Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
AN
INDUSTRIAL TRAINING REPORT
ON
SWITCHYARD & GENERATOR PROTECTION SYSTEM
AT
Dr. SK GOEL
(HOD,EN Dept.)
INTRODUCTION
Indian PSU Public Sector Undertaking, engaged in the business of generation of electricity and
allied activities.The total installed capacity of the company is 45548 MW (including JVs) with
own 18 coal-based and 7 gas-based stations and 6 coal based and 1 gas based in JV/ Subsidiary
NTPC VISION
To be the worlds largest and best power producer, powering Indias growth.
NTPC MISSION
Develop and provide reliable power, related products and services at competitive prices,
integrating multiple energy sources with innovative and eco-friendly technologies and
contribute to society.
National Capital Power Station (NCPS) Or NTPC Dadri, is the power project to meet the power
demand of National Capital Region (India). It has a huge coal-fired thermal power plant and a
gas-fired plant and has a small solar power plant. It is located in Gautam Budh Nagar district of
Uttar Pradesh about 25 km from Ghaziabad and about 9 km from Dadri. It is nearly 48 km from
New Delhi towards Hapur. NTPC Dadri is a branch of National Thermal Power Corporation,
It is a switching station establishing main link between generating station and transmission
system. It influences the security of power supply. It steps up or steps down the voltage levels
depending on the network node. It switches ON or OFF the reactive power control devices which
Current transformers
Potential transformers
Interconnecting transformers(ICT)
Isolators
Circuit breakers
Supports
Earthing switches
Lightening arresters
Wave traps
Protection logics.
Potential transformers
Interconnecting transformers(ICT)
Circuit breakers : Makes or automatically breaks the electrical circuits under Loaded
condition.
charge to
Lightning arrestors : Safe guards the equipment by discharging the high currents due
to Lightning. Lightening arresters are provided at the terminals of the transformers for
protection against lightening or any surges developing in the system. The practice is
Overhead earth wire : Protects the Over Head transmission line from Lightning
strokes.
telemetering.
Reactive Power control devices : Controls the reactive power imbalance in the grid by
Current Limiting Reactors : Limits the Short circuit currents in case of faulty
conditions.
Capacitor voltage transformers (CVTS): The "Capacitor voltage transformers
(CVTS)" are used at 220 KV and above. For the lower voltages, electro-magnetic type
power form generating stations to the load centers. The important components of the
carries double the power than that of a single circuit line. The conductors
used for the transmission lines are aluminum conductors steel reinforced
normally of bolted steel lattice type. Angle sections are bolted together to
form a square base lattice structure. The structures are provided with cross
arms through which insulator strings are hung for supporting the
conductors.
lines 5 to 6 discs insulator are used for 132 KV lines, 9 to 10 and for 220
the transmission line against lightning strikes. These wires are supported
400KV lines, 2 ground wires are used with reduced shield angle of 20.
These earth wires are of galvanized stranded steel, high tensile steel
quality. Earth wire is connected to the tower steel. The tower footings are
U = 5.5(0.62 L + 3P/100)
Where,
P=Power to be transmitted in KW
Figure:1 Switchyard showing PLCC insulators and Circuit Breaker
Figure:2 Single Line Diagram showing stage-II Power Transmission
There are two main buses and one transfer bus for changeover of bus. The Main Bus as well as
Transfer Bus is of 400KV. The generator Transformer steps up the voltage from 20KV to
Figure-3 Details of line showing the transmission of power from NTPC Dadri to different places.
A generator is a device that converts mechanical energy to electrical energy for use in an
external circuit. The source of mechanical energy may vary widely from a hand crank to
an internal combustion engine. Generators provide nearly all of the power for electric power
grids.
Water cooled
Air cooled
Hydrogen cooled
Stator-stator frame
End Shield
stator Winding Assembly - Stator Winding , Winding Assembly, Connecting Bus bar
Rotor - Rotor Shaft, Rotor Wedges, Rotor Coils, Wound Rotor, Rotor Assembly
Completing Assembly - Bearing Assembly, Shaft Seal Assembly, Oil Catchers, Insert
Cover etc
Exciter
Auxiliary System
Manufacturer BHEL
Rated Maximum Output 577 KVA
Power Factor 0.85 Lagging
Power Output rating 490MW
Stator Voltage 21 KV
Stator Current 15800 Amp
Rotor Voltage 334 V
Rotor Current 3973 Amp
RPM 3000
Frequency 50 Hz
Connection Y-Y
Phase 3
Coolant Water & Hydrogen
Manufacturer BHEL
Rated Maximum Output 247 KVA
Power Factor 0.85 Lagging
Power Output rating 210 MW
Stator Voltage 16.5 KV
Stator Current 8645 Amp
Rotor Voltage 355 V
Rotor Current 3000 Amp
RPM 3000
Frequency 50 Hz
Connection Y-Y
Phase 3
Coolant Water & Hydrogen
The modern generators are generally provided with the following protections:
1. Over load protection: This protection is provided to safeguard the generator from rise in
temperature in the stator winding due to overload. This protection initiates an alarm to
guide the operator for reducing the load. If overload is accompanied by under voltage,
2. Negative sequence current protection: Negative phase sequence currents will flow
through the generator for phase-to-phase faults, during asymmetrical loading, due to open
3. Unit differential protection: This protection is intended to safeguard the generator against
phase to phase fault or three phase short circuits in the windings; or inter connected bus
ducts between the generator and generator transformer; or the transformer against phase
to phase fault in primary, or phase to earth fault in the secondary side up to the protected
generator to run as an induction generator. Generally all the generators shall be designed
to run as induction generator with a reduced load for a short period but the rotor will get
over-heated from the induced current flowing in the rotor iron particularly at the retaining
prohibited. Further when generator runs as an induction generator it draws the reactive
power from the grid and there may be a voltage dips in the system, which is not desirable
5. Reverse Power Protection: When the input to the prime mover suddenly goes off and the
generator is in service delivering power to the system, the machine will not cease to
function, but would continue to rotate at the same speed; now as motor deriving the
requisite energy from the system to keep the frictional and windage losses Both the
direction and magnitude of the active power between the system and the machine
therefore changes, while the reactive or watt less power controlled by the field excitation
remains unaltered. Although this abnormal condition would not harm the generator, it
could, however damage the prime mover. It has been the general practice to provide
protection against any such contingencies, by thermal or mechanical devices in the form
6. Over voltage and over fluxing protection: The generator can develop dangerously high
voltages in the event of mal-operation of AVR or a load throws off while generator
is at lower speed. Its persistence can cause gradual overheating and damage to the
provided for the backup protection of generator against external three phase and phase to
phase faults in the 400/220 KV system which may be hanging on due to failure of this
own system primary protection. The zone of 216 should be extended beyond 400 KV/220
KV switchyard as far as possible and it should be connected to trip the generator after a
time delay of 1 to 1.5 seconds so that the generator is tripped only when 400 KV/220 KV
protections has not cleared the faults even in the second zone.
Seal oil system: Generator shaft seals are supplied with pressurized seat oil to prevent
hydrogen losses at the shaft and ingress of air into the generator. During normal
operation, shaft seals are supplied with seal oil by a separate system, consisting of
hydrogen side seal oil circuit and air side seal oil circuit. The oil used in seal oil circuit is
same as that used in turbine generator journal bearings. During normal operation, in the
air side AC pump draws seal oil from the seal oil storage tank and feeds it to the seals via
cooler and filters which drains towards the air side and return back to the seal oil storage
tank. Similarly H2 side oil pump supplies oil to seal through a separate strainer and
cooler. By dividing the seal oil system into two separate circuits, hydrogen losses at the
seals are kept to a minimum and good hydrogen purity is also maintained. For the air side
seal oil circuit three seal oil pumps are provided. In the event of failure of one AC pump
the second AC pumps automatically takes over. If both pumps fail the seal oil supply is
taken over by the standby D.C. pump. On the other hand one seal oil pump is used for oil
circulation in H2 side seal oil circuit. In the event of failure of this pump, seal oil in
hydrogen side is derived from air side seal oil circuit. Prolonged operation in this fashion
Primary water system: When the turbine generator is on load heat produced in the stator
through hollow conductors of the stator windings and passage ways within the terminals.
The losses occurring in the generator stator winding components e.g. Stator winding,
terminal bushings and phase connectors are dissipated directly through water. The
cooling water being in contact with the high voltage winding must have an electrical
conductivity of the order of 0.5 to 1 micro mho/cm. Primary water supply system
2X100% duty pump through a strainer type filter with magnet bar and cooler. The
primary water is drawn from the primary water tank and passes to a primary water
manifold (inlet) via coolers and filters and from there to stator bars via Teflon hoses. The
primary water leaving the stator winding is passed through similar Teflon hoses to anther
primary water manifold (outlet) and is then returned to the primary water tank. A separate
flow path from a point before the stator winding inlet cools the bushings and phase
connectors.
multi-stage axial fan located at the turbine end. The fan draws hot gas from the air gap
and delivers it to the coolers where it is cooled and re-circulated. Gas system comprises
of the following components. As a precaution against explosion hazard, the air must
neither be directly replaced with hydrogen during generate- filling nor the hydrogen
directly replaced with air driving emptying operation. In both the cases CO2 is used for
scavenging.