Sei sulla pagina 1di 16

Performance of Concrete

Members Subjected to Large


Hydrocarbon Pool Fires
Renata I. Zwiers, PhD
Senior Research Engineer
Fire!Thermal Technology Section
Construction Technology
Laboratories, Inc.
Skokie, Illinois

Bruce J. Morgan, PhD


Principal Engineer
Structural Evakuation
and Analysis Section
Construction Technology
Laboratories, Ina.
Skokie, Illinois

he performance of structural rnem- exposed to the standard ASTM Desig-


T bers and assemblies exposed to fire nation: E119 building fire and when
conditions resulting from large, outdoor, they are exposed to a hydrocarbon pool
free burning, fluid hydrocarbon fueled fire. The hydrocarbon pool fire selected
pool fires is of concern in the design of for this analysis is defined in ASTM
Hydrocarbon Processing Industry (HP!) Designation: E5 P191, "Proposed Test
facilities and other facilities where this Methods for Determining Effects of
type of fire can occur. Fire resistance Large Hydrocarbon Pool Fires on
ratings for most structural concrete Structural Members and Assemblies."a
components have been determined in Significant differences that exist be-
accordance with ASTM Designation: tween the two fire models can be iden-
E119, "Standard Methods of Fire Tests tified as follows:
of Building Construction and Mate- Higher temperature of the hydro-
rials." i However, since outdoor hydro- carbon pool fire during the first 2 hours.
carbon pool fires are significantly differ- Requirement for hot moving gases
ent than building fires, special hydro- in the hydrocarbon pool fire model as
carbon pool fire models and associated compared to no such requirement in the
test procedures have been developed. standard building fire model.
In this paper, a comparative evalua- Total flame engulfment (bottom,
tion is made on the performance of con- sides and top) of beams in the hydrocar-
crete beams and columns when they are bon pool fire test as compared to the

120
SUMMARY
The purpose of this investigation was to exist in hydrocarbon pool fires.
determine analytically if the performance 2. Temperatures in the cross sections
of concrete beams and columns in a due to the hydrocarbon pool test fire were
hydrocarbon pool test fire would differ sig- about 10 to 25 minutes ahead of those due
nificantly from their performance in a stan- to the standard test fire. Differences were
dard test fire. The investigation consisted greatest during the first hour at points near
of a finite element analysis to obtain the surface.
temperature distributions in typical cross 3. The nominal moment strength of a
sections, a comparison of the resulting beam section (calculated at 1.2 and 3 hour
temperature distribution in the cross sec- exposures) was reduced only an additional
tion, and a strength analysis of a beam 5 to 12 percent of original strength when
based on temperature distribution data. the beams were exposed to the hydrocar-
The following three findings are based bon pool fire rather than the standard test
on the results of the investigation: fire. Most of this difference in strength
1. In contrast to other structural compo- capacity was because the beam was ex-
nents with sprayed-on or lightly attached posed on four sides (top, bottom and
insulation, concrete has a very good re- sides) in the hydrocarbon pool fire, while
sistance to the erosive and abrasive ef- only the bottom and sides of the beam
fects of hot moving gases which typically were exposed in the standard test fire.

typical three-sided exposure (bottom component to the standard fire until it


and sides) of beams in the standard can no longer support its load.
building fire test. To analytically determine the fire en-
These differences are discussed in durance of a component based on
more detail in a later section. The pur- strength criteria, temperature distribu-
pose of this paper is to determine tion in a cross section can be obtained
analytically whether these differences from a finite element analysis. These
significantly affect the fire endurance of data can then be used to calculate the
concrete components typically used in strength of the component at selected
HPI facilities. times, The procedure for strength
calculations is outlined in Refs. 3, 4 and
5. Presently, strength analysis guide-
lines in the cited publications are lim-
BACKGROUND
ited to analysis of beams and slabs. No
Experimental and Analytical analytical procedures are outlined for
Methods for Determining Fire evaluating column strength in a fire.
However, as in the analysis of beam and
Endurance of Concrete Structural
slab strength, these latter strengths will
Components
to a large degree depend on the temper-
A typical pipe rack found in HPI ature distribution in the columns,
facilities is shown in Fig. 1. It consists Therefore, in addition to a strength
of beams, columns and struts. A stan- analysis of a beam section, this investi-
dard ASTM Designation: E119 fire test gation includes a comparison of temper-
would involve loading a structural com- ature distributions in beam and column
ponent (beam or column) to its full de- cross sections resulting from exposure to
sign load and then exposing the loaded the two different fires.

PCI JOURNALUanuary-February 1989 121


Expansion Joint

Concrete
te
Struts

Precast
Concrete
Columns

(a) Side view

Expansion Jolnl
Precast Concrero Struts

Precast Concrete Booms


Precast Concrete Columns

(b) Plan view

Fig. 1. HPI pipe rack assembly.

Comparison of the Standard


fire and movement of combustion prod-
Building Fire and the Selected
ucts away from the fire. Such constraints
Hydrocarbon Pool Fire on circulation do not typically exist in
A typical oil pool fire will have HPI facilities.
higher initial temperatures and greater The standard furnace time-tempera-
heat fluxes than those associated with ture curve for a building fire is shown in
the standard building fire. The differ- Fig. 2. 1 Unlike the standard building
ence in temperatures is due to the dif- fire, the selected hydrocarbon pool fire
ference in the nature of the fuel found in model does not specify a furnace time-
buildings and HPI facilities, while the temperature relation.' Instead, the E5
difference in heat flux is a result of vary P191 Fire Test specifies that a heat flux
-ingcostra ulionfar.F of 55,000 Btu/ft2/hr be incident upon a
example, in a building fire, the primary test specimen within 5 minutes of test
source of air movement is through doors initiation. The heat flux is required to
and windows. This results in significant consist of both radiative and convective
constraints on the movement of air to the components with approximately a ten to

122
2000

1500

Exposure
Temperature, 1000
'F

500

0 05 1 1.5 2 2.5 3
Time, hrs

Fig. 2. Furnace time-temperature curves.

one radiative to convective heat flux rial. However, while this may be signifi-
ratio. As noted in Ref 2, an enclosed cant for members with certain
furnace with optically opaque walls at sprayed-on or lightly attached insula-
1865F, containing optically transparent tion, it should not be a factor in the fire
gases at 1865F, generates the required resistance of components fabricated
radiative heat flux of approximately from materials with good high temper-
50,000 Btu/ft2/hr. ature resistance to surface erosion and
Based on these data, a furnace time- abrasion such as concrete. Therefore,
temperature curve for the radiative this latter effect is not modeled in the
component of a hydrocarbon pool fire current analysis,
can be developed. This resulting time-
temperature curve is also shown in Fig.
2. The convective heat flux component Flame Engulfment
of 5000 Btu/tt2/hr needed to meet the To simulate actual construction con-
55,000 Btu/(t 2llir total heat flux require- ditions in a building, ASTM Designa-
ment would come about from engulfing tion: E119 requires that columns under-
the test object with the 1865F gas going a fire test be exposed on all four
moving at approximately 33 ft/sec. sides, while beams be exposed on three
The circulating hot gases in a hydro- sides. In buildings, beams generally
carbon pool fire can affect the fire resis- support floor or ceiling assemblies that
tance of a structural component in two protect the beam from complete expo-
ways. First, they will affect the temper- sure. However, in HPI pipe rack as-
ature distribution within the component semblies both beams and columns can
due to the additional heat flux generated be exposed to the fire from all sides.
by the hot gases. The resulting higher This is reflected in ASTM Designation:
cross-sectional temperatures can be E5 P191 guidelines which require that
determined using a finite element both beams and columns be exposed to
analysis. The other possible effect of furnace temperatures on all tour sides.
moving gases is erosion of surface mate- Figs. 3a and 3b show how tempera-

PCI JOURNAL/January-February 1989 123


Isothermal
Line

T1
T2
T3
Ta
Ts Reinforcing
Steel

(a) Total flame engulfment

Isothermal
Line

T
T2
T3
4
rs .Reinforcing
Steel

(b) Exposure on three sides

"T il T 2 T T 4 . T 5 are temperatures, where T1<T2<T3<T4<T5

Fig. 3. Typical temperature distribution in beam cross section.

tune distributions within a beam cross nation: E5 P191. For a comparative


section would differ as a result of the evaluation of these two cases, simply
two types of exposures. For a given examining temperature distributions
time, temperatures at the top of the may not he sufficient. Strength calcula-
beam tested according to ASTM Desig- tions should be carried out to determine
nation: E119 would be significantly if changes in the concrete temperature
lower than temperatures at the top of the of the compression block significantly
beam tested according to ASTM Desig- affect beam performance.

124
24"
20"

16"

24'
20.
7 6'

18"

24'
20"

Fig, 4, Selected column and beam cross sections.

THE FINITE ELEMENT ties of 145 and 110 pcf, respectively,


MODEL were used.
The furnace time-temperature rela-
Three column and two beam cross tions used in the analysis are shown in
sections were selected for analysis using Fig. 2. The TASEF computer program is
the TASEF (Temperature Analysis of capable of simulating both radiative and
Structures Exposed to Fire) 6 digital convective heat flux inputs. The hy-
computer program. The selected col- drocarbon pool fire model included a
umn cross sections were 16 x 16, convective heat transfer coefficient of
20 x 20, and 24 x 24 in. The beam cross 2.4 Btu/ft2fhr/F so that the convective
sections were 12 x 20 and 18 x 24 in. heat flux incident on the cross section
The column and beam cross sections would be the approximately 5000 Btu/
selected for the analysis are shown in ft2/hr needed to generate the required
Fig. 4. Concrete thermal properties total heat flux of 55,000 Btu/ft21hr.
were based on Refs. 6, 7, 8, 9 and 10. The cross sections of components that
The properties from these references are totally engulfed in the fire are dou-
were refined based on calibration bly symmetric. Therefore, only one
TASEF computer runs of beam and col- quarter of each cross section was mod-
uwnn cross sections using experimental eled. For analysis of a beam exposed to
temperature distribution data for com- fire on three sides, the same quarter
parison. Both normal weight and struc- section model was used. However, data
tural lightweight concretes with densi- were extrapolated as shown in Fig. 5.

PCI JOURNAUJanuary-February 1989 125


r............................................._.......^

............................................^ f

^...._....._
- ^-'- -^
Extrapolated
Distribution

1
LEJJH Calculated
:..,. J I Temperature
Distribution

(a) Exposure on four sides

i E

I
Extrapolated
Distribution

E ^

Calculate
Temperature
Distribution

b __...._......_...-.-.- .....

(b) Exposure on three sides

Fig. 5. Finite element model and extrapolation of data.

The smallest cross section was modeled the two fires in Figs. 6 through 13. Data
with 140 elements while the largest are presented fin points 1, 2, 3 and 4 in.
cross section was modeled with 225 from the exposed surface in both normal
elements, Localized material failures weight and lightweight aggregate con-
that might occur during an actual expo- crete components. Calculations indi-
sure, such as cracking or spalling, were cated that the temperatures depended
not modeled. primarily on the distance from the ex-
posed surface rather than on specimen
dimensions. Therefore, curves in Figs. 6
RESULTS OF through 13 are representative of tem-
TEMPERATURE ANALYSIS perature distributions for any of the
cross sections shown in Fig. 4.
Time-temperature data obtained from Table 1 lists the maximum tempera-
the finite element analysis are shown for ture difference occurring at each of the

126
Table 1. Maximum temperature differences at selected points.
Temperature at time of
maximum difference, 'F
Distance Time of maximum Time
from Type of temperature difference E E5 P191 delay,
surface, in. concrete hours : minutes fire fire Difference minutes*
weight 0;15 439 815 376 15
1 Lightweight 0:15 383 624 241 10
Normal weight 0:30 393 554 161 15
2 Lightweight 0:30 226 361 135 10
Normal weight 0:45 306 404 98 10
3 Lightweight 1:00 231 318 87 10
Normal weight 1:00 225 302 77 10
4 Lightweight 1:45 267 311 44 10
'Additional time needed for temperature in Column 4 of table to reach temperature in Column 5 oftable.
11ote: 1 in. _ 25.4 mm; tc = (t F 31)!1.8,

four points during the 3 hour exposure 815F temperature 30 minutes after the
period. It also shows the time at which start of the fire (Fig. 6). The temperature
this maximum difference occurred. For rise at 1 in. from the surface due to the
points 1, 2, 3 and 4 in. from the surface standard building fire is then about 15
in normal weight aggregate concrete, minutes slower than the temperature
the maximum temperature difference rise at 1 in. from the surface due to the
occurred during the first hour of the test, hydrocarbon pool fire.
This was also the case for points 1, 2 Temperature rise delays for points 1, 2,
and 3 in. from the surface in lightweight 3 and 4 in. from the surface are listed in
aggregate concrete. For the point 4 in. Table I for times at which the maximum
from the surface in lightweight aggre- temperature difference occurs. Informa-
gate concrete the maximum temperature tion about temperature rise delays at
difference occurred during the second other times can be obtained from Figs. 6
hour of the test. However, the mag- through 13. For points 1 in. from the sur-
nitude of this latter maximum tempera- face, the temperature rise delays ranged
ture difference was only 44F. from about 10 to 25 minutes. For points 2
Table 1 also lists the additional time in. or more from the surface, the temper-
required for a point in a component ex- ature rise delays ranged from about 10 to
posed to the standard building fire to 15 minutes.
reach the temperature existing at the
same point in a component exposed to
the hydrocarbon pool fire. For example, ANALYSIS OF BEAM
for a point I in. from the surface in a STRENGTH
normal weight aggregate concrete com-
ponent, the maximum temperature dif- The strength of the heath cross section
ference due to the two fires occurs at 15 shown in Fig. 14 was analyzed for 1, 2
minutes. At that time, the temperature and 3 hour exposures to both the stan-
in the component exposed to the hydro- dard building fire and the hydrocarbon
carbon pool fire is 815F. When the pool fire. Normal weight as well as
component is exposed to the standard lightweight concretes were modeled.
building fire, the same point reaches the Strength calculations followed standard

PCI JOURNALIJanuary-February 1989 127


1700

1500
E5
1300

1100

T F 900

700

500

300

100
0:00 0:30 1:00 1:30 2:00 2:3(
Time, hrmin

Fig. 6. Temperature 1 in, from the surface in a normal weight concrete section.

1700

1500

1300

1100

Temp 900 G

700

500

300

100
0:00 0:30 1:00 1:30 2:00 2:30 3:00 1
Time, hrmin

Fig. 7. Temperature 2 in. from the surface in a normal weight concrete section.

procedures outlined for simple sup- perature relation for hot rolled steel
ported beams exposed to high temper- shown in Ref. 3. For a steel temperature
atures. 3 s Calculations for a 2 hour ex- of 930F, the steel strength is about 69
posure of a normal weight concrete percent of room temperature strength,
beam are shown in Table 2 and are while for a temperature of 1000F, the
briefly outlined in the following para- steel strength is about 64 percent of
graphs. Similar calculations were car- room temperature strength. As a result,
ried out for other cases. steel strengths for a 2 hour exposure to
Temperatures at steel locations were the standard building fire and to the
obtained from the finite element hydrocarbon pool fire are 41.4 and 38.4
analysis. Tensile strength of the steel ksi, respectively.
was calculated using the strength/tern- Compressive strength of the concrete

128
1

0:00 0:30 1:00 1:30 2:00 2:30 3:00


Time, hrmin

Fig. 8. Temperature 3 in. from the surface in a normal weight concrete section.

0:00 0:30 1:00 1:30 2:00 2:3C 3:00


Time, hr:min

Fig. 9. Temperature 4 in. from the surface in a normal weight concrete section.

was calculated using the strengthitem- Calculations using the carbonate aggre-
perature relation in Ref. 3. Actually, two gate model would result in somewhat
strength/temperature curves are pre- higher beam strengths.
sented in Ref. 3 for normal weight con- Information about concrete strength
crete. One curve is for siliceous aggre- in Ref. 3 is provided up to 1400F. At
gate concrete while the other is for car- higher temperatures, concrete strength
bonate aggregate concrete. The carbo- decreases rapidly. As a result, concrete
nate aggregate concrete has a signifi- at temperatures greater than 1400F is
cantly higher resistance to high teniper- generally disregarded. This is accom-
atures than the siliceous aggregate con- plished by modifying cross section di-
crete. For the analysis in this paper, the mensions. Fig. 15 shows the reduced
siliceous aggregate model was used. width, b, and reduced distance, d, used

PCI JOURNAUJanuary-February 1989 129


1700

1500

1300
E
1100

900

700

500

300

100
0:00 0:30 1:00 1:30 2:00 2:30 3:00
Time, hr:min

Fig. 10. Temperature 1 in. from the surface in a lightweight concrete section.

1700

1500
1300
1100

Ten 900
700
500
300

100
0:00 0:30 1:00 1:30 2:00 2:30 3:00
Time, hr:min
Fig. 11. Temperature 2 in. from the surface in a lightweight concrete section.

to calculate the reduced moment the standard building fire and 868F for
strengths. the beam exposed to the hydrocarbon
To determine an average concrete pool fire).
strength, a concrete temperature was Tables 3 and 4 summarize the results
calculated for the compressive block of of strength calculations for 1, 2 and 3
the modified section by averaging the hour exposure cases analyzed. De-
top and bottom temperature of the com- pending on type of concrete and expo-
pressive block. The percent of remain- sure period, the calculated strength after
ing concrete strength was then obtained exposure to the hydrocarbon pool fire
from Ref. 3 based on this average tem- was 15 to 37 ft-kips less than the calcu-
perature (842F for the beam exposed to lated strength after exposure to the stan-

130
II

0:00 0:30 1:00 1:30 2:00 2:30 3:00


Time, hrmin
Fig. 12. Temperature 3 in. from the surface in a lightweight concrete section.

1700

1500

1300

1100

Tm 900

700

500

300

100
0:00 0:30 1:00 1:30 2:00 2:30 3:00
Time, hr:min

Fig. 13. Temperature 4 in. from the surface in a lightweight concrete section.

dard building fire. This represents an are listed in Table 5. Average concrete
additional reduction of 5 to 12 percent of strength, f,, was not significantly af-
original beam strength due to the hydro- fected by the type of fire, while steel
carbon pool fire. The strength of the strength, f,,, and effective beam widths,
lightweight concrete beam was less af- b, were somewhat affected. Tn general,
fected by the type of fire than the silice- the most significant factor for the re-
ous aggregate concrete beam. Differ- duced beam strength in the hydrocar-
ences were smallest during the first bon pool fire appeared to be the re-
hour of exposure. duced distance, d, resulting from a four-
Concrete strength, steel strength, and sided rather than a three-sided ex-
b and d values used in the calculations posure.

PCI JOURNAL/January-February 1989 131


Table 2. Strength calculations for beam cross sections (normal weight concrete,
2 hour exposure).
Standard Hydrocarbon
Parameter building fire pool fire
Steel temperature (F) 928F 1009F

Steel strength (ksi) (0.69)(60) = 41.4 ksi (0.64)(60) = 38.4 ksi

Average concrete 259 + 1425= 366 +1399 = 8b8F


temperature (F) 2 842F 2

Average concrete
strength (ksi) (0.95) 4 = 3.8 ksi (0.95)(4) = 3.8 ksi

d (in.) 17.5 in. 16 in.

b (in.) 9.5 in. 9 in.

(4)(41.4) = 5.4 in. (4)(38.4) = 5.3 in.


a = `9f" (in.)
0.85ffb (0.85}(3.8)(9.5) (0.85)(3.8)(9)

M . = A Jv [ ct - 2 `
(4X41.4)[ 17.5- 24] (4)(18.4) r 16_-]
53

(ft-kips) J = 204 ft -kips = 171 ft-kips


tiutc: l in. - 15.4 loin; I k.vi = 6.895 MPa; 1 it-kip = 1356 N-m; tc = (tr - 32)/1.8.

17.5'

0 0 0 0 2.5"
As=4.Dsq In.
tY = 60 ksi
f^ = 4 ksi
M n = 291 ft kips
(at room temp)

Fig. 14. Beam cross section for strength analysis.

132
Concrete reaching
temperatures
greater than 1400 F

16- (d) 17.5 (d1

f" 7
(a) Hydrocarbon pool fire (b) Standard building fire

Fig. 15. Modified beam cross sections (normal weight concrete at 2 hours).

Table 3. Strength of siliceous concrete beam.

Strength in Strength in hydro-


Fire exposure standard fire carbon pool fire Difference,
period, hours test, ft-kips test, ft-kips ft-kips
1 242 217 25
2 204 171 33
3 135 9R 37
Note: 1 ft-kip = 1356 .\-in.

Table 4. Strength of lightweight concrete beam.

Strength in Strength in
Fire exposure standard fire hydrocarbon pool Difference,
period, hours test, ft -kips fire test, it-kips ft -kips

1 244 229 15
2 225 199 26
3 202 169 33
\ otc: I ft-kip = 1356 N-m.

CONCLUSIONS moving gases, the effect of initial higher


temperatures, and the effect of total
Three significant differences between flame engulfment.
the standard test fire model and the se- Typical concrete column and beam
lected hydrocarbon pool test fire model sections were evaluated analytically to
were identified as the effect of hot determine if differences in the test fires

PCJ JOURNAUJanuary-February 1989 133


Table 5. Strength parameter values.

Parameter valve
Fire exposure Building Hydrocarbon
Type of concrete period, hours Parameter fire pool fire
f, ksi 4 4
1 f,, ksi 49.2 47.4
b, in. 10.5 10.0
d, in. 17.5 16.5
ff,ksi 3.8 3.8
Siliceous 2 f, ksi 41.4 38.4
9.0
aggregate h, in. 9.5
d, in. 17.5 16.0
f,, ksi 3.4 3.4
3 f,,, ksi 26.4 21.6
b, in. 8.5 8.0
cf. in. 17.5 15.5
f,ksi 3.6 3.6
f,,, ksi 50.4 50.4
b, in. 11,0 10.5
c1, in. 17.5 16.8
f, ksi 3.6 3.6
Lightweight f,,, ksi 46.8 45.
2 h, in. 10.0 9.5
aggregate
d, in. 17.5 16.3
f, ksi 3.6 3.6
3 f, ksi 36.0 38.4
b, in. 9.0 9.0
d, in. 17,5 16.0
Note: I in. = 25.4 mm; 1 ksi = 6.895 41Pa.

would significantly affect the fire en- a 12 x 20 in. beam cross section for 1, 2
durance of these elements. Because and 3 hour exposure periods. The
concrete has good resistance to erosion analysis was made for both normal
and abrasion, the erosive effects of hot weight (siliceous) and lightweight
moving gases were considered to he in- aggregate concretes. The nominal mo-
significant for concrete components. ment strength of the beam section was
This may not be true for other t ypes of reduced only by an additional 5 to 12
structural components with sprayed-on percent of original strength when the
or lightly attached insulation. beams were exposed to a hydrocarbon
By means of a finite element analysis, pool fire rather than the standard test
cross section temperature distributions fire. Most of this difference in strength
were calculated for both fire exposures. capacity was because the beam was ex-
These indicated that temperatures due posed on four sides (top, bottom and
to the hydrocarbon pool test fire were sides) in the hydrocarbon pool fire,
about 10 to 25 minutes ahead of temper- while only the bottom and sides of the
atures due to the standard test fire. beam were exposed in the standard
A strength analysis was performed on building fire.

134
REFERENCES
1. ASTM Committee E-5, "Standard Meth- Program for Temperature Analysis of
ods of Fire Tests of Building Construc- Structures Exposed to Fire," Report No.
tion and Materials, ASTM Designation: 79-2, Department of Structural Mechan-
E119," American Society for Testing and ics, Lund Institute of Technology, Lund,
Materials, 1985 Annual Book of Stan- Sweden, 1979.
dards, V. 04.07, 1985, 7. Forsen, N. E., "A Theoretical Study on
2. ASTM Committee E-5, "Proposed Test the Fire Resistance of Concrete Stnic-
Methods for Determining Effects of lures," SINTEF Report No. STF65
Large Hydrocarbon Pool Fires on Struc- A82062, Norwegian Institute of Tech-
tural Members and Assemblies, ASTM nology, University of Trondheim,
Designation: E5 P191, - American Soci- Trondheim, Norway, 1982, 213 pp.
ety for Testing and Materials, 1986 An- 8. Ellingwood, B., and Shaver, J. N., "Ef-
nual Book Standards, V. 04.07, 1985. fects of Fire on Reinforced Concrete
3. PCI Design Handbook -Precast and Pre- Members," Journal of the Structural
stressed Concrete, Prestressed Concrete Division, American Society of Civil
Institute, Chicago, Illinois, Third Edi- Engineers, V. 106, No. ST11, Novem-
tion, 1985.
. ber 1980,
4. ACI Committee 216, "Guide for Deter- 9. Anderberg, Y., "Fire-Exposed Hyper-
mining the Fire Endurance of Concrete static Concrete Structures An Experi-
Elements (ACI 216R-81)," American mental and Theoretical Study," Bulletin
Concrete Institute, Detroit, Michigan, 55, Lund Institute of Technology, Lund,
1981, 44 pp. Sweden, 1976, 186 pp.
5. CRSI Reinforced Concrete Fire Resis- 10. Harmathy, T. Z., "Thermal Properties of
tance, Concrete Reinforcing Steel Insti- Concrete at Elevated Temperatures,"
tute, Chicago, Illinois, 1980. Journal of Materials, V. 5, No. 1, March
6. Wickstrom, U., "TASEF-2 A Computer 1970, pp. 47-74.

METRIC (SI) CONVERSION FACTORS


1 in. = 25.4 mm 1 ksi = 6.895 MPa
1ft=0.3048m 1pcf=16.02kglm'
1 ft-kip = 1356 N-m to - (tr .. 32)/1.8
1 Btulftzlhr!F = 5.678 Wlm2!C

NOTE: Discussion of this paper is invited. Please submit


your comments to PCI Headquarters by October 1, 1989.

PCI JOURNAUJanuary-February 1989 135

Potrebbero piacerti anche