BHEL - 1500 MW CCPP, PRAGATI - III PE-DC-314-636-C002

Design of Clarified Water Tank B1.1

ANALYSIS & DESIGN OF CLARIFIED WATER TANK RETAINING WALL AND BASE RAFT

Roof slab
EL(+) 5.950M

0 mm
300 mm

EL(+)1.500M WATER TANK

Grade slab
EL(-)0.500M (FGL)
EL(-)0.500M

500 mm
3000 mm EARTH FILL
EARTH FILL

1250 mm 1250 mm
EL(-) 3.100M

Toe Heel
EL(-) 3.500M

Note: All dimensions shown in the above fig. are in millimetres and all levels are in metres.

file:///conversion/tmp/scratch/364241414.xls 08/27/2017
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
Input data
Reference level = RL 49.00
Level at Top of Water tank = RL (+) 55.20
Maximum Water level = RL (+) 54.50
Level at Top of Base slab of tank = RL 48.90
Level at FGL = RL (+) 49.50
Depth of free board = RL (+) 0.70
Depth of Water Storage in the tank for Design = 6.30 m
Depth of Water Storage in the tank = 5.60 m

Soil data
NGL = RL (+) 49.50 m
FGL = RL (+) 49.50 m
Founding level (RL at the bottom of tank wall base slab) = RL (+) 46.90 m
Net safe bearing capacity considered at founding level = 200.00 kN/m2
Depth of soil fill for gross SBC calculation = 2.60 m
Gross Safe bearing pressure = 220.80 kN/m2
Allowable increase in bearing capacity under seismic/wind load case = 25 %
Gross Safe bearing pressure under seismic/wind load case = 270.80 kN/m2
Co-efficient of Earth pressure at rest, K r = 0.50
Depth of soil fill from NGL to FGL = 0.00 m

Tank wall data


Level Self weight
Item Height Thickness Remarks
From To of wall

RL (m) RL (m) m m kN
W1 47.2 48.9 1.700 0.55 23.4 Base of wall at invert level
W2 48.9 53.2 4.3 0.25 26.9 Rectangular portion
W3 48.9 53.2 4.3 0.3 16.1 Triangular portion
W4 53.2 55.2 2 0.25 12.5 Top of wall

Assume thickness of foundation of wall = 0.300 m


Assume thickness of base slab of tank = 0.200 m
Assume thickness of PCC = 0.100 m
Assume thicknesss of boulder filing below base slab of tank = 0.000 m
Length of base raft = 2.300 m
Length of toe = 0.750 m
Length of heel = 1.000 m
Thickness of wall at base = 0.550 m
Depth of soil fill on the toe slab from FGL = 2.30 m

Cover slab thickness = 0.150 m


Screed concrete thickness = 0.050 m
LL on cover slab = 1.500 kN /m2
Intensity of surcharge = 10.00 kN /m2

Material properties
Unit weight of concrete = 25 kN /m3
Unit weight of PCC = 24 kN /m3
Unit weight of water = 10 kN /m3
Unit weight of soil, gs = 18 kN /m3
Unit weight of boulder filling = 23 kN /m3
Unit weight of submerged soil, gsw = 8 kN /m3
Since tank is on the ground, wall is subjected to water pressure only from inside.

Conditon 1 : - a.Tank Full Condition: - Soil Pressure below base slab (inside) + Water Pressure from inside (above base slab) +
Water Pressure & Soil Surcharge below base slab (inside)+ No soil outside+ Dead Load & Live Load as applicable

b.Tank Full Condition: - Soil Pressure below base slab (inside) + Water Pressure from inside (above base slab) +
Water Pressure & Soil Surcharge below base slab (inside)+ No soil outside+ Dead Load & Live Load as applicable + SL

c.Tank Full Condition: - Soil Pressure below base slab (inside) + Water Pressure from inside (above base slab) +
Water Pressure & Soil Surcharge below base slab (inside)+ No soil outside+ Dead Load & Live Load as applicable + WL

10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)

Conditon 2 : - Tank Empty Condition: - Soil Pressure (outside) +Surcharge pressure (outside) + Soil Pressure below base

slab (inside) + Dead Load & Live Load as applicable

Tank Empty Condition: - Soil Pressure (outside) +Surcharge pressure (outside) + Soil Pressure below base
slab (inside) + Dead Load & Live Load as applicable+SL

Tank Empty Condition: - Soil Pressure (outside) +Surcharge pressure (outside) + Soil Pressure below base
slab (inside) + Dead Load & Live Load as applicable+WL

Base pressure check for Outer wall foundation

Condition 1 Tank full condition


55.20 Wr+WLL

Wb
54.50 MWL

Mwa ------Tank full cond'n-Moment due to water


0.250

W4 Fwa
53.20 5.60
Wwa

Toe side-Outside W2
face
49.50 Heel side-Water face
W3

48.90 Wgs Wg
CG of Resultant of forces

'e'
W1
CG of foundaton

Wsur Wts+Wtsw+Wtw Wbf


48.50
Whs+Whsw+whw
GWT
0.750 0.550 1.000

Wb
0.300
46.90
O 2.300

Distance Moment
Sl. No. Description Component Force from origin about Remarks
'O' origin 'O'

kN/m m kNm/m
1 W1 Wall 23.38 1.025 23.96
2 W2 Wall 26.88 1.175 31.58
3 W3 Wall 16.13 0.850 13.71
4 W4 Wall 12.50 1.175 14.69

5 Wb Base slab 17.25 1.150 19.84


6 Whs Soil above heel slab 3.60 1.800 6.48
7 Whsw Submerged soil above heel slab 10.40 1.800 18.72
8 Whw Water above heel slab 13.00 1.800 23.40
9 Wts Soil above toe slab 13.50 0.375 5.06
10 Wtsw Submerged soil above toe slab 7.80 0.375 2.93
11 Wtw Water above toe slab 9.75 0.375 3.66
12 Wbf Boulder filling 0.00 1.800 0.00
13 Wwa Water above base slab inside tank 63.00 1.800 113.40
14 Wg Grade slab 5.00 1.800 9.00
15 Wgs Screed concret load on Grade slab 0.90 1.800 1.62
16 Wr Cover slab 8.44 2.581 21.78 Length of Cover Slab is 2.25m
17 Ws Screed concret load on cover slab 2.70 2.581 6.97 Length of Cover Slab is 2.25m
18 WLL LL on cover slab 3.38 2.581 8.71 Length of Cover Slab is 2.25m
19 Wsur Surcharge 7.50 0.375 2.81
20 Mw Moment due to water inside tank Refer table below
Sum of values 245.09 328.31

10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)

Check for soil base pressure


Moment about Moment
Vertical Net moment Resultant
origin (from
about origin Eccentricity about
Sl. No. Case force Staad) of forces
CG
kN kNm kNm m m kNm
1 DL+HW 245.09 20.27 348.58 1.422 0.272 66.664
2 DL+HW+SL 245.09 41.80 370.10 1.510 0.360 88.232
3 DL+HW+WL 245.09 16.72 345.02 1.408 0.258 63.233
Case 1 DL + LL
Pmax = (SV/A) + (SM/Z) =
[245.0875/(2.3x1)] + [(245.0875x0.27x6)/(1x2.3^2] = 182.17 kN/m2
Check for SBCgross 182.17 kN/m2 < 220.80 kN/m2 Safe

Pmin = (SV/A) - (SM/Z) =


[245.0875/(2.3x1)] - [(245.0875x0.27x6)/(1x2.3^2] = 30.95 kN/m2
Check for SBCgross 30.95 kN/m2 < 220.80 kN/m2 Safe

2.3
0.55
0.75 1 m

30.95 182.17

80.26
116.42

Case 2 DL + LL + SL
Pmax = (SV/A) + (SM/Z) =
[245.0875/(2.3x1)] + [(245.0875x0.36x6)/(1x2.3^2] = 206.63 kN/m2
Check for SBCgross 206.63 kN/m2 < 270.80 kN/m2 Safe

Pmin = (SV/A) - (SM/Z) =


[245.0875/(2.3x1)] - [(245.0875x0.36x6)/(1x2.3^2] = 6.49 kN/m2
Check for SBCgross 6.49 kN/m2 < 270.80 kN/m2 Safe

2.300
0.55
0.75 1 m

6.49 206.63

71.75
119.61

Case 3 DL + LL + WL
Pmax = (SV/A) + (SM/Z) =
[245.0875/(2.3x1)] + [(245.0875x0.26x6)/(1x2.3^2] = 178.28 kN/m2
Check for SBCgross 178.28 kN/m2 < 270.80 kN/m2 Safe

Pmin = (SV/A) - (SM/Z) =


[245.0875/(2.3x1)] - [(245.0875x0.26x6)/(1x2.3^2] = 34.84 kN/m2
Check for SBCgross 34.84 kN/m2 < 270.80 kN/m2 Safe

2.300
0.55
0.75 1 m

34.84 178.28

81.61
115.91
Base pressure
Sl. No. Case Toe side Toe-wall jn Heel side Heel-wall jn
1 DL+LL 30.95 80.26 182.17 116.42
2 DL+LL+SL 6.49 71.75 206.63 119.61
3 DL+LL+WL 34.84 81.61 178.28 115.91
Max value 34.84 81.61 206.63 119.61

10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
Note:-As Conditon 2 is not the governing conditon for the analysis& design the calculation for the same is not covered in the document.

Base pressure check for compartment wall foundation

a. Tank Full Condition: - Soil Pressure below base slab (inside) + Water Pressure from inside on one compartment (above base slab)
+ Water Pressure & Soil Surcharge below base slab (inside) + Dead Load & Live Load as applicable

b. Tank Full Condition: - Soil Pressure below base slab (inside) + Water Pressure from inside on one compartment (above base slab)
+ Water Pressure & Soil Surcharge below base slab (inside) + Dead Load & Live Load as applicable+SL

Level Self weight


Item Height Thickness Remarks
From To of wall
EL (m) EL (m) m m kN
W1 47.2 48.9 1.700 0.55 23.4 Base of wall at invert level
W2 48.9 53.2 4.3 0.25 26.9 Rectangular portion
W3 48.9 53.2 4.3 0.15 16.1 Triangular portion (2 NOS)
W4 53.2 55.2 2 0.25 12.5 Top of wall

Length of base raft = 2.000 m


Length of toe = 0.725 m
Length of heel = 0.725 m

Distance Moment
Sl. No. Description Component Force from origin about Remarks
'O' origin 'O'

kN/m m kNm/m
1 W1 Wall 23.38 1.000 23.38
2 W2 Wall 26.88 1.000 26.88
3 W3a Wall 8.06 0.775 6.25
4 W4 Wall 12.50 1.000 12.50
4a W3b Wall 8.06 1.225 9.88
5 Wb Base slab 17.25 1.000 17.25
6 Whs Dry Soil above heel slab 2.61 1.638 4.27
Whsw Submerged Soil above heel slab 7.54 1.638 12.35
Whw Water above heel slab 9.43 1.638 15.43
7 Wts Dry Soil above toe slab 2.61 0.363 0.95
Wtsw Submerged Soil above toe slab 7.54 0.363 2.73
Wtw Water above toe slab 9.43 0.363 3.42
8 Wbf Boulder filling 0.00 1.000 0.00
9 Wwa Water above base slab inside tank 91.35 1.000 91.35
10 Wg Grade slab 7.25 1.000 7.25
11 Wgs Screed concret load on grade slab 1.74 1.000 1.74
12 Wr Cover slab 16.88 2.563 43.24 Length of Cover Slab is 4.500m
13 Ws Screed concret load on cover slab 5.40 2.563 13.84 Length of Cover Slab is 4.500m
14 WLL LL on cover slab 6.75 2.563 17.30 Length of Cover Slab is 4.500m
15 Wsur Surcharge 0.00 0.000 0.00
16 Mw Moment due to water inside tank Refer table below
Sum of values 264.64 309.99

Moment about Moment


Vertical Net moment Resultant
origin (from
about origin Eccentricity about
Sl. No. Case force Staad) of forces
CG
kN kNm kNm m m kNm
1 DL+LL 264.64 -46.01 263.98 0.998 0.152 40.225
2 DL+LL+SL 264.64 -67.84 242.16 0.915 0.235 62.190

Under tank full condition, moments are zero, hence base pressure is checked only for direct compression
Pmax, Pmin = (SV/A) = 132.32 kN/m2

Check for SBCgross 132.32 kN/m2 < 220.80 kN/m2 Safe

When one side of tank is full and other side is empty, the condition is similar to outer wall and the base pressure check is found to
be safe for a wall foundation of 2.0m wide.

Bending moment & Shear force calculation

10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
The base pressure under toe side is maximum during wind load case and under heel side it is maximum under seismic load case.
Hence design values are considered accordingly.
Bending moment in the base raft on the toe side, at the face of wall due to the soil base pressure and downward forces acting above
toe slab
Mtoe = (34.84*0.75*1*0.75*0.5) + ((81.61-34.84)*0.5*0.75*1*(1/3)*0.75)
- (0.75*0.3*1*25*0.75*0.5) - (31.05*0.75*0.5) = 0.43 kNm (Sagging - Bottom tension)

Shear force in the base raft on the toe side, at the face of wall due to the soil base pressure and downward forces acting above toe slab

Vtoe = (34.84*0.75*1) + ((81.61-34.84)*0.5*0.75*1)


- (0.75*0.3*1*25) - (31.05) = 7.00 kN

Bending moment in the base raft on the heel side, at the face of wall due to the soil base pressure and downward forces acting above
heel slab.
Mheel = (119.61*1*1*1*0.5) + ((206.63-119.61)*0.5*1*1*(2/3)*1)
- (1*0.3*1*25*1*0.5) - (68.9000000000001*1*0.5) - (27x1x0.5) = 37.11 kNm (Sagging - Bottom tension)

Shear force in the base raft on the toe side, at the face of wall due to the soil base pressure and downward forces acting above heel slab.

Vheel = (119.61*1*1) + ((206.63-119.61)*0.5*1*1) = 59.72 kN


- (1*0.3*1*25) - (68.9000000000001) - (27)

Check for stability


Since the wall is a part of tank wall, wall is stable against Sliding and Overturning.
Since the invert level of the slab is above the expected water table uplift check is not required as per soil report

10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
CMWSSB ------------------------------------------------------
Structural Design Calculation for
Design of Wall footing:- Treated Water Storage tank
Pump house (Vallam Vadagal)
Forces for Wall Footing design:
Max.Sagging Bending moment in the footing at the face of wall heel side
Mmax,sag = 37.11 kNm
(Sagging - Bottom tension)
Max.Sagging Bending moment in the footing at the face of wall toe side
Mmax,sag = 0.43 kNm
(Sagging - Bottom tension)
Max.Hogging Bending moment in the footing at the face of wall heel side
Mmax,hog = 0.00 kNm
(Hogging - Top tension)
Max.Hogging Bending moment in the footing at the face of wall toe side
Mmax,hog = 0.00 kNm
(Hogging - Top tension)

Maximum shear force in the footing = 59.72 kN

Reinforcment Calculation for wall footing


Bottom Reinforcement calculation:
Grade of concrete, fck = 30 N/mm2
Grade of steel, fy = 500 N/mm2

Assumed depth of wall footing, D = 300 mm


Clear Cover = 50 mm
Effective depth, d = 244 mm
Factored Moment Mu = 1.2 x 37.11
= 44.53 kN.m/m

M = 0.133 x fck x b x d2
44.53 x 10^6 = 0.133 x 30 x 1000 x d^2
Required depth d = 105.65 mm
< 244 mm Hence Ok

Maximum sagging BM (bottom tension), M = 37.11 kNm


Mu/bd2 (R) = 1.2 x 37.11x1E6 / ( 1000 x 244^2 )
= 0.748

Percentage steel /m, pt


ptmin
Pt =
f ck
2f y [
1 1
4 .598R
f ck
x 100
] = 0.177
= 0.12 %
Depth = 244 mm
Area of steel required, Astreqd. = 431.88 mm2
Diameter of the bar = 12 mm
Spacing of the bar = 175 mm
Area of steel provided, Astprov. = 646.27 mm2 SAFE
Provide reinforcement as 12 @ 175 c/c Both ways

Top Reinforcement calculation:


Maximum hogging BM (top tension), M = 0.00 kNm
Mu/bd2 (R) = 1.2 x 0x1E6 / ( 1000 x 244^2 )
= 0.000

Percentage steel /m, pt


Pt =
f ck
2f y [
1 1
4 .598R
f ck ]
x 100
= 0

=
ptmin = 0.12 %
Depth of Surface Zone = 244 mm
Area of steel required, Astreqd. = 292.80 mm2
Diameter of the bar = 10 mm
Spacing of the bar = 200 mm
Area of steel provided, Astprov. = 392.70 mm2 SAFE
Provide reinforcement as 10 @ 200 c/c Both ways

Check for shear:


Maximum Shear force at the face of the wall = 59.72 kN
Actual Shear stress t = 1.2 x 59.72 x 1000 / (1000 x244)
= 0.294 N/mm
% of reinforcement Provided = 0.265
Allowable shear stress = 0.38 N/mm SAFE
(as per IS:456, table 19)
Reinforcement Summary
RC wall Footing Reinforcement:

Bottom face (Both ways) = 12 dia @ 175mm c/c


Top face (Both ways) = 10 dia @ 200mm c/c

10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)

Design of External / Internal Wall :-

The Wall behaves like a propped cantilever and the wall length (a) to height (b) ratio is more than 3 as per IS 3370 or
1.50 as per Moody's Chart. The predominant bending moment in wall is the vertical bending moment.

The Vertical bending moment is calculated in STAAD for the propped cantilever wall member .

The horizontal moment is calculated as per Moody's chart tables by limiting the a/b ratio to 1.5 along with the applicable
boundary conditons for the tank.

The reinforcement required for horizontal & vertical bending is verified against the minimum reinforcement criteria
as mentioned in code

Design Parameters :
Grade of concrete, fck = 30 N/mm2
Grade of steel, fy = 500 N/mm2
Parameters for RC wall design
Clear cover For Wall, Water Face = 45 mm
Soil face = 50 mm

Bending Moment & Shear Force Table

Critical Case :-Tank Full Condition: - Soil Pressure below base slab (inside) + Water Pressure from inside (above base slab) +
Water Pressure & Soil Surcharge below base slab (inside)+ No soil outside+ Dead Load & Live Load as applicable + SL

Bending Distance
Case

Moment Shear Force Thickness of Wall Elevation from from


"BM" "SF" "d " Base "RL" Bottom Remarks
kNm KN mm m m

BM on outside face of wall @


1 -41.78 -92.163 550 RL+46.90 0.00 RL+46.90 (support)
BM on inside face of wall @
2 78.348 -146.113 550 RL+47.90 1.00 RL+47.90 (span)
BM on inside face of wall @ base
3 292.238 215.59 550 RL+48.90 2.00 slab levRL RL+48.90(support)

BM on outside Face of wall @


4 -73.66 -0.313 280 RL+52.800 5.90 RL+52.80 (span)

BM on outside Face of wall @


5 -70.876 -3.305 250 RL+53.200 6.30 RL+53.20 (span)

BM on outside / inside Face of


6 0 -50.58 250 RL+55.200 8.30 wall @ RL+55.20 (support)

RL+50.9 to BM on inside Face of wall @


7 0 84.299 550 EL55.20 4.0 to 8.3 RL+50.9 to RL+55.20 (span)

Forces for RC Wall for Design: (from STAAD)

BM causing tension in the outside face:


Bending moment in the RC wall due to case 1
RL+46.90 to RL+48.90 M1 = -41.78 kNm
Bending moment in the RC wall due to case 4
RL+48.90 to RL+52.80 M4 = -73.66 kNm
Bending moment in the RC wall due to case 5
RL+53.20 to RL+55.20 M5 = -70.88 kNm

BM causing tension in the inside face:


Bending moment in the RC wall due to case 2
RL+46.90 to RL+48.90 M2 = 78.35 kNm
Bending moment in the RC wall due to case 3
RL+48.90 to RL+50.40 M3 = 292.24 kNm
Bending moment in the RC wall due to case 3
RL+50.9 to RL+55.2 M7 = 0.00 kNm

SF in the RC wall:
Shear force in the RC wall due to case 1 V1 = 92.163 kN

10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
Shear force in the RC wall due to case 4 V4 = -0.313 kN
Shear force in the RC wall due to case 6 V6 = 50.580 kN
Shear force in the RC wall due to case 3 V3 = 215.590 kN
Shear force in the RC wall due to case 2 V2 = 146.113 kN
Shear force in the RC wall due to case 7 V7 = 84.299 kN

Thickness check for bending moment:

A) RL+46.90 to RL+48.90
Provided thickness of wall = 550 mm
Maximum Bending Moment M = 292.24 kN.m/m
Factored Moment Mu = 1.2 x 292.238
= 350.69 kN.m/m

M = 0.133 x fck x b x d2
350.69 x 10^6 = 0.133 x 30 x 1000 x d^2
Required depth d = 296.46 mm
< 495 mm Hence Ok

B) RL+48.90 to RL+52.80
Provided thickness of wall = 280 mm
Maximum Bending Moment M = 73.66 kN.m/m
Factored Moment Mu = 1.2 x 73.66
= 88.39 kN.m/m

M = 0.133 x fck x b x d2
88.39 x 10^6 = 0.133 x 30 x 1000 x d^2
Required depth d = 148.84 mm
< 224 mm Hence Ok

C) RL+53.2 to RL+55.20
Provided thickness of wall = 250 mm
Maximum Bending Moment M = 70.88 kN.m/m
Factored Moment Mu = 1.2 x 70.876
= 85.05 kN.m/m

M = 0.133 x fck x b x d2
85.05 x 10^6 = 0.133 x 30 x 1000 x d^2
Required depth d = 146.00 mm
< 194 mm Hence Ok

Reinforment calculation

Vertical Reinforcement Calculations:

A) RL+46.90 to RL+50.40
Inside Face
Max. Factored moment in Wall Mu =1.2 x 292.238 = 350.69 kNm
Effective depth of the wall d = 495.0 mm

R = Mu/bd2
= (350.69 x10^6)/(1000 x495 x 495)
= 1.4

Pt =
f ck
2f y [
1 1
4 .598R
f ck ]
x 100 Pt = 0.349

ptmin (As per Clause 8.1 IS:3370 Part-II 2009) = 0.35 %


Depth of Surface Zone = 275 mm
Area of steel required, Astreqd. = 1729 mm
Diameter of the bar = 20 mm
Spacing of the bar = 100 mm
Area of steel provided, Astprov. = 3140 mm SAFE

Outside Face
Max. Factored moment in Wall Mu =1.2 x 41.78 = 50.14 kNm
Effective depth of the wall d = 494.0 mm

10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
R = Mu/bd2
= (50.14 x10^6)/(1000 x494 x 494)
= 0.2

ptmin
Pt =
f ck
2f y[
1 1
4 .598R
f ck ]
x100 Pt = 0.048

(As per Clause 32.5 IS:456:2000) = 0.12 %


Depth of Surface Zone = 494 mm
Area of steel required, Astreqd. = 593 mm
Diameter of the bar = 12 mm
Spacing of the bar = 100 mm
Area of steel provided, Astprov. = 1130 mm SAFE

B) RL+50.40 to RL+52.80
Inside Face
Max. Factored moment in Wall Mu =1.2 x 0 = 0.00 kNm
Effective depth of the wall d = 229.0 mm

R = Mu/bd2
= (0 x10^6)/(1000 x229 x 229)
= 0.0
Pt =
f ck
2f y [
1 1
4 .598R
f ck ]
x 100
Pt = 0.000

ptmin (As per Clause 8.1 IS:3370 Part-II 2009) = 0.35 %


Depth of Surface Zone = 140 mm
Area of steel required, Astreqd. = 490 mm
Diameter of the bar = 12 mm
Spacing of the bar = 200 mm
Area of steel provided, Astprov. = 565 mm SAFE

Outside Face
Max. Factored moment in Wall Mu =1.2 x 73.66 = 88.39 kNm
Effective depth of the wall d = 224.0 mm

R = Mu/bd2
= (88.39 x10^6)/(1000 x224 x 224)
= 1.8

ptmin
Pt =
f ck
2f y[
1 1
4 .598R
f ck ]
x100 Pt = 0.437

(As per Clause 8.1 IS:3370 Part-II 2009) = 0.35 %


Depth of Surface Zone = 140 mm
Area of steel required, Astreqd. = 978 mm
Diameter of the bar = 12 mm
Spacing of the bar = 100 mm
Area of steel provided, Astprov. = 1130 mm SAFE

C) RL+53.20 to RL+55.20
Inside Face
Max. Factored moment in Wall Mu =1.2 x 0 = 0.00 kNm
Effective depth of the wall d = 199.0 mm

R = Mu/bd2
= (0 x10^6)/(1000 x199 x 199)
= 0.0

Pt =
f ck
2f y [
1 1
4 .598R
f ck ]
x 100 Pt = 0.000

ptmin (As per Clause 8.1 IS:3370 Part-II 2009) = 0.35 %


Depth of Surface Zone = 125 mm
Area of steel required, Astreqd. = 438 mm
Diameter of the bar = 12 mm
Spacing of the bar = 200 mm
Area of steel provided, Astprov. = 565 mm SAFE

Outside Face
Max. Factored moment in Wall Mu =1.2 x 70.876 = 85.05 kNm
Effective depth of the wall d = 192.0 mm

10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)

R = Mu/bd2
= (85.05 x10^6)/(1000 x192 x 192)
= 2.3

ptmin
Pt =
f ck
2f y[
1 1
4 .598R
f ck ]
x100 Pt = 0.588

(As per Clause 8.1 IS:3370 Part-II 2009) = 0.35 %


Depth of Surface Zone = 125 mm
Area of steel required, Astreqd. = 1129 mm
Diameter of the bar = 16 mm
Spacing of the bar = 100 mm
Area of steel provided, Astprov. = 2010 mm SAFE

Horizontal Reinforcement calculations:

Consider Figure 13 from Moody's Chart (Walls fixed along 3 edges & Hinged along one edge) for a/b ratio = 1.5
Horizontal Bending & Shear Coefficients for a/b = 1.5
Support Moment Coeff (Maximum) ax1 = 0.0232
Span Moment Coeff(Maximum) ax2 = 0.0089
Shear Coeff rx = 0.2503
Water Pressure / m pw = 63.00 kN/m
Soil Pressure ps = 17.00 kN/m
Width of Wall Considered b = 1000.00 mm
Support Moment (Maximum) Mx1w = 0.0232 x 63 x 1000^2 x 10^-6
= 1.46 kN-m
Mx1s = 0.0232 x 17 x 1000^2 x 10^-6
= 0.39 kN-m
Span Moment (Maximum) Mx2w = 0.0089 x 63 x 1000^2 x 10^-6
0.56 kN-m
Mx2s = 0.0089 x 17 x 1000^2 x 10^-6
= 0.15 kN-m
Shear Force Vxw = 0.2503 x 63 x 1000 x 10^-3
= 15.77 kN
Vxs = 0.2503 x 17 x 1000 x 10^-3
= 4.26 kN
A) RL+46.90 to RL+50.40
Inside Face & Outside Face-Support Moments
Max. Factored moment in Wall Mu =1.5 x 1.4616 = 2.19 kNm
Effective depth of the wall d = 494.0 mm

R = Mu/bd2
= (2.19 x10^6)/(1000 x494 x 494)
= 0.009

Pt =
f ck
2f y [
1 1
4 .598R
f ck ]
x 100 Pt = 0.002

ptmin (As per Clause 8.1 IS:3370 Part-II 2009) = 0.35 %


Depth of Surface Zone = 275 mm
Area of steel required, Astreqd. = 963 mm
Diameter of the bar = 16 mm
Spacing of the bar = 200 mm
Area of steel provided, Astprov. = 1005 mm SAFE

Inside Face & Outside Face-Span Moments


Max. Factored moment in Wall Mu =1.5 x 0.5607 = 0.84 kNm
Effective depth of the wall d = 494.0 mm

R = Mu/bd2
= (0.84 x10^6)/(1000 x494 x 494)
= 0.003

Pt =
f ck
2f y [
1 1
4 .598R
f ck ]
x 100 Pt = 0.001

ptmin (As per Clause 8.1 IS:3370 Part-II 2009) = 0.35 %


Depth of Surface Zone = 275 mm
Area of steel required, Astreqd. = 963 mm
Diameter of the bar = 16 mm
Spacing of the bar = 200 mm

10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
Area of steel provided, Astprov. = 1005 mm SAFE

B) RL+50.40 to RL+55.20
Inside Face & Outside Face-Support Moments
Max. Factored moment in Wall Mu =1.5 x 1.4616 = 2.19 kNm
Effective depth of the wall d = 224.0 mm

R = Mu/bd2
= (2.19 x10^6)/(1000 x224 x 224)
= 0.044

Pt =
f ck
2f y [
1 1
4 .598R
f ck ]
x 100 Pt = 0.010

ptmin (As per Clause 8.1 IS:3370 Part-II 2009) = 0.35 %


Depth of Surface Zone = 140 mm
Area of steel required, Astreqd. = 490 mm
Diameter of the bar = 12 mm
Spacing of the bar = 200 mm
Area of steel provided, Astprov. = 565 mm SAFE

Inside Face & Outside Face-Span Moments


Max. Factored moment in Wall Mu =1.5 x 0.5607 = 0.84 kNm
Effective depth of the wall d = 224.0 mm

R = Mu/bd2
= (0.84 x10^6)/(1000 x224 x 224)
= 0.017

Pt =
f ck
2f y [
1 1
4 .598R
f ck ]
x 100 Pt = 0.004

ptmin (As per Clause 8.1 IS:3370 Part-II 2009) = 0.35 %


Depth of Surface Zone = 140 mm
Area of steel required, Astreqd. = 490 mm
Diameter of the bar = 12 mm
Spacing of the bar = 200 mm
Area of steel provided, Astprov. = 565 mm SAFE

Check for shear in the Wall:

A) RL+46.90 to RL+52.40
Maximum Shear force at the face of Wall @ Base = 215.59 kN
Factored Shear Force = 258.71 kN
Actual Shear stress = Vu / bd
Actual Shear stress t = 258.71 x 1000 / (1000 x495)
= 0.523 N/mm
% of reinforcement Provided = 0.634
Allowable shear stress = 0.55 N/mm SAFE

B) RL+53.20 to RL+55.20
Maximum Shear force at the face of Wall @ Top = 50.58 kN
Factored Shear Force = 60.70 kN
Actual Shear stress = Vu / bd
Actual Shear stress t = 60.7 x 1000 / (1000 x194)
= 0.313 N/mm
% of reinforcement Provided = 1.036
Allowable shear stress = 0.66 N/mm SAFE

Additonal Check in Grade Slab

Design of Grade Slab for Tension


Direct tension in the slab = 215.59 kN
Factored Direct tension = 258.71 kN
Depth of the slab = 200 mm
Ast,reqd = 258.71 x 10^3 / (0.87 x 500) = 892.10 mm
Reinforcement per face = 446.05 mm
Diameter of the bar = 12 mm
Spacing of the reinforcement = 200 mm
Provided area of reinforcement = 565.49 mm

10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)

Anchorage Length required for Tension


Diameter of the bar provided = 12 mm
Grade of steel = Fe 500
Permissible stress in steel reinforcement = 0.87fy
(Table 22, IS 456 : 2000) 435 N/mm
Permissible bond stress = 1.5 N/mm
(Table 21, IS 456 : 2000)
Increase in Permissible stress in steel for deformed bars = 1.6 x 1.5
as per cl. B-2.1.2 = 2.4 N/mm
Anchorage length required = 12 x 435 / (4 x 2.4)
= 543.75 mm
Length provided = 600 mm SAFE

12 dia bar at 200 Spacing at junction of Wall & Grade Slab & at all other places as per Grade slab design

Additonal Check in Side Walls

Design of Wall for Tension


Direct tension in the Wall = 15.77 kN
Factored Direct tension = 23.65 kN
Depth of the wall = 250 mm
Ast,reqd = 23.65 x 10^3 / (0.87 x 500) = 81.56 mm
Reinforcement per face = 40.78 mm
Diameter of the bar = 12 mm
Spacing of the reinforcement = 200 mm
Provided area of reinforcement = 565.49 mm

Anchorage Length required for Tension


Diameter of the bar provided = 12 mm
Grade of steel = Fe 500
Permissible stress in steel reinforcement = 0.87fy
(Table 22, IS 456 : 2000) 435 N/mm
Permissible bond stress = 1.5 N/mm
(Table 21, IS 456 : 2000)
Increase in Permissible stress in steel for deformed bars = 1.6 x 1.5
as per cl. B-2.1.2 = 2.4 N/mm
Anchorage length required = 12 x 435 / (4 x 2.4)
= 543.75 mm
Length provided = 600 mm SAFE

The internal wall design is same as the External wall; The reinforcment provided on the tank base inside face is provided
on the both faces of the inside wall assuming that one tank is always empty and the other one is full & vice-versa.
Similarly the reinforcment provided at outer face of wall at the span locations are provided on both faces of the inner wall
as one tank is always empty & other is fulle& vice-versa.Separate design for the wall is not provided

10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)

Design of Compartment Wall :-

The Wall behaves like a propped cantilever and the wall length (a) to height (b) ratio is more than 3 as per IS 3370 or
1.50 as per Moody's Chart. The predominant bending moment in wall is the vertical bending moment.

The Vertical bending moment is calculated in STAAD for the propped cantilever wall member .

The horizontal moment is calculated as per Moody's chart tables by limiting the a/b ratio to 1.5 along with the applicable
boundary conditons for the tank.

The reinforcement required for horizontal & vertical bending is verified against the minimum reinforcement criteria
as mentioned in code

Design Parameters :
Grade of concrete, fck = 30 N/mm2
Grade of steel, fy = 500 N/mm2
Parameters for RC wall design
Clear cover For Wall, Water Face = 45 mm
Soil face = 50 mm

Bending Moment & Shear Force Table

Critical Case :-Tank Full Condition: - Soil Pressure below base slab (On one side) + Water Pressure on oneside (above base slab) +
Water Pressure & Soil Surcharge below base slab (both side)+ Dead Load & Live Load as applicable + SL

Bending Distance
Case

Moment Shear Force Thickness of Wall Elevation from from


"BM" "SF" "d " Base "RL" Bottom Remarks
kNm KN mm m m

BM on other face of wall @


1 43.523 87.614 450 RL+46.90 0.00 RL+46.90 (support)
BM on inside face of wall @
2 -44.091 87.614 450 RL+47.90 1.00 RL+47.90 (span)
BM on inside face of wall @ base
3 -176.776 -197.257 450 RL+48.90 2.00 slab levRL RL+48.90(support)

BM on other Face of wall @


4 122.408 0.223 450 RL+52.300 5.40 RL+52.30 (span)

BM on other Face of wall @


5 107.531 31.362 450 RL+53.200 6.30 RL+53.20 (span)

BM on other / inside Face of wall


6 0 68.887 450 RL+55.200 8.30 @ RL+55.20 (support)

RL+50.9 to BM on inside Face of wall @


7 0 117.413 450 EL55.20 4.0 to 8.3 RL+50.9 to RL+55.20 (span)

Forces for RC Wall for Design: (from STAAD)

BM causing tension in the outside face:


Bending moment in the RC wall due to case 1
RL+46.90 to RL+48.90 M1 = 43.52 kNm
Bending moment in the RC wall due to case 4
RL+48.90 to RL+52.30 M4 = 122.41 kNm
Bending moment in the RC wall due to case 5
RL+53.20 to RL+55.20 M5 = 107.53 kNm

BM causing tension in the opposite face:


Bending moment in the RC wall due to case 2
RL+46.90 to RL+48.90 M2 = 44.09 kNm
Bending moment in the RC wall due to case 3
RL+48.90 to RL+50.40 M3 = 176.78 kNm
Bending moment in the RC wall due to case 3
RL+50.9 to RL+55.2 M7 = 0.00 kNm

SF in the RC wall:
Shear force in the RC wall due to case 1 V1 = 87.614 kN

10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
Shear force in the RC wall due to case 4 V4 = 0.223 kN
Shear force in the RC wall due to case 6 V6 = 68.887 kN
Shear force in the RC wall due to case 3 V3 = 197.257 kN
Shear force in the RC wall due to case 2 V2 = 87.614 kN
Shear force in the RC wall due to case 7 V7 = 117.413 kN

Thickness check for bending moment:

A) RL+46.90 to RL+48.90
Provided thickness of wall = 450 mm
Maximum Bending Moment M = 176.78 kN.m/m
Factored Moment Mu = 1.2 x 176.776
= 212.13 kN.m/m

M = 0.133 x fck x b x d2
212.13 x 10^6 = 0.133 x 30 x 1000 x d^2
Required depth d = 230.58 mm
< 395 mm Hence Ok

B) RL+48.90 to RL+52.30
Provided thickness of wall = 450 mm
Maximum Bending Moment M = 122.41 kN.m/m
Factored Moment Mu = 1.2 x 122.408
= 146.89 kN.m/m

M = 0.133 x fck x b x d2
146.89 x 10^6 = 0.133 x 30 x 1000 x d^2
Required depth d = 191.87 mm
< 392 mm Hence Ok

C) RL+53.2 to RL+55.20
Provided thickness of wall = 450 mm
Maximum Bending Moment M = 107.53 kN.m/m
Factored Moment Mu = 1.2 x 107.531
= 129.04 kN.m/m

M = 0.133 x fck x b x d2
129.04 x 10^6 = 0.133 x 30 x 1000 x d^2
Required depth d = 179.83 mm
< 392 mm Hence Ok

Reinforment calculation

Vertical Reinforcement Calculations:

A) RL+46.90 to RL+50.40
Inside Face / Opposite Face
Max. Factored moment in Wall Mu =1.2 x 176.776 = 212.13 kNm
Effective depth of the wall d = 395.0 mm

R = Mu/bd2
= (212.13 x10^6)/(1000 x395 x 395)
= 1.4

Pt = 0.331

ptmin (As per Clause 8.1 IS:3370 Part-II 2009) = 0.35 %


Depth of Surface Zone = 225 mm
Area of steel required, Astreqd. = 1307 mm
Diameter of the bar = 20 mm
Spacing of the bar = 125 mm
Area of steel provided, Astprov. = 2512 mm SAFE

B) RL+50.40 to RL+52.30
Inside Face /Opposite Face
Max. Factored moment in Wall Mu =1.2 x 122.408 = 146.89 kNm
Effective depth of the wall d = 392.0 mm

10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)

R = Mu/bd2
= (146.89 x10^6)/(1000 x392 x 392)
= 1.0

Pt = 0.228

ptmin (As per Clause 8.1 IS:3370 Part-II 2009) = 0.35 %


Depth of Surface Zone = 225 mm
Area of steel required, Astreqd. = 896 mm
Diameter of the bar = 16 mm
Spacing of the bar = 125 mm
Area of steel provided, Astprov. = 1608 mm SAFE

C) RL+53.20 to RL+55.20
Inside Face / Opposite Face
Max. Factored moment in Wall Mu =1.2 x 107.531 = 129.04 kNm
Effective depth of the wall d = 392.0 mm

R = Mu/bd2
= (129.04 x10^6)/(1000 x392 x 392)
= 0.8

Pt = 0.200

ptmin (As per Clause 8.1 IS:3370 Part-II 2009) = 0.35 %


Depth of Surface Zone = 225 mm
Area of steel required, Astreqd. = 788 mm
Diameter of the bar = 16 mm
Spacing of the bar = 125 mm
Area of steel provided, Astprov. = 1608 mm SAFE

Horizontal Reinforcement calculations:

Consider Figure 13 from Moody's Chart (Walls fixed along 3 edges & Hinged along one edge) for a/b ratio = 1.5
Horizontal Bending & Shear Coefficients for a/b = 1.5
Support Moment Coeff (Maximum) ax1 = 0.0232
Span Moment Coeff(Maximum) ax2 = 0.0089
Shear Coeff rx = 0.2503
Water Pressure / m pw = 63.00 kN/m
Soil Pressure ps = 17.00 kN/m
Width of Wall Considered b = 1000.00 mm
Support Moment (Maximum) Mx1w = 0.0232 x 63 x 1000^2 x 10^-6
= 1.46 kN-m
Mx1s = 0.0232 x 17 x 1000^2 x 10^-6
= 0.39 kN-m
Span Moment (Maximum) Mx2w = 0.0089 x 63 x 1000^2 x 10^-6
0.56 kN-m
Mx2s = 0.0089 x 17 x 1000^2 x 10^-6
= 0.15 kN-m
Shear Force Vxw = 0.2503 x 63 x 1000 x 10^-3
= 15.77 kN
Vxs = 0.2503 x 17 x 1000 x 10^-3
= 4.26 kN
A) RL+46.90 to RL+50.40
Inside Face & Opposite Face-Support Moments
Max. Factored moment in Wall Mu =1.5 x 1.4616 = 2.19 kNm
Effective depth of the wall d = 395.0 mm

R = Mu/bd2
= (2.19 x10^6)/(1000 x395 x 395)
= 0.014

Pt = 0.003

ptmin (As per Clause 8.1 IS:3370 Part-II 2009) = 0.35 %


Depth of Surface Zone = 225 mm
Area of steel required, Astreqd. = 788 mm
Diameter of the bar = 12 mm
Spacing of the bar = 140 mm

10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
Area of steel provided, Astprov. = 807 mm SAFE

Inside Face & Opposite Face-Span Moments


Max. Factored moment in Wall Mu =1.5 x 0.5607 = 0.84 kNm
Effective depth of the wall d = 395.0 mm

R = Mu/bd2
= (0.84 x10^6)/(1000 x395 x 395)
= 0.005

Pt = 0.001

ptmin (As per Clause 8.1 IS:3370 Part-II 2009) = 0.35 %


Depth of Surface Zone = 225 mm
Area of steel required, Astreqd. = 788 mm
Diameter of the bar = 12 mm
Spacing of the bar = 140 mm
Area of steel provided, Astprov. = 807 mm SAFE

B) RL+50.40 to RL+55.20
Inside Face & Opposite Face-Support Moments
Max. Factored moment in Wall Mu =1.5 x 1.4616 = 2.19 kNm
Effective depth of the wall d = 392.0 mm

R = Mu/bd2
= (2.19 x10^6)/(1000 x392 x 392)
= 0.014

Pt = 0.003

ptmin (As per Clause 8.1 IS:3370 Part-II 2009) = 0.35 %


Depth of Surface Zone = 225 mm
Area of steel required, Astreqd. = 788 mm
Diameter of the bar = 12 mm
Spacing of the bar = 140 mm
Area of steel provided, Astprov. = 807 mm SAFE

Inside Face & Opposite Face-Span Moments


Max. Factored moment in Wall Mu =1.5 x 0.5607 = 0.84 kNm
Effective depth of the wall d = 392.0 mm

R = Mu/bd2
= (0.84 x10^6)/(1000 x392 x 392)
= 0.005

Pt = 0.001

ptmin (As per Clause 8.1 IS:3370 Part-II 2009) = 0.35 %


Depth of Surface Zone = 225 mm
Area of steel required, Astreqd. = 788 mm
Diameter of the bar = 12 mm
Spacing of the bar = 140 mm
Area of steel provided, Astprov. = 807 mm SAFE

Check for shear in the Wall:

A) RL+46.90 to RL+52.40
Maximum Shear force at the face of Wall @ Base = 197.26 kN
Factored Shear Force = 236.71 kN
Actual Shear stress = Vu / bd
Actual Shear stress t = 236.71 x 1000 / (1000 x395)
= 0.599 N/mm
% of reinforcement Provided = 0.636
Allowable shear stress = 0.55 N/mm UNSAFE

Providing Additional Reinforcement to take care of Shear @ the junction of tank slab & Wall

Diameter of the bar = 10 mm


Spacing of the bar = 125 mm

10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
Area of steel provided, Astprov. = 628 mm
% of reinforcement Provided = 0.826
Allowable shear stress = 0.61 N/mm SAFE

B) RL+53.20 to RL+55.20
Maximum Shear force at the face of Wall @ Top = 68.89 kN
Factored Shear Force = 82.66 kN
Actual Shear stress = Vu / bd
Actual Shear stress t = 82.66 x 1000 / (1000 x392)
= 0.211 N/mm
% of reinforcement Provided = 0.410
Allowable shear stress = 0.46 N/mm SAFE

Additonal Check in Grade Slab

Design of Grade Slab for Tension


Direct tension in the slab = 197.26 kN
Factored Direct tension = 236.71 kN
Depth of the slab = 200 mm
Ast,reqd = 236.71 x 10^3 / (0.87 x 500) = 816.24 mm
Reinforcement per face = 408.12 mm
Diameter of the bar = 12 mm
Spacing of the reinforcement = 200 mm
Provided area of reinforcement = 565.49 mm

Anchorage Length required for Tension


Diameter of the bar provided = 12 mm
Grade of steel = Fe 500
Permissible stress in steel reinforcement = 0.87fy
(Table 22, IS 456 : 2000) 435 N/mm
Permissible bond stress = 1.5 N/mm
(Table 21, IS 456 : 2000)
Increase in Permissible stress in steel for deformed bars = 1.6 x 1.5
as per cl. B-2.1.2 = 2.4 N/mm
Anchorage length required = 12 x 435 / (4 x 2.4)
= 543.75 mm
Length provided = 600 mm SAFE

12 dia bar at 200 Spacing at junction of Wall & Grade Slab & at all other places as per Grade slab design

Additonal Check in Side Walls

Design of Wall for Tension


Direct tension in the Wall = 15.77 kN
Factored Direct tension = 23.65 kN
Depth of the wall = 250 mm
Ast,reqd = 23.65 x 10^3 / (0.87 x 500) = 81.56 mm
Reinforcement per face = 40.78 mm
Diameter of the bar = 12 mm
Spacing of the reinforcement = 200 mm
Provided area of reinforcement = 565.49 mm

Anchorage Length required for Tension


Diameter of the bar provided = 12 mm
Grade of steel = Fe 500
Permissible stress in steel reinforcement = 0.87fy
(Table 22, IS 456 : 2000) 435 N/mm
Permissible bond stress = 1.5 N/mm
(Table 21, IS 456 : 2000)
Increase in Permissible stress in steel for deformed bars = 1.6 x 1.5
as per cl. B-2.1.2 = 2.4 N/mm
Anchorage length required = 12 x 435 / (4 x 2.4)
= 543.75 mm
Length provided = 600 mm SAFE

10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)

Design of Baffle Wall :-

The Wall behaves like a propped cantilever and it is always in contact with water on both sides. There is no predominant bending
moment for the wall in the horizontal and vertical direction & hence minimum reinforcment is provided on both faces as per IS 3370

Design Parameters :
Grade of concrete, fck = 30 N/mm2
Grade of steel, fy = 500 N/mm2
Parameters for RC wall design
Clear cover For Wall, Water Face = 45 mm
Soil face = 50 mm
Thickness ofWall = 200 mm

Bending Moment & Shear Force Table

Critical Case :-Tank Full Condition or Tank Empty conditon Vertical Compression is the predominant governing Case

Thickness check for bending moment:

A) RL+48.90 to RL+55.20
Provided thickness of wall = 200 mm
Maximum Bending Moment M = 0.00 kN.m/m
Factored Moment Mu = 1.5 x 0
= 0.00 kN.m/m

M = 0.133 x fck x b x d2
0 x 10^6 = 0.133 x 30 x 1000 x d^2
Required depth d = 0.00 mm
< 150 mm Hence Ok

Reinforment calculation

Vertical Reinforcement Calculations:

A) RL+48.90 to RL+55.20
Inside Face / Opposite Face
Max. Factored moment in Wall Mu =1.5 x 0 = 0.00 kNm
Effective depth of the wall d = 150.0 mm

R = Mu/bd2
= (0 x10^6)/(1000 x150 x 150)
= 0.0

Pt = 0.000

ptmin (As per Clause 8.1 IS:3370 Part-II 2009) = 0.35 %


Depth of Surface Zone = 100 mm
Area of steel required, Astreqd. = 350 mm
Diameter of the bar = 10 mm
Spacing of the bar = 200 mm
Area of steel provided, Astprov. = 393 mm SAFE

Horizontal Reinforcement calculations:

Support Moment Coeff (Maximum) ax1 = 0 (Water on both sides of Wall)


Span Moment Coeff(Maximum) ax2 = 0 (Water on both sides of Wall)
Shear Coeff rx = 0 (Water on both sides of Wall)
Water Pressure / m pw = 63.00 kN/m
Soil Pressure ps = 17.00 kN/m
Width of Wall Considered b = 1000.00 mm
Support Moment (Maximum) Mx1w = 0 x 63 x 1000^2 x 10^-6
= 0.00 kN-m

10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
Mx1s = 0 x 17 x 1000^2 x 10^-6
= 0.00 kN-m
Span Moment (Maximum) Mx2w = 0 x 63 x 1000^2 x 10^-6
0.00 kN-m
Mx2s = 0 x 17 x 1000^2 x 10^-6
= 0.00 kN-m
Shear Force Vxw = 0 x 63 x 1000 x 10^-3
= 0.00 kN
Vxs = 0 x 17 x 1000 x 10^-3
= 0.00 kN
A) RL+48.90 to RL+55.20
Inside Face & Opposite Face-Support Moments
Max. Factored moment in Wall Mu =1.5 x 0 = 0.00 kNm
Effective depth of the wall d = 150.0 mm

R = Mu/bd2
= (0 x10^6)/(1000 x150 x 150)
= 0.000

Pt = 0.000

ptmin (As per Clause 8.1 IS:3370 Part-II 2009) = 0.35 %


Depth of Surface Zone = 100 mm
Area of steel required, Astreqd. = 350 mm
Diameter of the bar = 10 mm
Spacing of the bar = 200 mm
Area of steel provided, Astprov. = 393 mm SAFE

Inside Face & Opposite Face-Span Moments


Max. Factored moment in Wall Mu =1.5 x 0 = 0.00 kNm
Effective depth of the wall d = 150.0 mm

R = Mu/bd2
= (0 x10^6)/(1000 x150 x 150)
= 0.000

Pt = 0.000

ptmin (As per Clause 8.1 IS:3370 Part-II 2009) = 0.35 %


Depth of Surface Zone = 100 mm
Area of steel required, Astreqd. = 350 mm
Diameter of the bar = 10 mm
Spacing of the bar = 200 mm
Area of steel provided, Astprov. = 393 mm SAFE

Check for shear in the Wall:

A) RL+48.90 to RL+55.20
Maximum Shear force at the face of Wall @ Base = 0.00 kN
Factored Shear Force = 0.00 kN
Actual Shear stress = Vu / bd
Actual Shear stress t = 0 x 1000 / (1000 x150)
= 0.000 N/mm
% of reinforcement Provided = 0.262
Allowable shear stress = 0.38 N/mm SAFE

10P107-C0004-015
BHEL - 1500 MW CCPP, PRAGATI - III PE-DC-314-654-C006
Design of Raw water Reservoir C.4

ANALYSIS AND DESIGN OF RAW WATER RESERVOIR COMPARTMENT WALL

1. Analysis of Raw water Reservoir Compartment Wall:

Raw water reservoir compartment wall is analysed and designed for the water pressure at the critical
condition of one compartment full of water and ther compartment is empty.

EL(+)2.000M
Max. Water Lvl [ EL(+) 1.500m ]

#REF! #REF!
RESERVOIR w8c RESERVOIR
COMPARTMENT -1
w1 #REF! COMPARTMENT -2
EL(+)0.500M
#REF! #REF!
#REF!

w2 w8b #REF!
EL(-)1.000M

#REF!
#REF!
P4
Grade slab w3 w8a
#REF! #REF!
EL(-) 4.000M
Base Raft p p4
300 Heel Heel 4

EL(-) 5.000M w4
Grade slab
O
1 2
#REF!

1. a. Load Calculation:

Vertical Loads:

Self weight of retaining wall,


W1 (250mm thick) = #REF! kN

W2 (500 mm thick) = #REF! kN


W3 (1000mm thick) = #REF! kN

W4, Self weight of Base raft = #REF!


= #REF! kN

file:///conversion/tmp/scratch/364241414.xls 08/27/2017
BHEL - 1500 MW CCPP, PRAGATI - III PE-DC-314-654-C006
Design of Raw water Reservoir C.5

Weight of water inside the tank


W8a = #REF!
= #REF! kN
W8b = #REF!
= #REF! kN
W8c = #REF!
= #REF! kN

Lateral Loads:

p4, Lateral pressure due to Water inside the tank = gw h


= #REF!
= #REF! kN/m2
P4, Lateral force due to Water inside the tank = #REF!
#REF! kN
1.b. Base soil pressure Calculation :

Taking moments about origin O,

Distance
from origin Moment
Sl. No. Description Force (kN) 'O' (m) (kNm)
1 W1 #REF! #REF! #REF!
2 W2 #REF! #REF! #REF!
3 W3 #REF! #REF! #REF!
4 W4 #REF! #REF! #REF!
5 W8a #REF! #REF! #REF!
6 W8b #REF! #REF! #REF!
7 W8c #REF! #REF! #REF!
8 P4 #REF! #REF! #REF!

SV = #REF! kN SM = #REF! kNm

Location of resultant force = #REF! m

Eccentercity = #REF! m

Base soil pressure


Pmax = (SV/A) + (SM/Z)
= #REF! = #REF! kN/m2
Check for SBCgross 124.38 kN/m2
#REF! #REF!

Pmin = (SV/A) - (SM/Z)


= #REF! = #REF! kN/m2
Check for SBCgross 124.38 kN/m2
#REF! #REF!

file:///conversion/tmp/scratch/364241414.xls 08/27/2017
BHEL - 1500 MW CCPP, PRAGATI - III PE-DC-314-654-C006
Design of Raw water Reservoir C.6

#REF!
#REF!
m #REF!
m #REF! m

#REF! #REF! #REF!kN/m2 #REF! kN/m2


kN/m2 kN/m2

1.c. Bending moment & Shear force calculation:

Bending moment in the base raft at the section-1 for the


base soil pressure and downward forces acting above the heel slab.
M1 = #REF!
#REF!
= #REF! kNm (Sagging - Bottom tension)

Shear Force in the base raft at the section-1 for the


base soil pressure and downward forces acting above the heel slab.
V1 = #REF!
#REF!
= #REF! kN

Bending moment in the base raft at the section-2 for the


base soil pressure and downward forces acting above the heel slab.
M2 = #REF!
#REF!
#REF!
= #REF! kNm (Hogging - Top tension)

Shear Force in the base raft at the section-2 for the


base soil pressure and downward forces acting above the heel slab.
V2 = #REF!
#REF!
= #REF! kN

1. d. Check For Overturning:

Overturning moments,
Moment due to lateral water pressure
#REF! = #REF! kNm
Total overturning moment, Mo

Restoring moments, Mr
#REF!
#REF! = #REF! kNm

Factor of Safety against Overtutning, FOS = 0.9Mr


Mo

= #REF!
#REF!

file:///conversion/tmp/scratch/364241414.xls 08/27/2017
BHEL - 1500 MW CCPP, PRAGATI - III PE-DC-314-654-C006
Design of Raw water Reservoir C.7

= #REF!

file:///conversion/tmp/scratch/364241414.xls 08/27/2017
BHEL - 1500 MW CCPP, PRAGATI - III PE-DC-314-654-C006
Design of Raw water Reservoir C.8

2. Retaining Wall Base Raft Design:

2.a. Design Parameters :


Grade of concrete, fck = 25 N/mm2
Grade of steel, fy = 500 N/mm2
Permissible Stress in Steel at Earth Face, sst = 190 N/mm2
(As per Table 2 of IS:3370 (Part - II) - 1965)
Permissible Bending Stress in concrete for tension, scbt = 1.8 N/mm2
Permissible Bending Stress in compression, scbc = 8.5 N/mm3
Grade of concrete Fck = 25 N/mm2
Modular ratio m (280/3s cbc
) = 10.98
k mscbc/(mscbc+sst) = 0.329
j 1- k / 3 = 0.89
Q scbc.j.k = 1.25
Clear cover = 50 mm

2.b. Forces for Base raft design:


Sagging BMs (Bottom Tension)

Maximum Sagging Bending moment in the base raft occurs at Section-1


Mmax,sag = #REF! kNm
(Sagging - Bottom tension)
Hogging BMs (Top Tension)

Maximum hogging Bending moment in the base raft occurs at Section-2


Mmax,hog = #REF! kNm
(Hogging - Top tension)

Maximum shear force in the base raft = #REF! kN

2.c. Min. thickness required for the uncracked section

Maximum BM (from the forces given in 3.a) = #REF! kNm


M = fxZ
M = f x b x d2 / 6
d required = SQRT( 6 * M / b * f)

= #REF!

= #REF! mm
Provided depth of the base raft = 300 mm
Check for base raft thickness = #REF!

2.d. Reinforcement Calculations:


Bottom Reinforcement calculation:
Maximum Sagging (bottom tension) Bending moment in the base raft
at the face of the wall = #REF! kNm
Diameter of the bar = 20 mm
Spacing of the bar = 200 mm
Effective depth of the base raft = 240 mm

file:///conversion/tmp/scratch/364241414.xls 08/27/2017
BHEL - 1500 MW CCPP, PRAGATI - III PE-DC-314-654-C006
Design of Raw water Reservoir C.9

Minimum percentage of reinforcement = 0.12 %


Minimum area of steel, Astmin = 288 mm2
Area of steel reqd. for BM , AstBM = M
(sst x j x d)

= #REF!
190 x 0.89 x 240
Area of steel reqd. for BM , AstBM = #REF! mm2
Hence Area of steel required, Astreqd. = #REF! mm2
Area of steel provided, Astprov. = 1570.80 mm2
Check for base raft (at toe side) Reinforcement = #REF!
Provide reinforcement as 20 @ 200 c/cBoth ways

Top Reinforcement calculation:


Maximum Hogging (top tension) Bending moment in the =
base raft at the face of the wall = #REF! kNm
Diameter of the bar = 20 mm
Spacing of the bar = 200 mm
Effective depth of the base raft = 240 mm
Minimum percentage of reinforcement = 0.12 %
Minimum area of steel, Astmin = 288 mm2
Area of steel reqd. for BM at the heel side, AstBM = M
(sst x j x d)

#REF!
190 x 0.89 x 240

Area of steel reqd. for BM at the heel side, AstBM = #REF! mm2
Hence Area of steel required, Astreqd. = #REF! mm2
Area of steel provided, Astprov. = 1570.80 mm2
Check for base raft (at heel side) Reinforcement = #REF!
Provide reinforcement as 20 @ 200 Both ways

2.e. Check for shear:

Maximum Shear force at the face of the wall = #REF! kN


Actual Shear stress = Q
(b x j x d)

= #REF!
1000 x 0.89 x 240

#REF! N/mm

Allowable shear stress = 1.90 N/mm


(As per Table 1 of IS:3370 (Part - II) - 1965)
Check for shear #REF!

file:///conversion/tmp/scratch/364241414.xls 08/27/2017
BHEL - 1500 MW CCPP, PRAGATI - III PE-DC-314-654-C006
Design of Raw water Reservoir C.10

3. DESIGN OF WALL:

3.a. Design Parameters :


Grade of concrete Fck = 25 N/mm2
Grade of steel, fy = 500 N/mm2
Permissible Stress in Steel at Water Face, = 150 N/mm2
Permissible Stress in Steel at Earth Face = 190 N/mm2
(As per Table 2 of IS:3370 (Part - II) - 1965)
Permissible Bending Stress in tension scbt = 1.8 N/mm2
Permissible Bending Stress in compression scbc = 8.5 N/mm3
Modular ratio m (280/3s cbc
) = 10.98
(IS 456 Annex B 2.1.2)
k mscbc/(mscbc+sst) = 0.38
j 1- k / 3 = 0.87
Q scbc.j.k = 1.42
Clear cover For Wall, Water Face = 50 mm
Soil face = 50 mm
Effective cover Wall = 62.5 mm

3.b. Forces for Wall Design:

BMs and SFs causing tension in the water face:


Bending moments in the retaining wall for the lateral forces shown in 1.a,
At EL(-) 4.000m = #REF! = #REF! kNm
At EL(-) 1.000m
#REF! = #REF! kNm
At EL(+) 0.500m
#REF! = #REF! kNm

Shear Forces in the retaining wall for the lateral forces in shown in 1.a,
At EL(-) 4.000m = #REF! kN

3.c. Min. Thickness required for the uncracked section


M = fxZ
M = f x b x d2 / 6
d required = SQRT[ 6 * M / (b*f) ]
For BM tension at water face,
Minimum wall thickness required At EL(-) 4.000m = #REF!
= 1000*1.8
= #REF! mm
Minimum wall thickness required At EL(-) 1.000m = #REF! mm
Minimum wall thickness required At EL(+) 0.500m = #REF! mm
Thickness of Wall provided:
For BM tension at water face,
Provided thickness of wall At EL(-) 4.000m = 1000 mm > #REF! mm
Provided thickness of wall At EL(-) 1.000m = 500 mm > #REF! mm
Provided thickness of wall At EL(+) 0.500m = 250 mm > #REF! mm

Hence the provided thickness of wall is sufficient for Uncracked section.

file:///conversion/tmp/scratch/364241414.xls 08/27/2017
BHEL - 1500 MW CCPP, PRAGATI - III PE-DC-314-654-C006
Design of Raw water Reservoir C.11

3.d. Thickness required for Bending Moment:


Thickness required At EL(-) 4.000m
Maximum Bending Moment M = #REF! kN.m/m
M = Q.b.d2
#REF! x 10^6
= 1.42 x 1000 x d^2
Required depth d = #REF! mm
#REF! 1000 mm
#REF!
Thickness Required At EL(-) 1.000m
Maximum Bending Moment M = #REF! kN.m/m
M = Q.b.d2
#REF! x 10^6
= 1.42 x 1000 x d^2
Required depth d = #REF! mm
#REF! 500 mm
#REF!
Thickness Required At EL(+) 0.500m
Maximum Bending Moment M = #REF! kN.m/m
M = Q.b.d2
#REF! x 10^6
= 1.42 x 1000 x d^2
Required depth d = #REF! mm
#REF! 250 mm
#REF!
3.e. Minimum Reinforcement in Wall
(As per Clause7.1 IS:3370 Part-II 1965)
Minimum percentage of reinforcement on each face = 0.08 %
Minimum area of steel required for 1000mm = 800 mm
Minimum area of steel required for 500mm = 400 mm
Minimum percentage of reinforcement on each face = 0.103 %
Minimum area of steel required for 250mm = 257 mm

3.f. Vertical Reinforcement calculations in wall (water face)


Reinforcement Calculations: (from EL(-)4.00m to EL(-)1.00m)
Max. moment in Wall M = #REF! kNm
Effective depth of the wall d = 937.5 mm
Ast,reqd = #REF! = #REF! mm
Minimum Ast Requied = 800 mm
Diameter of the bar = 25 mm
Spacing of the bar = 200 mm
Ast,prov = 2453 mm
#REF!
Check for Permissible concrete stress in tension due to bending:
(from EL(-)4.00m to EL(-)1.00m)
Taking moment about inside face, depth of neutral axis from inside face
b x h x h/2 + (m-1) Ast x d + (m-1) Asc x c
x= b x h + (m-1) x Ast + (m-1) x Asc = 500.0 mm

The second moment of area about neutral axis,


INA = bx3/3 + b(h-x)3/3 + (m-1) x Ast x (d-x)2 + (m-1) x Asc x (x-c)2
= 9.3E+10 mm4
Tensile stress in concrete due to bending ftb = M/(INA/x)
= #REF! N/mm
Permissible tensile stress in concrete in bending stb = 1.80 N/mm
#REF!

file:///conversion/tmp/scratch/364241414.xls 08/27/2017
BHEL - 1500 MW CCPP, PRAGATI - III PE-DC-314-654-C006
Design of Raw water Reservoir C.12

Reinforcement Calculations: (from EL(-)1.00m to EL(+)0.500m)


Max. moment in Wall M = #REF! kNm/m
Effective depth of the wall d = 442 mm
Ast,reqd = #REF! = #REF! mm
Minimum Ast Requied = 400 mm
Area of steel required = #REF! mm
Diameter of the bar = 16
Spacing of the bar = 200
Ast,prov = 1005 mm
#REF!
Check for Permissible concrete stress in tension due to bending:
(from EL(-)1.00m to EL(+)0.500m)
Taking moment about inside face, depth of neutral axis from inside face
b x h x h/2 + (m-1) Ast x d + (m-1) Asc x c
x= = 250.1 mm
b x h + (m-1) x Ast + (m-1) x Asc
The second moment of area about neutral axis,
INA = bx3/3 + b(h-x)3/3 + (m-1) x Ast x (d-x)2 + (m-1) x Asc x (x-c)2
= 1.1E+10 mm4
Tensile stress in concrete due to bending ftb = M/(INA/x)
= #REF! N/mm
Permissible tensile stress in concrete in bending stb = 1.80 N/mm
#REF!

Reinforcement Calculations: (from EL(+)0.500m to EL(+)2.000m)


Max. moment in Wall M = #REF! kNm/m
Effective depth of the wall d = 194 mm
Ast,reqd = #REF! = #REF! mm
Minimum Ast Requied = 257 mm
Area of steel required = #REF! mm
Diameter of the bar = 12 mm
Spacing of the bar = 200 mm
Ast,prov = 565 mm
SAFE

Check for Permissible concrete stress in tension due to bending:


(from EL(+)0.500m to EL(+)2.000m)
Taking moment about inside face, depth of neutral axis from inside face
b x h x h/2 + (m-1) Ast x d + (m-1) Asc x c
x= b x h + (m-1) x Ast + (m-1) x Asc = 125.1 mm

The second moment of area about neutral axis,


INA = bx3/3 + b(h-x)3/3 + (m-1) x Ast x (d-x)2 + (m-1) x Asc x (x-c)2
= 1.4E+09 mm4
Tensile stress in concrete due to bending ftb = M/(INA/x)
= #REF! N/mm
Permissible tensile stress in concrete in bending stb = 1.80 N/mm
#REF!

file:///conversion/tmp/scratch/364241414.xls 08/27/2017
BHEL - 1500 MW CCPP, PRAGATI - III PE-DC-314-654-C006
Design of Raw water Reservoir C.13

3.g. Horizontal Reinforcement calculations in wall (Both faces)


Reinforcement Calculations: (from EL(-)4.00m to EL(-)1.00m)
Minimum percentage of reinforcement on each face = 0.08 %
Ast,reqd = (0.08/100) x 1000 x 1000 = 800 mm
Diameter of the bar = 16 mm
Spacing of the bar = 200 mm
Ast,prov = 1005 mm
SAFE
Reinforcement Calculations: (from EL(-)1.00m to EL(+)0.500m)
Minimum percentage of reinforcement on each face = 0.08 %
Ast,reqd = (0.08/100) x 1000 x 500 = 400 mm
Diameter of the bar = 12 mm
Spacing of the bar = 200 mm
Ast,prov = 565 mm
SAFE
Reinforcement Calculations: (from EL(+)0.500m to EL(+)2.000m)
Minimum percentage of reinforcement on each face = 0.103 %
Ast,reqd = (0.08/100) x 1000 x 250 = 257 mm
Diameter of the bar = 12 mm
Spacing of the bar = 200 mm
Ast,prov = 565 mm
SAFE

3.h. Check for shear in the Wall:

Maximum Shear force at the face of the wall = #REF! kN


Actual Shear stress = Q
(b x j x d)
#REF! N/mm
Allowable shear stress = 1.90 N/mm
(As per Table 1 of IS:3370 (Part - II) - 1965)
Check for shear #REF!

4.a. Design of Grade Slab for Tension


Direct tension in the slab (from 3.b) = #REF! kN
Depth of the slab = 300 mm
Ast,reqd = #REF! = #REF! mm
Reinforcement per face = #REF! mm
Diameter of the bar = 20 mm
Spacing of the reinforcement = 200 mm
Provided area of reinforcement = 1570.80 mm

4.b. Anchorage Length required for Tension in Grade Slab Rebar:


Diameter of the bar provided = 20 mm
Grade of steel = Fe 500
Permissible stress in steel reinforcement = 0.55fy
(Table 22, IS 456 : 2000) 275 N/mm
Permissible bond stress = 0.9 N/mm
(Table 21, IS 456 : 2000)
Increase in Permissible stress in steel for deformed bars = 1.6 x 0.9
as per cl. B-2.1.2 = 1.44 N/mm
Anchorage length required = 20 x 275 / (4 x 1.44)
= 954.86 mm

file:///conversion/tmp/scratch/364241414.xls 08/27/2017
BHEL - 1500 MW CCPP, PRAGATI - III PE-DC-314-654-C006
Design of Raw water Reservoir C.14

Length provided = 1500 mm


SAFE

5. Reinforcement Summary

5.a. Wall Reinforcement


Water face vertical Reinforcement (Provided on both the faces)
(from EL(-)4.00m to EL(-)1.00m) = 25 dia @ 200mm c/c
(from EL(-)1.00m to EL(+)0.500m) = 16 dia @ 200mm c/c
(from EL(+)0.500m to EL(+)2.000m) = 12 dia @ 200mm c/c
Horizontal reinforcement - (Both face)
(from EL(-)4.00m to EL(-)1.00m) = 16 dia @ 200mm c/c
(from EL(-)1.00m to EL(+)0.500m) = 12 dia @ 200mm c/c
(from EL(+)0.500m to EL(+)2.000m) = 12 dia @ 200mm c/c

5.b. Retaining wall Base Raft Reinforcement:


Bottom face (Both ways) = 20 dia @ 200mm c/c
Top face (Both ways) = 20 dia @ 200mm c/c

5.c. Grade Slab Reinforcement:

(i). Reinforcement in the direction perpendicular to the wall:


Top and bottom = 20 dia 200mm c/c
(Upto 1.5m from face of Base
Raft inner edge)

= 16 dia 200mm c/c


(Beyond above Reinforcement)

(ii). Reinforcement in the direction parallel to the wall:


Top and bottom = 16 dia 200mm c/c

file:///conversion/tmp/scratch/364241414.xls 08/27/2017