ELECTRICAL CHARACTERISTICS
Resistance at 20oC Current Carrying Capacity Approx Short Circuit
Test
Size Reactance per Current at 1
Conductor Insulator In ground In air Voltage
Conductor sec
DC. Calculated - 30oC 30oC
Amps Amps Ohm/km
mm2 Ohm/km M.Ohm/km kA kV/15 min
Trefoil / Flat Trefoil / Flat Trefoil / Flat
1.5 11.9 62 33 ( 1 Ph) 26 (1 Ph) - 0.17 4
2.5 7.14 57 45 (1 Ph) 35 (1 Ph) - 0.29 4
4 4.47 52 58 (1 Ph) 46 (1 Ph) - 0.46 4
6 2.97 44 74 (1 Ph) 58 (1 Ph) - 0.70 4
10 1.77 36 98 (1 Ph) 80 (1 Ph) - 1.16 4
16 1.12 26 98/107 86/100 0.110/0.254 1.86 4
25 0.708 26 125/138 120/135 0.107/0.242 2.91 4
35 0.514 22 151/165 145/170 0.097/0.228 4.07 4
50 0.379 22 178/196 180/205 0.096/0.189 5.81 4
70 0.262 19 218/240 225/260 0.094/0.210 8.14 4
95 0.189 18 263/289 280/320 0.091/0.203 11.05 4
120 0.150 16 298/329 330/375 0.088/0.196 13.95 4
150 0.122 16 338/374 380/430 0.086/0.192 17.44 4
185 0.0972 16 383/418 440/490 0.086/0.184 21.51 4
240 0.0740 16 436/481 530/590 0.082/0.174 27.91 4
300 0.0590 15 490/552 610/680 0.082/0.170 34.88 4
400 0.0461 14 579/632 740/920 0.078/0.163 46.51 4
500 0.0366 14 659/730 860/960 0.078/0.157 58.14 4
NYM
PVC Insulated and PVC Sheathed
(SPLN 42-2 1981)
ELECTRICAL CHARACTERISTIC
Resistance at 20oC Current Carrying Reactance
No. of Capacity Short Circuit Test
Size per
Cores. Conductor Insulator Current at 1 sec Voltage
Conductor
DC. Calculated - In air 30oC
- mm2 Ohm/km M.Ohm.km Amps Ohm/km kA kV/5 min
4 4.47 40 34 - 0.46 2
1
6 2.97 34 44 - 0.70 2
10 1.77 33 61 - 1.16 2
16 1.12 27 82 - 1.86 2
NYFGbY ( 3 Core)
PVC Insulated Galvanised, Flat Steel Wire Armoured, PVC Sheathed
(SPLN 43-2: 1981)
ELECTRICAL CHARACTERISTIC
Resistance at 20oC Current Carrying Capacity
No. of Short Circuit Test
Size
Cores. Conductor Insulator In ground In air Current at 1 Sec Voltage
DC. Calculated - 30oC 30oC
- mm2 Ohm/km M.Ohm.km Amps Amps kA kV/10 min
1.5 12.1 62 24 18 0.17 4
2.5 7.28 57 32 25 0.29 4
4 4.56 52 41 34 0.46 4
6 3.03 44 52 44 0.70 4
10 1.81 36 69 60 1.16 4
16 1.14 26 89 80 1.86 4
25 0.74 26 116 105 2.91 4
35 0.524 22 138 130 4.07 4
3
50 0.387 22 165 160 5.81 4
70 0.268 19 205 200 8.14 4
95 0.193 18 245 245 11.05 4
120 0.153 16 280 285 13.95 4
150 0.124 16 320 325 17.44 4
185 0.0991 16 355 370 21.51 4
240 0.0754 16 415 435 27.91 4
300 0.0601 16 465 500 34.88 4
NYFGbY ( 4 Core)
PVC Insulated, Galvanised Flat Steel Wire Armoured, PVC Sheathed
(SPLN 43-2: 1981)
ELECTRICAL CHARACTERISTIC
Resistance at 20oC Current Carrying Capacity
No. of Short Circuit
Size Conductor Insulator In ground In air Test Voltage
Cores. Current at 1 sec
DC. Calculated - 30oC 30oC
(x) mm2 Ohm/km M.Ohm.km Amps Amps kA kV/10 min
1.5 12.1 26 24 18 0.17 4
2.5 7.28 57 32 25 0.29 4
4 4.56 52 41 34 0.46 4
6 3.03 44 52 44 0.70 4
10 1.81 36 69 60 1.16 4
16 1.14 26 89 80 1.86 4
25 0.74 26 116 105 2.91 4
35 0.524 22 138 130 4.07 4
4
50 0.387 22 165 160 5.81 4
70 0.268 19 205 200 8.14 4
95 0.193 18 245 245 11.05 4
120 0.153 16 280 285 13.95 4
150 0.124 16 315 325 17.44 4
185 0.0991 16 355 370 21.51 4
240 0.0754 16 415 435 27.91 4
300 0.0601 15 465 500 34.88 4
INSULATED ALUMINIUM TWISTED
CONDUTORS FOR L. V. OVERHEAD LINE
ELECTRICAL CHARACTERISTICS
Permissible Currents
Nominal Sectional Resistance of Ambient Temperature
Area of Phase Conductor at 20oC
20oC 30oC 40oC
mm2 Ohm/km Amps Amps Amps
10 3.02 65 60 50
16 1.91 85 80 70
1/4" x 1" x 4000 5.81 290,500.00 1/4" x 6" x 4000 34.84 1,742,000.00
1/4" x 2" x 4000 11.62 581,000.00 3/8" x 3" x 4000 26.12 1,306,000.00
1/4" x 3" x 4000 17.42 871,000.00 3/8" x 6" x 4000 52.25 2,612,500.00
1/4" x 4" x 4000 23.24 1,162,000.00 1/2" x 3" x 4000 34.84 1,742,000.00
HARGA = Rp50,000 / Kg
(Exclude transportation)
TYPES OF DERATING FACTORS FOR CABLES
1.5) Derating Factor for Grouping Single Core Cable in Trefoil Formation (At 2D Apart)
NUMBER OF GROUP 1 2 3 4 5 6 8 10 Amps = 1 / No. of Groups
XLPE Cables 1.00 0.89 0.82 0.78 0.75 0.73 0.70 0.68
PVC Cables 1.00 0.90 0.82 0.79 0.76 0.74 0.71 0.69
1.6) Derating Factor for Grouping Single Core Cable in Flat Formation (At 70mm Apart)
NUMBER OF GROUP 1 2 3 4 5 6 8 10 Amps = 1 / No. of Groups
XLPE Cables 1.00 0.87 0.77 0.73 0.70 0.68 0.65 0.63
PVC Cables 1.00 0.87 0.78 0.74 0.70 0.68 0.65 0.63
3 2 x I x L / (S x A ) 3 x I x L x cos / (S x A)
4 KVA - meters for 5% Voltage Drop KVA - meters for 5% Voltage Drop
d) 35sq mm = 10,549