Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
The magnitude of the stator mmf wave and its relative angular
position with respect to the rotor mmf wave depend on the
synchronous machine load
The electromagnetic torque on the rotor acts in a direction so
as to bring the magnetic fields into alignment.
If the rotor field leads the armature field, the torque acts in
opposition to the rotation with the machine acting as a
generator.
On the other hand, if the rotor field lags the armature field, the
torque acts in the direction of rotation with the machine acting
as a motor.
Need for dq-axis
We see that the magnetic circuits and all rotor windings are
symmetrical with respect to both polar axis and the inter-polar axis.
Therefore, for the purpose of identifying synchronous machine
characteristics, two axes are defined as shown in previous fig.
The direct (d) axis, centered magnetically in the centre of the
north pole.
The quadrature (q) axis, 90 electrical degrees ahead of the d-axis.
The position of the rotor relative to the stator is measured by the
angle between the d-axis and the magnetic axis of phase a
winding.
The selection of the q-axis as leading the d-axis is purely arbitrary.
Stator and rotor circuits of a synchronous machine
Stator circuit equations
The voltage equations of the three phases are
The reason for resolving the mmf into the d- and q-axis components is
that each acts on specific air-gap geometry of defined configuration .
Air-gap fluxes per pole along the two axes are
Similarly,
Mutual inductance between stator and rotor windings
The variation in the mutual inductance is due to the
relative motion between the windings themselves.
When a stator winding is lined up with a rotor winding,
the flux linking the two windings is maximum and the
mutual inductance is maximum.
When the two windings are displaced by 900, no flux
links the two circuits and the mutual inductance is zero.
With a sinusoidal distribution of mmf and flux waves,
Similarly,
and
Rotor circuit equations
The rotor circuit voltage equations are
Similarly,
The above transformations also apply to stator flux linkages and voltages.
Stator voltage equations in dq0 components
The angle is the angle between the axis of phase a and the d-
axis.
Compared to the use of physical units the per unit system offers
computational simplicity by eliminating units and expressing system
quantities as dimensionless ratios.
Dividing throughout by
Similarly,
Per Unit Rotor Voltage Equations
Dividing throughout by
Similarly,
Per Unit Power and Torque
d ( s) G( s)e fd ( s) Ld ( s)id ( s)
q ( s) Lq ( s)iq ( s)
The order of the numerator and denominator
polynomials of Ld(s) and Lq(s) are equal to the
number of rotor circuits in the respective axis.
The denominator of G(s) is the same as Ld(s) but
the numerator is different and one order less.
The operational parameters can be obtained with
the help of the equivalent circuits shown below.
GENERATOR CONSIDERATION
LIMITERS AND
PROTECTIVE
CIRCUITS
TERMINAL VOLTAGE
TRANSDUCER AND LOAD
COMPENSATION
DC excitation system
AC excitation system
Static excitation system
The rating is generally 2kW to 3 kW/MVA
STATIC EXCITATION SYSTEM
(a). POTENTIAL SOURCE CONTROLLED RECTIFIER
SYSTEM
GENERAL
In this system, the excitation power is supplied through a
transformer from the generator terminal or the station auxiliary
bus and is regulated by a controlled rectifier
LIMITATION
The maximum excitation output voltage is dependent on the
input ac voltage. Hence during system fault conditions causing
depressed generator terminal voltage , the available exciter
voltage is reduced.
POTENTIAL SOURCE CONTROLLED RECTIFIER SYSTEM
(b). COMPOUND SOURCE RECTIFIER
SYSTEM
GENERAL
GENERAL
This system utilizes controlled rectifiers in the
exciter output circuits and the compounding of
voltage and current derived source within the
generator stator to provide excitation power
COMPOUND CONTROLLED RECTIFIER EXCITATION SYSTEM
In all the cases Field flashing is required. It is
generally carried out via station battery
DYNAMIC PERFORMANCE MEASURE
(b)
P=EtItcos=(Xad/Xs)Etifdsini
Q=EtItsin=(Xad/Xs)Etifdcosi-(Et /Xs)
The relationship between the active and reactive powers for a given field
current is a circle at (-Et /Xs)on the Q axis and with (Xad/Xs)Etifd as the
radius as shown in figure c
(c)
(c). END REGION HEATING LIMIT
The localized heating in the end region of the armature
imposes a third limit on the operation of a synchronous
machine. This limit affects the capability of the machine in the
under excited condition
REACTIVE CAPABILITY
CURVES OF A HYDROGEN-
COOLED GENERATOR AT
RATED VOLTAGE
Fig. 1.
Fig. 2.
Fig. 3.
Fig. 4.
Fig. 5.
Multi Machine Dynamics
Single line diagram
TRANSIENT STABILITY
Disturbances threatening the stability of a
system:
Network failure
Tripping of a generation unit
Erroneous action in the network operation
Relatively small change in the network
state, if damping is poor
8/4/2017 110
Energy fluctuation as a result of disturbance:
Between capacitors and inductances
Between rotating masses (most important
factor)
Boilers in power plants, combustion
chambers or the kinetic energy of water
8/4/2017 111
Changes can be seen in
the quantities P, Q, V, I
time constants between 10 ms10 s
period of oscillations between 0.55 s
8/4/2017 112
The stability of synchronous
machines depends on the state of the
network and the nature of the
disturbance.
8/4/2017 113
The stability related to synchronous
operation is categorized according to the
nature of the phenomenon usually as
follows:
Steady-state stability
Dynamic stability
Transient stability
8/4/2017 114
Steady-state stability
Stability with respect to small changes
(random variation of loading, compensating
device)
8/4/2017 115
Dynamic stability
After a fault, an individual synchronous machine
may remain in synchronism during the first swing.
After this, strong electromechanical oscillations
occur.
116
Transient stability
Transient stability refers to stability with
respect to large changes.
When the criterion for stability is that the
generator remains in synchronism during the
first swing.
Changes refer to faults that determine the
network dimensioning and operation (busbar
fault; tripping of generation).
117
Swing Equation
During any disturbance the rotor will decelerate or accelerate w.r.t.
synchronously rotating mmf .So a relative motion begins.The equation
describing this relative motion is called Swing Equation.
If pm is the shaft power input to the machine
pe is the electrical power
pa is the accelerating power
Differential eqn. Governing rotor dynamics is
M(d2 e/dt2 ) = Pm-Pe ------ (1)
Measurement of the angular position of the rotor w.r.t. a synchronously
rotating frame of reference is called Torque angle or Power Angle
= e Ws t
From this equation
d2 /dt2=d2 e/dt2 ------ (2)
substituting eqn 2 in 1
M(d2 e/dt2 ) = M(d2 /dt2) = Pm-Pe -----(3)
Equal Area Criterion
jXd jXL
Pm
+ Fixed (Infinite Bus)
Pe
E/ V/0
P Pe
B DE Pm1
A Pm
o
At A is = s
At B is > s
At D is < s
At E again is = s
So system is First swing stable!
8/4/2017 123
Stable Equilibriumsmall increase in mechanical power
P
Pe
C E
D Pm1
A B Pm
o 1
First swing
-syn
Stable
0
1
0
08/4/2017 Time124
P
Pe
C E
Pm1
A Pm
o x 2
x
x 1
8/4/2017 125
POWER SYSTEM STABILITY
The stability related to synchronous operation is categorized
according to the nature of the phenomenon usually as follows:
Steady-state stability
Dynamic stability
Transient stability
Steady-state stability
Stability with respect to small changes (random variation of
loading, compensating device)
Dynamic stability
After a fault, an individual synchronous machine may remain in
synchronism during the first swing.
After this, strong electromechanical oscillations occur.
POWER SYSTEM STABILITY
Transient stability
Transient stability refers to stability with respect to large changes.
When the criterion for stability is that the generator remains in
synchronism during the first swing.
Changes refer to faults that determine the network dimensioning
and operation (bus bar fault; tripping of generation).
where
POWER SYSTEM STABILITY
Fundamental Concepts of Stability of Dynamic Systems:
State-Space Representation:
If the derivatives of the state variables are not explicit functions of
time, the system is said to be Autonomous.
Then,
Where
The set of points traced by the system state in the state space as the
system moves -- State trajectory.
POWER SYSTEM STABILITY
Fundamental Concepts of Stability of Dynamic Systems:
Linearization:
Let, x0: The initial state vector,
uo: The input vector corresponding to the equilibrium point about
which the small-signal performance is to be investigated
Hence,
The values of s which satisfy the above are known as eigen values
of matrix A, and above equation is referred to as the characteristic
equation of matrix A.
POWER SYSTEM STABILITY
Fundamental Concepts of Stability of Dynamic Systems:
Eigen Properties of the State MatrixEigen values
The eigen values of a matrix are given by the values of the scalar
parameter for which there exist non-trivial solutions (i.e., other than
=0) to the equation
Where,
A is an nxn matrix (real for a physical system such as a power
system) is an nx1 vector.
Where, ci =
POWER SYSTEM STABILITY
The time response of the ith state variable is thus
given as
&
The right eigenvector gives the mode shape, i.e., the relative activity
of the state variables when a particular mode is excited.
Eg: The degree of activity of the state variable xk in the ith mode is
given by the element ki of the right eigenvector i.
POWER SYSTEM STABILITY
Fundamental Concepts of Stability of Dynamic Systems:
Mode shape and eigenvectors:
The magnitudes of the elements of i give the extents of the
activities of the n state variables in the ith mode, and the angles
of the elements give phase displacements of the state variables
with regard to the mode.
Eigenvalue sensitivity
So,
this was that the shaft speed measured at the generator end had a high component of the
16 Hz torsional mode
Torsional masses
Typical lumped-mass model of a generating unit driven by a tandem compound
reheat turbine.
The five torsional masses represent the rotors of the generator, two low-
pressure (LP) turbine sections, an intermediate-pressure (IP) turbine section,
and a high-pressure (HP) turbine section.
TORSIONAL INTERACTION WITH POWER SYSTEM
CONTROLS
Shaft speed measured at the generator end has a high component of the 16 Hz
torsional mode. The stabilizer transfer function is designed to provide zero
phase shift between the input speed signal and air-gap torque at the system
mode frequency of 1.67 Hz, so as to result in a purely damping torque
component as shown in Figure 15.7(a)
However, the generator characteristics are such that this results in a phase lag of
about 1350 at 16 Hz. As shown in Figure 15.7(b), the effect is to produce a
negative damping torque component and hence instability of the 16 Hz torsional
mode.
Torsional mode instability through excitation control may also be caused by a
terminal voltage limiter which uses feedback of terminal voltage to control
excitation through a very high gain.
This can cause torsional instability, unless some kind of filtering is provided to
attenuate high frequency components of the voltage signal.
PSS based on shaft speed signal (delta-omega): (limitations)
PSS based on shaft speed signal has been used successfully on hydraulic units.
Among the important considerations in the design of equipment for the
measurement of speed deviation is the minimization of noise caused by shaft
run-out and other causes.
For noise frequencies below 5 Hz, the level must be less than 0.02%, since
significant changes in terminal voltage can be produced by low-frequency
changes in the field voltage.
The application of shaft speed-based stabilizers to thermal units requires a
careful consideration of the effects on torsional oscillations.
The stabilizer, while damping the rotor oscillations, can cause instability of the
torsional modes.
While stabilizers based on direct measurement of shaft speed have been used on
many thermal units, this type of stabilizer has several limitations.
The primary disadvantage is the need to use a torsional filter which also
introduces a phase lag at lower frequencies.
A destabilizing effect is developed on the "exciter mode", due to this filter lag,
thus imposing a maximum limit on the allowable stabilizer gain.
Terminal frequency has been used as the stabilizing signal for several PSS
applications.
In some cases, terminal voltage and current are used to derive the frequency of a
voltage behind a simulated machine reactance so as to approximate the machine
rotor speed.
In these systems, as in the case of speed-based stabilizers, care must be taken to
filter torsional modes when they are used on steam turbine units.
The sensitivity of the frequency signal to rotor oscillations increases as the
external transmission system becomes weaker, tending to offset the reduction in
gain from stabilizer output to electrical torque that results from a weaker
transmission system
The gain of a frequency-based stabilizer may be adjusted to obtain the best
possible performance under weak ac transmission system conditions where the
contribution of the stabilizer is required most.
The frequency signal is more sensitive to modes of oscillation between large
areas than to modes involving only individual units, including those between
units within a power plant.
Thus it is possible to obtain greater damping contributions to interarea modes of
oscillation.
Limitation of Frequency-based stabilizers:
During a rapid transient, the terminal frequency signal will undergo a sudden phase
shift. This results in a spike in the field voltage that is reflected in the generator
output quantities.
The frequency signal often contains power system noise caused by large industrial
loads such as arc furnaces. In many cases this has prevented the use of frequency as
an input signal.
Em xm Tmn I Tmn V
1 1
X qi I Qi VDi
tan i
X qi I Di VQi
i Ym v
For Q = 0,
Power Voltage Relationships :
From load flow equations following expression can be obtained,
or,
Generator Reactive Power Requirement (contd.):
Solving the equation with respect to Qg yields,