ANALYSIS & DESIGN OF CLARIFIED WATER TANK RETAINING WALL AND BASE RAFT
Roof slab
EL(+) 5.950M
0 mm
300 mm
Grade slab
EL(-)0.500M (FGL)
EL(-)0.500M
500 mm
3000 mm EARTH FILL
EARTH FILL
1250 mm 1250 mm
EL(-) 3.100M
Toe Heel
EL(-) 3.500M
Note: All dimensions shown in the above fig. are in millimetres and all levels are in metres.
file:///conversion/tmp/scratch/364241414.xls 08/27/2017
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
Input data
Reference level = RL 49.00
Level at Top of Water tank = RL (+) 55.20
Maximum Water level = RL (+) 54.50
Level at Top of Base slab of tank = RL 48.90
Level at FGL = RL (+) 49.50
Depth of free board = RL (+) 0.70
Depth of Water Storage in the tank for Design = 6.30 m
Depth of Water Storage in the tank = 5.60 m
Soil data
NGL = RL (+) 49.50 m
FGL = RL (+) 49.50 m
Founding level (RL at the bottom of tank wall base slab) = RL (+) 46.90 m
Net safe bearing capacity considered at founding level = 200.00 kN/m2
Depth of soil fill for gross SBC calculation = 2.60 m
Gross Safe bearing pressure = 220.80 kN/m2
Allowable increase in bearing capacity under seismic/wind load case = 25 %
Gross Safe bearing pressure under seismic/wind load case = 270.80 kN/m2
Co-efficient of Earth pressure at rest, K r = 0.50
Depth of soil fill from NGL to FGL = 0.00 m
RL (m) RL (m) m m kN
W1 47.2 48.9 1.700 0.55 23.4 Base of wall at invert level
W2 48.9 53.2 4.3 0.25 26.9 Rectangular portion
W3 48.9 53.2 4.3 0.3 16.1 Triangular portion
W4 53.2 55.2 2 0.25 12.5 Top of wall
Material properties
Unit weight of concrete = 25 kN /m3
Unit weight of PCC = 24 kN /m3
Unit weight of water = 10 kN /m3
Unit weight of soil, gs = 18 kN /m3
Unit weight of boulder filling = 23 kN /m3
Unit weight of submerged soil, gsw = 8 kN /m3
Since tank is on the ground, wall is subjected to water pressure only from inside.
Conditon 1 : - a.Tank Full Condition: - Soil Pressure below base slab (inside) + Water Pressure from inside (above base slab) +
Water Pressure & Soil Surcharge below base slab (inside)+ No soil outside+ Dead Load & Live Load as applicable
b.Tank Full Condition: - Soil Pressure below base slab (inside) + Water Pressure from inside (above base slab) +
Water Pressure & Soil Surcharge below base slab (inside)+ No soil outside+ Dead Load & Live Load as applicable + SL
c.Tank Full Condition: - Soil Pressure below base slab (inside) + Water Pressure from inside (above base slab) +
Water Pressure & Soil Surcharge below base slab (inside)+ No soil outside+ Dead Load & Live Load as applicable + WL
10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
Conditon 2 : - Tank Empty Condition: - Soil Pressure (outside) +Surcharge pressure (outside) + Soil Pressure below base
Tank Empty Condition: - Soil Pressure (outside) +Surcharge pressure (outside) + Soil Pressure below base
slab (inside) + Dead Load & Live Load as applicable+SL
Tank Empty Condition: - Soil Pressure (outside) +Surcharge pressure (outside) + Soil Pressure below base
slab (inside) + Dead Load & Live Load as applicable+WL
Wb
54.50 MWL
W4 Fwa
53.20 5.60
Wwa
Toe side-Outside W2
face
49.50 Heel side-Water face
W3
48.90 Wgs Wg
CG of Resultant of forces
'e'
W1
CG of foundaton
Wb
0.300
46.90
O 2.300
Distance Moment
Sl. No. Description Component Force from origin about Remarks
'O' origin 'O'
kN/m m kNm/m
1 W1 Wall 23.38 1.025 23.96
2 W2 Wall 26.88 1.175 31.58
3 W3 Wall 16.13 0.850 13.71
4 W4 Wall 12.50 1.175 14.69
10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
2.3
0.55
0.75 1 m
30.95 182.17
80.26
116.42
Case 2 DL + LL + SL
Pmax = (SV/A) + (SM/Z) =
[245.0875/(2.3x1)] + [(245.0875x0.36x6)/(1x2.3^2] = 206.63 kN/m2
Check for SBCgross 206.63 kN/m2 < 270.80 kN/m2 Safe
2.300
0.55
0.75 1 m
6.49 206.63
71.75
119.61
Case 3 DL + LL + WL
Pmax = (SV/A) + (SM/Z) =
[245.0875/(2.3x1)] + [(245.0875x0.26x6)/(1x2.3^2] = 178.28 kN/m2
Check for SBCgross 178.28 kN/m2 < 270.80 kN/m2 Safe
2.300
0.55
0.75 1 m
34.84 178.28
81.61
115.91
Base pressure
Sl. No. Case Toe side Toe-wall jn Heel side Heel-wall jn
1 DL+LL 30.95 80.26 182.17 116.42
2 DL+LL+SL 6.49 71.75 206.63 119.61
3 DL+LL+WL 34.84 81.61 178.28 115.91
Max value 34.84 81.61 206.63 119.61
10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
Note:-As Conditon 2 is not the governing conditon for the analysis& design the calculation for the same is not covered in the document.
a. Tank Full Condition: - Soil Pressure below base slab (inside) + Water Pressure from inside on one compartment (above base slab)
+ Water Pressure & Soil Surcharge below base slab (inside) + Dead Load & Live Load as applicable
b. Tank Full Condition: - Soil Pressure below base slab (inside) + Water Pressure from inside on one compartment (above base slab)
+ Water Pressure & Soil Surcharge below base slab (inside) + Dead Load & Live Load as applicable+SL
Distance Moment
Sl. No. Description Component Force from origin about Remarks
'O' origin 'O'
kN/m m kNm/m
1 W1 Wall 23.38 1.000 23.38
2 W2 Wall 26.88 1.000 26.88
3 W3a Wall 8.06 0.775 6.25
4 W4 Wall 12.50 1.000 12.50
4a W3b Wall 8.06 1.225 9.88
5 Wb Base slab 17.25 1.000 17.25
6 Whs Dry Soil above heel slab 2.61 1.638 4.27
Whsw Submerged Soil above heel slab 7.54 1.638 12.35
Whw Water above heel slab 9.43 1.638 15.43
7 Wts Dry Soil above toe slab 2.61 0.363 0.95
Wtsw Submerged Soil above toe slab 7.54 0.363 2.73
Wtw Water above toe slab 9.43 0.363 3.42
8 Wbf Boulder filling 0.00 1.000 0.00
9 Wwa Water above base slab inside tank 91.35 1.000 91.35
10 Wg Grade slab 7.25 1.000 7.25
11 Wgs Screed concret load on grade slab 1.74 1.000 1.74
12 Wr Cover slab 16.88 2.563 43.24 Length of Cover Slab is 4.500m
13 Ws Screed concret load on cover slab 5.40 2.563 13.84 Length of Cover Slab is 4.500m
14 WLL LL on cover slab 6.75 2.563 17.30 Length of Cover Slab is 4.500m
15 Wsur Surcharge 0.00 0.000 0.00
16 Mw Moment due to water inside tank Refer table below
Sum of values 264.64 309.99
Under tank full condition, moments are zero, hence base pressure is checked only for direct compression
Pmax, Pmin = (SV/A) = 132.32 kN/m2
When one side of tank is full and other side is empty, the condition is similar to outer wall and the base pressure check is found to
be safe for a wall foundation of 2.0m wide.
10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
The base pressure under toe side is maximum during wind load case and under heel side it is maximum under seismic load case.
Hence design values are considered accordingly.
Bending moment in the base raft on the toe side, at the face of wall due to the soil base pressure and downward forces acting above
toe slab
Mtoe = (34.84*0.75*1*0.75*0.5) + ((81.61-34.84)*0.5*0.75*1*(1/3)*0.75)
- (0.75*0.3*1*25*0.75*0.5) - (31.05*0.75*0.5) = 0.43 kNm (Sagging - Bottom tension)
Shear force in the base raft on the toe side, at the face of wall due to the soil base pressure and downward forces acting above toe slab
Bending moment in the base raft on the heel side, at the face of wall due to the soil base pressure and downward forces acting above
heel slab.
Mheel = (119.61*1*1*1*0.5) + ((206.63-119.61)*0.5*1*1*(2/3)*1)
- (1*0.3*1*25*1*0.5) - (68.9000000000001*1*0.5) - (27x1x0.5) = 37.11 kNm (Sagging - Bottom tension)
Shear force in the base raft on the toe side, at the face of wall due to the soil base pressure and downward forces acting above heel slab.
10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
CMWSSB ------------------------------------------------------
Structural Design Calculation for
Design of Wall footing:- Treated Water Storage tank
Pump house (Vallam Vadagal)
Forces for Wall Footing design:
Max.Sagging Bending moment in the footing at the face of wall heel side
Mmax,sag = 37.11 kNm
(Sagging - Bottom tension)
Max.Sagging Bending moment in the footing at the face of wall toe side
Mmax,sag = 0.43 kNm
(Sagging - Bottom tension)
Max.Hogging Bending moment in the footing at the face of wall heel side
Mmax,hog = 0.00 kNm
(Hogging - Top tension)
Max.Hogging Bending moment in the footing at the face of wall toe side
Mmax,hog = 0.00 kNm
(Hogging - Top tension)
M = 0.133 x fck x b x d2
44.53 x 10^6 = 0.133 x 30 x 1000 x d^2
Required depth d = 105.65 mm
< 244 mm Hence Ok
=
ptmin = 0.12 %
Depth of Surface Zone = 244 mm
Area of steel required, Astreqd. = 292.80 mm2
Diameter of the bar = 10 mm
Spacing of the bar = 200 mm
Area of steel provided, Astprov. = 392.70 mm2 SAFE
Provide reinforcement as 10 @ 200 c/c Both ways
10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
The Wall behaves like a propped cantilever and the wall length (a) to height (b) ratio is more than 3 as per IS 3370 or
1.50 as per Moody's Chart. The predominant bending moment in wall is the vertical bending moment.
The Vertical bending moment is calculated in STAAD for the propped cantilever wall member .
The horizontal moment is calculated as per Moody's chart tables by limiting the a/b ratio to 1.5 along with the applicable
boundary conditons for the tank.
The reinforcement required for horizontal & vertical bending is verified against the minimum reinforcement criteria
as mentioned in code
Design Parameters :
Grade of concrete, fck = 30 N/mm2
Grade of steel, fy = 500 N/mm2
Parameters for RC wall design
Clear cover For Wall, Water Face = 45 mm
Soil face = 50 mm
Critical Case :-Tank Full Condition: - Soil Pressure below base slab (inside) + Water Pressure from inside (above base slab) +
Water Pressure & Soil Surcharge below base slab (inside)+ No soil outside+ Dead Load & Live Load as applicable + SL
Bending Distance
Case
SF in the RC wall:
Shear force in the RC wall due to case 1 V1 = 92.163 kN
10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
Shear force in the RC wall due to case 4 V4 = -0.313 kN
Shear force in the RC wall due to case 6 V6 = 50.580 kN
Shear force in the RC wall due to case 3 V3 = 215.590 kN
Shear force in the RC wall due to case 2 V2 = 146.113 kN
Shear force in the RC wall due to case 7 V7 = 84.299 kN
A) RL+46.90 to RL+48.90
Provided thickness of wall = 550 mm
Maximum Bending Moment M = 292.24 kN.m/m
Factored Moment Mu = 1.2 x 292.238
= 350.69 kN.m/m
M = 0.133 x fck x b x d2
350.69 x 10^6 = 0.133 x 30 x 1000 x d^2
Required depth d = 296.46 mm
< 495 mm Hence Ok
B) RL+48.90 to RL+52.80
Provided thickness of wall = 280 mm
Maximum Bending Moment M = 73.66 kN.m/m
Factored Moment Mu = 1.2 x 73.66
= 88.39 kN.m/m
M = 0.133 x fck x b x d2
88.39 x 10^6 = 0.133 x 30 x 1000 x d^2
Required depth d = 148.84 mm
< 224 mm Hence Ok
C) RL+53.2 to RL+55.20
Provided thickness of wall = 250 mm
Maximum Bending Moment M = 70.88 kN.m/m
Factored Moment Mu = 1.2 x 70.876
= 85.05 kN.m/m
M = 0.133 x fck x b x d2
85.05 x 10^6 = 0.133 x 30 x 1000 x d^2
Required depth d = 146.00 mm
< 194 mm Hence Ok
Reinforment calculation
A) RL+46.90 to RL+50.40
Inside Face
Max. Factored moment in Wall Mu =1.2 x 292.238 = 350.69 kNm
Effective depth of the wall d = 495.0 mm
R = Mu/bd2
= (350.69 x10^6)/(1000 x495 x 495)
= 1.4
Pt =
f ck
2f y [
1 1
4 .598R
f ck ]
x 100 Pt = 0.349
Outside Face
Max. Factored moment in Wall Mu =1.2 x 41.78 = 50.14 kNm
Effective depth of the wall d = 494.0 mm
10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
R = Mu/bd2
= (50.14 x10^6)/(1000 x494 x 494)
= 0.2
ptmin
Pt =
f ck
2f y[
1 1
4 .598R
f ck ]
x100 Pt = 0.048
B) RL+50.40 to RL+52.80
Inside Face
Max. Factored moment in Wall Mu =1.2 x 0 = 0.00 kNm
Effective depth of the wall d = 229.0 mm
R = Mu/bd2
= (0 x10^6)/(1000 x229 x 229)
= 0.0
Pt =
f ck
2f y [
1 1
4 .598R
f ck ]
x 100
Pt = 0.000
Outside Face
Max. Factored moment in Wall Mu =1.2 x 73.66 = 88.39 kNm
Effective depth of the wall d = 224.0 mm
R = Mu/bd2
= (88.39 x10^6)/(1000 x224 x 224)
= 1.8
ptmin
Pt =
f ck
2f y[
1 1
4 .598R
f ck ]
x100 Pt = 0.437
C) RL+53.20 to RL+55.20
Inside Face
Max. Factored moment in Wall Mu =1.2 x 0 = 0.00 kNm
Effective depth of the wall d = 199.0 mm
R = Mu/bd2
= (0 x10^6)/(1000 x199 x 199)
= 0.0
Pt =
f ck
2f y [
1 1
4 .598R
f ck ]
x 100 Pt = 0.000
Outside Face
Max. Factored moment in Wall Mu =1.2 x 70.876 = 85.05 kNm
Effective depth of the wall d = 192.0 mm
10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
R = Mu/bd2
= (85.05 x10^6)/(1000 x192 x 192)
= 2.3
ptmin
Pt =
f ck
2f y[
1 1
4 .598R
f ck ]
x100 Pt = 0.588
Consider Figure 13 from Moody's Chart (Walls fixed along 3 edges & Hinged along one edge) for a/b ratio = 1.5
Horizontal Bending & Shear Coefficients for a/b = 1.5
Support Moment Coeff (Maximum) ax1 = 0.0232
Span Moment Coeff(Maximum) ax2 = 0.0089
Shear Coeff rx = 0.2503
Water Pressure / m pw = 63.00 kN/m
Soil Pressure ps = 17.00 kN/m
Width of Wall Considered b = 1000.00 mm
Support Moment (Maximum) Mx1w = 0.0232 x 63 x 1000^2 x 10^-6
= 1.46 kN-m
Mx1s = 0.0232 x 17 x 1000^2 x 10^-6
= 0.39 kN-m
Span Moment (Maximum) Mx2w = 0.0089 x 63 x 1000^2 x 10^-6
0.56 kN-m
Mx2s = 0.0089 x 17 x 1000^2 x 10^-6
= 0.15 kN-m
Shear Force Vxw = 0.2503 x 63 x 1000 x 10^-3
= 15.77 kN
Vxs = 0.2503 x 17 x 1000 x 10^-3
= 4.26 kN
A) RL+46.90 to RL+50.40
Inside Face & Outside Face-Support Moments
Max. Factored moment in Wall Mu =1.5 x 1.4616 = 2.19 kNm
Effective depth of the wall d = 494.0 mm
R = Mu/bd2
= (2.19 x10^6)/(1000 x494 x 494)
= 0.009
Pt =
f ck
2f y [
1 1
4 .598R
f ck ]
x 100 Pt = 0.002
R = Mu/bd2
= (0.84 x10^6)/(1000 x494 x 494)
= 0.003
Pt =
f ck
2f y [
1 1
4 .598R
f ck ]
x 100 Pt = 0.001
10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
Area of steel provided, Astprov. = 1005 mm SAFE
B) RL+50.40 to RL+55.20
Inside Face & Outside Face-Support Moments
Max. Factored moment in Wall Mu =1.5 x 1.4616 = 2.19 kNm
Effective depth of the wall d = 224.0 mm
R = Mu/bd2
= (2.19 x10^6)/(1000 x224 x 224)
= 0.044
Pt =
f ck
2f y [
1 1
4 .598R
f ck ]
x 100 Pt = 0.010
R = Mu/bd2
= (0.84 x10^6)/(1000 x224 x 224)
= 0.017
Pt =
f ck
2f y [
1 1
4 .598R
f ck ]
x 100 Pt = 0.004
A) RL+46.90 to RL+52.40
Maximum Shear force at the face of Wall @ Base = 215.59 kN
Factored Shear Force = 258.71 kN
Actual Shear stress = Vu / bd
Actual Shear stress t = 258.71 x 1000 / (1000 x495)
= 0.523 N/mm
% of reinforcement Provided = 0.634
Allowable shear stress = 0.55 N/mm SAFE
B) RL+53.20 to RL+55.20
Maximum Shear force at the face of Wall @ Top = 50.58 kN
Factored Shear Force = 60.70 kN
Actual Shear stress = Vu / bd
Actual Shear stress t = 60.7 x 1000 / (1000 x194)
= 0.313 N/mm
% of reinforcement Provided = 1.036
Allowable shear stress = 0.66 N/mm SAFE
10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
12 dia bar at 200 Spacing at junction of Wall & Grade Slab & at all other places as per Grade slab design
The internal wall design is same as the External wall; The reinforcment provided on the tank base inside face is provided
on the both faces of the inside wall assuming that one tank is always empty and the other one is full & vice-versa.
Similarly the reinforcment provided at outer face of wall at the span locations are provided on both faces of the inner wall
as one tank is always empty & other is fulle& vice-versa.Separate design for the wall is not provided
10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
The Wall behaves like a propped cantilever and the wall length (a) to height (b) ratio is more than 3 as per IS 3370 or
1.50 as per Moody's Chart. The predominant bending moment in wall is the vertical bending moment.
The Vertical bending moment is calculated in STAAD for the propped cantilever wall member .
The horizontal moment is calculated as per Moody's chart tables by limiting the a/b ratio to 1.5 along with the applicable
boundary conditons for the tank.
The reinforcement required for horizontal & vertical bending is verified against the minimum reinforcement criteria
as mentioned in code
Design Parameters :
Grade of concrete, fck = 30 N/mm2
Grade of steel, fy = 500 N/mm2
Parameters for RC wall design
Clear cover For Wall, Water Face = 45 mm
Soil face = 50 mm
Critical Case :-Tank Full Condition: - Soil Pressure below base slab (On one side) + Water Pressure on oneside (above base slab) +
Water Pressure & Soil Surcharge below base slab (both side)+ Dead Load & Live Load as applicable + SL
Bending Distance
Case
SF in the RC wall:
Shear force in the RC wall due to case 1 V1 = 87.614 kN
10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
Shear force in the RC wall due to case 4 V4 = 0.223 kN
Shear force in the RC wall due to case 6 V6 = 68.887 kN
Shear force in the RC wall due to case 3 V3 = 197.257 kN
Shear force in the RC wall due to case 2 V2 = 87.614 kN
Shear force in the RC wall due to case 7 V7 = 117.413 kN
A) RL+46.90 to RL+48.90
Provided thickness of wall = 450 mm
Maximum Bending Moment M = 176.78 kN.m/m
Factored Moment Mu = 1.2 x 176.776
= 212.13 kN.m/m
M = 0.133 x fck x b x d2
212.13 x 10^6 = 0.133 x 30 x 1000 x d^2
Required depth d = 230.58 mm
< 395 mm Hence Ok
B) RL+48.90 to RL+52.30
Provided thickness of wall = 450 mm
Maximum Bending Moment M = 122.41 kN.m/m
Factored Moment Mu = 1.2 x 122.408
= 146.89 kN.m/m
M = 0.133 x fck x b x d2
146.89 x 10^6 = 0.133 x 30 x 1000 x d^2
Required depth d = 191.87 mm
< 392 mm Hence Ok
C) RL+53.2 to RL+55.20
Provided thickness of wall = 450 mm
Maximum Bending Moment M = 107.53 kN.m/m
Factored Moment Mu = 1.2 x 107.531
= 129.04 kN.m/m
M = 0.133 x fck x b x d2
129.04 x 10^6 = 0.133 x 30 x 1000 x d^2
Required depth d = 179.83 mm
< 392 mm Hence Ok
Reinforment calculation
A) RL+46.90 to RL+50.40
Inside Face / Opposite Face
Max. Factored moment in Wall Mu =1.2 x 176.776 = 212.13 kNm
Effective depth of the wall d = 395.0 mm
R = Mu/bd2
= (212.13 x10^6)/(1000 x395 x 395)
= 1.4
Pt = 0.331
B) RL+50.40 to RL+52.30
Inside Face /Opposite Face
Max. Factored moment in Wall Mu =1.2 x 122.408 = 146.89 kNm
Effective depth of the wall d = 392.0 mm
10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
R = Mu/bd2
= (146.89 x10^6)/(1000 x392 x 392)
= 1.0
Pt = 0.228
C) RL+53.20 to RL+55.20
Inside Face / Opposite Face
Max. Factored moment in Wall Mu =1.2 x 107.531 = 129.04 kNm
Effective depth of the wall d = 392.0 mm
R = Mu/bd2
= (129.04 x10^6)/(1000 x392 x 392)
= 0.8
Pt = 0.200
Consider Figure 13 from Moody's Chart (Walls fixed along 3 edges & Hinged along one edge) for a/b ratio = 1.5
Horizontal Bending & Shear Coefficients for a/b = 1.5
Support Moment Coeff (Maximum) ax1 = 0.0232
Span Moment Coeff(Maximum) ax2 = 0.0089
Shear Coeff rx = 0.2503
Water Pressure / m pw = 63.00 kN/m
Soil Pressure ps = 17.00 kN/m
Width of Wall Considered b = 1000.00 mm
Support Moment (Maximum) Mx1w = 0.0232 x 63 x 1000^2 x 10^-6
= 1.46 kN-m
Mx1s = 0.0232 x 17 x 1000^2 x 10^-6
= 0.39 kN-m
Span Moment (Maximum) Mx2w = 0.0089 x 63 x 1000^2 x 10^-6
0.56 kN-m
Mx2s = 0.0089 x 17 x 1000^2 x 10^-6
= 0.15 kN-m
Shear Force Vxw = 0.2503 x 63 x 1000 x 10^-3
= 15.77 kN
Vxs = 0.2503 x 17 x 1000 x 10^-3
= 4.26 kN
A) RL+46.90 to RL+50.40
Inside Face & Opposite Face-Support Moments
Max. Factored moment in Wall Mu =1.5 x 1.4616 = 2.19 kNm
Effective depth of the wall d = 395.0 mm
R = Mu/bd2
= (2.19 x10^6)/(1000 x395 x 395)
= 0.014
Pt = 0.003
10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
Area of steel provided, Astprov. = 807 mm SAFE
R = Mu/bd2
= (0.84 x10^6)/(1000 x395 x 395)
= 0.005
Pt = 0.001
B) RL+50.40 to RL+55.20
Inside Face & Opposite Face-Support Moments
Max. Factored moment in Wall Mu =1.5 x 1.4616 = 2.19 kNm
Effective depth of the wall d = 392.0 mm
R = Mu/bd2
= (2.19 x10^6)/(1000 x392 x 392)
= 0.014
Pt = 0.003
R = Mu/bd2
= (0.84 x10^6)/(1000 x392 x 392)
= 0.005
Pt = 0.001
A) RL+46.90 to RL+52.40
Maximum Shear force at the face of Wall @ Base = 197.26 kN
Factored Shear Force = 236.71 kN
Actual Shear stress = Vu / bd
Actual Shear stress t = 236.71 x 1000 / (1000 x395)
= 0.599 N/mm
% of reinforcement Provided = 0.636
Allowable shear stress = 0.55 N/mm UNSAFE
Providing Additional Reinforcement to take care of Shear @ the junction of tank slab & Wall
10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
Area of steel provided, Astprov. = 628 mm
% of reinforcement Provided = 0.826
Allowable shear stress = 0.61 N/mm SAFE
B) RL+53.20 to RL+55.20
Maximum Shear force at the face of Wall @ Top = 68.89 kN
Factored Shear Force = 82.66 kN
Actual Shear stress = Vu / bd
Actual Shear stress t = 82.66 x 1000 / (1000 x392)
= 0.211 N/mm
% of reinforcement Provided = 0.410
Allowable shear stress = 0.46 N/mm SAFE
12 dia bar at 200 Spacing at junction of Wall & Grade Slab & at all other places as per Grade slab design
10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
The Wall behaves like a propped cantilever and it is always in contact with water on both sides. There is no predominant bending
moment for the wall in the horizontal and vertical direction & hence minimum reinforcment is provided on both faces as per IS 3370
Design Parameters :
Grade of concrete, fck = 30 N/mm2
Grade of steel, fy = 500 N/mm2
Parameters for RC wall design
Clear cover For Wall, Water Face = 45 mm
Soil face = 50 mm
Thickness ofWall = 200 mm
Critical Case :-Tank Full Condition or Tank Empty conditon Vertical Compression is the predominant governing Case
A) RL+48.90 to RL+55.20
Provided thickness of wall = 200 mm
Maximum Bending Moment M = 0.00 kN.m/m
Factored Moment Mu = 1.5 x 0
= 0.00 kN.m/m
M = 0.133 x fck x b x d2
0 x 10^6 = 0.133 x 30 x 1000 x d^2
Required depth d = 0.00 mm
< 150 mm Hence Ok
Reinforment calculation
A) RL+48.90 to RL+55.20
Inside Face / Opposite Face
Max. Factored moment in Wall Mu =1.5 x 0 = 0.00 kNm
Effective depth of the wall d = 150.0 mm
R = Mu/bd2
= (0 x10^6)/(1000 x150 x 150)
= 0.0
Pt = 0.000
10P107-C0004-015
45 MLD TTRO PROJECT KOYEMBEDU
------------------------------------------------------
CMWSSB Structural Design Calculation for
Treated Water Storage tank
Pump house (Vallam Vadagal)
Mx1s = 0 x 17 x 1000^2 x 10^-6
= 0.00 kN-m
Span Moment (Maximum) Mx2w = 0 x 63 x 1000^2 x 10^-6
0.00 kN-m
Mx2s = 0 x 17 x 1000^2 x 10^-6
= 0.00 kN-m
Shear Force Vxw = 0 x 63 x 1000 x 10^-3
= 0.00 kN
Vxs = 0 x 17 x 1000 x 10^-3
= 0.00 kN
A) RL+48.90 to RL+55.20
Inside Face & Opposite Face-Support Moments
Max. Factored moment in Wall Mu =1.5 x 0 = 0.00 kNm
Effective depth of the wall d = 150.0 mm
R = Mu/bd2
= (0 x10^6)/(1000 x150 x 150)
= 0.000
Pt = 0.000
R = Mu/bd2
= (0 x10^6)/(1000 x150 x 150)
= 0.000
Pt = 0.000
A) RL+48.90 to RL+55.20
Maximum Shear force at the face of Wall @ Base = 0.00 kN
Factored Shear Force = 0.00 kN
Actual Shear stress = Vu / bd
Actual Shear stress t = 0 x 1000 / (1000 x150)
= 0.000 N/mm
% of reinforcement Provided = 0.262
Allowable shear stress = 0.38 N/mm SAFE
10P107-C0004-015
BHEL - 1500 MW CCPP, PRAGATI - III PE-DC-314-654-C006
Design of Raw water Reservoir C.4
Raw water reservoir compartment wall is analysed and designed for the water pressure at the critical
condition of one compartment full of water and ther compartment is empty.
EL(+)2.000M
Max. Water Lvl [ EL(+) 1.500m ]
#REF! #REF!
RESERVOIR w8c RESERVOIR
COMPARTMENT -1
w1 #REF! COMPARTMENT -2
EL(+)0.500M
#REF! #REF!
#REF!
w2 w8b #REF!
EL(-)1.000M
#REF!
#REF!
P4
Grade slab w3 w8a
#REF! #REF!
EL(-) 4.000M
Base Raft p p4
300 Heel Heel 4
EL(-) 5.000M w4
Grade slab
O
1 2
#REF!
1. a. Load Calculation:
Vertical Loads:
file:///conversion/tmp/scratch/364241414.xls 08/27/2017
BHEL - 1500 MW CCPP, PRAGATI - III PE-DC-314-654-C006
Design of Raw water Reservoir C.5
Lateral Loads:
Distance
from origin Moment
Sl. No. Description Force (kN) 'O' (m) (kNm)
1 W1 #REF! #REF! #REF!
2 W2 #REF! #REF! #REF!
3 W3 #REF! #REF! #REF!
4 W4 #REF! #REF! #REF!
5 W8a #REF! #REF! #REF!
6 W8b #REF! #REF! #REF!
7 W8c #REF! #REF! #REF!
8 P4 #REF! #REF! #REF!
Eccentercity = #REF! m
file:///conversion/tmp/scratch/364241414.xls 08/27/2017
BHEL - 1500 MW CCPP, PRAGATI - III PE-DC-314-654-C006
Design of Raw water Reservoir C.6
#REF!
#REF!
m #REF!
m #REF! m
Overturning moments,
Moment due to lateral water pressure
#REF! = #REF! kNm
Total overturning moment, Mo
Restoring moments, Mr
#REF!
#REF! = #REF! kNm
= #REF!
#REF!
file:///conversion/tmp/scratch/364241414.xls 08/27/2017
BHEL - 1500 MW CCPP, PRAGATI - III PE-DC-314-654-C006
Design of Raw water Reservoir C.7
= #REF!
file:///conversion/tmp/scratch/364241414.xls 08/27/2017
BHEL - 1500 MW CCPP, PRAGATI - III PE-DC-314-654-C006
Design of Raw water Reservoir C.8
= #REF!
= #REF! mm
Provided depth of the base raft = 300 mm
Check for base raft thickness = #REF!
file:///conversion/tmp/scratch/364241414.xls 08/27/2017
BHEL - 1500 MW CCPP, PRAGATI - III PE-DC-314-654-C006
Design of Raw water Reservoir C.9
= #REF!
190 x 0.89 x 240
Area of steel reqd. for BM , AstBM = #REF! mm2
Hence Area of steel required, Astreqd. = #REF! mm2
Area of steel provided, Astprov. = 1570.80 mm2
Check for base raft (at toe side) Reinforcement = #REF!
Provide reinforcement as 20 @ 200 c/cBoth ways
#REF!
190 x 0.89 x 240
Area of steel reqd. for BM at the heel side, AstBM = #REF! mm2
Hence Area of steel required, Astreqd. = #REF! mm2
Area of steel provided, Astprov. = 1570.80 mm2
Check for base raft (at heel side) Reinforcement = #REF!
Provide reinforcement as 20 @ 200 Both ways
= #REF!
1000 x 0.89 x 240
#REF! N/mm
file:///conversion/tmp/scratch/364241414.xls 08/27/2017
BHEL - 1500 MW CCPP, PRAGATI - III PE-DC-314-654-C006
Design of Raw water Reservoir C.10
3. DESIGN OF WALL:
Shear Forces in the retaining wall for the lateral forces in shown in 1.a,
At EL(-) 4.000m = #REF! kN
file:///conversion/tmp/scratch/364241414.xls 08/27/2017
BHEL - 1500 MW CCPP, PRAGATI - III PE-DC-314-654-C006
Design of Raw water Reservoir C.11
file:///conversion/tmp/scratch/364241414.xls 08/27/2017
BHEL - 1500 MW CCPP, PRAGATI - III PE-DC-314-654-C006
Design of Raw water Reservoir C.12
file:///conversion/tmp/scratch/364241414.xls 08/27/2017
BHEL - 1500 MW CCPP, PRAGATI - III PE-DC-314-654-C006
Design of Raw water Reservoir C.13
file:///conversion/tmp/scratch/364241414.xls 08/27/2017
BHEL - 1500 MW CCPP, PRAGATI - III PE-DC-314-654-C006
Design of Raw water Reservoir C.14
5. Reinforcement Summary