mm > 2569.72 mm
e% = 2 3 L I
V x S
I = 333.37 AMP.
L = 180 M
220 x 304
= 3.10 %
6.3 TABLERO E 3:
DATOS:
CIRCUITO: L3
MEMORIA TECNICA.
PROYECTO ELECTRICOS INDUSTRIALES Y COMERCIALES
TENSION 220 V
No. FASES 3F
F.P. 0.9
= 73.57 AMP.
EL CABLE CON AISLAMIENTO THHW LS DEL No. 4 CONDUCE 95 AMP EN TUBO A 90,
APLICANDO UN FACTOR POR TEMPERATURA FT = 1 POR LO QUE SE PROPONE 1
CONDUCTOR POR FASE, UN CIRCUITO POR TUBO QUEDANDO:
QUEDANDO
4 4 AWG EN TUBERIA
4
2
A CUATRO CABLES = 147.41 x 4 = 589.65 mm
2 2
A TUBO = Pi x ( 51 ) = 2042.83 mm
MEMORIA TECNICA.
PROYECTO ELECTRICOS INDUSTRIALES Y COMERCIALES
2 2
FACTOR DE RELLENO 40% = 817.13 mm > 589.65 mm
e% = 2 3 L I
V x S
I = 73.57 AMP.
L = 10 M
S= 2 x 1.732 x 73.57 x 10
220 x 21.15
= 0.55 %
6.4 TABLERO E 4:
DATOS:
CIRCUITO: L4
TENSION 220 V
No. FASES 3F
F.P. 0.9
MEMORIA TECNICA.
PROYECTO ELECTRICOS INDUSTRIALES Y COMERCIALES
= 136.63 AMP.
EL CABLE CON AISLAMIENTO THHW LS DE 3/0 AWG CONDUCE 225 AMP EN TUBO A 90,
APLICANDO UN FACTOR POR TEMPERATURA FT = 1 POR LO QUE SE PROPONE 1
CONDUCTOR POR FASE, UN CIRCUITO POR TUBO QUEDANDO:
QUEDANDO
4
2
A CUATRO CABLES = 314.16 x 4 = 1256.64 mm
2 2
A TUBO = Pi x ( 76 ) = 4536.47 mm
4
2 2
FACTOR DE RELLENO 40% = 1814.59 mm > 1256.64 mm
MEMORIA TECNICA.
PROYECTO ELECTRICOS INDUSTRIALES Y COMERCIALES
e% = 2 3 L I
V x S
I = 136.63 AMP.
L = 130 M
220 x 85.01
= 2.99 %