Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
org
Published in IET Power Electronics
Received on 23rd May 2013
Revised on 26th November 2013
Accepted on 26th December 2013
doi: 10.1049/iet-pel.2013.0407
ISSN 1755-4535
Abstract: With the existence of virtual impedance, the load harmonic currents would decrease the detection accuracy of
fundamental power calculated in DQ method, thus inuence the performance of droop control system in microgrid inverters.
Quantitative analysis of the fundamental power detection error is conducted and general expressions of inverter output power
in the presence of virtual impedance are established. The concept of virtual harmonic power is proposed to approximately
describe the error. Furthermore, the small signal stability analysis method is applied to present a detailed performance
analysis of the control system as virtual harmonic power is taken into consideration. The analysis indicates that under the
non-linear load condition, the value of droop coefcients and the type of designed virtual output impedance will inuence the
stability of the control system, which means that droop coefcients and virtual output impedance should be carefully selected
to gain sufcient stability margin. Simulation and experiment are both carried out and comparison of linear and non-linear
load condition is presented in detail which veries the theoretical analysis.
3 Analysis of fundamental power detection including the harmonic components are presented in the
error following equations (see (1))
In this section, quantitative analysis of the fundamental power In expressions (1) and (2), f denotes fundamental angle
detection error of droop controller is presented in detail when frequency; Ufm and Unm denote fundamental and nth
harmonic components exist in the output voltages and harmonic voltage amplitude, respectively; Ifm and Inm
currents. Typical condition that single inverter supplying denote fundamental and nth harmonic current amplitude,
non-linear loads is discussed. The load current is respectively; f and n denote fundamental and nth
assumed to be i, which contains fundamental current, harmonic voltage phase, respectively; Ifm and Inm denote
positive-sequence harmonic current and negative-sequence fundamental and nth harmonic current phase, respectively.
harmonic current. With the existence of virtual impedance The expression of DQ transformation is shown as follows
Zv, output voltages of the inverter would contain harmonic (see (2))
components. As there are no zero sequence currents in
three-phase three-wire neutral non-grounded systems, the T
cos vf t sin vf t
harmonic components with orders of 6k + 3 do not exist in
2p 2p
2
the load currents, thus the load harmonics with the orders fa
fd cos v t sin vf t
of 6k 1 are needed to be taken into consideration. =
f
3 3 fb
fq 3
Typically, the components with orders of 6k + 1 are 2p 2p fc
positive-sequence components, whereas the components cos vf t + sin vf t +
3 3
with orders of 6k1 are negative-sequence components.
The expressions of the output voltages and currents (3)
+1
ua = Ufm cos (vf t + uf ) + Unm cos (nvf t + un )
k=1 n=6k+1
+1
2 2
u = U cos v t + u p + Unm cos (nvf t + un + p)
b fm f f
3 3
k=1 n=6k1
2
+ Unm cos nvf t + un p (1)
3
n=6k+1
+1
2 2
= v + u + p + v + u p
u c U fm cos f t f U nm cos n f t n
3 3
k=1 n=6k1
2
+ Unm cos nvf t + un + p
n=6k+1 3
+1
i = I cos ( v t + w ) + Inm cos (nvf t + wn )
a fm f f
k=1 n=6k+1
2
+1 2
ib = Ifm cos vf t + wf p + Inm cos nvf t + wn + p
3 3
k=1 n=6k1
2
+ Inm cos nvf t + wn p (2)
3
n=6k+1
+1
2 2
ic = Ifm cos vf t + wf + p + Inm cos nvf t + wn p
3 3
k=1 n=6k1
2
+ Inm cos nvf t + wn + p
n=6k+1 3
ud =
3
Ufm cos uf + Unm cos[(n + 1)vf t + un )]
k=1 n=6k1
frequency of more than six times of the fundamental
+ 1
q
2 fm f nm f n
Similarly, the rst three items in the instantaneous reactive
k=1 n=6k1
+ 1 power q would be reserved with the effect of the LPF. As a
+ 1
p = 3U I cos ( u w ) + 3Un In cos (un wn )
f f f f
k=1 n=6k+1
+ 1
+ 3{Uf In cos [(n 1)vf t + (wn uf )]
k=1 n=6k+1
+Un If cos [(n 1)vf t + (un wf )]}
+1
+1
+ 3{U6k1 I6j+1 cos [6(j + k)vf t + (w6j+1 + u6k1 )]
j=0 k=1
+U6j+1 I6k1 cos [6( j + k)vf t + (u6j+1 + w6k1 )}
+1
q = 3Uf If sin (uf wf ) + 3Un In sin (un wn ) (7)
k=1 n=6k+1
3Un In sin (un wn )
n=6k1
+ 1
+ 3{ U I sin [(n 1) v t + ( w u )
f n f n f
k=1 n=6k+1
Un If sin [(n 1)vf t + (wf un )]}
+ 1+ 1
+ 3{U6k1 I6j+1 sin [6(j + k)vf t + (w6j+1 + u6k1 )
j=0 k=1
+ U6j+1 I6k1 sin [6(j + k)vf t + (u6j+1 + w6k1 )}
+1
n=6k+1 Zvn In cos (un wn )
2
Ph
a = = k=1
Pf Zvf I 2 cos (uf wf )
+1 f (10)
Qh k=1 [ n=6k+1 Zvn In sin (un wn )
2
n=6k1 Zvn In sin (un wn )]
2
b = =
Qf Zvf If2 sin (uf wf )
s5 A C E
5 Influence analysis of harmonic power to s4 B D F
droop controller s3 a1 a2 0
s2 b1 b2 0
s1 c1 0 0
According the value of the determinant corresponding to the s0 d1 0 0
system matrix of the state (17), the characteristic equation of
Fig. 6 Closed-loop system pole distribution with different types of virtual impedance
a Left, resistive virtual impedance (0 < 1, = 0); and right, capacitive virtual impedance ( = 0, 0.5 < 0)
b Left, inductive virtual impedance ( = 0, 0 1); and right, resistiveinductive virtual impedance (0 < 1, 0 1)
real poles in the right diagram deviate away from the real axe, It is mentioned in the former section that the inuence of
thus, the damping ratio decreases and anti-interference ability different virtual impedances to the fundamental power
of the system becomes weaker. Generally speaking, when the detection accuracy would not be the same. Typically, the
virtual harmonic power exists, the range of droop ratios would
be narrowed for the purpose of sufcient stability margin. Table 3 Simulation parameters
Parameter Symbol Value in stable Unit
Table 2 System equilibrium points state
Parameters Symbol Value in stable Unit active power droop ratio m 1 103 V/W
state reactive droop ratio n 2.5 103 (rad/s)/
Var
cutoff frequency of LPF c 62.8 rad/s virtual inductance Lv 0.01 mH
active power droop ratio m 1 103 V/W linear load inductance Ll 15 mH
reactive power droop n 3 104 (rad/s)/ linear load resistance Rl 5
ratio Var peak value of fifth Ip5 50 A
common bus voltage V 308 V harmonic source
amplitude line inductance 1 L1 0.06 mH
output voltage amplitude E 315 V line resistance 1 R1 0.2
line inductance L 0.06 mH line inductance 2 L2 0.1 mH
line resistance R 0.2 line resistance 2 R2 0.3
Fig. 7 Comparison diagram of dynamic waveforms with linear and non-linear loads
Up: output current of phase A; middle: output current difference of phase A; and down: reference angle frequency
a Linear load
b Non-linear load
detection result of fundamental active power would always be capacitive, inductive, resistiveinductive virtual impedance
larger than the real value, whereas that of the fundamental to the droop controller.
reactive power could be larger or smaller than the real It can be seen from Fig. 6 that dynamic performance and
value. The closed-loop pole distribution diagrams are stability of the system would not be greatly inuenced by
shown in Fig. 6 to indicate the inuence of the resistive, the resistive virtual impedance, whereas the inductive,