Sei sulla pagina 1di 34

SubstationCommissioning

SubstationCommissioning
Whatissubstation
commissioning?
Provingtheproper
operationofanewly
Installed
Replaced
Modified
Repaired
pieceofequipment
beforeitisplacedinto
service
SubstationCommissioning
New/replaced/repaired New/replaced/repaired
circuitbreakers transformers
SubstationCommissioning
Greenfieldsubstation
SubstationCommissioning
ControlDevices
SubstationCommissioning
Newrelaysormodified
relaysettings
SubstationCommissioning
Allcommissioningtasks
requireagoodplan.In
ordertoproveproper
operation,the
technicianmust
understandproper
operation.
SubstationCommissioning
Safety
Alwaysmitigatesafety
concerns
LOTO
Clearance,Hold,Tagout
Mayrequirehelpfrom
otherdepartments
Whenindoubt,stop
SubstationCommissioning
Levelsofcommissioning
Simple
Moderate
Difficult
SubstationCommissioning
Creatingagameplan Coolingsystem
SimpleChecklist contactorreplacement
Fans/Pumpsworking
properly?
Allstages?
SCADAalarms?

Simplecomponent
replacementshouldbe
checkedforproper
operation
SubstationCommissioning
Moderatetodifficultcommissioning
Intensefamiliaritywithallaspectsofthetaskat
handisntalwaysnecessary.Sometimesthereare
othergroupsinvolvedinthecommissioning
process.Generalfamiliaritywithotherwork
groupsresponsibilitiesishighlyencouraged.
Thoroughknowledgeandexpertiseinthe
responsibilitiesoftherelaytechnicianisrequired.
SubstationCommissioning
SUBSTATION COMMISSIONING
Comprehensive CHECKLIST

checklistneededfor TRANSFORMER INFORMATION


MANUFACTURER:

SERIELNUMBER:

morecomplicated MVA:

NUMBEROFWINDINGS:

commissioningtasks
SELFNUMBER:

WINDINGHVOLTAGE:

WINDINGXVOLTAGE:

WINDINGYVOLTAGE:

WINDINGZVOLTAGE:

LTC?:YN

LTCSENSINGVOLTAGELEVEL:

LTCSENSINGVOLTAGESOURCE:

COOLINGSYSTEM:

COOLINGSYSTEMVOLTAGELEVEL:

COOLINGSYSTEMVOLTAGESOURCE:

COOLINGSYSTEMCONFIGURATION:OAFAOAFAFOFA

NUMBEROFPRESURERELIEFDEVICES:

STYLEOFSUDDENPRESSUREDEVICE:RAPIDRISEFAULTPRESSUREBUCHOLTZNA

N2SYSTEM:YN

TYPEOFN2REGULATION:SINGLESTAGEMULTISTAGED

MANUFACTURERRECOMMENDEDN2PRESSURE:


SubstationCommissioning
Largecomponentreplacement
TransformersandCircuitBreakers
Acceptancetestscanbeperformedwithoutprintsand
relaysettings
CTsaturation,ratio,polarity,andinsulationtesting
VTratio,polarity,insulationtesting
PowerFactortesting
Transformerturnsratiotesting
Acceptancetestingreallyonlyprovesthattheequipmentwas
builttospecificationsatthefactory,itsurvivedthetraveland
installation,andisthebaselineforfutureperformance
comparison.
SubstationCommissioning
Testingthatrequires Thesetestsinclude:
printsandsettingsis DCCircuitchecks
reallythecruxofthe ACCircuitchecks
commissioningprocess. Relaytesting
TripChecks
Communication
processorprogramming
PointtoPointtesting
SubstationCommissioning
DCChecks
DCcircuitcheckscanbeaccomplishedinafew
differentways,butallmustbedocumentedto
stayontrack.
Agoodplacetostartiscomparingtheschematics
tothewiringdiagrams.Mistakescanbeidentified
andpossiblyrectifiedduringconstruction,orupon
arrivalofequipmenttothejobsite.
Goodtimetoreviewmistakeswithengineering
SubstationCommissioning
DCChecks
Circuitscanbepre
testedwithcontinuity
beforeDCVisapplied
(+)DCVcanbeapplied
without()DCVand
checkscanbemade
DCVcanbeapplied
withoutpretesting
andthelocationofthe
smokecanbenoted
SubstationCommissioning
DCChecks
Notethevoltagerating
ofthepowersupplyand
theI/Ooftherelay
beforepoweringup
NoteproperDCV
polarity.Mostdevices
arenotpolarity
sensitive,butsomeare
andwillnotwork
properlyunless
connectedproperly
SubstationCommissioning
DCChecks
Yellowliningprintsisa
goodwaytokeeptrack
ofwhathaschecked
good
Testswitches,startwith
allopen,thenmarkand
closewhenchecked
good
Leavecheckedtest
switchesclosed
SubstationCommissioning
ACVoltageChecks
GoalofACvoltagecircuit Secondarywireschecked
checksistoproveproper withcontinuityaslong
phasingandpolarity asallconductorsare
throughoutthecircuit isolated
Existingphasingcanbe LiveBusorLine
identifiedwith voltagecanbeused
equipmentthathas Phasebetweennewand
beeninservice oldsecondarywires
Meteringscreenon
microprocessorrelay
SubstationCommissioning
ACCurrentChecks
Veryimportanttobe
testedproperly
Primaryloadingwith
predictioncurrentflow
sheet
ProvesCTratio,CT
circuitpolarity,andCT
circuitcontinuityinone
test
SubstationCommissioning
ACCurrentChecks
Secondaryinjectionalso
viabletest.
Onlywaytotest
transformerCTcircuits
Extremecaremustbe
takentogetpolarity
correct
Documentedsameas
Primaryloadtest
Predictedresults
SubstationCommissioning
RelayTesting
Testingtherelayismanagedindifferentways,but
thegoalistoprovetherelaysettings,relaylogic,
andrelayfunctionsareallworkingtoasset
settings
Elementtestingcanbeaccomplishedviamanual
orautomatictesting
Strivetotestrelaylogicwithrealdynamictesting
SubstationCommissioning
DynamicLogicTesting
Dontjustpulse/jumpercontacts,createrelay
reactionbyinjectingvaluesintotherelay
Uselogicdiagramsandyellowlinethemasthey
aretestedisagreatwaytounderstandtherelay
logic
Betteryet,drawyourownlogicdiagramsandtest
them
SubstationCommissioning
SubstationCommissioning
DynamicLogicTesting
Makebreakerrecloseor
notreclose
Blockclosebyinjecting
falsesyncvalues
Blocktransfertripping
withc/oswitch
RollLORwithBreaker
FailureorDTTRX
SubstationCommissioning
TripChecks
Vitaltoprovingproper
operationofalldevices
Electricaland
mechanical
SubstationCommissioning
CircuitBreakers
Tripfromallknown
trippingsources
Tripfrommechanical
devicessuchaslowgas
Testeachtripcoil
individually
Tripbreakerfailureback
updevices
Tripto/fromremote
sourcesifusingTransfer
Trip
SubstationCommissioning
Transformers
Tripfromallknown
tripping sources
Tripfrommechanical
devicessuchaslowoil
andsuddenpressure
Tripfromcoolingrelated
issues
Tripbreakerfailureback
upschemes
Tripandlockout
SubstationCommissioning
Communication
ProcessorProgramming
Metertesting
TOP006testing
Communicationcircuit
testing
Endtoendtesting
Precheckalarmcircuits
SubstationCommissioning
PointtoPoint
Completefinalcheckof
properoperationofall
newdevicesinthe
substation
Controlpoints
Analogpoints
Alarmpoints
Verifiedtoremote
controlcenter
SubstationCommissioning
EnergizationDay
Expectations
Couldbealongday
Problemsmayarise
Plantomitigateproblems
Personalsafety
Nonfieldpersonnelin
substation
Confident
Allprotectivedevicesin
service
SubstationCommissioning
PostEnergization
Settingfiles
Red/Greenprints
Completeall
documentation
Honeydolist
Bestcommissioningjobs
arethesubstationsyou
neverhearfrom
SubstationCommissioning
Conclusions
Awellthoughtoutplanwillguaranteethebest
chanceforasuccessfulcommissioningjob
regardlessofsizeofscope
Striveforaplanthatwilldoublecheckyourself
Askforhelpwhenitsneeded
Haveconfidenceinyourapproach
ThankYou

Potrebbero piacerti anche