BAGHDAD WEST NORTH 400/132/11kV SUBSTATION

TEST REPORT FOR PROTECTION RELAY

Internal Validation FAT SAT

MICOM P142 NON DIRECTIONALOVER CURRENT & DIRECTIONAL EARTH FAULT


PROTECTION RELAY

1.Front plate Information

Relay type P142


Manufacturer ALSTOM
Model number P14281HB6M0510J
Serial number 34045009/03/17
Rated current In 1 Amps
Auxiliary Voltage Uaux 110V DC
Panel Reference EL02
Feeder Reference
Substation Reference BAGHDAD WEST NORTH 400/132/11kV IRAQ S/S

2.Test kit Details:-


Test set Model :CMC 256-6
Serial no. :HH581R
Test kit calibration Calibrated on :1-06-2015
Calibration due :31-05-2016
Relay Setting software Type : N/A
Version : N/A

Product Checks

3.With the Relay De-Energised:-

Visual Inspection
Rating information correct for installation?
Case earth installed?
External wiring checked against diagram?
Test block connections checked?

4.Watchdog Contact:-

Supply Off Terminals (Close)


Supply On - Terminals (Open)

TEST REPORT FOR P142 50/51/51N/67 N Page 1 of 5


BAGHDAD WEST NORTH 400/132/11kV SUBSTATION

TEST REPORT FOR PROTECTION RELAY

5. Measurement accuracy Checks:-

Displayed current (Primary / Secondary) Secondary


Phase CT ratio 2000/1A

Injected cur\rent =1 Amps

Input CT Expected Current Displayed Current


Ia 2000 2.001
Ib 2000 2.005
Ic 2000 2.005

Displayed Voltage (Primary / Secondary) Secondary


Phase VT ratio 132KV/110V

Injected voltage = 63.5 V

Input VT Expected Voltage Displayed Voltage


VAB 132KV 132.1
VBC 132KV 132.0
VCA 132KV 132.1

6. Setting checks:-

Application specific function setting applied? Yes/No

TEST REPORT FOR P142 50/51/51N/67 N Page 2 of 5


BAGHDAD WEST NORTH 400/132/11kV SUBSTATION

TEST REPORT FOR PROTECTION RELAY

9. Non Directional Definite Time Over Current Protection (50):-

Delay type: DMT DT:1 Sec


I>>
Phase Measured pickup
Current settings Operating Time In
Reference Current (in Amps)
(in Amps) (Sec)
R .501 1.047
Y 0.50 .500 1.031
B .501 1.032
Pickup current tolerance :5% Operating time tolerance = <30ms

10.Non Directional Definite Time Earth Fault over current Protection (50N):-
Delay type: DMT

Delay type: DMT DT:1 Sec


IN>>
Phase Measured pickup
Current settings Operating Time In
Reference Current (in Amps)
(in Amps) (Sec)
N 0.4 .401 1.055
Pickup current tolerance :5% Operating time tolerance = <30ms

11.Non Directional Indefinite Mean Time Over Current Protection (51):-


Operating time test:- Curve :IDMT Normal Inverse

OPERATING TIME AT MULTIPLES OF PICKUP CURRENT (sec)


I>
Phase Setting 10*Is
TMS
Reference (Is) 2*Is 5*Is
(Amps)
Calculated Measured Calculated Measured Calculated Measured
R 1.0 10.029 10.04 4.279 4.285 2.970 2.982
Y 0.5 1.0 10.029 10.04 4.279 4.286 2.970 2.979
B 1.0 10.029 10.04 4.279 4.293 2.970 2.987
Pickup current tolerance :1.05*Is 5% Operating time tolerance : 5% or 40ms which ever is greater

12.Non Directional Indefinite Mean Time Earth Fault Protection (51N):-


Operating time test:- Curve :IDMT Normal Inverse
OPERATING TIME AT MULTIPLES OF PICKUP CURRENT (sec)
IN>
Setting 10*Is
Reference TMS
(Is) 2*Is 5*Is
(Amps)
Calculated Measured Calculated Measured Calculated Measured
N 0.200 1.0 10.029 10.013 4.279 4.301 2.970 2.986
Pickup current tolerance :1.05*Is 5% Operating time tolerance : 5% or 40ms which ever is greater

13. Directional Definite Time Earth fault Protection (67N):- DT:1Sec

Phase Current settings Measured pickup Operating Time(s)


Reference (in Amps) Current (in Amps)

N 2.0 1.990 1.060


Pickup current tolerance: 5% Operating time tolerance = <30ms

TEST REPORT FOR P142 50/51/51N/67 N Page 3 of 5


BAGHDAD WEST NORTH 400/132/11kV SUBSTATION

TEST REPORT FOR PROTECTION RELAY

14. Directional Indefinite Mean Time Earth Fault Protection (67N):-


OPERATING TIME AT MULTIPLES OF PICKUP CURRENT (sec)
Reference

IN>
Setting 10*Is
TMS
(Is) 2*Is 5*Is
(Amps)
Calculated Measured Calculated Measured Calculated Measured
N 0.200 1.0 10.029 10.15 4.279 4.318 2.97 3.010
Pickup current tolerance: 1.05*Is 5% Operating time tolerance: 5% or 40ms which ever is greater

E/F: Voltage Applied: Van: 50 (0deg), Vbn: 63.5(-120Deg), Vcn: 63.5(120Deg)


Current Applied: RCA (Torque Angle) : -45Deg Delay Type: DMT
Sl. No. Reference Operating region Expected
1 In 0-45-225 0-45-225

Functionality Check
Item Description Result
1
Relay contact Output checks
2
Relay Digital Input Checks
3
Relay LED Checks
6
Master Trip Relay Checks

Remarks:-

TEST REPORT FOR P142 50/51/51N/67 N Page 4 of 5


BAGHDAD WEST NORTH 400/132/11kV SUBSTATION

TEST REPORT FOR PROTECTION RELAY

TESTED BY: WITNESSED BY: APPROVED BY:


Name: Name: Name:
Company: Company: Company:
Sign : Sign : Sign :
Date : Date : Date :

TEST REPORT FOR P142 50/51/51N/67 N Page 5 of 5