NOTES:

1. THIS TYPICAL DRAWING SHOWS THE MIN. CLEAR DISTANCES BETWEEN THE PIPE
FLANGES AND THE WALLS OR BOTTOM SLAB.
SECTION A-A REMOVABLE SUPPORT AERATION PIPE DETAIL
AERATION PIPE WITH GALVANIZED STEEL MESH 2. FOR THE SMALL PIPE DIAMETERS THE CLEAR DISTANCE BETWEEN THE PIPE AND

REMOVABLE CONCRETE SLABS LADDER 1:10 THE BOTTOM SLAB WILL BE AT LEAST 40 cm.

LIFTING LUGS 1:25 3. THE WIDTH OF THE WALLS, THE BOTTOM SLABS AND THE REMOVABLE
CONCRETE SLABS DEPENDS ON THE SHAFT DIMENSIONS AND THE LOCAL SOIL
REMOVABLE SUPPORTING HANDLE SECTION C-C CONDITIONS.
STAINLESS STEEL
MANHOLE COVER WATERTIGHT 4. THE SIZE OF THE REMOVABLE CONCRETE SLABS, THE NUMBERS OF THE LIFTING
PIPE DN 100 OR DN DEVICES AND THE AERATION PIPES DEPEND ON THE SIZES OF THE SHAFTS.
HOT DIP GALVANIZED STEEL LADDER DETAIL 150
5. THE WALL DUCTS FOR THE CABLE WILL BE WATERTIGHT

6. THE ARRANGEMENT OF THE STAIRS, THE LADDERS, THE PLATFORMS, THE


FGL FGL FGL FGL MECHANICAL AND THE ELECTRICAL EQUIPMENT WILL BE DETERMINED
INDIVIDUALLY DEPENDING ON THE RESPECTIVE SHAFT.
REMOVABLE SUPPORTING INSECT
MESH 7. THE LOCATION AND THE NUMBER OF THE ACCESSES (MANHOLES) DEPEND ON
B B HANDLE THE SIZE OF THE SHAFTS AND THE LOCAL ACCESSIBILITY.
MANHOLE COVER D D
8. THE NUMBER AND DIAMETER OF AERATION PIPES DEPENDS ON THE SIZE OF THE
SHAFT
CL
WATERPROOFING MEMBRANE AND
BOP TOP
9. ALL DIMENSIONS ARE GIVEN IN mm (MILLIMETERS)
PROTECTION BOARD min. 800
WALL DUCT, WATERTIGHT GRATING
LEGEND:
EQUIPMENT SUPPORT (VALVES, (GALVANIZED) FGL = FINISHED GROUND LEVEL
FLOWMETER) SECTION D-D
TOP = TOP OF PIPE
CONSTRUCTION JOINT 1:10
BOP = BOTTOM OF PIPE
PUMP SUMP
BLINDING
5
0
REFERENCE DRAWINGS
DRAWING No.: DRAWING TITLE:

6x25..........
50
DETAIL: REMOVABLE CONCRETE SLABS
1:10
SECTION B-B SIDE VIEW CAGE
DETAIL: CAGE
1:20 TYPICAL
VALVES OR OTHER
FITTINGS
1:50
DISMANTLING PIECE,
IF REQUIRED C 180
WALL DUCT,
WATERTIGHT CLEAR DISTANCE BETWEEN VARIABLE (DEPENDING ENGINEER'S STAMP CONTRACTOR'S STAMP

FLANGES AND WALL ON THE SPAN)

MIDDLE HOOP BAR


40 50x6 mm
50
40 BOTTOM HOOP BAR
VAG

EK N

75x6 mm
CLEAR DISTANCE BETWEEN SIDE RAIL
FLANGES AND WALL 75x75x6 mm
NEOPRENE BEARINGS 350
A A

PERMANENTLY MASTIC VERTICAL BAR


SEALING COMPOUND WITH 30x6 mm
BACKING ROD
C
min. 400 VARIABLE (DEPENDING ON THE
DEPENDING ON HEIGHT OF THE SHAFT)
PIPE DIAMETER

DETAIL: JOINT SEALING FOR TOP SLAB PRECAST DETAIL FOR CABLE PASSAGE
CONCRETE ELEMENTS FOR YARD SHAFTS 1:10
1:5 0

B
Issue for Tender

Issue for Draft Tender


BR
BR
Ofner

Ofner
12.08.2008

25.07.2008
A Issue for Engineering Report BR HARB 10.12.2007

REV. DESCRIPTION DRAWN CHECKED DATE

SALINE WATER CONVERSION CORPORATION


152015 KINGDOM OF SAUDI ARABIA
MASTIC SEALING COMPOUND
WITH BACKING ROD VARIABLE (DEPENDING ON THE AL LITH
COVER SLAB HEIGHT OF THE SHAFT) WALL DUCT (WATERTIGHT) WATER TRANSMISSION SYSTEM
TYPE LINK SEAL OR EQUIVALENT
CABLE 1:20 CONSULTING
ILF CONSULTING ENGINEERS
DN 75 ENGINEERS

BELL END PVC


ANCHOR FLANGE LINK SEAL OR EQUIVALENT Subconsultant: DRAWING TITLE:
CONDUIT
SLEEVE PIPE POLYURETHANE FOAM
FOAM FILLING
PHENOL FREE BITUMEN COATING
P H S TYPICAL YARD SHAFT
300 300
SILICON GENERAL ARRANGEMENT

SCALE: DRAWING SHEET REV.


No.:

--- QP10 - Q- 610 - 0