MEMORIA DE CALCULO
El ministerio de vivienda y construccin da sus valores en base al clima y los habitantes as:
TIPO LTRS/HAB./DIA.
Alumnado externo 40
Alumnado cuarto interno 70
Alumnado interno 200
Personal no residente 50 USAMOS
Personal residente 200
DOTACION OBSERVACION
DESCRIPCION UNIDAD CANTIDAD SUB TOTAL
(lit/dia) ES
Alumnado no residente Personas 85 50 4250
Personal administrativo no residente Personas 15 50 750
Areas verdes m2 0 0 0
Agua Contra Incendios Glb 0
Dotacion total= 5000Lts/dia.
Segn R.N.E
Volumen cisterna. 2.4 Almacenamiento
3/4 De la ydotacion
regulacion,
total. numeral
= (e).3750 Lts 10.00 m3
Volumen tanque elevado 1/3 De la dotacion total. = 1667 Lts 2.00 m3
VOLUMENES FINALES
Ancho Largo Altura Alt. diseo Volumen final
Cisterna 2.00 3.60 1.40 1.70 12.24 m3
Tanque elevado 1.00 1.10 1.50 1.90 2.09 m3
Segn
El R.N.E especifica que el volumen minimo que debe contener R.N.Eelevado y/o cisterna debe ser = >
un tanque
1m3. CISTERNA 2.4 Almacenamiento y regulacion, numeral (c y d).
CUMPLE
El R.N.E especifica que el volumen minimo que debe contener un tanque elevado y/o cisterna debe ser = >
CUMPLE
1m3. TANQUE ELEVADO
MEJORAMIENTO DEL SERVICIO EDUCATIVO EN LA INSTITUCIN EDUCATIVA SECUNDARIA JOSE ANTONIO ENCINAS FRANCO DE TOTORA OROPESA, DISTRITO DE
OROPESA, ROVINCIA DE ANTABAMBA, REGIN - APURMAC
a) La dotacin de agua para riego de areas verdes de 2 litros por m2 de jardn por da a razn de segun la
norma I.S. 010.
b) La dotacin de agua para oficinas ser de 6 litros por habitante por da.
d) La dotacin de agua para oficinas ser de 20 litros por habitante por da.
c)Dotacin de agua para locales educacionales y residenciales educacionales.
a) La dotacin de agua para riego de areas verdes de 2 litros por m2 de jardn por da.
1er NIVEL 2do NIVEL 3er NIVEL 4to NIVEL 5to NIVEL TOTAL
AREA DE JARDINES 414.13 m2 0.00 m2 0.00 m2 0.00 m2 0.00 m2 414.13 m2
DATOS
DETERMINAR
A) Seleccionar el diametro del medidor
B) Diametro de la tuberia de alimentacion a la cisterna
SOLUCION:
Volumen
Q
Tiempo
MEJORAMIENTO DEL SERVICIO EDUCATIVO EN LA INSTITUCIN EDUCATIVA SECUNDARIA JOSE ANTONIO ENCINAS FRANCO DE TOTORA OROPESA, DISTRITO DE
OROPESA, ROVINCIA DE ANTABAMBA, REGIN - APURMAC
Volumen
Q = 15000 1.042 lts/seg
Tiempo 14400
H= 14.16 lbs/pulg2
H= 9.97 m
- Medidor
en el abaco de medidores se tiene
en el abaco
Q= 1.041667
D= 3/4 "
S= 0.85 m/m
UNIDADES DE GASTO
APARATOS
TIPO
SANITARIOS TOTAL AGUA FRA AGUA CALIENTE
PRIMER NIVEL
SEGUNDO NIVEL
TERCER NIVEL
CUARTO NIVEL
NUM. DE NUM. DE
APARATOS GASTO
- -
2 6
- -
2 4
2 6
- -
2 6
- -
- -
- -
2 2
- -
- -
- -
- -
- -
- -
- -
- -
24
SEGUNGO NIVEL
ALIMENTADOR "II"
NUM. DE NUM. DE
APARATOS GASTO
- -
- -
- -
2 4
2 6
- -
2 6
- -
- -
- -
2 2
- -
- -
- -
- -
- -
- -
- -
- -
18
TERCER NIVEL
ALIMENTADOR "II"
NUM. DE NUM. DE
APARATOS GASTO
- -
- -
- -
2 4
2 6
- -
2 6
- -
- -
- -
2 2
- -
- -
- -
- -
- -
- -
- -
- -
18
NUM. DE NUM. DE
APARATOS GASTO
- -
- -
- -
2 4
2 6
- -
2 6
- -
- -
- -
2 2
- -
- -
- -
- -
- -
- -
- -
- -
18
TABLA N 3 DE GASTOS PROBABLES PARA APLICACIN DEL MTODO DE HUNTER
GASTOS GASTO
NDE NDE GASTO
NDE UNIDADES PROBABLES VLVULA PROBABLE VLVULA
UNIDADES UNIDADES PROBABLE
TANQUE TANQUE
3 0.12 - 120 1.83 2.72 1,100 8.27
4 0.18 130 1.91 2.8 1,200 8.7
5 0.23 0.91 140 1.98 2.85 1,300 9.15
6 0.25 0.94 150 2.06 2.95 1,400 9.56
7 0.28 0.97 160 2.14 3.04 1,500 9.9
8 0.29 1 170 2.22 3.12 1,600 10.42
9 0.32 1.05 180 2.29 3.2 1,700 10.85
10 0.34 0.06 190 2.37 3.25 1,800 11.25
12 0.38 0.12 200 2.45 3.36 1,900 11.71
14 0.42 0.17 210 2.53 3.44 2,000 12.14
16 0.46 0.22 220 2.6 3.51 2,100 12.57
18 0.5 0.27 230 2.65 3.58 2,200 13
20 0.54 0.33 240 3.75 3.65 2,300 13.42
22 0.58 0.37 250 2.84 3.71 2,400 13.86
24 0.61 1.42 260 2.91 3.79 2,500 14.29
26 0.67 1.45 270 2.99 3.87 2,600 14.71
28 0.71 1.51 280 3.07 3.94 2,700 15.12
30 0.75 1.55 290 3.15 4.04 2,800 15.53
32 0.79 1.59 300 3.32 4.12 2,900 15.97
34 0.82 1.63 320 3.37 4.24 3,000 16.2
36 0.85 1.67 340 3.52 4.35 3,100 16.51
38 0.88 1.7 380 3.67 4.46 3,200 17.23
40 0.91 1.74 390 3.83 4.6 3,300 17.85
42 0.95 1.78 400 3.97 4.72 3,400 18.07
44 1 1.82 420 4.12 4.84 3,500 18.4
46 1.03 1.84 440 4.27 4.96 3,600 18.91
48 1.09 1.92 460 4.42 5.08 3,700 19.23
50 1.13 1.97 480 4.57 5.2 3,800 19.75
55 1.19 2.04 500 4.71 5.31 3,900 20.17
60 1.25 2.11 550 5.02 5.57 4,000 20.5
65 1.31 2.17 600 5.34 5.83
70 1.36 2.23 650 5.85 6.09
75 1.41 2.29 700 5.95 6.35
80 1.45 2.35 750 6.2 6.61 Para el nmero de unidades de esta columna
85 1.5 2.4 800 6.6 6.84 es indiferente que los artefactos sean de
90 1.56 2.45 850 6.91 7.11 tanques o de vlvula.
95 1.62 2.5 900 7.22 7.36
Para el nmero de unidades de esta columna
es indiferente que los artefactos sean de
tanques o de vlvula.
1/2" 1
3/4" 2.9
1" 6.2
1 1/4" 10.9
1 1/2" 17.4
2" 37.8
2 1/2" 65.5
3" 110.5
4" 189
6" 527
8" 1,250
10" 2,090
PRIMER NIVEL
TRAMOS EQUIVALENCIA DIAMETROS DIAGRAMA DE RAMALES
ALIMENTADOR "X"
DE 1 1/2"
CD 2 1/2"
BC 3 3/4"
AB 4 1"
OA 5 1"
IJ 1 1/2"
HI 2 1/2"
GH 3 3/4"
FG 4 1"
OF 5 1"
XO 10 1 1/4"
s.
s salidas a l, de tal modo que la
sub-ramales por el alimentador
rios para dar la misma descarga.
MENTACION
A DE RAMALES
A DE RAMALES
MENTACION
A DE RAMALES
1/2"
3/4"
1"
1/2"
3/4"
1"
1"
A DE RAMALES
MENTACION
A DE RAMALES
A DE RAMALES
MENTACION
A DE RAMALES
A DE RAMALES
CURSO DIRIGIDO: INSTALACIONES INTERIORES
Paso 3.- Deacuerdo ala distribucion de agua para cada alimentador, el total de gastos acumulados a nivel del piso
de azotea sera:
De la tabla N 3:
Para 180 U.H. 2.29 Lit/seg
Para 188 U.H. X Lit/seg
Para 190 U.H. 2.37 Lit/seg
10 . 0.08
8 . x
x= 0.064
X= 2.29+0.064
X= 2.354 Lit/seg.
Paso 6.- El punto mas desfavorable es el punto "E", por estar mas alejado horizontalmente y tener menor altura
estatica respecto al tanque elevado.
Paso 7.-
a) Consideramos una presion minima de salida de 2.55 mt.
ALTURA DISPONIBLE
La altura disponible comprende el resultado obtenido al descontar la presin mnima requerida a la altura
esttica entre el punto de consumo ms desfavorable y el nivel mnimo de agua en el tanque elevado
CURSO DIRIGIDO: INSTALACIONES INTERIORES
El punto mas defavorable de consumo.- es la ducha ubicada a mayor dist. del pto de de alimentacion (II)en
el quinto nivel dicha ducha tiene una altura de 1.8m sobre el piso terminado.
entonces calculamos la altura disponible.
HD = 3.5 mt.
LONGITUD EQUIVALENTE
la longitud equivalente comprende la longitud real de tubera a la que se aumenta un determinado
porcentaje de prdida de carga por accesorios estimndose ste en un 20% como un primer tanteo y para
simplicidad de los clculos.
El punto mas defavorable de consumo es la ducha ubicada a 14 mt del pto de de alimentacion (II) PTO "F"en
el quinto nivel dicha ducha tiene una altura de 1.8m sobre el piso terminado.
TRAMO AB :
del monograma, teniendo en cuenta de no sobrepasar el Smax = 0.114
Q= 2.354 Lit/seg.
Asumiendo diametro
= 1 1/2"
del abaco tenemos
S= 180/1000 = 0.18 > 0.114
volvemos a asumir un diametro mayor
Asumiendo diametro
= 2"
del abaco tenemos
S= 45/1000 = 0.045 < 0.114 ok!
Presion en B :
Altura estatica = 2.55 m
PB = altura estatica - hf. AB = bf. AB.
CURSO DIRIGIDO: INSTALACIONES INTERIORES
TRAMO BD :
De la tabla N 3:
Para 95 U.H. 1.62 Lit/seg
Para 96 U.H. X Lit/seg
Para 100 U.H. 1.67 Lit/seg
5 . 0.05
1 . x
x= 0.01
X= 1.62+0.01
X= 1.63 Lit/seg.
Q= 1.63 Lit/seg.
Asumiendo diametro
= 1 1/2"
del abaco tenemos
S= 92/1000 = 0.09 < 0.114 ok!
Presion en D :
Altura estatica = 2.55
PD = altura estatica - hf. BD
PD = 2.55-(0.138+0.406) 2.006 m.
TRAMO DF :
De la tabla N 3:
Para 95 U.H. 1.62 Lit/seg
Para 96 U.H. X Lit/seg
Para 100 U.H. 1.67 Lit/seg
5 . 0.05
1 . x
x= 0.01
X= 1.62+0.01
X= 1.63 Lit/seg.
Q= 1.63 Lit/seg.
Asumiendo diametro
= 1 1/2"
CURSO DIRIGIDO: INSTALACIONES INTERIORES
Presion en F :
Altura estatica = 5.35
PF = altura estatica - hf. DF
PF = 2.55+2.80-(0.138+0.406+0.302) = 4.504 m.
TRAMO FH :
De la tabla N 3:
Para 75 U.H. 1.41 Lit/seg
Para 78 U.H. X Lit/seg
Para 80 U.H. 1.45 Lit/seg
5 . 0.04
3 . x
x= 0.024
X= 1.41+0.024
X= 1.434 Lit/seg.
Q= 1.434 Lit/seg.
Asumiendo diametro
= 1 1/4"
del abaco tenemos
S= 180/1000 = 0.18 < 1.41 ok!
Presion en H :
CURSO DIRIGIDO: INSTALACIONES INTERIORES
TRAMO HJ :
Smax = 6.699 = 2.0 > 1
3.36
De la tabla N 3:
Q= 1.25 Lit/seg
Asumiendo diametro
= 1"
del abaco tenemos
S= 300/1000 = 0.3 < 1.58 ok!
Presion en J :
Altura estatica = 10.95 m
PJ = altura estatica - hf. HJ
PJ = 10.95 -(0.138+0.406+0.302+0.605+1) = 8.50 m.
TRAMO JL :
Smax = 8.499 = 2.5 >1
3.36
De la tabla N 3:
Q= 0.95 Lit/seg
Asumiendo diametro
= 1"
del abaco tenemos
S= 240/1000 = 0.24 < 2.5 ok!
Presion en L :
Altura estatica = 13.75
PJ = altura estatica - hf. JL
CURSO DIRIGIDO: INSTALACIONES INTERIORES
TRAMO LN :
Smax = 10.489 = 3.1 >1
3.36
De la tabla N 3:
Q= 0.61 Lit/seg
Asumiendo diametro
= 1"
del abaco tenemos
S= 110/1000 = 0.11 < 3.1 ok!
Presion en N :
TO DE AGUA DE
ente forma:
n) considerando el
la presin, debiendo
nima requerida, de lo
requerida a la altura
anque elevado
CURSO DIRIGIDO: INSTALACIONES INTERIORES
de alimentacion (II)en
eterminado
mer tanteo y para
AB 2.55 0.51 3.06 188 2.354 0.120 38.71 50 2" 0.0019634954 1.20
BD 3.76 0.752 4.512 96 1.630 0.149 32.21 38 1 1/2" 0.0011341149 1.44
DF 2.8 0.56 3.36 96 1.630 0.149 32.21 38 1 1/2" 0.0011341149 1.44
FH 2.8 0.56 3.36 78 1.434 0.161 30.21 32 1 1/4" 0.0008042477 1.78
HJ 2.8 0.56 3.36 60 1.250 0.174 28.21 32 1 1/4" 0.0008042477 1.55
JL 2.8 0.56 3.36 42 0.950 0.204 24.59 25 1" 0.0004908739 1.94
LN 3.1 0.62 3.72 24 0.610 0.265 19.71 25 1" 0.0004908739 1.24
BC 3.0 0.6 3.6 92 1.584 0.152 31.76 38 1 1/2" 0.0011341149 1.40
CE 2.8 0.56 3.36 92 1.584 0.152 31.76 38 1 1/2" 0.0011341149 1.40
EG 2.8 0.56 3.36 68 1.340 0.167 29.21 32 1 1/4" 0.0008042477 1.67
GI 2.8 0.56 3.36 44 1.000 0.198 25.23 32 1 1/4" 0.0008042477 1.24
IK 2.8 0.56 3.36 26 0.670 0.251 20.65 25 1" 0.0004908739 1.36
KM 3.1 0.62 3.72 14 0.420 0.329 16.35 19 3/4" 0.0002835287 1.48
N
A` - A 12.00 2.4 14.4 239 2.74 0.110 41.77 50 2" 0.0019634954 1.40 0.039
A-B 5.80 1.16 6.96 239 2.74 0.110 41.77 50 2" 0.0019634954 1.40 0.039
B-D 15.5 3.1 18.6 212 2.54 0.115 40.21 50 2" 0.0019634954 1.29 0.034
D-E 23.90 4.78 28.68 212 2.54 0.115 40.21 50 2" 0.0019634954 1.29 0.034
E-G 10.10 2.02 12.12 212 2.54 0.115 40.21 50 2" 0.0019634954 1.29 0.034
G-H 4.4 0.88 5.28 195 2.41 0.119 39.17 50 2" 0.0019634954 1.23 0.031
H-I 4.6 0.92 5.52 17 0.48 0.304 17.48 19 3/4" 0.0002835287 1.69 0.172
I - I` 5.5 1.1 6.6 17 0.48 0.304 17.48 19 3/4" 0.0002835287 1.69 0.172
TO PROBABLE TANQUE
ALTURA
PRESION ESTATICA PRESION
hreal (abc) INICIAL (m) FINAL (m)
(m)
ALIMENTADOR "II"
AB 2.55 3.06 188 2.354 0.114 2" 0.00202683 1.16 0.045 0.138 2.41
BD 3.76 4.51 96 1.63 0.114 1 1/2" 0.00114009 1.43 0.09 0.406 2.01
DF 2.8 3.36 96 1.63 0.114 1 1/2" 0.00114009 1.43 0.09 0.302 4.50
FH 2.8 3.36 78 1.434 1.415 1 1/4" 0.00079173 1.81 0.18 0.605 6.70
HJ 2.8 3.36 60 1.25 2 1" 0.00050671 2.47 0.3 1.008 8.49
JL 2.8 3.36 42 0.95 2.5 1" 0.00050671 1.87 0.24 0.806 10.48
LN 3.1 3.72 24 0.61 3.1 1" 0.00050671 1.20 0.11 0.409 13.18
ALIMENTADOR "I"
BC 3 3.60 92 1.584 0.16 1 1/2" 0.00114009 1.39 0.215 0.774 1.64
CE 2.8 3.36 92 1.584 0.16 1 1/2" 0.00114009 1.39 0.215 0.722 3.85
EG 2.8 3.36 68 1.34 1.22 1 1/4" 0.00079173 1.69 0.12 0.403 6.25
GI 2.8 3.36 44 1 1.93 1" 0.00050671 1.97 0.28 0.941 8.11
IK 2.8 3.36 26 0.67 2.49 1" 0.00050671 1.32 0.145 0.487 10.49
KM 3.1 3.72 14 0.42 3.20 1" 0.00050671 0.83 0.052 0.193 13.18
GOBIERNO REGIONAL DE APURMAC
GERENCIA REGIONAL DE INFRAESTRUCTURA SUB GERENCIA DE ESTUDIOS DEFINITIVOS
I.EI N957-PACHACONAS
GOBIERNO REGIONAL DE APURMAC
GERENCIA REGIONAL DE INFRAESTRUCTURA SUB GERENCIA DE ESTUDIOS DEFINITIVOS
Accesorios a utilizar
Valvula de paso 1 und
Valvula de compuerta 1 und
Codos 90 2 und
Codos 45 1 und
*Segn dato en campo
H=PR - PS - HT........(02)
TABLA N10
CARGA DISPONIBLE
Datos.
PR Presion en la red. 24.00 Libras/pulg2.
PS Presion a la salida. 2.84 Libras/pulg2.
HT Alura red a tanque. 7.38 Libras/pulg2.
Resultado.
H Carga disponible. 13.78 Libras/pulg2.
H Carga disponible. 9.70 m.c.a
I.EI N957-PACHACONAS
GOBIERNO REGIONAL DE APURMAC
GERENCIA REGIONAL DE INFRAESTRUCTURA SUB GERENCIA DE ESTUDIOS DEFINITIVOS
I.EI N957-PACHACONAS
GOBIERNO REGIONAL DE APURMAC
GERENCIA REGIONAL DE INFRAESTRUCTURA SUB GERENCIA DE ESTUDIOS DEFINITIVOS
TABLA N19
Segn R.N.C -IS .010
2.4 Almacenamiento y regulacion, numeral (m).
DIAMETRO DE LA TUBERIA DE REBOSE EN FUNCION A LA CAPACIDAD DE
DEPOSITO
Capacidad de deposito (Lts.) Diametro de la tubo de rebose
Hasta 5000 50mm(2")
5001 a 12000 75mm(3")
12001 a 30000 100mm(4")
Mayor a 30000 150mm(6")
Manual rotoplas
4.00 CALCULO DE REDES DE AGUA FRIA.
4.01 DESCRIPCION DE AMBIENTES SEGN PLANO DE ARQUITECTURA.
TABLA N21
DESCRIPCION DE AMBIENTES DEL CENTRO EDUCATIVO
NIVEL USO
I.EI N957-PACHACONAS
GOBIERNO REGIONAL DE APURMAC
GERENCIA REGIONAL DE INFRAESTRUCTURA SUB GERENCIA DE ESTUDIOS DEFINITIVOS
01deposito de limpieza,02aula,01ss.hh/nios,01ss.hh/nias,02deposito de
materiales,01aula de
Primer nivel psicomotricidad,01direccion/topico,01cocina,01deposito de
alimentos,01ss.hh.
RAMAL
TUBERIA DE ALIMENTACION
SUB RAMAL
V.C.1/2"
EF 4 1/2
HG 5 1/2
GF 6 1/2
B
FC 7 1/2
I
CI 8 1/2 C
*Segn plano de instalaciones de agua fria.
PRIMER NIVEL
APARATO CANTIDAD UND DE GASTO(*) TOTAL
Urinario. 2.00 2.5 5
Lavamano. 8.00 0.75 6
Inodoro. 5.00 3 15
Lavadero de cocina. 2.00 2 4
Ducha 0.00 1.5 0
*Segn tabla 26 30
Consumo maximo simultaneo probable al 80%. 24
I.EI N957-PACHACONAS
GOBIERNO REGIONAL DE APURMAC
GERENCIA REGIONAL DE INFRAESTRUCTURA SUB GERENCIA DE ESTUDIOS DEFINITIVOS
I.EI N957-PACHACONAS
GOBIERNO REGIONAL DE APURMAC
GERENCIA REGIONAL DE INFRAESTRUCTURA SUB GERENCIA DE ESTUDIOS DEFINITIVOS
Cualquier
Diametro del
horizontal de
tubo(mm).
desague.
32(1 1/4") 1
40(1 1/2") 3
50(2") 6
65(2 1/2") 12
75(3") 20
100(4") 160
125(5") 360
150(6") 620
200(8") 1400
250(10") 2500
300(12") 3900
375(15") 7000
50(2") 10 24 6
65(2 1/2") 20 42 9
75(3") 30 60 16
100(4") 240 500 90
125(5") 540 1100 200
150(6") 960 1900 350
200(8") 220 3600 600
250(10") 3800 5660 1000
300(12") 6000 8400 1500
375(15") - - -
I.EI N957-PACHACONAS
GOBIERNO REGIONAL DE APURMAC
GERENCIA REGIONAL DE INFRAESTRUCTURA SUB GERENCIA DE ESTUDIOS DEFINITIVOS
75(3") 60 - 24 -
100(4") 100 2.1 15 60
100(4") 200 1.8 15 54
100(4") 500 - 10.8 42
I.EI N957-PACHACONAS
GOBIERNO REGIONAL DE APURMAC
GERENCIA REGIONAL DE INFRAESTRUCTURA SUB GERENCIA DE ESTUDIOS DEFINITIVOS
TABLA N40
TABLA DE ESPECIFICACIONES TECNICAS
Peso Unidad 600 Lts. 1300Lts 3000Lts 7000Lts
Volumen de lodo extraido aproximado. Lts. 100 184 800 1500
Volumen solo aguas negras domiciliarias. Personas. 5 10 25 57
Capacidad de aguas negras y jabonosas. Personas. 2 5 10 23
Capacidad oficinas. Personas. 20 50 100 3000
Nota: Se Recomienda ingresar solo las agua negras al biodigestor y las aguas grises conectar directamente al pozo de
percolacion o campo de infiltracion.
I.EI N957-PACHACONAS
GOBIERNO REGIONAL DE APURMAC
GERENCIA REGIONAL DE INFRAESTRUCTURA SUB GERENCIA DE ESTUDIOS DEFINITIVOS
TABLA N44
Rapido de 1 a 4 minutos 4 9 20
Medio de 4 a 8 minutos 5 11 25
Lento de 8 a 12 minutos 6 13 30
Muy Let. de 12 a 24 minutos 9 19 43
(*) Resultado del test de percolacion efectuado en el terreno.
No se considera
*Segn tabla 44
TABLA N46
TABLA DE COEFICIENTE DE ESCURRIMIENTO
Coeficiente de Coeficiente de
Tipo de superficie Tipo de superficie
escurrimiento escurrimiento
Donde:
Ac = Area de captacion, en Ha.
C = Coeficiente de escurrimiento,adimensional.
i = Intensidad de precipitacion para una duracion igual al tiempo de concentracion,en mm/hr.
Qp = Gasto pluvial, en Ltrs./seg.
TABLA N49
CALCULO DEL GASTO PLUVIAL
Datos:
Ac = 190.35 m2 (*) Ver plano de techo.
Ac = 0.019 Ha
C = 1 Adimensional
i = 30 mm/h Tabla n21
Qp (Ltrs/seg.) 1.59
*Para el techo mas critico.
I.EI N957-PACHACONAS
GOBIERNO REGIONAL DE APURMAC
GERENCIA REGIONAL DE INFRAESTRUCTURA SUB GERENCIA DE ESTUDIOS DEFINITIVOS
TABLA N50
BAJANTES DE AGUAS PLUVIALES
Dametro de la bajante. Intensidad de lluvia (mm/h)
50 75 100 125 150 200
Pulgada. mm
m2 de areas servidas (proy/horz).
3" 75 400 270 200 160 135 100
4" 100 850 570 245 340 285 210
5" 125 800 640 535 400
6" 150 835 625
= /^(/)^(/)
FORMULA GENERAL
Donde:
S = Pendiente(m/m).
R = Radio hidraulico(m).
A = Area de la seccion(m2).
Qp = Caudal de descarga(m3/seg).
n = Coeficiente de rugocidad.
TABLA N52
DRENAJE PLUVIAL HORIZONTAL
Datos:
S = 0.005 Pendiente(m/m). b y
R = 0.102941 Radio hidraulico(m). 0.35 0.25
Qp = 0.000397 Caudal de descarga(m3/seg).
n = 0.016 Coeficiente de rugocidad.
Q(m3/seg) caudal de descarga 0.00135
I.EI N957-PACHACONAS
GOBIERNO REGIONAL DE APURMAC
GERENCIA REGIONAL DE INFRAESTRUCTURA SUB GERENCIA DE ESTUDIOS DEFINITIVOS
I.EI N957-PACHACONAS
Segn R.N.C
2.2 Dotaciones, numeral (f y u).
DOTACION DE AGUA
OBSERVACIO
NES
Plano Arq.
Segn R.N.C
2.4 Almacenamiento y regulacion, numeral (e).
Observacion
(3/4 de max.cons.horario)
(1/3 de max.cons.horario)
I.EI N957-PACHACONAS
Segn R.N.C -IS .010
2.4 Almacenamiento y regulacion, numeral (c y d).
CUMPLE
CUMPLE
I.EI N957-PACHACONAS
I.EI N957-PACHACONAS
I.EI N957-PACHACONAS
Segn R.N.C -IS .010
Anexos, Anexo n01
RA EL CALCULO DE LAS TUBERIAS DE DISTRIBUCION DE AGUA EN LOS
EDICICIOS(APARATO DE USO PRIVADO)
Unidad de gasto.
Agua caliente
0.75
0.75
2
1.5
1.5
I.EI N957-PACHACONAS
Segn R.N.C -IS .010
Anexos, Anexo n03
OBABLE PARA APLICACIN DEL METODO DE HUNTER
Gasto probable
Valvula
8.27
8.70
9.15
9.56
9.90
10.42
10.85
11.25
11.71
12.14
12.57
13.00
13.42
13.86
14.29
14.71
15.12
15.53
15.97
16.20
16.51
17.23
17.85
18.07
18.40
18.91
19.23
19.75
20.17
20.50
I.EI N957-PACHACONAS
ONAMIENTO DE LOS SUB-RAMALES DE ALIMENTACION
PRIMER PLANTA
DIAGRAMA DE RAMALES
F
A
H G E D
V.C.1/2"
B
I
C
I.EI N957-PACHACONAS
I.EI N957-PACHACONAS
Segn R.N.C -Anexos
Anexo n09
SIONES DE LOS TUBOS DE VENTILACION PRINCIPAL
I.EI N957-PACHACONAS
Segn R.N.C -Anexos
Anexo n09
SIONES DE LOS TUBOS DE VENTILACION PRINCIPAL
I.EI N957-PACHACONAS
TABLA DE ESPECIFICACIONES TECNICAS
7000Lts
1500
57
23
3000
lo las agua negras al biodigestor y las aguas grises conectar directamente al pozo de
on.
I.EI N957-PACHACONAS
DAD DE CAMARAS SEGN CAPACIDAD DE BIODIGESTOR
OBSERVACIONES
DIMENSIONES ADOPTADOS
7000 Ltrs.
OBSERVACIONES
0.1
I.EI N957-PACHACONAS
0.15
0.2
0.17
0.22
0.35
I.EI N957-PACHACONAS
BAJANTES DE AGUAS PLUVIALES
Intensidad de lluvia (mm/h)
200
m2 de areas servidas (proy/horz).
100
210
400
625
I.EI N957-PACHACONAS
Tipo Material
Punto Unidades Dimetros
Gasto (lps) rea (m)
De A Mueble Calculado (mm)Comercial (mm)Comercial (plg)
-- A
A B 24 1.04 36.39 33 1" 0.00086
DESCRIPCION
Instituciones educativas
IEI 957 Pachaconas
IEI 1065 Pacsica
IEI 1070 Pincahuacho
IEI 1087 Patibamba Baja
IEI 1100 Pichiuca
Fecha: 11/10/2015 MTODO DE HUNTER
Longitud Carga Piezomtrica (m)
Velocidad Carga Carga
Equivalente K Hf
(m/s) Anterior Actual Esttica (m) Dinmica (m)
(m)
4.2 2.8 1.4
1.22 31.2 66463.203125 2.24 4.2 1.96 0 1.96
DESCRIPCION
Descriptiva