Sei sulla pagina 1di 7

An Investigation of Protection Devices

Coordination Effects on Distributed Generators


Capacity in Radial Distribution Systems
J. A. Saed, S. Favuzza, M. G. Ippolito, F. Massaro
Universit di Palermo, Palermo, (Italy)
e-mail: jaser.saed@unipa.it

Abstract In the recent years, with the concept of Smart devices coordination, the impact of DG should be taken
Grid, there are a great interest in integration of renewable into account when planning DG interconnection.
energy based distributed generation (DG) units at Most of the existing distribution systems are radial
distribution level. Along with a number of benefits,
with unidirectional power flows from substation to
penetration of DG units in the distribution system imposes
some serious challenges; protection requirements turns up customers. Over-current protection is used for such
as one of the most critical challenge in DG integration. In systems because of its simplicity and low cost [12].
this paper the possibility and the potentiality of occurring However, once a DG or several DGs are connected
mis-coordination between protection devices in radial within the main utility system, this pure radial nature is
distribution network is studied. The impacts of protection lost. Thus the protection of distribution networks using
devices coordination on DG capacity are investigated. The
over-current protective devices becomes a challenging
penetration level, number, and location of interconnected
DGs are used as parameters in order to verify the effects of task due to the change in the fault current levels and
DG on fault current level. The threshold value of DG direction; the protective devices may not respond in the
capacity is presented while the existing protection scheme way they were initially designed [13].
for distribution network can be maintained. Detailed A typical distribution protection system consists of
simulations using MATLAB and PowerWorld simulators relays, re-closers and fuses. An over-current relay is
are inserted in order to explain and verify the results.
usually placed at a substation where a feeder originates.
Index Terms--Distributed Generation, Fuse, Protection
Re-closers are usually installed on main feeders with
Coordination, Recloser. fuses on laterals. Re-closers are necessary in a
distribution system as 80% of all faults that take place in
I. INTRODUCTION distribution systems are temporary; it gives to a
In the recent years the electrical power networks are temporary fault a chance to clear before allowing a fuse
undergoing rapid restructuring and developing process to blow. The coordination between fuses, re-closers and
worldwide. Advancement in technologies and concern relays is well established; however, when DG units are
about the environmental impacts have led to increase connected to a distribution network, a loss of
interconnection of renewable energy based distributed coordination among network protection devices may be
generations (DG) in distribution networks [1-4]. The occurring. There are two possible ways to overcome this
increasing penetration of distributed generation, added to mis-coordination. One way is to upgrade the protection
the distribution power system, creates new technical and system components or to change the whole system
economical challenges [5]. This increase has been protection if needed; another way is to maintain the old
supported by economic incentives [6-7] and new protective devices coordination unchanged up to a
technologies [8-9]. It will be necessary to consider many specific DG penetration level. In this research the impact
issues concerning these challenges [10-11], in terms of of integrating DG on the protective devices coordination
physical integration; protection is one important topic of using the second way is studied. The choice of this way
these challenges. High penetration of DG will have depends on the fact that it is cheaper one when studying
unfavorable impact on the traditional protection methods that impact in the developing countries distribution
because the distribution system is no longer radial in networks. In order to overcome the mis-coordination
nature and is not supplied by a single main power source occurred in some cases, modifications will be suggested
[1]. The impact depends on the number, location and size to upgrade the conventional protection system.
of injected DG. When a fault occurs in a distribution
II. PROTECTION OF DISTRIBUTION SYSTEM
network, it is important to quickly locate the fault by
identifying either a faulty bus or a faulty line section in A. Protection Coordination Fundamental
the network. To ensure safe and selective protection In typical distribution systems such as the network
shown in Fig. 1, the general coordination consists of a
This work was funded by the Italian Ministry of University and circuit breaker, a recloser, and lateral fuse. A lateral fuse
Scientific Research as a part of the PRIN 2008 project.

978-1-4673-4430-2/13/$31.00 2013 IEEE 686


is responsible for the permanent fault that occurs in part operation time
of the lateral feeder. However, if the fault is temporary or
the fault occurs on the main feeder in front the recloser, it ;
will be the device that trips the circuit instead in order to
confine the interrupted area. The operation of the recloser  (2)

also includes the function of backup protection when a
fuse fails to blow up. The breaker is responsible for the B. DG Impact on Distribution Protection
fault that occurs behind the recloser. In addition, the The distributed generations have significant impacts
breaker is used as the whole backup protection for the on the system and equipment operation in terms of
whole feeder when both the recloser and lateral fuses fail steady-state operation, dynamic operation, reliability,
in their functions. The time coordination between these power quality, stability and safety for both customers and
protection devices is fulfilled in coordination margin Z3 electricity suppliers. These impacts may be either
shown in Fig. 2; the descriptions TC and MM for the fuse positively or negatively, depending on the distribution
denote total clearing and minimum melting system, distributed generators and load characteristics
characteristics, respectively, and the descriptions S and F [16]. Previous studies have shown that the DG causes
for the recloser denote slow and fast operation modes, several challenges concerning the protection of
respectively [14]. distribution networks; the most commonly mentioned
ones are: exceeding the interruption capacity of
protection device from its rating, false tripping of feeders,
relay operation error, and mis-coordination of protection
devices [17].
Comprehensive studies are required to explore the
problems related to the integration of DG in classical
distribution networks. The characteristics of short circuit
current and hence the rating and coordination of the
Fig. 1 Schematic diagram for typical radial distribution system with
protection devices are depending on the network
DGs. structure. Considering the typical distribution network
shown in Fig 1, the following scenarios cover the most
frequent changes regarding how the connection of DG
units to the distribution networks may impact the
protective devices coordination.
a) Scenario 1
This scenario occurs when the fault current through
the recloser and the fuse is the same; the increasing in the
fault current, due to the presence of DGs, may cause that
the total fault current exceeds the maximum coordination
limit If,max shown in Fig. 2 and hence mis-coordination
will occurred. The mis-coordination can be solved by
selecting another fuse time-current curve and/or having
new setting for recloser to correspond with fault current
from DG. Another solution is to determine the maximum
capacity of the DG in order to keep the existing
Fig. 2 Sample coordination between protection devices.
protection scheme for distribution network unchanged
The selectivity rules for recloser and fuse coordination [18], [19].
as shown in zone Z3 can be expressed as [15]: b) Scenario 2
1) For all fault current values through a fuse in
In this scenario, the fault currents still lie within the
question , the fuse operation time t( )
allowed range, also, the fault current seen by the fuse is
should be greater than the reclosers fast operation
different and higher than the fault current seen by the
time t( ). recloser. In order to maintain the coordination between
; protection devices, the recloser F curve must disconnect
the circuit before fuse MM. Hence, the margin for DG
 (1)
 fault current can be calculated from the points that fuse
2) For all fault current values through the fuse in MM operates at the same time as the recloser F.
question , the total clear time of the fuse, Naturally, the disparity between these currents will
depend on the size and type of DG and its placement on
should be less than the reclosers slow
the main feeder. Larger size, more fault injection capacity

687
and shorter distance of DG from load feeder will result in characteristics, and time-current curves of each feeder.
greater disparity and vice versa. As shown in Fig. 3, for a The possibility of occurrence for this scenario is higher
given fault current in fuse (IFuse), if the disparity between when the size of DG is very large, determining high fault
IFuse and the corresponding recloser current (IRecloser) is currents. Fig. 5 shows a case in which this scenario may
more than the margin shown (CM2), the coordination be occur; in this situation the faulted and healthy feeders
will be lost [20]. have different time-current curves which leads healthy
feeder to trip first, although the current is much smaller
than the fault current at the faulted feeder. This problem
may probably solve by using directional over-current
relays at substation breakers; this suggestion is possible
and does not require a great investment. However, if both
faulted and healthy feeders have similar circuit breakers
and setting, the operating time of the circuit breaker in the
faulted feeder will be faster and the operating sequence of
both circuit breakers can be discriminated [18], [19].

Fig. 3 Coordination Margins between protection devices.

c) Scenario 3
As the penetration of DG increases, the value of fault
current flowing from substation will decreases; this
situation may result in recloser or circuit breaker not
responding to the fault. Fig. 4 describes this scenario; it
shows an example of fault current in which the protection Fig. 5 Short-circuit currents through the breakers of both feeders.
device may not operate in presence of DG. This problem
may be solved by either selecting a new time-current III. PROPOSED SYSTEM STUDIES
curve or by installing a smaller generation unit that will
not significantly decrease the short-circuit current The characteristics of short circuit current and the
through the recloser or CB [18]. ratings of the protection devices depend on the network
structures. In this study the feeder 1 of typical radial
distribution power system shown in Fig. 1 is considered.
Detailed analysis for this radial configuration with
different numbers, locations and capacities of distributed
generators are conducted in this study. To analyze the
impact of DG on fault current level and protection
devices coordination, different cases shown in Table I
have been simulated and discussed.

TABLE I
DIFFERENT CASES CONSIDERED IN THIS STUDY
Case No. Case DG location
Description
a Without DG No DG interconnected
b1 A single DG With DG1
b2 interconnected With DG2
b3 With DG3
Fig. 4 Short-circuit currents through the recloser or CB with and without c1 Two DGs With (DG1+DG2)
DG Scenario 3. c2 interconnected With (DG1+DG3)
c3 With (DG2+DG3)
d) Scenario 4 d Three DGs With (DG1+DG2+DG3)
interconnected
In this scenario, the resulting current flow due to the
presence of DG may result in an undesirable tripping of Let us consider the case with three interconnected
the CB in non faulted feeder. The breaker at the healthy DGs (Case d); Table II describes the currents passing
feeder may trip first, depending on the distribution through the circuit breaker, the recloser, and the fuse
system structure, distributed generators, load during the fault; the different fault positions considered in

688
this table are shown in Fig. 1. For other cases considered
in Table I, the protection devices fault current can be 1) Coordination Margin 1 (CM1): for the cases where
evaluated using Table II by considering the effect of the IR= IF, 
connected DGs and eliminating the current effects for the 2) Coordination Margin 2 (CM2): for the cases where
unconnected DGs; as an example, for case b1, set IR < IF, 
IDG2=IDG3=0 in Table II and so on.
3) In general:  )
TABLE II
TIMES FAULT CURRENT PASSING THROUGH PD CASE (D) IV. SIMULATION RESULTS
Fault Description
Position A typical 22kV radial distribution system with the
P5 ICB=IS, topology shown in Fig. 1 has been considered. All bus
IR=IS+IDG1+ IDG2, loads are 1 MW with power factor 0.92. The distributed
IFault = IS+IDG1+ IDG2+ IDG3
P4 ICB=IS,
generator buses are modeled as PQ bus with power factor
IR=IS+IDG1+ IDG2, of 0.92. For each feeder segment the following values
IFuse4=IFault = IS+IDG1+ IDG2+ IDG3 have been considered for resistance and reactance:
P3 ICB=IS, R=0.2066 per unit and X=0.64876 per unit. MATLAB
IR=IS+IDG1+ IDG2,
IFuse3=IFault = IS+IDG1+ IDG2+ IDG3 and PowerWorld software has been used to simulate the
P2 ICB=IS, proposed system. The following sections show and
IR=IDG3, discuss the obtained results.
IFuse2=IFault = IS+IDG1+ IDG2+ IDG3
P1 ICB=IS, A. Without DG Case- Result Analysis
IR=IDG3,
IFuse1=IFault = IS+IDG1+ IDG2+ IDG3 The system is simulated in normal case before adding
any DG to determine the normal currents flow in each
Fig. 6 shows a general configuration for radial branch after that the proposed network is simulated for
distribution system when several DGs are connected; for three phase fault type at different buses and different
a distribution system with this topology, the following locations in order to find the maximum fault current
equations describe the current passing through circuit passing through each protection device. Based on those
breaker CB, the recloser R, and the fuse F during the currents, the appropriate protection devices are selected
fault. according to [21], [22]. The obtained results are
For upstream faults (respect to the recloser): summarized in Table III. Coordination of the protection
devices is shown via the time-current curves in Fig. 7.
(3)
 TABLE III
(5) RESULTS OF NORMAL OPERATION AND FAULT ANALYSIS WITHOUT DG
PD Max. Load Max. Fault
For downstream faults (respect to the recloser): Current (A) Current (kA)
(6) Circuit Breaker 120 2.2449
Recloser 60 0.9358
 Fuse 1 30 1.1990
(8) Fuse 2 30 0.8763
Fuse 3 30 0.6871
Fuse 4 30 0.5623

B. Effect on Fault Current of DG Location and Capacity


Variation.
It is clear from Table II that the current passing
through each protection device varies and depends on the
case and current injected from the DG; it means that the
time response for protection devices will be change and
mis-coordination may be occur. In order to study the
effect of distributed generators capacity on the system
behavior, the penetration level of DG can be calculated as
a function of the total complex power generation from
DGs ( ) over complex power peak load demand
( ).
Fig. 6 Radial distribution system with several distributed generators

 (9)

In order to satisfy the coordination conditions
described earlier and referring to the value of fault
To verify the effect of DG capacity and location on
currents passing through the recloser and the fuse, there
the fault current passing through each protection device, a
are two coordination margins. These margins are shown
in Fig. 3 and mathematically can be described as:

689
three phase solid fault at position P4 is applied to the test recloser and the value gradually decreases when the DG
network shown in Fig. 8. is located in front of the recloser.
1
PL=20%
PL=40%
0.9
PL=60%
PL=80%
0.8

0.7

Fault current(kA)
0.6

0.5

0.4

0.3

0.2
2 3 4 5 6 7 8 9 10 11
DG Location
Fig. 10 Recloser fault current Vs. DG location
Fig. 7 Time-current curves for the proposed radial network
Fig. 11 shows the value of fault current flowing
through the fuse 4; as the distance between the DG and
the fault location decreases, the value of the fault current
increases. On the other hand, as the penetration level
increases the fault current gradually increases.

1.6
Fig. 8 Schematic diagram for the test radial distribution network
1.5

Fig. 9 shows the value of fault current passing 1.4


through the CB with different values of PL; it can be 1.3
clearly seen that the DG have a significant effect on the
Fault current(kA)

1.2
fault current flowing from substation; as expected, larger
penetration level influence the substation fault current 1.1

more than smaller penetration level. Moreover, the effect 1


of DG is most significant near the middle of the feeder.
0.9
0.34
0.8 PL=20%
PL=40%
0.32 0.7 PL=60%
PL=80%

2 3 4 5 6 7 8 9 10 11
0.3
DG Location
Fault current(kA)

Fig. 11 Fuse 4 fault current Vs. DG location


0.28
C. Effect of DG on Protection Coordination
0.26 In particular, the integration of DG in the distribution
PL=20% system impacts the system protection devices ratings and
0.24 PL=40% coordination. Adding DG to the system leads to
PL=60%
redistribution of branches currents, hence the
PL=80%
0.22 conventional protection concepts must be revised. The
2 3 4 5 6 7 8 9 10 11
DG Location
effect of DG on protective device coordination is
Fig. 9 CB fault current Vs. DG location sensitive to distribution system configuration, DG size
and DG location. A comprehensive analysis was done in
Fig. 10 shows the value of fault current passing
order to test and verify the coordination requirements for
through the recloser; based on this graph, as the distance
different cases mentioned in Table I; Table IV
between the DG and the recloser decreases the value of IR
summarizes the results; the penetration level for DGs in
increases when the DG source is located behind the
all cases are varied from 5% to 100%. As an example for
recloser and the value increases as the distance between
scenario 1 mentioned earlier, consider a fault occurred at
the DG and the recloser increases when the DG is located
position P3. Fig. 12 shows the value of IF3 versus DG
in front of the recloser. The graph also shows that, as the
penetration level. It is clear that as the penetration level
penetration of DG increases, the value of IR gradually
increases the fault current gradually increases. On the
increases when the DG source is located behind the

690
other hand, if the fault current exceed I F,max=1740 A (case mis-coordination occurred have been reviewed. It is
c3 and d), the coordination will be lost. shown that the fault current passing through each
protection device depends on the DG size, number, and
TABLE IV
COORDINATION TEST RESULTS
location. This fault current can be managed to stay within
Case Coordination of Protection the coordination limits, a comprehensive analysis must be
Devices done before integrating DG sources in a distribution
a Valid network, and then suitable devices will be chosen to
b1 Valid
b2 Valid recover the coordination.
b3 Valid
c1 Valid when PL < 56% REFERENCES
c2 Valid when PL < 48% [1] S. A. M. Javadian, M. R. Haghifam, and N. Rezaei, A
c3 Valid when PL < 28% fault location and protection scheme for distribution
d Valid when PL < 7% systems in presence of DG using MLP neural networks,
in Power & Energy Soc. Gen. Meet PES09 IEEE, 2009,
1.85 pp. 1-8.
[2] V. Cosentino, S. Favuzza, G. Graditi, M. G. Ippolito, F.
Massaro, E. Riva Sanseverino, and G. Zizzo, Smart
1.8
renewable generation for an islanded system. Technical
Fault current passing through Fuse 3 (kA)

and economic issues of future scenarios, Energy, vol. 39,


1.75 pp. 196- 204, Feb. 2012.
[3] S. Favuzza, G. Graditi, M. G. Ippolito, F. Massaro, R.
Musca, E. Riva Sanseverino, and G. Zizzo, Transition of a
1.7
distribution system towards an active network. Part I:
Preliminary design and scenario perspectives, in
1.65
International Conference on Clean Electrical Power
ICCEP11, Italy, 2011, pp. 9- 14.
Case b3 [4] V. Cosentino, S. Favuzza, G. Graditi, M. G. Ippolito, F.
1.6 Case c2 Massaro, E. Riva Sanseverino, and G. Zizzo, Transition
Case c3
Case d
of a distribution system towards an active network. Part II:
economical analysis of selected scenario, in International
1.55
10 20 30 40 50 60 70 80 90 100 Conference on Clean Electrical Power ICCEP11, Italy,
DG Penetration Level (%) 2011, pp. 15- 20
Fig. 12 Fuse 3 fault current Vs. DGs penetration level [5] L.Dusonchet, S. Favuzza, F. Massaro, G. Morello, Analisi
economica finanziariadegli investimenti sul fotovoltaico in
Fig. 13 shows the value of fault current passing Italia, LEnergia Elettrica n.03/09 maggio-giugno 2009
through the CB when a fault occurred at position P 4; pp.37-51
based on this graph, the fault current through CB is [6] V. Di Dio, R. Miceli, C. Rando, and G. Zizzo, Dynamics
photovoltaic generators: Technical aspects and economical
decreasing as the penetration of DG increases, in this valuation, in Power Electronics Electrical Drives
situation; if ICB have a value lower than ICB,min=160 A, Automation and Motion (SPEEDAM), 2010 International
scenario 3 is valid and the circuit breaker will not operate. Symposium on, 2010, pp. 635640.
[7] V. Di Dio, S. Favuzza, D. La Cascia, and R. Miceli,
0.22
Economical Incentives and Systems of Certification for
Case c1
Case c2
the Production of Electrical Energy from Renewable
0.2
Case c3
Energy Resources, in Clean Electrical Power, 2007.
ICCEP 07. International Conference on, 2007, pp. 277
Fault current passing through CB (kA)

Case d
0.18 282.
[8] R. Candela, V. Di Dio, E. Riva Sanseverino, and P.
0.16
Romano, Reconfiguration Techniques of Partial Shaded
PV Systems for the Maximization of Electrical Energy
0.14
Production, in Clean Electrical Power, 2007. ICCEP 07.
International Conference on, 2007, pp. 716719.
0.12
[9] V. Di Dio, D. La Cascia, R. Miceli, and C. Rando, A
0.1
mathematical model to determine the electrical energy
production in photovoltaic fields under mismatch effect,
in 2009 International Conference on Clean Electrical
0.08
Power, ICCEP 2009, 2009, pp. 4651.
0.06
[10] M. Brenna, MC. Falvo, F. Foiadelli, L. Martirano, F.
10 20 30 40 50 60 70 80 90 100 Massaro, D. Poli, and A. Vaccaro, Challenges in Energy
DG Penetration Level (%) Systems for the Smar-Cities of the future, in International
Fig. 13 CB fault current Vs. DGs penetration level Conference & Exhibition ENERGYCON 2012, Italy,
2012, pp. 818-825
V. CONCLUSION [11] M.L. Di Silvestre, S. Favuzza, M.G. Ipoolito, F. Massaro,
E. Riva Sanseverino, Analysis of impacts on electric
This paper has analyzed the effect of distributed power system operation of load management in resisdential
generators on fault current level and on protection and tertiary buildings, in International Conference &
Exhibition ENERGYCON 2012, Italy, 2012, pp. 777-782
devices coordination in the radial distribution networks. [12] H. Cheung, A. Hamlyn, L. Wang, C. Yang, and R.
Different scenarios for mis-coordination problems caused Cheung, Investigations of impacts of distributed
by DG have been discussed. The solutions to overcome generations on feeder protections, in Power & Energy
Soc. Gen. Meet PES09 IEEE, 2009, pp. 1-7.

691
[13] M. Dewadasa, A. Ghosh, and G. Ledwich, Fold back [18] J. A. Martinez and J. M. Arnedo, impact of distributed
current control and admittance protection scheme for a generation on distribution protection and power quality, in
distribution network containing distributed generators, Power & Energy Soc. Gen. Meet PES09 IEEE, 2009, pp.
IEEE Generation, Transmission & Distribution, IET, vol. 1-6.
4, pp. 952-962, August 2010. [19] S. Chaitusaney and A. Yokoyama, Reliability analysis of
[14] S. Chaitusaney, and A. Yokoyama, Prevention of distribution system with distributed generation considering
reliability degradation from recloserfuse miscoordination loss of protection coordination, in 9th International
due to distributed generation, IEEE Transaction on Power Conference on Probabilistic Methods Applied to Power
Delivery, vol. 23, no. 4, October 2008. Systems PMAPS, Sweden, 2006, pp. 1-8.
[15] H. B. Funmilayo and K. L. Butler-Purry, An approach to [20] A. Girgis and S. Brahma, "Effect of distributed generation
mitigate the impact of distributed generation on the on protective device coordination in distribution system",
overcurrent protection scheme for radial feeders, in in Large Engineering Systems Conference on Power
Power Sys. Conf. and Exp. PSCE09, IEEE/PES, 2009, pp. Engineering LESCOPE01 IEEE, 2001, pp. 115 119.
1-11. [21] J. Glover, M. Sarma, T. Overbye, Power system analysis
[16] N. Rugthaicharoencheep, and S. Auchariyamet, Technical and design, 5th ed., Cengage Learning, 2012.
and Economic Impacts of distributed generation on [22] W. Ruschel, A. Ashley, Coordination of relays, reclosers,
distribution system, World Academy of Science, and sectionalizing fuses for overhead lines in the oil
Engineering and Technology 64, 2012. patch, IEEE Trans. Industry Applications, vol. 25, no. 6,
[17] S. A. A. Shahriari, A. Y. Varjani and M. R. Haghifam, pp. 1041-1048, 1989.
"Cost reduction of distribution network protection in
presence of distributed generation using optimized fault
current limiter allocation," Electrical Power and Energy
Systems, vol. 43, pp. 1453-1459, August 2012.

692

Potrebbero piacerti anche