Air-Cooled Series R

Helical-Rotary Liquid Chiller

Model RTAC 120 to 400


(400 to 1500 kW 50 Hz)
Built for the Industrial and
Commercial Markets

Model RTAC size 155

RLC-PRC005-E4
Introduction

The Trane Model RTAC Air-Cooled What Is New


Helical-Rotary Chiller is the result of The RTAC offers high reliability
a search for higher reliability, higher coupled with greatly improved
energy efficiency, and lower sound energy efficiency, vastly reduced
levels for todays environment. physical footprint, and improved
In an effort to reduce energy acoustical performance, due to its
consumed by HVAC equipment and advanced design, low-speed, direct-
to continually produce chilled water, drive compressor, and proven
Trane has developed the Model Series R performance.
RTAC chiller with higher efficiencies The major advantages of the
and a more reliable design than any Series R, Model RTAC are:
other air-cooled chiller available on 99.5% reliability rate
the market today. Smaller physical footprint
Lower sound levels
The Model RTAC chiller uses the
Higher energy efficiency
proven design of the Trane helical-
Designed specifically for
rotary compressor, which embraces
operating with environmentally-
all of the design features that have
safe HFC-134a.
made the Trane helical-rotary
compressor liquid chillers such a The Series R Model RTAC helical-
success since 1987. rotary chiller is an industrial-grade
design, built for both the industrial
and commercial markets. It is ideal
for schools, hospitals, retailers,
office buildings, and industrial
applications.

Figure 1 - Model RTAC size 350

American Standard Inc. 2002 RLC-PRC005-E4


Contents

Introduction 2

Features and Benefits 4

Options 9

Application Considerations 10

Selection Procedure 13

General Data 14

Performance Data 28

Controls 42

Job Site Data 46

Electrical Data 47

Dimensional Data 50

Mechanical Specifications 55

RLC-PRC005-E4 3
Features and Benefits

The Series R Field-serviceable compressor for


Helical-Rotary Compressor easy maintenance.
Unequaled reliability. The next Suction-gas-cooled motor. The
generation Trane helical-rotary motor operates at lower
compressor is designed, built, temperatures for longer motor
and tested to the same life.
demanding and rugged standards Five minute start-to-start and two
as the Trane scroll compressors, minute stop-to-start anti-recycle
the centrifugal compressors, and timer allows for closer water-loop
the previous generation helical- temperature control.
rotary compressors used in both
air- and water-cooled chillers for
more than 15 years.
Years of research and testing. The
Trane helical-rotary compressor
has amassed thousands of hours
of testing, much of it at severe
operating conditions beyond
normal commercial air-
conditioning applications.
Proven track record. The Trane
Company is the worlds largest
manufacturer of large helical-
rotary compressors used for
refrigeration. Over 300,000
compressors worldwide have
proven that the Trane helical-
rotary compressor has a reliability
rate of greater than 99.5% in the
first year of operation
unequalled in the industry.
Resistance to liquid slugging. The
robust design of the Series R
compressor can ingest amounts
of liquid refrigerant that normally
would severely damage
reciprocating compressor valves,
piston rods, and cylinders.
Fewer moving parts. The helical-
rotary compressor has only two
rotating parts: the male rotor and
the female rotor. Unlike
reciprocating compressors, the
Trane helical-rotary compressor
has no pistons, connecting rods,
suction and discharge valves, or
mechanical oil pump. In fact, a
typical reciprocating compressor
has 15 times as many critical parts
as the Series R compressor. Fewer
moving parts leads to increased
reliability and longer life.
Direct-drive, low-speed, semi-
hermetic compressor for high
efficiency and high reliability.

4 RLC-PRC005-E4
Features and Benefits

Improved Acoustical Figure 2 - Cutaway of a compressor


Performance
Sound levels are reduced
significantly by addressing two
major sources: the compressor and
the refrigerant piping. First, the
compressor has been specifically
designed to minimize sound
generation. Second, the refrigerant
components and piping have been
optimized to reduce sound
propagation throughout the system.

Superior Efficiency Levels:


The Bar Has Been Raised
The standard-efficiency Trane Model
RTAC has COP levels up to
2.90 kW/kW [9.9 EER] (including
fans), while the premium-efficiency,
or high-efficiency, units leap to COP
levels of 3.10 kW/kW [10.58 EER]
(including fans).
The modern technology of the RTAC
with the efficient direct-drive
compressor, the unique evaporator
design, the electronic expansion
valve, and the revolutionary Tracer
Chiller Controls, has permitted Trane
to achieve these efficiency levels, Capacity Control and Load
unmatched in the industry. Matching
The combination patented
Precise Rotor Tip Clearances
unloading system on Trane helical-
Higher energy efficiency in a helical-
rotary compressors uses the
rotary compressor is obtained by
variable unloading valve for the
reducing the rotor tip clearances.
majority of the unloading function.
This next-generation compressor is
This allows the compressor to
no exception. With todays
modulate infinitely, to exactly match
advanced manufacturing
building load and to maintain
technology, clearances can be
chilled-water supply temperatures
controlled to even tighter
within 0.3C [0.5F] of the set
tolerances. This reduces the leakage
point. Reciprocating and helical-
between high- and low-pressure
rotary chillers that rely on stepped
cavities during compression,
capacity control must run at a
allowing for more efficient
capacity equal to or greater than the
compressor operation.
load, and typically can only
maintain water temperature to
around 1C [2F]. Much of this
excess capacity is lost because
overcooling goes toward removing
building latent heat, causing the
building to be dried beyond normal
comfort requirements. When the
load becomes very low, the
compressor also uses a step
unloader valve, which is a single
unloading step to achieve the
minimum unloading point of the
compressor. The result of this
design is optimized part-load
performance far superior to single
reciprocating compressors and
step-only helical-rotary
compressors.
RLC-PRC005-E4 5
Features and Benefits

Compact Physical Size Factory-Installed and Tested


The Trane Model RTAC 120 to 200 Controls and Options Speed
chiller averages a 20% reduction in Installation
physical footprint, when compared All Series R chiller options,
against the previous design. This including main power-supply
improvement makes the RTAC the disconnect, low ambient control,
smallest air-cooled chiller in the ambient temperature sensor, low
industry and a prime candidate for ambient lockout, communication
installations that have space interface and ice-making controls
constraints. All physical sizes were are factory installed and tested.
changed without sacrificing the side Some manufacturers send
clearances needed to supply fresh accessories in pieces to be field
airflow without coil starvationthe installed. With Trane, the customer
tightest operational clearances in saves on installation expense and
the industry. has assurance that ALL chiller
Close Spacing Installation controls and options have been
The air-cooled Series R chiller has tested and will function as
the tightest recommended side expected.
clearance in the industry,
1.2 meters, but that is not all. In
situations where equipment must
be installed with less clearance than
recommended, which frequently
occurs in retrofit applications,
restricted airflow is common.
Conventional chillers may not work
at all. However, the air-cooled Series
R chiller with the Adaptive Control
microprocessor will make as much
chilled water as possible given the
actual installed conditions, stay on-
line during any unforeseen
abnormal conditions, and optimize
its performance. Consult your sales
engineer for more details.
Factory Testing Means Trouble-Free
Start-up
All air-cooled Series R chillers are
given a complete functional test at
the factory. This computer-based
test program completely checks the
sensors, wiring, electrical
components, microprocessor
function, communication capability,
expansion valve performance, and
fans. In addition, each compressor
is run-tested to verify capacity and
efficiency. Where applicable, each
unit is factory preset to the
customers design conditions. An
example would be the leaving-
liquid temperature set point. The
result of this test program is that
the chiller arrives at the job site fully
tested and ready for operation.

6 RLC-PRC005-E4
Features and Benefits

Figure 3 - Ice storage demand cost Superior Control with constant supply of glycol solution.
savings Air-cooled chillers selected for these
Tracer Chiller Controls lower leaving-fluid temperatures
LOAD The Adaptive Control are also selected for efficient
microprocessor system enhances production of chilled fluid at
the air-cooled Series R chiller by nominal comfort-cooling conditions.
providing the very latest chiller The ability of Trane chillers to serve
ICE control technology. With the double duty in ice production and
Adaptive Control microprocessor, comfort cooling greatly reduces the
unnecessary service calls and capital cost of ice-storage systems.
unhappy tenants are avoided. The When cooling is required, ice-chilled
CHILLER unit does not nuisance-trip or glycol is pumped from the ice
unnecessarily shut down. Only storage tanks directly to the cooling
MN 6 A.M. NOON 6 P.M. MN
when the Tracer chiller controls have coils. No expensive heat exchanger
exhausted all possible corrective is required. The glycol loop is a
actions, and the unit is still violating sealed system, eliminating
an operating limit, will the chiller expensive annual chemical
shut down. Controls on other treatment costs. The air-cooled
equipment typically shut down the chiller is also available for comfort-
chiller, usually just when it is cooling duty at nominal cooling
needed the most. conditions and efficiencies. The
For Example: modular concept of glycol ice-
A typical five-year-old chiller with storage systems, and the proven
dirty coils might trip out on high- simplicity of Trane Tracer controls,
pressure cutout on a 38C [100F] allow the successful blend of
day in August. A hot day is just reliability and energy-saving
when comfort cooling is needed the performance in any ice-storage
most. In contrast, the air-cooled application.
Series R chiller with an Adaptive The ice-storage system is operated
Control microprocessor will stage in six different modes, each
fans on, modulate the electronic optimized for the utility cost at a
expansion valve, and modulate the particular time of day.
slide valve as it approaches a high- 1. Provide comfort cooling with
pressure cutout, thereby keeping chiller
the chiller on line when you need it 2. Provide comfort cooling with ice
the most.
3. Provide comfort cooling with ice
System Options: Ice Storage and chiller
Trane air-cooled chillers are well- 4. Freeze ice storage
suited for ice production. The
5. Freeze ice storage when comfort
unique ability to operate at
decreased ambient temperature cooling is required
while producing ice results in 6. Off
approximately the same amount of
work for the compressor. An air-
cooled machine typically switches
to ice production at night. Two
things happen under this
assumption. First, the leaving brine
temperature from the evaporator is
lowered to around -5.5 to -5C [22 to
24F]. Second, the ambient
temperature has typically dropped
about 8.3 to 11C [15 to 20F] from
the peak daytime ambient. This
effectively places a lift on the
compressors that is similar to
daytime running conditions. The
chiller can operate in lower ambient
at night and successfully produce
ice to supplement the next days
cooling demands.
The Model RTAC produces ice by
supplying ice storage tanks with a

RLC-PRC005-E4 7
Features and Benefits

Tracer optimization software


controls operation of the required
equipment and accessories to easily
move from one mode of operation
to another. For example: even with
ice-storage systems, there are
numerous hours when ice is neither
produced nor consumed, but saved.
In this mode, the chiller is the sole
source of cooling. For example, to
cool the building after all ice is
produced but before high electric al-
demand charges take effect, Tracer
sets the air-cooled chiller leaving-
fluid set point to its most efficient
setting and starts the chiller, chiller
pump, and load pump.
When electrical demand is high, the
ice pump is started and the chiller is
either demand limited or shut down
completely. Tracer controls have the
intelligence to optimally balance
the contribution of the ice and the
chiller in meeting the cooling load.
The capacity of the chiller plant is
extended by operating the chiller
and ice in tandem. Tracer rations the
ice, augmenting chiller capacity
while reducing cooling costs. When
ice is produced, Tracer will lower the
air-cooled chiller leaving-fluid set
point and start the chiller, ice and
chiller pumps, and other
accessories. Any incidental loads
that persists while producing ice
can be addressed by starting the
load pump and drawing spent
cooling fluid from the ice storage
tanks.
For specific information on ice
storage applications, contact your
local sales office.

8 RLC-PRC005-E4
Options

High Efficiency and Condenser Corrosion Protection Low Noise Version


Performance Option Copper fins and Black Epoxy Coated The unit is equipped with low-speed
This option provides oversized heat aluminium fins are available on all fans and a compressor sound-
exchangers with two purposes. sizes for corrosion protection. Job attenuating enclosure. All the
One, it allows the unit to be more site conditions should be matched sound-emitting parts, like
energy efficient. Two, the unit will with the appropriate condenser fin refrigerant lines are acoustically
have enhanced operation in high- materials to inhibit coil corrosion treated with sound-absorbent
ambient conditions. and ensure extended equipment material.
Low-Temperature Brine life. Night Noise Setback
The hardware and software on the Service Valves At night, on contact closure all the
unit are factory set to handle low- Provides a service valve on the fans run at low speed, bringing the
temperature brine applications, suction lines of each circuit to overall sound level further down.
typically below 5C [41F]. facilitate compressor servicing. Only available on Low Noise,
Ice Making High-Ambient Option non High Ambient units.
The unit controls are factory set to The high-ambient option consists of Ground Fault Detection
handle ice making for thermal special control logic to permit high- Sensing ground current for
storage applications. ambient (up to 52C [125F]) improved chiller protection.
Tracer Summit Communication operation. This option offers the Pressure Gauges
Interface best performance when coupled A set of two pressure gauges per
Permits bi-directional with the premium efficiency and refrigerant circuit, one for low
communication to the Trane performance option. pressure and one for high pressure.
Integrated Comfort system. Low-Ambient Option Flow Switch
LonTalk Communication Interface The low-ambient option consists of For field installation on the chilled-
special control logic and fans to water outlet connection.
LCI-C
permit low-ambient (down to -18C Under/Over-voltage protection
Provides the LonMark chiller
[0F]) operation. Controls the variation of the power
profile input/outputs for use with a
generic BAS (Building Automation Power Disconnect Switch supply voltage. If the value exceeds
System) A disconnect switch with a through- the minimum or maximum voltage,
the-door handle, plus compressor the unit is shut down.
Remote Input Options
protection fuses, is provided to IP20 protection
Permits remote chilled-liquid set
disconnect main power. Provides a protection against direct
point, remote current-limit set point,
or both, by accepting a 4-20 mA or Neoprene Isolators contacts inside the control panel.
2-10 VDC analog signal. Isolators provide isolation between The current-carrying parts are
the chiller and the structure to help shrouded in order to prevent
Remote Output Options
eliminate vibration transmission. accidental contact.
Permits alarm relay outputs, ice-
Neoprene isolators are more
making outputs, or both.
effective and recommended over
Protection Grilles spring isolators.
Protection grilles cover the
Victaulic Connection Kit
complete condensing coils and the
Provides a kit that includes a set of
service areas beneath the coils.
two pipe stubs and Victaulic
Coil Protection couplings.
A coated wire mesh that covers the
condenser coils only.

RLC-PRC005-E4 9
Application Considerations

Figure 4 - GPM Out of Range scaling, stratification, and poor


control. The maximum evaporator
10C water flow rate is also given in the
5 L/s general data section. Flow rates
exceeding those listed may result in
10C excessive tube erosion.
CV Pump
7.6 L/s
5 L/s Flow Rates Out of Range
Many process cooling jobs require
flow rates that cannot be met with
the minimum and maximum
Load published values within the Model
10C RTAC evaporator. A simple piping
2.5 L/s change can alleviate this problem.
13.7C For example: a plastic injection
7.6 L/s molding process requires 5.0 L/s [80
gpm] of 10C [50F] water and
returns that water at 15.6C [60F].
15.6C The selected chiller can operate at
CV pump
5 L/s these temperatures, but has a
7.5 L/s
minimum flow rate of 7.6 L/s [120
Important chillers. Use of either will lead to a gpm]. The following system can
Certain application constraints shortened chiller life. Trane satisfy the process.
should be considered when sizing, encourages the employment of a Flow Control
selecting, and installing Trane air- reputable water-treatment Trane requires the chilled water flow
cooled Series R chillers. Unit and specialist, familiar with local water control in conjunction with the Air-
system reliability is often dependent conditions, to assist in this Cooled Series R Chiller to be done
on properly and completely determination and in the by the chiller.
complying with these establishment of a proper water- This will allow the chiller to protect
considerations. When the treatment program. itself in potentially harmful
application varies from the Effect of Altitude on Capacity conditions.
guidelines presented, it should be Air-cooled Series R chiller capacities Leaving-Water Temperature Limits
reviewed with your local sales given in the performance data Trane air-cooled Series R chillers
engineer. tables are for use at sea level. At have three distinct leaving-water
Unit Sizing elevations substantially above sea categories: standard, low
Unit capacities are listed in the level, the decreased air density will temperature, and ice making. The
performance data section. reduce condenser capacity and, standard leaving-solution
Intentionally oversizing a unit to therefore, unit capacity and temperature range is 4.4 to 15.6C
ensure adequate capacity is not efficiency. [40 to 60F]. Low-temperature
recommended. Erratic system Ambient Limitations machines produce leaving-liquid
operation and excessive Trane air-cooled Series R chillers are temperatures less than 4.4C [40F].
compressor cycling are often a designed for year-round operation Since liquid supply temperature set
direct result of an oversized chiller. over a range of ambient points less than 4.4C [40F] result
In addition, an oversized unit is temperatures. The air-cooled Model in suction temperatures at or below
usually more expensive to RTAC chiller will operate in ambient the freezing point of water, a glycol
purchase, install, and operate. If temperatures of 0 to 46C [32 to solution is required for all low-
oversizing is desired, consider using 115F]. Selecting the high-ambient temperature machines. Ice-making
two units. option will allow the chiller to machines have a leaving-liquid
Water Treatment operate in ambient temperatures of temperature range of -6.7 to 15.6C
Dirt, scale, products of corrosion, 52C [125F], and selecting the low- [20 to 60F]. Ice-making controls
and other foreign material will ambient option will increase the include dual set point controls and
adversely affect heat transfer operational capability of the water safeties for ice making and
between the water and system chiller to ambient temperatures as standard cooling capabilities.
components. Foreign matter in the low as -18C [0F]. For operation Consult your local sales engineer
chilled-water system can also outside of these ranges, contact the for applications or selections
increase pressure drop and, local sales office. involving low temperature or ice
consequently, reduce water flow. making machines. The maximum
Water Flow Limits water temperature that can be
Proper water treatment must be The minimum water flow rates are
determined locally, depending on circulated through an evaporator
given in Tables G1 - G16. Evaporator when the unit is not operating is
the type of system and local water flow rates below the tabulated
characteristics. Neither salt nor 42C [108F].
values will result in laminar flow
brackish water is recommended for and cause freeze-up problems,
use in Trane air-cooled Series R

10 RLC-PRC005-E4
Application Considerations

Figure 5 - Temperature Out of Range pump is unnecessary. The


15.6C 29.4C evaporator in the Model RTAC can
2.2 L/s 7.6 L/s withstand up to 50 percent water
flow reduction as long as this flow
15.6C
CV Pump
is equal to or above the minimum
7.6 L/s flow-rate requirements. The
microprocessor and capacity
control algorithms are designed to
take a maximum of 10 percent
Load change in water flow rate per
minute.
15C 35C
Ice Storage Provides
5.4 L/s 5.4 L/s
21C Reduced Electrical Demand
7.6 L/s
An ice-storage system uses a
standard chiller to make ice at
night, when utilities charge less for
35C 35C
CV Pump 7.6 L/s
electricity. The ice supplements, or
2.2 L/s
even replaces, mechanical cooling
during the day, when utility rates
are at their highest. This reduced
Leaving-Water Temperature temperature drops of less than need for cooling results in big
Out of Range 3.3C [6F] may result in inadequate utility cost savings.
Many process cooling jobs require refrigerant superheat. Sufficient Another advantage of ice storage is
temperature ranges that cannot be superheat is always a primary standby cooling capacity. If the
met with the minimum and concern in any direct-expansion chiller is unable to operate, one or
maximum published values for the refrigerant system and is especially two days of ice may still be
Model RTAC evaporator. A simple important in a package chiller available to provide cooling. In that
piping change can alleviate this where the evaporator is closely period of time, the chiller can be
problem. For example: a laboratory coupled to the compressor. When repaired before building occupants
load requires 7.6 L/s [120 gpm] of temperature drops are less than feel any loss of comfort.
water entering the process at 29.4C 3.3C [6F], an evaporator
[85F] and returning at 35C [95F]. runaround loop may be required. The Trane Model RTAC chiller is
The accuracy required is higher uniquely suited to low-temperature
Variable Flow in the Evaporator
than the cooling tower can give. The applications like ice storage
An attractive chilled-water system
selected chiller has adequate because of the ambient relief
option may be a variable primary
capacity, but has a maximum experienced at night. This allows
flow (VPF) system. VPF systems
leaving-chilled-water temperature of the Model RTAC chiller to produce
present building owners with
15.6C [60F]. ice efficiently, with less stress on
several cost-saving benefits that are
In the example shown, both the the machine.
directly related to the pumps. The
chiller and process flow rates are most obvious cost savings result Simple and smart control strategies
equal. This is not necessary. For from eliminating the secondary are another advantage the Model
example, if the chiller had a higher distribution pump, which in turn RTAC chiller offers for ice-storage
flow rate, there would be more avoids the expense incurred with applications. Trane Tracer building
water bypassing and mixing with the associated piping connections management systems can actually
warm water. (material, labor), electrical service, anticipate how much ice needs to
Supply-Water Temperature Drop and variable-frequency drive. be made at night, and operate the
The performance data for the Trane Building owners often cite pump- system accordingly. The controls
air-cooled Series R chiller is based related energy savings as the are integrated right into the chiller.
on a chilled-water temperature drop reason that prompted them to Two wires and preprogrammed
of 6C [10.8F]. Chilled-water install a VPF system. With the help software dramatically reduce field
temperature drops from 3.3 to 10C of a software analysis tool such as installation cost and complex
[6 to 18F] may be used as long as System Analyzer, TRACE, or programming.
minimum and maximum water DOE-2, you can determine whether Short Water Loops
temperature, and minimum and the anticipated energy savings The proper location of the
maximum flow rates, are not justify the use of variable primary temperature control sensor is in the
violated. Temperature drops outside flow in a particular application. It supply (outlet) water connection or
this range are beyond the optimum may also be easier to apply variable pipe. This location allows the
range for control, and may primary flow in an existing chilled- building to act as a buffer and
adversely affect the water plant. Unlike the decoupled assures a slowly-changing return-
microcomputers ability to maintain design, the bypass can be water temperature. If there is not a
an acceptable supply-water positioned at various points in the sufficient volume of water in the
temperature range. Further, chilled-water loop and an additional system to provide an adequate

RLC-PRC005-E4 11
Application Considerations

buffer, temperature control can be Typical Unit Installation


lost, resulting in erratic system Outdoor HVAC equipment must be
operation and excessive located to minimize noise and
compressor cycling. A short water vibration transmission to the
loop has the same effect as occupied spaces of the building
attempting to control using the structure it serves. If the equipment
building return water. Typically, a must be located in close proximity
two-minute water loop is sufficient to a building, it could be placed next
to prevent a short water loop. to an unoccupied space such as a
Therefore, as a guideline, ensure storage room, mechanical room,
that the volume of water in the etc. It is not recommended to locate
evaporator loop equals or exceeds the equipment near occupied,
two times the evaporator flow rate sound sensitive areas of the
per minute. For a rapidly changing building or near windows. Locating
load profile, the amount of volume the equipment away from structures
should be increased. To prevent the will also prevent sound reflection,
effect of a short water loop, the which can increase levels at
following item should be given property lines, or other sensitive
careful consideration: a storage points. When physically isolating
tank or larger header pipe to the unit from structures, it is a good
increase the volume of water in the idea to not use rigid supports, and
system and, therefore, reduce the to eliminate any metal-to-metal or
rate of change of the return water hard material contact, when
temperature. possible. This includes replacing
Applications Types spring or metal weave isolation
Comfort cooling with elastomeric isolators. Figure 6
illustrates isolation
Industrial process cooling
recommendations for the RTAC.
Ice or thermal storage
Low-temperature process cooling.

Figure 6 - Unit isolation recommendations

12 RLC-PRC005-E4
Selection Procedure

The chiller capacity tables cover the Selection procedure English units
most frequently encountered 1 ton = 3.5168 kW
leaving-liquid temperatures. The Evaporator flow rate in gpm =
tables reflect a 6C [10.8F] 24 x tons delta T (F)
temperature drop through the Delta T (F) = delta T (C) x 1.8
evaporator. For other temperature 1 gpm = 0.06309 L/s
drops, apply the appropriate
1 ft WG = 3 kPa
performance data adjustment
factors. For chilled brine selections, EER = COP 0.293
contact your local sales office. Minimun Leaving Chilled Water
To select a Trane air-cooled Series Temperature Setpoint
R chiller, the following The minimum leaving chilled water
information is required: temperature setpoint for water is
Selection Procedure SI Units 4.5C. For those applications
requiring lower setpoints, a glycol
1 solution must be used. Contact your
Design load in kW of refrigeration local sales office for additional
2 information
Design chilled-water temperature
drop
3
Design leaving-chilled-water
temperature
4
Design ambient temperature
Evaporator flow rates can be
determined by using the following
formula:
L/s = kW (capacity) x 0.239
temperature drop (C)
To determine the evaporator
pressure drop we use the flow rate
(L/s) and the evaporator water
pressure drop Figure P-1.
5
The final unit selection is:
Quantity (1) RTAC 140
Cooling capacity = 492.9 kW
Design ambient temperature 35C
Entering chilled-water
temperatures = 12C
Leaving chilled-water
temperatures = 7C
Chilled-water flow rate = 23.51 L/s
Evaporator water pressure
drop = 37 kPa
Compressor power input =
159.3 kW
Unit COP = 2.85 kW/kW
Contact the local sales engineer for
a proper selection at the given
operating conditions.

RLC-PRC005-E4 13
General Data

SI Units
Table G-1 - RTAC 140-200 Standard
Size 140 155 170 185 200
Compressor
Quantity 2 2 2 2 2
Nominal Size (1) tons 70/70 70/85 85/85 85/100 100/100
Evaporator
Evaporator Model H140 H155 H170 H185 H200
Water Storage l 112 122 127 135 147
Minimum Flow l/s 12 14 13 14 16
Maximum Flow l/s 44 48 48 50 54
Number of water passes 2 2 2 2 2
Condenser
Qty of Coils 4 4 4 4 4
Coil Length mm 3962/3962 4572/3962 4572/4572 5486/4572 5486/5486
Coil Height mm 1067 1067 1067 1067 1067
Fin series fins/ft 192 192 192 192 192
Number of Rows 3 3 3 3 3
Condenser Fans
Quantity (1) 4/4 5/4 5/5 6/5 6/6
Diameter mm 762 762 762 762 762
Total Air Flow m3/s 35.82 39.53 43.22 47.55 51.88
Nominal RPM 915 915 915 915 915
Tip Speed m/s 36.48 36.48 36.48 36.48 36.48
Motor kW kW 2.05 2.05 2.05 2.05 2.05
Min Starting/Operating Ambient(2)
Standard Unit C 0 0 0 0 0
Low Ambient Unit C -18 -18 -18 -18 -18
General Unit
Refrigerant HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a
No. Of independent
Refrigerant Circuits 2 2 2 2 2
% Minimum Load (3) 15 15 15 15 15
Refrigerant Charge (1) kg 75/75 79/75 79/79 113/108 113/113
Oil Charge (1) l 7.5/7.5 7.5/7.5 7.5/7.5 10/7.5 10/10
Operating Weight (4) kg 4533 4709 4846 5418 5539
Shipping Weight (4) kg 4435 4601 4744 5309 5418

Table G-2 - RTAC 120-200 High Efficiency


Size 120 130 140 155 170 185 200
Compressor
Quantity 2 2 2 2 2 2 2
Nominal Size (1) tons 60/60 60/70 70/70 70/85 85/85 85/100 100/100
Evaporator
Evaporator Model H140 H155 H170 H185 H200 H220 H240
Water Storage l 112 122 127 135 147 146 159
Minimum Flow l/s 12 14 13 14 16 14 16
Maximum Flow l/s 44 48 48 50 54 50 54
Number of water passes 2 2 2 2 2 2 2
Condenser
Qty of Coils 4 4 4 4 4 4 4
Coil Length mm 3962/3962 4572/3962 4572/4572 5486/4572 5486/5486 6400/2486 6400/6400
Coil Height mm 1067 1067 1067 1067 1067 1067 1067
Fin series fins/ft 192 192 192 192 192 192 192
Number of Rows 3 3 3 3 3 3 3
Condenser Fans
Quantity (1) 4/4 5/4 5/5 6/5 6/6 7/6 7/7
Diameter mm 762 762 762 762 762 762 762
Total Air Flow m3/s 35.82 39.53 43.22 47.55 51.88 56.17 60.47
Nominal RPM 915 915 915 915 915 915 915
Tip Speed m/s 36.48 36.48 36.48 36.48 36.48 36.48 36.48
Motor kW kW 2.05 2.05 2.05 2.05 2.05 2.05 2.05
Min Starting/Operating Ambient(2)
Standard Unit C 0 0 0 0 0 0 0
Low Ambient Unit C -18 -18 -18 -18 -18 -18 -18
General Unit
Refrigerant HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a
No. Of independent
Refrigerant Circuits 2 2 2 2 2 2 2
% Minimum Load (3) 15 15 15 15 15 15 15
Refrigerant Charge (1) kg 75/75 79/75 79/79 113/108 113/113 118/113 118/118
Oil Charge (1) l 7.5/7.5 7.5/7.5 7.5/7.5 7.5/7.5 7.5/7.5 10/7.5 10/10
Operating Weight (4) kg 4514 4568 4580 5231 5482 6056 6169
Shipping Weight (4) kg 4416 4460 4478 5122 5361 5936 6036

14 RLC-PRC005-E4
General Data

SI Units
Table G-3 - RTAC 140-200 Low Noise Standard
Size 140 155 170 185 200
Compressor
Quantity 2 2 2 2 2
Nominal Size (1) tons 70/70 70/85 85/85 85/100 100/100
Evaporator
Evaporator Model H140 H155 H170 H185 H200
Water Storage l 112 122 127 135 147
Minimum Flow l/s 12 14 13 14 16
Maximum Flow l/s 44 48 48 50 54
Number of water passes 2 2 2 2 2
Condenser
Qty of Coils 4 4 4 4 4
Coil Length mm 3962/3962 4572/3962 4572/4572 5486/4572 5486/5486
Coil Height mm 1067 1067 1067 1067 1067
Fin series fins/ft 192 192 192 192 192
Number of Rows 3 3 3 3 3
Condenser Fans
Quantity (1) 4/4 5/4 5/5 6/5 6/6
Diameter mm 762 762 762 762 762
Total Air Flow m3/s 25.61 28.27 30.93 34.02 37.11
Nominal RPM 680 680 680 680 680
Tip Speed m/s 27.5 27.5 27.5 27.5 27.5
Motor kW kW 1.05 1.05 1.05 1.05 1.05
Min Starting/Operating Ambient(2)
Standard Unit C 0 0 0 0 0
Low Ambient Unit C -18 -18 -18 -18 -18
General Unit
Refrigerant HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a
No. Of independent
Refrigerant Circuits 2 2 2 2 2
% Minimum Load (3) 15 15 15 15 15
Refrigerant Charge (1) kg 75/75 79/75 79/79 113/108 113/113
Oil Charge (1) l 7.5/7.5 7.5/7.5 7.5/7.5 10/7.5 10/10
Operating Weight (4) kg 4623 4799 4936 5508 5629
Shipping Weight (4) kg 4525 4691 4834 5399 5508

RLC-PRC005-E4 15
General Data

SI Units
Table G-4 - RTAC 120-200 High Efficiency Low Noise
Size 120 130 140 155 170 185 200
Compressor
Quantity 2 2 2 2 2 2 2
Nominal Size (1) tons 60/60 60/70 70/70 70/85 85/85 85/100 100/100
Evaporator
Evaporator Model H140 H155 H170 H185 H200 H220 H240
Water Storage l 112 122 127 135 147 146 159
Minimum Flow l/s 12 14 13 14 16 14 16
Maximum Flow l/s 44 48 48 50 54 50 54
Number of water passes 2 2 2 2 2 2 2
Condenser
Qty of Coils 4 4 4 4 4 4 4
Coil Length mm 3962/3962 4572/3962 4572/4572 5486/4572 5486/5486 6400/2486 6400/6400
Coil Height mm 1067 1067 1067 1067 1067 1067 1067
Fin series fins/ft 192 192 192 192 192 192 192
Number of Rows 3 3 3 3 3 3 3
Condenser Fans
Quantity (1) 4/4 5/4 5/5 6/5 6/6 7/6 7/7
Diameter mm 762 762 762 762 762 762 762
Total Air Flow m3/s 25.61 28.27 30.93 34.02 37.11 40.23 43.34
Nominal RPM 680 680 680 680 680 680 680
Tip Speed m/s 27.5 27.5 27.5 27.5 27.5 27.5 27.5
Motor kW kW 1.05 1.05 1.05 1.05 1.05 1.05 1.05
Min Starting/Operating Ambient(2)
Standard Unit C 0 0 0 0 0 0 0
Low Ambient Unit C -18 -18 -18 -18 -18 -18 -18
General Unit
Refrigerant HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a
No. Of independent
Refrigerant Circuits 2 2 2 2 2 2 2
% Minimum Load (3) 15 15 15 15 15 15 15
Refrigerant Charge (1) kg 75/75 79/75 79/79 113/108 113/113 118/113 118/118
Oil Charge (1) l 7.5/7.5 7.5/7.5 7.5/7.5 7.5/7.5 7.5/7.5 10/7.5 10/10
Operating Weight (4) kg 4604 4658 4670 5321 5572 6146 6259
Shipping Weight (4) kg 4506 4550 4568 5212 5451 6026 6126

Notes:
1. Data containing information on two circuits shown as follows: ckt1/ckt2
2. Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
3. Percent minimum load is for total machine at 10C ambient and 7C leaving chilled water temp. Not each individual circuit.
4. With aluminium fins

16 RLC-PRC005-E4
General Data

SI Units
Table G-5 - General Data RTAC 250-400 Standard
Size 250 275 300 350 375 400
Compressor
Quantity 3 3 3 4 4 4
Nominal Size (1) tons 70-70/100 85-85/100 100-100/100 85-85/85-85 100-100/85-85 100-100/100-100
Evaporator
Evaporator Model F250 F270 F300 F340 F370 F400
Water Storage L 205.9 228.2 250.6 267.2 277.4 306.2
Minimum Flow L/s 15.3 17.3 19.4 28.8 31.6 34.4
Maximum Flow L/s 47.1 57.3 67.5 82.8 91.7 104.5
Condenser
Quantity of Coils 4/4 4/4 4/4 4/4 4/4 4/4
Coil Length mm 3962/2743 4572/2743 5486/2743 4572/4572 5486/4572 5486/5486
Coil Height mm 1067 1067 1067 1067 1067 1067
Fin series fins/ft 192 192 192 192 192 192
Number of Rows 3 3 3 3 3 3
Condenser Fans
Quantity (1) 8/6 10/6 12/6 10/10 12/10 12/12
Diameter mm 762 762 762 762 762 762
Total Air Flow m3/s 61.8 69.2 77.8 86.4 95.1 103.7
Nominal RPM 915 915 915 915 915 915
Tip Speed m/s 36.48 36.48 36.48 36.48 36.48 34.48
Motor kW kW 2.05 2.05 2.05 2.05 2.05 2.05
Minimum Starting/Operating Ambient (2)
Standard Unit C 0 0 0 0 0 0
Low-Ambient Unit C -18 -18 -18 -18 -18 -18
General Unit
Refrigerant HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a
Number of Independent
Refrigerant Circuits 2 2 2 2 2 2
% Minimum Load (3) 13 13 13 10 10 10
Refrigerant Charge (1) kg 141/93 154/93 179/93 154/154 179/154 179/179
Oil Charge (1) L 18/11 18/11 20/11 18/18 20/18 20/20
Operating Weight (4) kg 8760 9560 10270 11790 12290 12890
Shipping Weight (4) kg 8550 9330 10020 11520 12010 12530

RLC-PRC005-E4 17
General Data

SI Units
Table G-6 - General Data RTAC 250-400 High Efficiency
Size 250 275 300 350 375 400
Compressor
Quantity 3 3 3 4 4 4
Nominal Size (1) tons 70-70/100 85-85/100 100-100/100 85-85/85-85 100-100/85-85 100-100/100-100
Evaporator
Evaporator Model F300 F320 F320 F400 F440 F480
Water Storage L 250.6 268.4 268.4 306.2 329.7 352.8
Minimum Flow L/s 19.4 21.6 21.6 28.8 31.6 34.4
Maximum Flow L/s 67.5 75.2 75.2 104.5 114.7 124.9
Condenser
Quantity of Coils 4/4 4/4 4/4 4/4 4/4 4/4
Coil Length mm 4572/2743 5486/3658 6401/3658 5486/5486 6401/5486 6401/6401
Coil Height mm 1067 1067 1067 1067 1067 1067
Fin series fins/ft 192 192 192 192 192 192
Number of Rows 3 3 3 3 3 3
Condenser Fans
Quantity (1) 10/6 12/6 14/6 12/12 14/12 14/14
Diameter mm 762 762 762 762 762 762
Total Air Flow m3/s 69.1 80.8 89.4 103.6 112.3 120.9
Nominal RPM 915 915 915 915 915 915
Tip Speed m/s 36.48 36.48 36.48 36.48 36.48 36.48
Motor kW kW 2.05 2.05 2.05 2.05 2.05 2.05
Minimum Starting/Operating Ambient (2)
Standard Unit C 0 0 0 0 0 0
Low-Ambient Unit C -18 -18 -18 -18 -18 -18
General Unit
Refrigerant HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a
Number of Independent
Refrigerant Circuits 2 2 2 2 2 2
% Minimum Load (3) 13 13 13 10 10 10
Refrigerant Charge (1) kg 154/93 179/111 195/111 179/179 195/179 195/195
Oil Charge (1) L 18/11 18/11 20/11 18/18 20/18 20/20
Operating Weight (4) kg 9280 10710 11240 12960 13640 14430
Shipping Weight (4) kg 9020 10435 10970 12650 13310 14030

18 RLC-PRC005-E4
General Data

SI Units
Table G-7 - General Data RTAC 250-400 Low Noise Standard
Size 250 275 300 350 375 400
Compressor
Quantity 3 3 3 4 4 4
Nominal Size (1) tons 70-70/100 85-85/100 100-100/100 85-85/85-85 100-100/85-85 100-100/100-100
Evaporator
Evaporator Model F250 F270 F300 F340 F370 F400
Water Storage L 205.9 228.2 250.6 267.2 277.4 306.2
Minimum Flow L/s 15.3 17.3 19.4 28.8 31.6 34.4
Maximum Flow L/s 47.1 57.3 67.5 82.8 91.7 104.5
Condenser
Quantity of Coils 4/4 4/4 4/4 4/4 4/4 4/4
Coil Length mm 3962/2743 4572/2743 5486/2743 4572/4572 5486/4572 5486/5486
Coil Height mm 1067 1067 1067 1067 1067 1067
Fin series fins/ft 192 192 192 192 192 192
Number of Rows 3 3 3 3 3 3
Condenser Fans
Quantity (1) 8/6 10/6 12/6 10/10 12/10 12/12
Diameter mm 762 762 762 762 762 762
Total Air Flow m3/s 44.2 49.5 55.7 61.9 68.0 74.2
Nominal RPM 680 680 680 680 680 680
Tip Speed m/s 27.5 27.5 27.5 27.5 27.5 27.5
Motor kW kW 1.05 1.05 1.05 1.05 1.05 1.05
Minimum Starting/Operating Ambient (2)
Standard Unit C 0 0 0 0 0 0
Low-Ambient Unit C -18 -18 -18 -18 -18 -18
General Unit
Refrigerant HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a
Number of Independent
Refrigerant Circuits 2 2 2 2 2 2
% Minimum Load (3) 13 13 13 10 10 10
Refrigerant Charge (1) kg 141/93 154/93 179/93 154/154 179/154 179/179
Oil Charge (1) L 18/11 18/11 20/11 18/18 20/18 20/20
Operating Weight (4) kg 8895 9695 10405 11970 12470 13070
Shipping Weight (4) kg 8685 9465 10155 11700 12190 12710

RLC-PRC005-E4 19
General Data

SI Units
Table G-8 - General Data RTAC 250-400 High Efficiency Low Noise
Size 250 275 300 350 375 400
Compressor
Quantity 3 3 3 4 4 4
Nominal Size (1) tons 70-70/100 85-85/100 100-100/100 85-85/85-85 100-100/85-85 100-100/100-100
Evaporator
Evaporator Model F300 F320 F320 F400 F440 F480
Water Storage L 250.6 268.4 268.4 306.2 329.7 352.8
Minimum Flow L/s 19.4 21.6 21.6 28.8 31.6 34.4
Maximum Flow L/s 67.5 75.2 75.2 104.5 114.7 124.9
Condenser
Quantity of Coils 4/4 4/4 4/4 4/4 4/4 4/4
Coil Length mm 4572/2743 5486/3658 6401/3658 5486/5486 6401/5486 6401/6401
Coil Height mm 1067 1067 1067 1067 1067 1067
Fin series fins/ft 192 192 192 192 192 192
Number of Rows 3 3 3 3 3 3
Condenser Fans
Quantity (1) 10/6 12/6 14/6 12/12 14/12 14/14
Diameter mm 762 762 762 762 762 762
Total Air Flow m3/s 49.4 57.9 64.1 74.1 80.3 86.5
Nominal RPM 680 680 680 680 680 680
Tip Speed m/s 27.5 27.5 27.5 27.5 27.5 27.5
Motor kW kW 1.05 1.05 1.05 1.05 1.05 1.05
Minimum Starting/Operating Ambient (2)
Standard Unit C 0 0 0 0 0 0
Low-Ambient Unit C -18 -18 -18 -18 -18 -18
General Unit
Refrigerant HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a
Number of Independent
Refrigerant Circuits 2 2 2 2 2 2
% Minimum Load (3) 13 13 13 10 10 10
Refrigerant Charge (1) kg 154/93 179/111 195/111 179/179 195/179 195/195
Oil Charge (1) L 18/11 18/11 20/11 18/18 20/18 20/20
Operating Weight (4) kg 9415 10845 11375 13140 13820 14610
Shipping Weight (4) kg 9155 10570 11105 12830 13490 14210
Notes:
1. Data containing information on two circuits shown as follows: ckt1/ckt2
2. Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
3. Percent minimum load is for total machine at 10C (50F) ambient and 7C (44F) leaving chilled water temperature, not each individual circuit.
4. With aluminium fins.

20 RLC-PRC005-E4
General Data

English Units
Table G-9 - RTAC 140-200 Standard
Size 140 155 170 185 200
Compressor
Quantity 2 2 2 2 2
Nominal Size (1) tons 70/70 70/85 85/85 85/100 100/100
Evaporator
Evaporator Model H140 H155 H170 H185 H200
Water Storage gallons 29.6 32.2 33.6 35.7 38.8
Minimum Flow gpm 190.2 221.9 206.1 221.9 253.6
Maximum Flow gpm 697.5 760.9 760.9 792.6 856.0
Number of water passes 2 2 2 2 2
Condenser
Qty of Coils 4 4 4 4 4
Coil Length ft 13/13 15/13 15/15 18/15 18/18
Coil Height ft 3.5 3.5 3.5 3.5 3.5
Fin series fins/ft 192 192 192 192 192
Number of Rows 3 3 3 3 3
Condenser Fans
Quantity (1) 4/4 5/4 5/5 6/5 6/6
Diameter in. 30 30 30 30 30
Total Air Flow cfm 75867 83725 91540 100710 109882
Nominal RPM 915 915 915 915 915
Tip Speed ft/s 120 120 120 120 120
Motor kW kW 2.05 2.05 2.05 2.05 2.05
Min Starting/Operating Ambient(2)
Standard Unit F 32 32 32 32 32
Low Ambient Unit F 0 0 0 0 0
General Unit
Refrigerant HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a
No. Of independent
Refrigerant Circuits 2 2 2 2 2
% Minimum Load (3) 15 15 15 15 15
Refrigerant Charge (1) lb 165/165 174/165 174/174 249/238 249/249
Oil Charge (1) gallons 2/2 2/2 2/2 2.6/2 2.6/2.6
Operating Weight (4) lb 9985 10372 10674 11934 12200
Shipping Weight (4) lb 9769 10134 10449 11694 11934

Table G-10 - RTAC 120-200 High Efficiency


Size 120 130 140 155 170 185 200
Compressor
Quantity 2 2 2 2 2 2 2
Nominal Size (1) tons 60/60 60/70 70/70 70/85 85/85 85/100 100/100
Evaporator
Evaporator Model H140 H155 H170 H185 H200 H220 H240
Water Storage gallons 29.6 32.2 33.6 35.7 38.8 38.6 42.0
Minimum Flow gpm 190.2 221.9 206.1 221.9 253.6 221.9 253.6
Maximum Flow gpm 697.5 760.9 760.9 792.6 856.0 792.6 856.0
Number of water passes 2 2 2 2 2 2 2
Condenser
Qty of Coils 4 4 4 4 4 4 4
Coil Length ft 13/13 15/13 15/15 18/15 18/18 21/18 21/21
Coil Height ft 3.5 3.5 3.5 3.5 3.5 3.5 3.5
Fin series fins/ft 192 192 192 192 192 192 192
Number of Rows 3 3 3 3 3 3 3
Condenser Fans
Quantity (1) 4/4 5/4 5/5 6/5 6/6 7/6 7/7
Diameter in. 30 30 30 30 30 30 30
Total Air Flow cfm 75867 83725 91540 100710 109882 118968 128075
Nominal RPM 915 915 915 915 915 915 915
Tip Speed ft/s 120 120 120 120 120 120 120
Motor kW kW 2.05 2.05 2.05 2.05 2.05 2.05 2.05
Min Starting/Operating Ambient(2)
Standard Unit F 32 32 32 32 32 32 32
Low Ambient Unit F 0 0 0 0 0 0 0
General Unit
Refrigerant HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a
No. Of independent
Refrigerant Circuits 2 2 2 2 2 2 2
% Minimum Load (3) 15 15 15 15 15 15 15
Refrigerant Charge (1) lb 165/165 174/165 174/174 249/238 249/249 260/249 260/260
Oil Charge (1) gallons 2/2 2/2 2/2 2/2 2/2 2.6/2 2.6/2.6
Operating Weight (4) lb 9943 10062 10088 11522 12075 13339 13588
Shipping Weight (4) lb 9727 9824 9863 11282 11808 13075 13295

RLC-PRC005-E4 21
General Data

English Units
Table G-11 - RTAC 120-200 Low Noise Standard
Size 140 155 170 185 200
Compressor
Quantity 2 2 2 2 2
Nominal Size (1) tons 70/70 70/85 85/85 85/100 100/100
Evaporator
Evaporator Model H140 H155 H170 H185 H200
Water Storage gallons 3.2 3.7 3.4 3.7 4.2
Minimum Flow gpm 697.5 760.9 760.9 792.6 856.0
Maximum Flow gpm 31.7 31.7 31.7 31.7 31.7
Number of water passes 2 2 2 2 2
Condenser
Qty of Coils 4 4 4 4 4
Coil Length ft 13/13 15/13 15/15 18/15 18/18
Coil Height ft 3.5 3.5 3.5 3.5 3.5
Fin series fins/ft 192 192 192 192 192
Number of Rows 3 3 3 3 3
Condenser Fans
Quantity (1) 4/4 5/4 5/5 6/5 6/6
Diameter in. 30 30 30 30 30
Total Air Flow cm 54242 59876 65510 72054 78600
Nominal RPM 680 680 680 680 680
Tip Speed ft/s 90 90 90 90 90
Motor kW kW 1.05 1.05 1.05 1.05 1.05
Min Starting/Operating Ambient(2)
Standard Unit F 32 32 32 32 32
Low Ambient Unit F 0 0 0 0 0
General Unit
Refrigerant HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a
No. Of independent
Refrigerant Circuits 2 2 2 2 2
% Minimum Load (3) 15 15 15 15 15
Refrigerant Charge (1) lb 165/165 174/165 174/174 249/238 249/249
Oil Charge (1) gallons 2/2 2/2 2/2 2.6/2 2.6/2.6
Operating Weight (4) lb 10183 10570 10872 12132 12399
Shipping Weight (4) lb 9967 10333 10648 11892 12132

22 RLC-PRC005-E4
General Data

English Units
Table G-12 - RTAC 120-200 High Efficiency Low Noise
Size 120 130 140 155 170 185 200
Compressor
Quantity 2 2 2 2 2 2 2
Nominal Size (1) tons 60/60 60/70 70/70 70/85 85/85 85/100 100/100
Evaporator
Evaporator Model H140 H155 H170 H185 H200 H220 H240
Water Storage gallons 29.6 32.2 33.6 35.7 38.8 38.6 42.0
Minimum Flow gpm 190.2 221.9 206.1 221.9 253.6 221.9 253.6
Maximum Flow gpm 697.5 760.9 760.9 792.6 856.0 792.6 856.0
Number of water passes 2 2 2 2 2 2 2
Condenser
Qty of Coils 4 4 4 4 4 4 4
Coil Length ft 13/13 15/13 15/15 18/15 18/18 21/18 21/21
Coil Height ft 3.5 3.5 3.5 3.5 3.5 3.5 3.5
Fin series fins/ft 192 192 192 192 192 192 192
Number of Rows 3 3 3 3 3 3 3
Condenser Fans
Quantity (1) 4/4 5/4 5/5 6/5 6/6 7/6 7/7
Diameter in. 30 30 30 30 30 30 30
Total Air Flow cfm 54242 59876 65510 72054 78600 85207 91794
Nominal RPM 680 680 680 680 680 680 680
Tip Speed ft/s 90 90 90 90 90 90 90
Motor kW kW 1.05 1.05 1.05 1.05 1.05 1.05 1.05
Min Starting/Operating Ambient(2)
Standard Unit F 32 32 32 32 32 32 32
Low Ambient Unit F 0 0 0 0 0 0 0
General Unit
Refrigerant HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a
No. Of independent
Refrigerant Circuits 2 2 2 2 2 2 2
% Minimum Load (3) 15 15 15 15 15 15 15
Refrigerant Charge (1) lb 165/165 174/165 174/174 249/238 249/249 260/249 260/260
Oil Charge (1) gallons 2/2 2/2 2/2 2/2 2/2 2.6/2 2.6/2.6
Operating Weight (4) lb 10141 10260 10286 11720 12273 13537 13786
Shipping Weight (4) lb 9925 10022 10062 11480 12007 13273 13493

Notes:
1. Data containing information on two circuits shown as follows: ckt1/ckt2
2. Minimum start-up/operation ambient based on a 5mph wind across the condenser.
3. Percent minimum load is for total machine at 50 F ambient and 44 F leaving chilled water temp. Not each individual circuit.
4. With aluminium fins.

RLC-PRC005-E4 23
General Data

English Units
Table G-13 - General Data RTAC 250-400 Standard
Size 250 275 300 350 375 400
Compressor
Quantity 3 3 3 4 4 4
Nominal Size (1) tons 70-70/100 85-85/100 100-100/100 85-85/85-85 100-100/85-85 100-100/100-100
Evaporator
Evaporator Model F250 F270 F300 F340 F370 F400
Water Storage gallons 54.4 60.3 66.2 70.6 73.3 80.9
Minimum Flow gpm 242 275 308 457 501 545
Maximum Flow gpm 747 909 1070 1313 1454 1656
Condenser
Quantity of Coils 4/4 4/4 4/4 4/4 4/4 4/4
Coil Length ft 13/9 15/9 18/9 15/15 18/15 18/18
Coil Height ft 3.5 3.5 3.5 3.5 3.5 3.5
Fin series fins/ft 192 192 192 192 192 192
Number of Rows 3 3 3 3 3 3
Condenser Fans
Quantity (1) 8/6 10/6 12/6 10/10 12/10 12/12
Diameter in. 30 30 30 30 30 30
Total Air Flow cfm 130877 146561 164894 183189 201516 219852
Nominal RPM 915 915 915 915 915 915
Tip Speed ft/s 120 120 120 120 120 120
Motor kW kW 2.05 2.05 2.05 2.05 2.05 2.05
Minimum Starting/Operating Ambient (2)
Standard Unit F 32 32 32 32 32 32
Low-Ambient Unit F 0 0 0 0 0 0
General Unit
Refrigerant HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a
Number of Independent
Refrigerant Circuits 2 2 2 2 2 2
% Minimum Load (3) 13 13 13 10 10 10
Refrigerant Charge (1) lb 310/205 340/205 395/205 340/340 395/340 395/395
Oil Charge (1) gallons 4.6/2.9 4.6/2.9 5.3/2.9 4.6/4.6 5.3/4.6 5.3/5.3
Operating Weight (4) lb 20184 22028 23664 27166 28318 29700
Shipping Weight (4) lb 19700 21498 23088 26544 27673 28871

24 RLC-PRC005-E4
General Data

English Units
Table G-14 - General Data RTAC 250-400 High Efficiency
Size 250 275 300 350 375 400
Compressor
Quantity 3 3 3 4 4 4
Nominal Size (1) tons 70-70/100 85-85/100 100-100/100 85-85/85-85 100-100/85-85 100-100/100-100
Evaporator
Evaporator Model F300 F320 F320 F400 F440 F480
Water Storage gallons 66.2 70.9 70.9 80.9 87.1 93.2
Minimum Flow gpm 308 342 342 457 501 545
Maximum Flow gpm 1070 1192 1192 1656 1818 1979
Condenser
Quantity of Coils 4/4 4/4 4/4 4/4 4/4 4/4
Coil Length ft 15/9 18/12 21/12 18/18 21/18 21/21
Coil Height ft 3.5 3.5 3.5 3.5 3.5 3.5
Fin series fins/ft 192 192 192 192 192 192
Number of Rows 3 3 3 3 3 3
Condenser Fans
Quantity (1) 10/6 12/6 14/6 12/12 14/12 14/14
Diameter in. 30 30 30 30 30 30
Total Air Flow cfm 146478 171139 189469 219606 237943 256280
Nominal RPM 915 915 915 915 915 915
Tip Speed ft/s 120 120 120 120 120 120
Motor kW kW 2.05 2.05 2.05 2.05 2.05 2.05
Minimum Starting/Operating Ambient (2)
Standard Unit F 32 32 32 32 32 32
Low-Ambient Unit F 0 0 0 0 0 0
General Unit
Refrigerant HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a
Number of Independent
Refrigerant Circuits 2 2 2 2 2 2
% Minimum Load (3) 13 13 13 10 10 10
Refrigerant Charge (1) lb 340/205 395/245 430/245 395/395 430/395 430/430
Oil Charge (1) gallons 4.6/2.9 4.6/2.9 5.3/2.9 4.6/4.6 5.3/4.6 5.3/5.3
Operating Weight (4) lb 21382 24677 25899 29862 31429 33249
Shipping Weight (4) lb 20783 24044 25276 29147 30668 32327

RLC-PRC005-E4 25
General Data

English Units
Table G-15 - General Data RTAC 250-400 Low Noise Standard
Size 250 275 300 350 375 400
Compressor
Quantity 3 3 3 4 4 4
Nominal Size (1) tons 70-70/100 85-85/100 100-100/100 85-85/85-85 100-100/85-85 100-100/100-100
Evaporator
Evaporator Model F250 F270 F300 F340 F370 F400
Water Storage gallons 54.4 60.3 66.2 70.6 73.3 80.9
Minimum Flow gpm 242 275 308 457 501 545
Maximum Flow gpm 747 909 1070 1313 1454 1656
Condenser
Quantity of Coils 4/4 4/4 4/4 4/4 4/4 4/4
Coil Length ft 13/9 15/9 18/9 15/15 18/15 18/18
Coil Height ft 3.5 3.5 3.5 3.5 3.5 3.5
Fin series fins/ft 192 192 192 192 192 192
Number of Rows 3 3 3 3 3 3
Condenser Fans
Quantity (1) 8/6 10/6 12/6 10/10 12/10 12/12
Diameter in. 30 30 30 30 30 30
Total Air Flow cfm 93599 104861 117982 131066 144181 157301
Nominal RPM 680 680 680 680 680 680
Tip Speed ft/s 90 90 90 90 90 90
Motor kW kW 1.05 1.05 1.05 1.05 1.05 1.05
Minimum Starting/Operating Ambient (2)
Standard Unit F 32 32 32 32 32 32
Low-Ambient Unit F 0 0 0 0 0 0
General Unit
Refrigerant HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a
Number of Independent
Refrigerant Circuits 2 2 2 2 2 2
% Minimum Load (3) 13 13 13 10 10 10
Refrigerant Charge (1) lb 310/205 340/205 395/205 340/340 395/340 395/395
Oil Charge (1) gallons 4.6/2.9 4.6/2.9 5.3/2.9 4.6/4.6 5.3/4.6 5.3/5.3
Operating Weight (4) lb 20495 22339 23975 27581 28733 30115
Shipping Weight (4) lb 20012 21809 23399 26959 28088 29286

26 RLC-PRC005-E4
General Data

English Units
Table G-16 - General Data RTAC 250-400 High Efficiency Low Noise
Size 250 275 300 350 375 400
Compressor
Quantity 3 3 3 4 4 4
Nominal Size (1) tons 70-70/100 85-85/100 100-100/100 85-85/85-85 100-100/85-85 100-100/100-100
Evaporator
Evaporator Model F300 F320 F320 F400 F440 F480
Water Storage gallons 66.2 70.9 70.9 80.9 87.1 93.2
Minimum Flow gpm 308 342 342 457 501 545
Maximum Flow gpm 1070 1192 1192 1656 1818 1979
Condenser
Quantity of Coils 4/4 4/4 4/4 4/4 4/4 4/4
Coil Length ft 15/9 18/12 21/12 18/18 21/18 21/21
Coil Height ft 3.5 3.5 3.5 3.5 3.5 3.5
Fin series fins/ft 192 192 192 192 192 192
Number of Rows 3 3 3 3 3 3
Condenser Fans
Quantity (1) 10/6 12/6 14/6 12/12 14/12 14/14
Diameter in. 30 30 30 30 30 30
Total Air Flow cfm 104788 122629 135749 157081 170205 183329
Nominal RPM 680 680 680 680 680 680
Tip Speed ft/s 90 90 90 90 90 90
Motor kW kW 1.05 1.05 1.05 1.05 1.05 1.05
Minimum Starting/Operating Ambient (2)
Standard Unit F 32 32 32 32 32 32
Low-Ambient Unit F 0 0 0 0 0 0
General Unit
Refrigerant HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a HFC 134a
Number of Independent
Refrigerant Circuits 2 2 2 2 2 2
% Minimum Load (3) 13 13 13 10 10 10
Refrigerant Charge (1) lb 340/205 395/245 430/245 395/395 430/395 430/430
Oil Charge (1) gallons 4.6/2.9 4.6/2.9 5.3/2.9 4.6/4.6 5.3/4.6 5.3/5.3
Operating Weight lb (4) 21694 24988 26210 30276 31843 33664
Shipping Weight lb (4) 21094 24355 25588 29562 31083 32742
Notes:
1. Data containing information on two circuits shown as follows: ckt1/ckt2
2. Minimum start-up/operation ambient based on a 5mph wind across the condenser.
3. Percent minimum load is for total machine at 50F ambient and 44F leaving chilled water temperature, not each individual circuit.
4. With aluminium fins.

RLC-PRC005-E4 27
Performance Data

Table P-1 - Standard Efficiency Units (SI Units)

Entering Condenser Air Temperature (C)


30 35 40 45
Evaporator
Leaving
Water Model Cooling Power Cooling Power Cooling Power Cooling Power
Temperature and Capacity Input Capacity Input Capacity Input Capacity Input
(C) Size (kW) (kW) COP (kW) (kW) COP (kW) (kW) COP (kW) (kW) COP
140 STD 492.9 142.0 3.17 461.3 153.8 2.76 429.0 166.8 2.38 395.9 181.0 2.04
155 STD 539.4 157.0 3.13 504.9 169.5 2.74 469.7 183.3 2.37 433.9 198.6 2.03
170 STD 586.8 172.2 3.10 550.3 185.5 2.72 512.6 200.3 2.36 474.0 216.7 2.03
185 STD 649.8 188.0 3.15 610.0 202.4 2.76 569.2 218.5 2.41 527.8 236.2 2.08
5 200 STD 713.8 204.0 3.18 671.2 219.5 2.80 627.3 236.8 2.45 581.9 255.9 2.11
250 STD 854.7 243.7 3.20 804.1 263.5 2.80 751.4 285.3 2.44 697.2 309.2 2.10
275 STD 957.1 275.4 3.16 900.1 296.5 2.79 841.0 320.0 2.43 780.2 345.9 2.10
300 STD 1083.3 307.7 3.21 1020.0 330.8 2.83 954.6 356.6 2.47 887.1 385.0 2.14
350 STD 1187.7 346.3 3.12 1115.3 373.0 2.74 1040.4 402.6 2.39 963.7 435.3 2.06
375 STD 1306.2 377.2 3.15 1229.2 406.0 2.78 1149.4 438.0 2.42 1066.8 473.4 2.10
400 STD 1434.5 409.9 3.19 1350.8 440.7 2.81 1264.0 474.9 2.46 1174.3 512.7 2.13
140 STD 526.4 147.4 3.27 492.9 159.3 2.85 458.8 172.5 2.47 424.0 186.9 2.12
155 STD 575.2 163.2 3.22 539.0 175.8 2.82 502.1 189.9 2.45 464.1 205.3 2.11
170 STD 625.1 179.2 3.19 586.5 192.6 2.80 546.7 207.6 2.44 506.0 224.1 2.11
185 STD 692.0 195.6 3.23 650.1 210.2 2.84 606.9 226.5 2.48 562.9 244.5 2.15
7 200 STD 760.2 212.4 3.27 715.2 228.2 2.88 668.4 245.7 2.52 620.6 265.2 2.18
250 STD 908.5 252.9 3.29 855.4 272.9 2.89 800.2 295.1 2.52 743.3 319.5 2.17
275 STD 1017.2 286.3 3.25 957.1 307.7 2.86 894.8 331.6 2.50 830.8 357.8 2.17
300 STD 1151.1 320.0 3.29 1084.7 343.7 2.90 1015.8 369.9 2.54 944.4 398.9 2.21
350 STD 1262.6 360.0 3.21 1186.6 387.0 2.82 1107.9 417.0 2.46 1027.0 450.1 2.13
375 STD 1387.8 392.1 3.23 1306.9 421.4 2.85 1222.9 454.0 2.50 1136.0 489.9 2.16
400 STD 1524.9 426.4 3.27 1436.6 457.8 2.89 1345.6 492.7 2.53 1251.0 531.2 2.20
140 STD 560.5 153.1 3.36 525.3 165.1 2.94 489.4 178.5 2.55 452.9 193.1 2.20
155 STD 612.1 169.7 3.31 573.8 182.4 2.91 534.8 196.6 2.53 495.1 212.2 2.18
170 STD 664.5 186.4 3.27 623.4 199.9 2.88 581.6 215.0 2.51 538.7 231.7 2.17
185 STD 735.2 203.5 3.31 690.9 218.4 2.92 645.5 234.9 2.55 598.8 253.1 2.21
9 200 STD 807.6 221.1 3.35 760.2 237.1 2.96 710.9 255.0 2.59 660.3 274.8 2.25
250 STD 963.4 262.3 3.37 907.8 282.7 2.97 849.8 305.3 2.59 790.4 330.0 2.24
275 STD 1078.0 297.5 3.32 1015.1 319.3 2.94 950.0 343.5 2.57 882.5 370.0 2.23
300 STD 1220.4 332.9 3.36 1150.8 357.0 2.98 1078.4 383.8 2.61 1003.5 413.3 2.27
350 STD 1338.9 374.1 3.28 1259.1 401.5 2.90 1176.5 431.8 2.53 1091.7 465.2 2.19
375 STD 1470.7 407.5 3.31 1386.0 437.4 2.93 1298.1 470.5 2.56 1207.0 506.9 2.23
400 STD 1617.0 443.6 3.34 1524.5 475.6 2.96 1428.6 511.2 2.60 1329.4 550.5 2.26

Notes :
1. Ratings based on sea level altitude and evaporatot fouling factor of 0.0176 mK/kW
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. kW input = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). The considered power input includes compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 5C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Operation above 40C = with High Ambient Option.

28 RLC-PRC005-E4
Performance Data

Table P-2 - High Efficiency Units (SI Units)

Entering Condenser Air Temperature (C)


30 35 40 45 52
Evaporator
Leaving
Water Model Cooling Power Cooling Power Cooling Power Cooling Power Cooling Power
Temperature and Capacity Input Capacity Input Capacity Input Capacity Input Capacity Input
(C) Size (kW) (kW) COP (kW) (kW) COP (kW) (kW) COP (kW) (kW) COP (kW) (kW) COP
120 HE 421.6 112.9 3.33 394.9 122.1 2.91 367.1 132.4 2.52 338.9 144.0 2.16 298.2 162.1 1.70
130 HE 465.9 124.1 3.34 436.3 134.2 2.92 406.5 145.5 2.53 375.5 158.0 2.17 329.5 176.6 1.72
140 HE 511.9 135.6 3.35 480.6 146.7 2.94 448.3 159.0 2.55 415.2 172.6 2.20 361.1 190.3 1.75
155 HE 557.3 150.1 3.30 523.2 161.9 2.90 488.0 175.1 2.53 452.2 189.7 2.18 394.1 209.0 1.74
170 HE 603.0 164.6 3.26 566.4 177.1 2.87 528.5 191.2 2.50 489.4 206.8 2.16 425.1 226.5 1.73
185 HE 669.1 180.6 3.30 629.7 194.2 2.92 588.9 209.5 2.55 547.1 226.4 2.21 463.8 240.7 1.77
5 200 HE 736.3 196.8 3.34 693.7 211.4 2.96 649.8 227.8 2.59 604.4 246.0 2.25 509.5 259.1 1.81
250 HE 886.4 239.3 3.33 833.3 258.0 2.93 778.4 278.9 2.55 722.2 301.8 2.20 515.1 274.0 1.72
275 HE 991.9 265.6 3.35 933.5 285.3 2.96 873.0 307.4 2.59 810.8 331.9 2.25 679.3 348.5 1.80
300 HE 1114.9 296.9 3.38 1052.3 318.6 2.99 986.9 343.0 2.63 919.1 370.0 2.29 757.7 379.8 1.84
350 HE 1225.0 332.0 3.29 1151.5 356.9 2.90 1075.5 384.9 2.53 997.1 415.9 2.19 844.2 442.8 1.75
375 HE 1354.7 364.2 3.32 1275.6 391.1 2.94 1193.7 421.2 2.57 1109.3 454.6 2.23 918.7 471.1 1.79
400 HE 1484.5 396.6 3.34 1399.7 425.3 2.97 1311.5 457.5 2.61 1220.8 493.2 2.27 1003.8 505.7 1.82
120 HE 451.5 117 3.45 423.3 126.4 3.03 394.1 136.9 2.62 363.9 148.6 2.25 303.1 157.6 1.78
130 HE 498.9 128.7 3.46 468.0 138.9 3.04 436.0 150.4 2.64 403.6 163.1 2.27 336.8 172.4 1.80
140 HE 547.8 140.6 3.47 514.7 151.8 3.05 480.6 164.3 2.66 445.8 178.0 2.29 367.1 184.4 1.83
155 HE 595.6 155.8 3.41 559.4 167.7 3.01 522.5 181.0 2.62 484.9 195.8 2.27 399.8 202.5 1.82
170 HE 644.1 171.1 3.37 605.1 183.7 2.97 565.0 197.9 2.60 523.9 213.6 2.25 432.5 220.5 1.80
185 HE 714.1 187.8 3.41 672.3 201.5 3.01 629.4 216.9 2.64 585.1 234.1 2.29 472.6 234.8 1.85
7 200 HE 785.8 204.7 3.44 740.8 219.5 3.05 694.4 236.1 2.68 646.2 254.6 2.33 517.9 252.3 1.89
250 HE 945.5 248.5 3.4 889.5 267.5 3.0 831.9 288.6 2.64 772.5 311.9 2.29 520.0 265.4 1.79
275 HE 1057.6 276.1 3.45 995.7 296 3.06 932.1 318.4 2.68 866.7 343.2 2.33 691.9 339.6 1.88
300 HE 1188.1 308.7 3.47 1122.0 330.8 3.09 1053.0 355.5 2.71 981.7 383.0 2.37 768.6 368.7 1.92
350 HE 1306.5 345 3.39 1228.8 370.2 3 1148.7 398.4 2.62 1066.4 429.7 2.28 857.9 430.1 1.83
375 HE 1444.7 378.7 3.42 1361.4 405.9 3.03 1274.9 436.4 2.66 1185.9 470.3 2.32 934.9 458.5 1.87
400 HE 1582.9 412.6 3.44 1493.6 441.8 3.06 1400.8 474.5 2.69 1304.8 510.8 2.35 1019.3 491.1 1.90
120 HE 482.4 121.4 3.57 452.2 130.9 3.13 421.6 141.5 2.72 389.9 153.4 2.34 307.0 152.0 1.86
130 HE 533.0 133.5 3.58 500.3 143.9 3.15 466.9 155.5 2.74 432.5 168.3 2.36 340.7 166.1 1.89
140 HE 584.7 145.8 3.59 549.9 157.1 3.16 514.0 169.7 2.76 477.5 183.5 2.39 374.1 178.8 1.92
155 HE 635.0 161.7 3.52 597.0 173.7 3.11 558.0 187.2 2.72 518.3 202.1 2.36 403.6 194.8 1.90
170 HE 686.3 177.8 3.46 645.2 190.6 3.06 602.6 204.8 2.68 559.4 220.7 2.33 438.5 213.2 1.89
185 HE 760.5 195.2 3.50 716.2 209.1 3.11 670.9 224.7 2.73 624.1 242.0 2.37 479.2 227.4 1.93
9 200 HE 837.2 212.9 3.54 789.3 227.9 3.14 740.1 244.8 2.77 689.5 263.5 2.41 525.6 244.8 1.97
250 HE 1006.3 258.0 3.53 947.2 277.3 3.12 886.7 298.7 2.73 824.2 322.3 2.37 528.5 259.5 1.85
275 HE 1124.8 287.0 3.55 1060.1 307.2 3.15 992.9 329.8 2.77 924.0 354.9 2.41 699.7 328.5 1.96
300 HE 1262.9 320.9 3.57 1193.3 343.3 3.17 1120.9 368.5 2.80 1045.7 396.5 2.44 777.7 358.1 2.00
350 HE 1389.5 358.4 3.48 1308.3 383.9 3.09 1223.9 412.4 2.71 1137.4 443.9 2.36 871.3 417.4 1.91
375 HE 1536.8 393.7 3.51 1448.9 421.3 3.12 1358.2 452.2 2.75 1264.7 486.5 2.39 943.7 443.3 1.95
400 HE 1684.2 429.2 3.54 1589.9 458.9 3.15 1492.5 492.1 2.78 1391.3 529.1 2.42 1031.6 477.2 1.98

Notes :
1. Ratings based on sea level altitude and evaporatot fouling factor of 0.0176 mK/kW
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. kW input = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). The considered power input includes compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 5C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Operation above 40C = with High Ambient Option.

RLC-PRC005-E4 29
Performance Data

Table P-3 - Standard Efficiency Low Noise Units (SI Units)

Entering Condenser Air Temperature (C)


30 35 40
Evaporator
Leaving
Water Model Cooling Power Cooling Power Cooling Power
Temperature and Capacity Input Capacity Input Capacity Input
(C) Size (kW) (kW) COP (kW) (kW) COP (kW) (kW) COP
140 LN 468.3 155.4 2.91 436.0 168.4 2.51 402.9 182.5 2.14
155 LN 513.0 171.2 2.89 477.8 185.0 2.50 442.0 200.1 2.14
170 LN 559.0 187.3 2.88 521.4 202.0 2.50 483.1 218.3 2.15
185 LN 619.5 204.4 2.92 578.7 220.4 2.54 536.9 238.0 2.19
5 200 LN 680.7 221.7 2.96 636.8 239.0 2.58 591.7 257.9 2.22
250 LN 815.0 266.2 2.95 762.3 288.1 2.56 701.4 307.7 2.21
275 LN 912.8 299.6 2.94 853.7 323.0 2.56 786.2 344.6 2.21
300 LN 1033.7 334.3 2.98 968.3 360.0 2.60 884.3 378.4 2.27
350 LN 1131.8 376.7 2.90 1056.9 406.3 2.52 976.0 436.2 2.17
375 LN 1246.8 409.9 2.93 1166.6 442.0 2.55 1079.8 474.2 2.21
400 LN 1369.5 445.1 2.97 1282.6 479.3 2.59 1171.2 503.6 2.25
140 LN 497.5 161.9 2.97 463.4 175.1 2.57 413.8 179.8 2.23
155 LN 544.6 178.5 2.95 507.4 192.5 2.55 457.1 199.6 2.22
170 LN 592.5 195.3 2.93 552.7 210.3 2.55 495.8 215.7 2.23
185 LN 656.4 213.2 2.97 613.5 229.5 2.59 549.9 234.9 2.27
7 200 LN 721.5 231.5 3.01 675.1 249.1 2.62 599.1 250.7 2.32
250 LN 862.5 277.1 3.01 807.3 299.4 2.61 712.0 299.1 2.31
275 LN 965.5 312.3 2.99 903.3 336.2 2.60 793.6 332.8 2.31
300 LN 1093.8 348.8 3.03 1024.9 375.2 2.65 898.3 369.2 2.36
350 LN 1197.9 392.6 2.95 1119.1 422.7 2.56 988.0 422.5 2.27
375 LN 1318.9 427.4 2.98 1234.8 460.1 2.60 1094.9 461.3 2.30
400 LN 1449.3 464.5 3.01 1357.9 499.5 2.63 1190.2 491.6 2.34
140 LN 527.1 168.6 3.02 491.2 182.0 2.62 419.1 173.4 2.34
155 LN 576.6 186.0 3.00 537.6 200.2 2.60 460.2 191.0 2.33
170 LN 626.6 203.6 2.98 584.7 218.8 2.59 502.8 209.0 2.33
185 LN 694.1 222.5 3.02 648.7 239.1 2.63 559.4 228.7 2.37
9 200 LN 763.0 241.7 3.05 713.8 259.8 2.67 608.3 243.2 2.42
250 LN 910.6 288.4 3.05 853.0 311.1 2.66 720.4 288.5 2.42
275 LN 1018.9 325.4 3.03 953.5 349.8 2.64 802.4 320.7 2.42
300 LN 1154.3 363.9 3.07 1081.9 391.0 2.68 910.6 357.2 2.47
350 LN 1264.4 409.1 2.99 1181.7 439.6 2.61 1001.0 408.3 2.37
375 LN 1392.0 445.5 3.02 1303.7 478.9 2.64 1106.5 444.8 2.41
400 LN 1530.2 484.7 3.05 1433.8 520.6 2.67 1206.3 475.8 2.45

Notes :
1. Ratings based on sea level altitude and evaporatot fouling factor of 0.0176 mK/kW.
2. Consult Trane representative for performance at temperatures outside of the ranges shown.
3. kW input = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). The considered power input includes compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 5C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Operation above 40C = with High Ambient Option.

30 RLC-PRC005-E4
Performance Data

Table P-4 - High Efficiency Low Noise Units (SI Units)

Entering Condenser Air Temperature (C)


30 35 40 45
Evaporator
Leaving
Water Model Cooling Power Cooling Power Cooling Power Cooling Power
Temperature and Capacity Input Capacity Input Capacity Input Capacity Input
(C) Size (kW) (kW) COP (kW) (kW) COP (kW) (kW) COP (kW) (kW) COP
120 HELN 406.5 121.6 3.19 378.7 131.8 2.76 350.6 143.0 2.36 321.7 155.5 2.00
130 HELN 449.3 133.7 3.20 419.1 144.8 2.77 388.5 157.1 2.38 357.2 170.5 2.02
140 HELN 494.4 146.2 3.22 462.0 158.3 2.79 429.3 171.6 2.40 395.6 186.2 2.05
155 HELN 538.0 161.3 3.18 503.1 174.2 2.77 467.3 188.5 2.38 431.1 204.2 2.04
170 HELN 582.3 176.4 3.15 544.6 190.2 2.74 506.0 205.4 2.37 466.6 222.3 2.03
185 HELN 646.6 193.7 3.19 605.8 208.7 2.78 564.3 225.4 2.41 521.4 243.6 2.07
5 200 HELN 711.3 211.2 3.22 667.3 227.3 2.82 622.3 245.2 2.44 575.9 264.9 2.10
250 HELN 851.2 258.9 3.15 796.7 279.5 2.74 740.5 302.2 2.36 628.7 295.1 2.06
275 HELN 957.1 285.1 3.22 896.6 306.8 2.81 834.7 330.9 2.43 771.4 357.4 2.09
300 HELN 1077.3 318.7 3.24 1012.3 342.7 2.84 944.7 369.4 2.47 875.1 398.6 2.13
350 HELN 1182.4 355.8 3.17 1106.8 383.2 2.77 1029.1 413.6 2.39 949.7 447.1 2.05
375 HELN 1308.3 390.4 3.20 1226.7 420.0 2.80 1142.7 452.9 2.43 1056.6 488.9 2.09
400 HELN 1434.2 425.1 3.23 1346.3 456.9 2.83 1255.9 492.0 2.46 1162.7 530.6 2.12
120 HELN 433.5 126.5 3.28 404.3 136.9 2.84 374.5 148.3 2.43 344.2 161.0 2.07
130 HELN 479.2 139.1 3.29 447.6 150.4 2.86 415.2 162.8 2.46 382.2 176.5 2.09
140 HELN 526.7 152.0 3.31 492.9 164.3 2.88 458.1 177.8 2.48 423.0 192.6 2.12
155 HELN 572.8 167.8 3.26 535.8 180.9 2.84 498.2 195.4 2.46 459.9 211.3 2.10
170 HELN 619.5 183.8 3.22 579.4 197.7 2.81 538.7 213.2 2.44 497.2 230.2 2.09
185 HELN 687.4 201.9 3.26 644.5 217.1 2.85 600.2 234.0 2.47 555.2 252.6 2.13
7 200 HELN 756.3 220.2 3.29 709.9 236.6 2.88 662.1 254.9 2.51 610.0 273.2 2.16
250 HELN 904.3 269.6 3.22 846.7 290.6 2.81 752.1 294.1 2.47 636.0 284.7 2.15
275 HELN 1016.5 297.0 3.28 952.8 319.2 2.88 887.4 343.6 2.50 809.7 363.8 2.16
300 HELN 1143.8 332.2 3.31 1074.8 356.8 2.90 1003.5 384.0 2.53 908.5 400.7 2.20
350 HELN 1256.3 370.5 3.24 1176.8 398.4 2.84 1094.9 429.2 2.46 1011.2 463.0 2.11
375 HELN 1390.2 406.9 3.27 1304.1 437.1 2.87 1215.5 470.4 2.49 1104.0 494.7 2.16
400 HELN 1523.5 443.4 3.29 1431.0 475.8 2.89 1335.4 511.7 2.52 1207.7 533.5 2.19
120 HELN 461.0 131.6 3.35 430.0 142.1 2.91 398.7 153.8 2.50 363.6 164.7 2.14
130 HELN 509.8 144.7 3.37 476.4 156.1 2.93 442.3 168.8 2.53 401.5 179.1 2.17
140 HELN 560.1 158.0 3.39 524.2 170.5 2.96 487.7 184.2 2.55 441.3 193.5 2.20
155 HELN 608.3 174.6 3.34 569.6 187.9 2.91 529.9 202.6 2.52 480.3 213.0 2.18
170 HELN 657.5 191.4 3.29 615.3 205.5 2.88 572.4 221.1 2.50 519.3 232.6 2.16
185 HELN 728.9 210.3 3.32 683.5 225.8 2.91 637.1 243.0 2.53 563.3 245.4 2.22
9 200 HELN 802.4 229.6 3.35 753.1 246.4 2.94 702.5 265.0 2.56 617.8 264.9 2.25
250 HELN 958.5 280.8 3.28 897.6 302.2 2.87 761.6 283.9 2.58 642.4 275.5 2.24
275 HELN 1077.0 309.5 3.35 1009.8 331.9 2.94 941.2 356.8 2.55 820.6 353.0 2.25
300 HELN 1210.9 346.3 3.37 1138.5 371.4 2.96 1063.6 399.2 2.58 922.9 390.2 2.29
350 HELN 1331.5 385.8 3.31 1247.8 414.0 2.90 1161.7 445.1 2.52 1032.3 453.6 2.20
375 HELN 1473.2 424.0 3.33 1382.5 454.7 2.93 1289.3 488.6 2.55 1118.4 479.5 2.25
400 HELN 1614.5 462.4 3.35 1517.2 495.5 2.95 1416.6 532.2 2.57 1220.8 515.9 2.28

Notes :
1. Ratings based on sea level altitude and evaporatot fouling factor of 0.0176 mK/kW
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. kW input = compressor power input only.
4. COP = Coefficient of Performance (kW/kW). The considered power input includes compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 5C.
6. Interpolation between points is permissible. Extrapolation is not permitted.
7. Operation above 40C = with High Ambient Option.

RLC-PRC005-E4 31
Performance Data

Table P-5 - Standard Efficiency Units (English Units)

Entering Condenser Air Temperature (F)


85 95 105 115
Evaporator
Leaving
Water Model Power Power Power Power
Temperature and Input Input Input Input
(F) Size Tons (kW) EER Tons (kW) EER Tons (kW) EER Tons (kW) EER
140 STD 141.2 140.8 11.00 131.2 153.8 9.40 121.0 168.3 8.00 110.5 184.3 6.70
155 STD 154.4 155.7 10.90 143.6 169.5 9.40 132.5 184.9 8.00 121.1 202.2 6.70
170 STD 168.1 170.8 10.80 156.5 185.5 9.30 144.6 202.1 8.00 132.4 220.6 6.70
185 STD 186.0 186.5 10.90 173.5 202.4 9.40 160.6 220.4 8.10 147.4 240.4 6.90
41 200 STD 204.3 202.4 11.00 190.9 219.5 9.60 176.9 238.8 8.20 162.6 260.4 7.00
250 STD 244.7 241.7 11.10 228.7 263.5 9.60 212.0 287.8 8.20 194.8 314.9 6.90
275 STD 274.0 273.2 11.00 256.0 296.5 9.50 237.3 322.8 8.20 217.9 352.0 6.90
300 STD 310.0 305.2 11.10 290.1 330.8 9.70 269.4 359.6 8.30 247.9 391.7 7.10
350 STD 340.1 343.6 10.80 317.2 373.0 9.40 293.5 406.1 8.00 269.1 443.0 6.80
375 STD 373.9 374.2 10.90 349.6 406.0 9.50 324.3 441.8 8.10 298.1 481.7 6.90
400 STD 410.6 406.7 11.00 384.2 440.7 9.60 356.7 478.9 8.30 328.2 521.5 7.00
140 STD 151.8 146.8 11.40 141.2 160.0 9.80 130.4 174.7 8.30 119.3 191.0 7.00
155 STD 165.9 162.6 11.20 154.4 176.6 9.70 142.6 192.3 8.30 130.5 209.7 7.00
170 STD 180.3 178.5 11.10 167.9 193.4 9.60 155.3 210.1 8.20 142.3 228.8 7.00
185 STD 199.4 194.9 11.20 186.1 211.1 9.70 172.4 229.4 8.40 158.3 249.7 7.10
45 200 STD 219.1 211.7 11.30 204.8 229.1 9.90 189.9 248.8 8.50 174.6 270.8 7.20
250 STD 261.8 251.8 11.40 244.9 274.0 9.90 227.4 298.9 8.50 209.2 326.3 7.20
275 STD 293.1 285.3 11.30 274.0 309.0 9.80 254.2 335.7 8.40 233.8 365.3 7.20
300 STD 331.6 319.0 11.40 310.6 345.1 9.90 288.6 374.5 8.60 265.9 407.3 7.30
350 STD 363.9 358.7 11.10 339.7 388.6 9.70 314.7 422.2 8.30 288.9 459.5 7.10
375 STD 399.8 390.7 11.20 374.2 423.2 9.80 347.4 459.6 8.40 319.7 500.2 7.20
400 STD 439.3 425.0 11.30 411.4 459.8 9.90 382.3 498.9 8.50 352.1 542.4 7.30
140 STD 162.7 153.1 11.70 151.5 166.5 10.10 140.0 181.4 8.60 127.6 196.5 7.30
155 STD 177.7 169.8 11.50 165.5 183.9 10.00 153.0 199.8 8.60 139.5 216.0 7.30
170 STD 192.8 186.6 11.40 179.7 201.6 9.90 166.2 218.5 8.50 151.8 235.9 7.20
185 STD 213.2 203.8 11.50 199.1 220.2 10.00 184.6 238.7 8.60 168.1 256.2 7.40
49 200 STD 234.3 221.4 11.60 219.1 239.2 10.10 203.3 259.3 8.70 184.4 276.3 7.50
250 STD 279.2 262.3 11.70 261.5 285.0 10.20 243.1 310.2 8.80 217.2 324.8 7.50
275 STD 312.5 297.8 11.60 292.4 321.9 10.10 271.6 349.0 8.70 243.3 365.4 7.50
300 STD 353.7 333.2 11.70 331.5 360.0 10.20 308.3 390.1 8.80 273.6 401.8 7.60
350 STD 388.2 374.5 11.40 362.7 404.8 9.90 336.4 438.7 8.60 302.4 462.6 7.30
375 STD 426.3 407.9 11.50 399.3 441.0 10.00 371.1 478.1 8.70 332.6 500.3 7.50
400 STD 468.6 444.1 11.60 439.2 479.7 10.20 408.5 519.6 8.80 362.4 535.3 7.60

Notes :
1. Ratins based on sea level altitude and evaporatot fouling factor of 0.0001 ft F hr/BTU
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. kW input = compressor power input only.
4. EER = Energy Efficiency Ratio (Btu/watt-hour).The considered power input includes compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 9F.
6. Interpolation betweeen points is permissible. Extrapolation is not permitted.
7. Above 104F ambient, the units will have the High Ambient option.

32 RLC-PRC005-E4
Performance Data

Table P-6 - High Efficiency Units (English Units)

Entering Condenser Air Temperature (F)


85 95 105 115 125
Evaporator
Leaving
Water Model Power Power Power Power Power
Temperature and Input Input Input Input Input
(F) Size Tons (kW) EER Tons (kW) EER Tons (kW) EER Tons (kW) EER Tons (kW) EER
120 HE 120.8 111.9 11.50 112.3 122.1 9.90 103.6 133.7 8.50 94.5 146.7 7.10 85.3 161.2 5.90
130 HE 133.4 123.1 11.60 124.1 134.2 10.00 114.6 146.8 8.50 104.8 161.0 7.20 94.8 176.6 5.90
140 HE 146.6 134.5 11.60 136.7 146.7 10.00 126.5 160.5 8.60 116.0 175.8 7.20 105.3 192.8 6.00
155 HE 159.5 148.8 11.40 148.8 161.9 9.90 137.7 176.6 8.50 126.4 193.1 7.20 114.7 211.4 6.00
170 HE 172.7 163.3 11.30 161.1 177.1 9.80 149.1 192.8 8.40 136.7 210.5 7.10 124.1 230.1 6.00
185 HE 191.6 179.2 11.40 179.1 194.2 10.00 166.2 211.3 8.60 152.9 230.4 7.30 134.9 243.5 6.10
41 200 HE 210.7 195.3 11.50 197.3 211.4 10.10 183.4 229.7 8.70 169.0 250.3 7.40 148.3 262.3 6.20
250 HE 253.8 237.3 11.50 237.0 258.0 10.00 219.7 281.3 8.60 201.8 307.2 7.30 151.4 278.4 6.00
275 HE 283.9 263.5 11.60 265.5 285.3 10.10 246.3 310.0 8.70 226.6 337.7 7.40 197.7 352.6 6.20
300 HE 319.1 294.6 11.70 299.3 318.6 10.20 278.6 345.9 8.80 257.1 376.4 7.60 220.7 384.7 6.40
350 HE 350.7 329.4 11.40 327.5 356.9 9.90 303.4 388.2 8.50 278.6 423.2 7.20 246.8 450.1 6.10
375 HE 387.8 361.5 11.50 362.8 391.1 10.00 336.9 424.7 8.70 310.1 462.5 7.40 267.5 476.8 6.20
400 HE 424.8 393.6 11.60 398.1 425.3 10.10 370.2 461.3 8.80 341.3 501.7 7.50 292.5 512.3 6.30
120 HE 130.3 116.5 12.00 121.3 126.9 10.40 112.0 138.7 8.80 102.4 151.9 7.40 88.4 158.9 6.20
130 HE 143.9 128.2 12.00 134.1 139.5 10.40 124.0 152.3 8.90 113.6 166.6 7.50 98.4 174.0 6.20
140 HE 158.0 140.0 12.10 147.5 152.4 10.40 136.7 166.3 9.00 125.5 181.8 7.60 107.3 186.4 6.40
155 HE 171.7 155.2 11.80 160.3 168.4 10.30 148.6 183.3 8.80 136.5 200.0 7.50 116.7 204.5 6.30
170 HE 185.7 170.5 11.70 173.4 184.5 10.20 160.6 200.3 8.80 147.5 218.1 7.40 126.1 222.6 6.20
185 HE 205.9 187.2 11.80 192.6 202.3 10.30 178.9 219.6 8.90 164.8 239.0 7.60 137.9 237.1 6.40
45 200 HE 226.5 204.0 11.90 212.2 220.4 10.40 197.4 239.0 9.00 182.1 259.9 7.80 151.2 255.0 6.60
250 HE 272.5 247.5 11.90 254.8 268.6 10.40 236.5 292.2 8.90 217.5 318.5 7.60 152.7 268.3 6.20
275 HE 304.8 275.2 12.00 285.2 297.3 10.50 265.0 322.3 9.00 244.0 350.4 7.70 201.9 343.1 6.50
300 HE 342.3 307.7 12.00 321.3 332.1 10.60 299.3 359.9 9.20 276.6 391.0 7.90 224.5 372.8 6.70
350 HE 376.6 343.8 11.80 352.0 371.7 10.30 326.5 403.3 8.90 300.3 438.7 7.50 250.2 434.1 6.40
375 HE 416.4 377.5 11.90 389.9 407.6 10.40 362.5 441.8 9.00 334.0 480.0 7.70 273.0 463.3 6.50
400 HE 456.2 411.4 11.90 427.8 443.6 10.50 398.3 480.3 9.10 367.6 521.4 7.80 297.7 496.6 6.60
120 HE 140.1 121.4 12.50 130.5 131.9 10.80 120.6 143.9 9.20 110.5 157.3 7.80 90.3 153.8 6.50
130 HE 154.8 133.5 12.50 144.4 145.0 10.80 133.6 158.0 9.30 122.6 172.5 7.90 99.8 167.2 6.60
140 HE 169.8 145.8 12.50 158.7 158.3 10.90 147.2 172.4 9.40 135.4 188.1 8.00 109.5 180.1 6.70
155 HE 184.3 161.8 12.30 172.2 175.1 10.70 159.7 190.2 9.20 146.9 207.0 7.90 118.8 197.4 6.60
170 HE 199.2 178.0 12.10 186.0 192.1 10.50 172.5 208.1 9.10 158.6 226.0 7.80 128.9 216.0 6.60
185 HE 220.7 195.5 12.20 206.6 210.8 10.70 192.0 228.3 9.30 177.0 247.9 7.90 140.5 229.5 6.70
49 200 HE 242.8 213.2 12.30 227.6 229.8 10.80 211.9 248.7 9.40 195.6 270.0 8.00 154.1 246.9 6.90
250 HE 291.9 258.2 12.30 273.2 279.5 10.70 253.7 303.5 9.20 230.0 323.6 7.90 154.7 260.3 6.50
275 HE 326.3 287.3 12.30 305.6 309.7 10.80 284.1 335.0 9.40 261.9 363.4 8.00 205.3 331.7 6.80
300 HE 366.2 321.3 12.40 344.0 346.2 10.90 320.8 374.5 9.50 296.7 406.2 8.10 228.0 361.3 7.00
350 HE 403.1 358.8 12.10 377.1 387.0 10.60 350.2 418.9 9.20 322.5 454.5 7.80 255.6 421.5 6.70
375 HE 445.7 394.2 12.20 417.8 424.8 10.70 388.7 459.4 9.30 358.7 498.2 8.00 276.9 447.5 6.80
400 HE 488.4 429.9 12.30 458.4 462.7 10.80 427.2 500.1 9.40 394.7 542.0 8.10 302.6 481.4 6.90

Notes :
1. Ratins based on sea level altitude and evaporatot fouling factor of 0.0001 ft F hr/BTU
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. kW input = compressor power input only.
4. EER = Energy Efficiency Ratio (Btu/watt-hour).The considered power input includes compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 9F.
6. Interpolation betweeen points is permissible. Extrapolation is not permitted.
7. Above 104F ambient, the units will have the High Ambient option.

RLC-PRC005-E4 33
Performance Data

Table P-7 - Standard Efficiency Low Noise Units (English Units)

Entering Condenser Air Temperature (F)


85 95 104
Evaporator
Leaving
Water Model Power Power Power
Temperature and Input Input Input
(F) Size Tons (kW) COP Tons (kW) COP Tons (kW) COP
140 LN 134.2 154.1 10.10 124.0 168.4 8.60 114.6 182.5 7.30
155 LN 147.0 169.7 10.00 135.9 185.0 8.50 125.7 200.1 7.30
170 LN 160.2 185.7 10.00 148.3 202.0 8.50 137.4 218.3 7.30
185 LN 177.4 202.7 10.10 164.6 220.4 8.70 152.7 238.0 7.50
41 200 LN 195.0 219.9 10.20 181.1 239.0 8.80 168.3 257.9 7.60
250 LN 233.4 263.9 10.20 216.8 288.1 8.70 199.5 307.7 7.50
275 LN 261.4 297.1 10.20 242.8 323.0 8.70 223.6 344.6 7.60
300 LN 296.0 331.6 10.30 275.4 360.0 8.90 251.5 378.4 7.70
350 LN 324.2 373.6 10.00 300.6 406.3 8.60 277.6 436.2 7.40
375 LN 357.1 406.6 10.20 331.8 442.0 8.70 307.1 474.2 7.50
400 LN 392.2 441.5 10.30 364.8 479.3 8.80 333.1 503.6 7.70
140 LN 143.5 161.2 10.30 132.7 175.8 8.80 117.9 179.2 7.60
155 LN 157.0 177.8 10.20 145.3 193.3 8.70 129.6 197.6 7.60
170 LN 170.9 194.6 10.20 158.2 211.2 8.70 141.3 215.2 7.60
185 LN 189.2 212.5 10.30 175.6 230.6 8.80 156.7 234.3 7.80
45 200 LN 208.0 230.8 10.40 193.2 250.3 9.00 170.7 250.0 8.00
250 LN 248.6 276.0 10.40 231.1 300.7 8.90 202.8 298.1 7.90
275 LN 278.2 311.2 10.40 258.5 337.7 8.90 226.1 331.9 7.90
300 LN 315.1 347.6 10.50 293.2 376.9 9.00 256.0 368.0 8.10
350 LN 345.2 391.2 10.20 320.3 424.6 8.80 281.6 421.4 7.80
375 LN 380.0 425.9 10.30 353.4 462.2 8.90 311.9 460.0 7.90
400 LN 417.6 463.0 10.50 388.6 501.8 9.00 339.1 490.0 8.00
140 LN 152.9 168.7 10.50 141.5 183.6 9.00 119.5 171.9 8.10
155 LN 167.2 186.2 10.40 154.8 202.0 8.90 131.3 189.6 8.10
170 LN 181.7 203.9 10.30 168.3 220.7 8.90 143.5 207.6 8.00
185 LN 201.2 222.8 10.50 186.7 241.3 9.00 159.6 227.1 8.20
49 200 LN 221.2 242.2 10.60 205.5 262.2 9.10 173.5 241.3 8.40
250 LN 263.9 288.6 10.60 245.5 313.8 9.10 206.5 288.3 8.30
275 LN 295.2 325.8 10.50 274.4 352.9 9.10 228.9 318.2 8.40
300 LN 334.5 364.5 10.70 311.3 394.6 9.20 259.7 354.2 8.50
350 LN 366.4 409.6 10.40 340.1 443.4 8.90 285.7 405.4 8.20
375 LN 403.3 446.1 10.50 375.1 483.2 9.00 315.7 441.4 8.30
400 LN 443.3 485.5 10.60 412.7 525.4 9.10 344.1 471.7 8.50

Notes :
1. Ratins based on sea level altitude and evaporatot fouling factor of 0.0001 ft F hr/BTU
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. kW input = compressor power input only.
4. EER = Energy Efficiency Ratio (Btu/watt-hour).The considered power input includes compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 9F.
6. Interpolation betweeen points is permissible. Extrapolation is not permitted.
7. Above 104F ambient, the units will have the High Ambient option.

34 RLC-PRC005-E4
Performance Data

Table P-8 - High Efficiency Low Noise Units (English Units)

Entering Condenser Air Temperature (F)


85 95 105 115
Evaporator
Leaving
Water
Temperature Unit kW kW kW kW
(F) Size Tons input EER Tons input EER Tons input EER Tons input EER
120 HELN 116.4 120.6 11.10 107.7 131.8 9.40 98.8 144.4 7.90 89.7 158.4 6.60
130 HELN 128.7 132.6 11.10 119.2 144.8 9.50 109.5 158.5 8.00 99.6 173.6 6.70
140 HELN 141.6 145.0 11.20 131.4 158.3 9.50 121.0 173.2 8.10 110.4 189.6 6.80
155 HELN 154.1 159.9 11.00 143.1 174.2 9.50 131.8 190.2 8.00 120.3 207.9 6.70
170 HELN 166.8 175.0 10.90 154.9 190.2 9.40 142.6 207.2 8.00 130.1 226.2 6.70
185 HELN 185.1 192.2 11.10 172.3 208.7 9.50 159.1 227.3 8.10 145.6 247.9 6.80
41 200 HELN 203.7 209.5 11.20 189.8 227.3 9.60 175.5 247.3 8.20 160.8 269.5 6.90
250 HELN 243.8 256.8 10.90 226.6 279.5 9.40 208.8 304.9 7.90 166.8 283.6 6.80
275 HELN 274.0 282.8 11.10 255.0 306.8 9.60 235.4 333.8 8.20 213.3 359.4 6.90
300 HELN 308.4 316.2 11.20 287.9 342.7 9.70 266.5 372.5 8.30 240.9 398.1 7.00
350 HELN 338.6 352.9 11.00 314.8 383.2 9.50 290.2 417.2 8.00 265.0 454.9 6.80
375 HELN 374.7 387.3 11.10 348.9 420.0 9.60 322.3 456.7 8.20 292.2 491.5 6.90
400 HELN 410.6 421.8 11.20 382.9 456.9 9.70 354.2 496.1 8.30 318.2 526.5 7.00
120 HELN 125.0 126.0 11.40 115.8 137.4 9.70 106.3 150.3 8.20 95.8 162.7 6.80
130 HELN 138.2 138.5 11.40 128.2 151.0 9.80 117.9 164.9 8.30 106.3 178.1 6.90
140 HELN 151.9 151.4 11.50 141.2 165.0 9.90 130.1 180.1 8.40 116.3 191.4 7.00
155 HELN 165.2 167.2 11.30 153.5 181.7 9.70 141.5 197.9 8.30 127.4 211.8 7.00
170 HELN 178.6 183.1 11.20 166.0 198.6 9.60 153.0 215.8 8.20 137.2 229.6 6.90
185 HELN 198.1 201.2 11.30 184.5 218.1 9.80 170.4 237.0 8.30 149.6 243.9 7.10
45 200 HELN 218.0 219.5 11.40 203.2 237.7 9.90 188.0 258.1 8.40 164.1 263.1 7.20
250 HELN 260.7 268.6 11.20 242.4 291.9 9.60 223.6 317.7 8.20 168.9 273.7 7.10
275 HELN 293.0 296.1 11.40 272.8 320.6 9.80 252.0 347.9 8.40 216.9 348.7 7.20
300 HELN 329.5 331.1 11.50 307.7 358.4 9.90 285.0 388.8 8.50 244.1 385.1 7.40
350 HELN 362.2 369.3 11.30 336.9 400.1 9.70 310.9 434.5 8.30 274.1 450.8 7.10
375 HELN 400.6 405.6 11.40 373.4 439.0 9.80 345.2 476.3 8.40 297.0 476.8 7.20
400 HELN 439.1 442.1 11.40 409.7 477.9 9.90 379.3 518.1 8.50 324.3 512.7 7.30
120 HELN 133.8 131.7 11.70 124.0 143.3 10.00 113.9 156.4 8.40 97.4 157.2 7.20
130 HELN 148.0 144.8 11.70 137.3 157.5 10.10 126.4 171.6 8.50 108.0 171.6 7.30
140 HELN 162.6 158.1 11.80 151.2 171.9 10.10 139.5 187.2 8.60 118.1 184.2 7.40
155 HELN 176.5 174.8 11.60 164.1 189.5 10.00 151.4 205.9 8.50 129.2 204.0 7.30
170 HELN 190.7 191.6 11.40 177.3 207.3 9.90 163.5 224.7 8.40 139.7 222.4 7.30
185 HELN 211.4 210.7 11.60 196.9 227.8 10.00 182.0 247.0 8.50 152.4 236.5 7.50
49 200 HELN 232.6 230.0 11.60 216.9 248.6 10.10 200.8 269.5 8.60 166.0 252.6 7.60
250 HELN 277.9 281.0 11.40 258.6 304.8 9.80 230.7 314.6 8.50 170.6 263.8 7.50
275 HELN 312.2 309.9 11.60 290.9 334.8 10.10 268.9 362.6 8.60 220.8 337.5 7.60
300 HELN 351.0 346.8 11.70 327.9 374.7 10.10 303.9 405.9 8.70 247.7 371.3 7.70
350 HELN 386.1 386.3 11.50 359.4 417.5 9.90 331.9 452.4 8.50 278.6 435.6 7.40
375 HELN 427.1 424.7 11.60 398.2 458.7 10.00 368.4 496.7 8.60 302.2 461.2 7.60
400 HELN 468.1 463.2 11.70 437.0 500.0 10.10 404.8 541.2 8.70 329.3 494.4 7.70

Notes :
1. Ratins based on sea level altitude and evaporatot fouling factor of 0.0001 ft F hr/BTU
2. Consult Trane representative for performance at temperatures outside of the ranges shown
3. kW input = compressor power input only.
4. EER = Energy Efficiency Ratio (Btu/watt-hour).The considered power input includes compressors, condenser fans and control power.
5. Ratings are based on an evaporator temperature drop of 9F.
6. Interpolation betweeen points is permissible. Extrapolation is not permitted.
7. Above 104F ambient, the units will have the High Ambient option.

RLC-PRC005-E4 35
Performance Data

SI Units - Data in accordance with ARI 550/590-98. Information about ARI: www.ari.org

Table P-9 - ARI Part-Load Performance for RTAC Standard Table P-10 - ARI Part-Load Performance for RTAC High
Efficiency Units (SI Units) Efficiency Units (SI Units)

% (kW) P.I. COP IPLV % (kW) P.I. COP IPLV


Unit Load cooling (kW) (kW/kW) (kW/kW) Unit Load cooling (kW) (kW/kW) (kW/kW)
140 100 492.9 172.8 2.85 3.93 120 100 423.3 139.7 3.03 4.10
75 369.7 115.8 3.19 75 317.3 92.9 3.41
50 246.5 54.3 4.54 50 211.7 45.3 4.67
25 123.2 28.5 4.32 25 105.8 23.7 4.46
155 100 539.0 191.2 2.82 3.91 130 100 468.0 154.2 3.04 4.16
75 404.4 127.1 3.18 75 350.9 101.2 3.47
50 269.5 60.6 4.45 50 234.0 50.0 4.68
25 134.7 29.6 4.54 25 117.0 25.0 4.68
170 100 586.5 209.3 2.80 3.85 140 100 514.7 169.0 3.05 4.04
75 439.6 137.7 3.19 75 386.1 116.5 3.31
50 293.2 66.7 4.40 50 257.4 55.1 4.67
25 146.6 35.1 4.18 25 128.7 30.0 4.29
185 100 650.1 228.9 2.84 3.99 155 100 559.4 185.7 3.01 4.01
75 487.5 148.1 3.29 75 419.7 127.8 3.28
50 325.1 71.4 4.55 50 279.7 61.1 4.58
25 162.5 37.0 4.39 25 139.9 30.9 4.53
200 100 715.2 248.7 2.88 3.83 170 100 605.1 204.0 2.97 3.95
75 536.4 173.7 3.09 75 453.6 137.7 3.29
50 357.6 79.8 4.48 50 302.6 66.9 4.52
25 178.8 43.7 4.09 25 151.3 36.2 4.17
250 100 855.4 296.4 2.89 4.34 185 100 672.3 223.5 3.01 4.08
75 641.3 171.6 3.74 75 504.2 148.5 3.39
50 427.6 91.4 4.68 50 336.1 72.2 4.66
25 213.8 40.3 5.31 25 168.1 38.1 4.41
275 100 957.0 334.6 2.86 4.20 200 100 740.8 242.9 3.05 3.94
75 717.6 193.7 3.70 75 555.7 173.5 3.20
50 478.5 105.8 4.52 50 370.4 80.4 4.60
25 239.2 49.4 4.85 25 185.2 44.9 4.13
300 100 1084.7 373.7 2.90 4.02 250 100 889.6 294.4 3.02 4.39
75 813.4 216.6 3.76 75 667.1 174.0 3.83
50 542.3 136.3 3.98 50 444.8 93.0 4.79
25 271.2 52.3 5.19 25 222.4 44.5 4.99
350 100 1186.7 420.6 2.82 4.15 275 100 995.7 326.0 3.05 4.36
75 889.8 243.6 3.65 75 746.8 192.8 3.87
50 593.3 134.9 4.40 50 498.0 107.6 4.63
25 296.7 58.4 5.08 25 248.9 48.3 5.16
375 100 1306.9 458.3 2.85 4.23 300 100 1122.0 363.9 3.08 4.13
75 980.0 265.8 3.69 75 841.2 215.6 3.90
50 653.5 144.8 4.51 50 560.9 140.0 4.01
25 326.8 63.3 5.16 25 280.5 51.0 5.50
400 100 1436.6 497.9 2.89 4.23 350 100 1228.8 410.5 2.99 4.25
75 1077.5 288.8 3.73 75 921.7 244.2 3.77
50 718.5 161.0 4.46 50 614.5 135.4 4.54
25 359.3 69.0 5.21 25 307.3 62.7 4.90
375 100 1361.4 449.5 3.03 4.32
Notes: 75 1021.0 267.7 3.81
1. IPLV values are rated in accordance with ARI Standard 550/590-98. 50 680.8 146.6 4.64
2. COP and IPLV values include compressors, condenser fans and control kW.
25 340.4 68.3 4.99
400 100 1493.6 488.5 3.06 4.32
75 1120.2 290.8 3.85
50 746.9 162.9 4.59
25 373.5 74.1 5.04

Notes:
1. IPLV values are rated in accordance with ARI Standard 550/590-98.
2. COP and IPLV values include compressors, condenser fans and control kW.

36 RLC-PRC005-E4
Performance Data

Table P-11 - ARI Part-Load Performance for RTAC Standard Table P-12 - ARI Part-Load Performance for RTAC High
Efficiency Low Noise Units (SI Units) Efficiency Low Noise Units (SI Units)

% (kW) P.I. COP IPLV % (kW) P.I. COP IPLV


Unit Load cooling (kW) (kW/kW) (kW/kW) Unit Load cooling (kW) (kW/kW) (kW/kW)
140 100 463.4 180.3 2.57 3.86 120 100 404.3 142.4 2.84 4.20
75 347.6 114.0 3.05 75 303.2 88.8 3.41
50 231.7 52.3 4.43 50 202.2 42.8 4.73
25 115.9 24.9 4.64 25 101.1 20.0 5.06
155 100 507.4 199.0 2.55 3.90 130 100 447.6 156.5 2.86 4.30
75 380.6 123.2 3.09 75 335.7 96.2 3.49
50 253.7 57.0 4.45 50 223.8 46.2 4.85
25 126.9 26.2 4.84 25 111.9 21.4 5.23
170 100 552.7 216.7 2.55 3.84 140 100 492.6 171.0 2.88 4.14
75 414.5 133.2 3.11 75 369.5 111.8 3.30
50 276.4 63.5 4.35 50 246.3 51.7 4.76
25 138.2 30.2 4.57 25 123.2 25.3 4.87
185 100 613.5 236.9 2.59 4.00 155 100 535.8 188.7 2.84 4.17
75 460.1 142.3 3.23 75 401.9 121.5 3.31
50 306.8 67.3 4.56 50 267.9 56.3 4.76
25 153.4 32.3 4.75 25 134.0 26.3 5.09
200 100 675.1 257.7 2.62 3.80 170 100 579.4 206.2 2.81 4.08
75 506.3 170.0 2.98 75 434.6 130.7 3.32
50 337.6 76.1 4.43 50 289.7 62.5 4.64
25 168.8 38.3 4.41 25 144.9 30.4 4.77
250 100 807.3 309.3 2.61 4.45 185 100 644.5 229.4 2.81 4.24
75 605.4 164.8 3.67 75 483.4 140.6 3.44
50 403.7 86.3 4.68 50 322.3 66.7 4.83
25 201.9 31.2 6.48 25 161.1 32.4 4.98
275 100 903.3 347.4 2.60 4.24 200 100 709.9 252.6 2.81 4.04
75 677.4 185.3 3.66 75 532.4 167.0 3.19
50 451.7 98.3 4.60 50 355.0 75.4 4.70
25 225.8 44.5 5.07 25 177.5 38.3 4.63
300 100 1024.9 387.6 2.64 4.09 250 100 846.7 301.9 2.80 4.67
75 768.4 207.0 3.71 75 634.9 164.5 3.86
50 512.4 123.8 4.14 50 423.4 84.6 5.01
25 256.2 47.8 5.36 25 211.7 33.1 6.40
350 100 1119.1 436.8 2.56 4.23 275 100 952.8 331.6 2.87 4.54
75 839.3 232.6 3.61 75 714.6 181.5 3.94
50 559.7 128.3 4.36 50 476.5 97.3 4.90
25 279.9 46.0 6.09 25 238.2 43.6 5.47
375 100 1234.8 475.4 2.60 4.35 300 100 1074.8 370.5 2.90 4.31
75 926.1 253.9 3.65 75 806.0 203.3 3.96
50 617.5 136.2 4.53 50 537.4 125.7 4.27
25 308.8 49.0 6.31 25 268.7 46.6 5.76
400 100 1357.9 516.1 2.63 4.32 350 100 1176.8 415.1 2.84 4.48
75 1018.4 276.0 3.69 75 882.6 228.0 3.87
50 679.0 153.5 4.42 50 588.5 126.3 4.66
25 339.6 54.2 6.27 25 294.3 48.6 6.06
375 100 1304.1 455.0 2.87 4.60
Notes: 75 978.0 250.4 3.91
1. IPLV values are rated in accordance with ARI Standard 550/590-98. 50 652.1 135.2 4.82
2. COP and IPLV values include compressors, condenser fans and control kW.
25 326.1 51.8 6.30
400 100 1431.0 495.0 2.89 4.54
75 1073.2 272.6 3.94
50 715.6 152.4 4.70
25 357.9 57.5 6.23

Notes:
1. IPLV values are rated in accordance with ARI Standard 550/590-98.
2. COP and IPLV values include compressors, condenser fans and control kW.

RLC-PRC005-E4 37
Performance Data

English Units - Data in accordance with ARI 550/590-98. Information about ARI:
www.ari.org
Table P-13 - ARI Part-Load Performance for RTAC Standard Table P-14 - ARI Part-Load Performance for RTAC High
Efficiency Units (English Units) Efficiency Units (English Units)

% (kW) P.I. COP IPLV % (kW) P.I. COP IPLV


Unit Load cooling (kW) (kW/kW) (kW/kW) Unit Load cooling (kW) (kW/kW) (kW/kW)
140 100 141.2 172.8 9.80 13.42 120 100 121.3 139.7 10.4 14.00
75 105.9 115.8 10.89 75 91.0 92.9 11.66
50 70.6 54.3 15.50 50 60.7 45.3 15.94
25 35.3 28.5 14.75 25 30.3 23.7 15.23
155 100 154.4 191.2 9.7 13.35 130 100 134.1 154.2 10.4 14.19
75 115.8 127.1 10.86 75 100.6 101.2 11.84
50 77.2 60.6 15.19 50 67.1 50.0 15.99
25 38.6 29.6 15.51 25 33.5 25.0 15.97
170 100 167.9 209.3 9.6 13.14 140 100 147.5 169.0 10.4 13.79
75 125.9 137.7 10.90 75 110.6 116.5 11.31
50 84.0 66.7 15.00 50 73.8 55.1 15.95
25 42.0 35.1 14.28 25 36.9 30.0 14.63
185 100 186.1 228.9 9.7 13.60 155 100 160.3 185.7 10.3 13.69
75 139.6 148.1 11.23 75 120.2 127.8 11.21
50 93.1 71.4 15.53 50 80.2 61.1 15.62
25 46.5 37.0 15.00 25 40.1 30.9 15.44
200 100 204.8 248.7 9.9 13.08 170 100 173.4 204.0 10.2 13.48
75 153.6 173.7 10.54 75 130.05 137.7 11.24
50 102.4 79.8 15.28 50 86.7 66.9 15.43
25 51.2 43.7 13.97 25 43.35 36.2 14.25
250 100 245.3 399.4 9.90 14.90 185 100 192.6 223.5 10.3 13.93
75 183.9 230.6 12.84 75 144.5 148.5 11.58
50 122.6 123.0 16.06 50 96.3 72.2 15.90
25 61.3 54.2 18.23 25 48.2 38.1 15.07
275 100 274.4 450.9 9.81 14.42 200 100 212.2 242.9 10.4 13.46
75 205.8 260.3 12.73 75 159.2 173.5 10.93
50 137.2 142.4 15.52 50 106.1 80.4 15.72
25 68.6 66.3 16.65 25 53.1 44.9 14.09
300 100 311.0 503.6 9.95 13.80 250 100 255.1 396.7 10.34 15.09
75 233.2 291.1 12.90 75 191.3 233.8 13.18
50 155.5 183.4 13.65 50 127.6 125.0 16.43
25 77.8 70.3 17.82 25 63.8 59.8 17.17
350 100 340.1 566.7 9.67 14.23 275 100 285.6 439.2 10.48 14.97
75 255.0 327.3 12.55 75 214.2 259.1 13.31
50 170.1 181.9 15.05 50 142.8 144.7 15.89
25 85.0 78.5 17.45 25 71.4 64.9 17.72
375 100 374.6 617.5 9.78 14.05 300 100 321.7 490.4 10.57 14.19
75 280.9 357.2 12.66 75 241.3 289.8 13.41
50 187.3 195.1 14.46 50 160.9 188.4 13.75
25 93.7 85.1 17.72 25 80.4 68.6 18.87
400 100 411.8 670.9 9.89 14.50 350 100 352.2 553.0 10.27 14.56
75 308.8 388.2 12.81 75 264.2 328.2 12.96
50 205.9 217.1 15.27 50 176.2 182.5 15.54
25 103.0 92.8 17.87 25 88.1 84.3 16.82
375 100 390.3 605.6 10.39 14.82
Notes: 75 292.7 359.7 13.10
1. IPLV values are rated in accordance with ARI Standard 550/590-98. 50 195.2 197.6 15.91
2. EER and IPLV values include compressors, condenser fans and control kW.
25 97.6 91.8 17.12
400 100 428.1 658.2 10.48 14.80
75 321.1 390.8 13.23
50 214.1 219.7 15.69
25 107.1 99.7 17.29

Notes:
1. IPLV values are rated in accordance with ARI Standard 550/590-98.
2. EER and IPLV values include compressors, condenser fans and control kW.

38 RLC-PRC005-E4
Performance Data

Table P-15 - ARI Part-Load Performance for RTAC Standard Table P-16 - ARI Part-Load Performance for RTAC High
Efficiency Low Noise (English Units) Efficiency Low Noise Units (English Units)

% (kW) P.I. COP IPLV % (kW) P.I. COP IPLV


Unit Load cooling (kW) (kW/kW) (kW/kW) Unit Load cooling (kW) (kW/kW) (kW/kW)
140 100 132.7 180.3 8.80 13.17 120 100 115.8 142.4 9.70 14.32
75 99.5 114.0 10.41 75 86.85 88.8 11.66
50 66.4 52.3 15.13 50 57.9 42.8 16.14
25 33.2 24.9 15.85 25 28.95 20.0 17.25
155 100 145.3 199.0 8.70 13.33 130 100 128.2 156.5 9.80 14.69
75 109.0 123.2 10.54 75 96.15 96.2 11.91
50 72.7 57.0 15.18 50 64.1 46.2 16.55
25 36.3 26.2 16.50 25 32.05 21.4 17.85
170 100 158.2 216.7 8.70 13.11 140 100 141.2 171.0 9.90 14.14
75 118.7 133.2 10.62 75 105.9 111.8 11.28
50 79.1 63.5 14.86 50 70.6 51.7 16.25
25 39.6 30.2 15.59 25 35.3 25.3 16.62
185 100 175.6 236.9 8.80 13.66 155 100 153.5 188.7 9.70 14.23
75 131.7 142.3 11.03 75 115.1 121.5 11.29
50 87.8 67.3 15.55 50 76.8 56.3 16.24
25 43.9 32.3 16.20 25 38.4 26.3 17.36
200 100 193.2 257.7 9.00 12.98 170 100 166 206.2 9.60 13.94
75 144.9 170.0 10.17 75 124.5 130.7 11.34
50 96.6 76.1 15.13 50 83.0 62.5 15.83
25 48.3 38.3 15.05 25 41.5 30.4 16.28
250 100 231.4 417.1 8.94 15.28 185 100 184.5 229.4 9.80 14.49
75 173.5 221.4 12.61 75 138.4 140.6 11.74
50 115.7 116.2 16.04 50 92.3 66.7 16.49
25 57.9 41.8 22.28 25 46.1 32.4 17.00
275 100 258.8 468.4 8.91 14.54 200 100 203.2 252.6 9.90 13.79
75 194.1 249.0 12.55 75 152.4 167.0 10.88
50 129.4 132.2 15.76 50 101.6 75.4 16.06
25 64.7 59.8 17.41 25 50.8 38.3 15.80
300 100 293.6 522.8 9.05 14.04 250 100 242.7 406.9 9.61 16.03
75 220.2 278.2 12.74 75 182.0 221.1 13.25
50 146.8 166.6 14.19 50 121.3 113.8 17.17
25 73.4 64.2 18.40 25 60.7 44.4 22.02
350 100 320.5 588.8 8.77 14.51 275 100 273.1 447.0 9.85 15.59
75 240.4 312.6 12.38 75 204.8 244.0 13.52
50 160.3 173.0 14.92 50 136.6 130.8 16.80
25 80.2 61.8 20.88 25 68.3 58.6 18.76
375 100 353.7 641.0 8.89 14.93 300 100 308.1 499.6 9.94 14.78
75 265.3 341.2 12.52 75 231.0 273.3 13.61
50 176.9 183.5 15.52 50 154.0 169.2 14.66
25 88.5 65.8 21.65 25 77.0 62.7 19.77
400 100 388.9 695.9 9.01 14.80 350 100 337.1 559.4 9.71 15.34
75 291.7 370.9 12.66 75 252.8 306.4 13.29
50 194.5 206.9 15.13 50 168.6 170.3 15.94
25 97.3 72.8 21.51 25 84.3 65.3 20.79
375 100 373.6 613.4 9.82 15.75
Notes: 75 280.2 336.5 13.41
1. IPLV values are rated in accordance with ARI Standard 550/590-98. 50 186.9 182.2 16.51
2. EER and IPLV values include compressors, condenser fans and control kW.
25 93.4 69.6 21.62
400 100 409.9 667.2 9.90 15.56
75 307.5 366.4 13.51
50 205.0 205.5 16.06
25 102.5 77.3 21.37

Notes:
1. IPLV values are rated in accordance with ARI Standard 550/590-98.
2. EER and IPLV values include compressors, condenser fans and control kW.

RLC-PRC005-E4 39
Performance Data

Table P-17 - Performance Data Adjustment Factors


Altitude
Sea level 600 m 1200 m 1800 m
Chilled Water
Temperature

Compressor

Compressor

Compressor

Compressor
Drop C

Evaporator

Evaporator

Evaporator

Evaporator
Flow Rate

Flow Rate

Flow Rate

Flow Rate
Capacity

Capacity

Capacity

Capacity
Fouling
Cooling

Cooling

Cooling

Cooling
kW

kW

kW

kW
Factor
Compressor
(SI)
4 0.998 1.500 0.999 0.986 1.485 1.011 0.974 1.466 1.026 0.96 1.443 1.044
5 1.000 1.200 1.000 0.989 1.188 1.011 0.975 1.172 1.027 0.961 1.154 1.045
0.0176 6 1.000 1.000 1.000 0.99 0.990 1.013 0.977 0.977 1.028 0.962 0.962 1.046
m K/kW 7 1.002 0.857 1.001 0.991 0.849 1.013 0.979 0.837 1.029 0.964 0.825 1.047
8 1.003 0.750 1.001 0.992 0.743 1.015 0.98 0.733 1.03 0.966 0.722 1.049
9 1.004 0.667 1.02 0.995 0.660 1.016 0.982 0.651 1.031 0.967 0.641 1.05
10 1.005 0.600 1.025 0.997 0.594 1.017 0.983 0.586 1.032 0.97 0.577 1.051
4 0.982 1.479 0.99 0.972 1.464 1.020 0.96 1.446 1.017 0.946 1.425 1.035
5 0.984 1.183 0.991 0.974 1.171 1.030 0.962 1.157 1.019 0.947 1.140 1.036
0.044 6 0.986 0.986 0.992 0.976 0.976 1.050 0.964 0.964 1.02 0.95 0.950 1.038
m K/kW 7 0.987 0.845 0.993 0.978 0.837 1.060 0.966 0.826 1.021 0.952 0.814 1.039
8 0.99 0.740 0.995 0.98 0.732 1.080 0.968 0.723 1.022 0.954 0.713 1.041
9 0.993 0.657 0.996 0.983 0.651 1.090 0.97 0.643 1.023 0.956 0.633 1.042
10 0.995 0.592 0.997 0.985 0.586 1.010 0.973 0.578 1.024 0.958 0.570 1.043

Altitude
Sea level 2000 ft 4000 ft 6000 ft
Chilled Water
Temperature

Compressor

Compressor

Compressor

Compressor
Drop C

Evaporator

Evaporator

Evaporator

Evaporator
Capacity

Capacity

Capacity

Capacity
Fouling
Cooling

Cooling

Cooling

Cooling
gpm

gpm

gpm

gpm
kW

kW

kW

kW
Factor
Compressor
(SI)
8 0.997 1.246 0.999 0.987 1.233 1.012 0.975 1.217 1.027 0.960 1.200 1.045
10 1 1 1 0.989 0.989 1.013 0.977 0.977 1.028 0.963 0.963 1.047
0.0001 12 1.003 0.835 1.001 0.992 0.826 1.014 0.979 0.816 1.030 0.965 0.804 1.048
14 1.004 0.717 1.002 0.993 0.710 1.016 0.981 0.701 1.031 0.966 0.690 1.049
16 1.006 0.629 1.003 0.995 0.622 1.016 0.982 0.614 1.032 0.968 0.605 1.050
8 0.982 1.227 0.991 0.972 1.215 1.003 0.961 1.200 1.018 0.947 1.183 1.036
10 0.986 0.985 0.992 0.975 0.975 1.005 0.963 0.963 1.020 0.950 0.950 1.038
0.00025 12 0.988 0.823 0.994 0.978 0.815 1.006 0.966 0.805 1.022 0.952 0.793 1.040
14 0.991 0.708 0.995 0.980 0.700 1.008 0.968 0.692 1.023 0.954 0.682 1.041
16 0.992 0.621 0.996 0.982 0.614 1.009 0.970 0.606 1.024 0.956 0.598 1.042

40 RLC-PRC005-E4
Performance Data

Figure P-18 - Evaporator Water Pressure Drop (SI)


Evaporator Water Pressure Drop (SI)
kPa

Water Flow Rate L/s


Legend

1 = RTAC 120HE - 140STD 9 = RTAC 275 STD


2 = RTAC 130HE - 155STD 10 = RTAC 300 STD - 250 HE
3 = RTAC 170 STD - 140 HE 11 = RTAC 275HE - 300 HE
4 = RTAC 185 STD - 155 HE 12 = RTAC 350 STD
5 = RTAC 200 STD - 170 HE 13 = RTAC 375 STD
6 = RTAC 185 HE 14 = RTAC 400 STD - 350 HE
7 = RTAC 200 HE 15 = RTAC 375 HE
8 = RTAC 250 STD 16 = RTAC 400 HE

Figure P-19 - Water Side Pressure Drop (English Units)

ft of WG

ft of WG

100

80
60
50 2
40 6 10 11 15
7 9 13 14 16
12
30

20

10
8

6
5
4
1
3
34 5 8

1
100 1000 10000
(GPM)

Water Flow Rate gpm


Legend

1 = RTAC 120HE - 140STD 9 = RTAC 275 STD


2 = RTAC 130HE - 155STD 10 = RTAC 300 STD - 250 HE
3 = RTAC 170 STD - 140 HE 11 = RTAC 275HE - 300 HE
4 = RTAC 185 STD - 155 HE 12 = RTAC 350 STD
5 = RTAC 200 STD - 170 HE 13 = RTAC 375 STD
6 = RTAC 185 HE 14 = RTAC 400 STD - 350 HE
7 = RTAC 200 HE 15 = RTAC 375 HE
8 = RTAC 250 STD 16 = RTAC 400 HE

RLC-PRC005-E4 41
Controls

capacity available until the problem


can be solved. Whenever possible,
the chiller is allowed to perform its
function: make chilled water. In
addition, microcomputer controls
allow for more types of protection,
such as over and under voltage!
(option) Overall, the safety controls
help keep the building or process
running and out of trouble.
Stand-alone controls
Figure 7 - Easy View Interfacing to stand-alone units is
very simple: only a remote
auto/stop for scheduling is required
for unit operation. Signals from the
chilled-water pump contactor
auxiliary, or a flow switch, are wired
to the chilled-water flow interlock.
Signals from a time clock or some
other remote device are wired to
the external auto/stop input.
Tracer Chiller Control human
interfaces
The Trane air-cooled Series R Model
RTAC chiller offers two easy-to-use
operator interface panels, the
Figure 8 - Dyna View
EasyView, and the DynaView.
Standard Features
External Auto/Stop
Safety Controls A job-site-provided contact closure
A centralized microcomputer offers will turn the unit on and off.
a higher level of machine Chilled Waterflow Interlock
protection. Because the safety A job-site-provided contact closure
controls are smarter, they limit from a chilled-water pump
compressor operation in order to contactor, or a flow switch, is
avoid compressor or evaporator required and will allow unit
failures, thereby minimizing operation if a load exists. This
nuisance shutdowns. Tracer feature will allow the unit to run in
Chiller Controls directly senses the conjunction with the pump system.
control variables that govern the External Interlock
operation of the chiller: motor A job-site-provided contact opening
current draw, evaporator pressure, wired to this input will turn the unit
condenser pressure. When any one off and require a manual reset of
of these variables approaches a the unit microcomputer. This closure
limit condition at which the unit is typically triggered by a job-site-
may be damaged or shut down on a provided system such as a fire
safety, Tracer Chiller Controls takes alarm.
corrective action to avoid shutdown
and keep the chiller operating. It Chilled Water Pump Control
does this through combined actions Unit controls provide an output to
of compressor slide-valve control the chilled-water pump(s).
modulation, electronic expansion- One contact closure to the chiller is
valve modulation, and fan staging. all that is required to initiate the
Tracer Chiller Controls optimizes chilled-water system. Chilled water
total chiller power consumption pump control by the chiller is a
during normal operating conditions. requirement on all the Air-Cooled
During abnormal operating Series R Chillers.
conditions, the microprocessor will
continue to optimize chiller
performance by taking the
corrective action necessary to avoid
shutdown. This keeps cooling

42 RLC-PRC005-E4
Controls

Alarm Indication Contacts LonTalk Communications


Four factory-installed contacts with
the following preset default Interface for Chillers
assignments: (LCI-C)
Alarm
LonTalk Communications Interface
Chiller running
for Chillers (LCI-C) provides a
Maximum capacity
generic automation system with the
Chiller limit.
LonMark chiller profile
Additional Features that May Be inputs/outputs. The inputs/ outputs
Added include both mandatory and
(require some optional factory- optional network variables. Note:
installed hardware) LonMark network variable names
Ice-making card are in parentheses when different
Tracer communication card from chiller naming convention.
Chilled water and remote current-
limit set point card. Chiller Inputs:
Note: All wiring outside the unit is Chiller Enable/Disable
supplied at the job site.
Chilled Liquid Setpoint (Cool
Easy Interface to A Generic Building
Setpoint)
Management System
Controlling the air-cooled Series R Current Limit Setpoint (Capacity
chiller with building management Limit Input)
systems is state-of-the-art, yet Ice Making (Chiller Mode)
simple with either the LonTalk
Communications Interface for Chiller Enable/Disable
Chillers (LCI-C) or Generic Building Allows for chiller to be started or
Management System Hardwire stopped depending on if certain
Points. operating conditions are met.
Simple Interface with Other Control Chilled Liquid Setpoint
Systems Allows for the external setting
Microcomputer controls afford independent of the front panel
simple interface with other control setpoint to adjust the leaving water
systems, such as time clocks, temperature setpoint.
building automation systems, and Current Limit Setpoints
ice storage systems. This means Allows for the external setting
you have the flexibility to meet job independent of the front panel
requirements while not having to setpoint to limit the capacity level of
learn a complicated control system. the chiller.
This setup has the same standard Ice Making
features as a stand-alone water Provides interface with ice making
chiller, with the possibility of having control systems. Please refer to
additional optional features. page 9 for more information.
What are LonTalk, Echelon, and Chiller Outputs:
LonMark?
LonTalk is a communications On/Off o Active Setpoint
protocol developed by the Echelon Average Percent RLA (Actual
Corporation. The LonMark Capacity Level)
association develops control
profiles using the LonTalk Active Current Limit Setpoint
communication protocol. LonTalk is (Capacity Limit)
a unit level communications Leaving Chilled Water Temperature
protocol, unlike BACNet used at the
system level. Entering Chilled Water
Temperature
Alarm Descriptor
Chiller Status

RLC-PRC005-E4 43
Controls

On/Off External Current Limit Setpoint -


Indicates the current state of the option
chiller
Allows the external setting
Active Setpoint independent of the front panel
Indicates the current value of the
setpoint by one of two means:
leaving water temperature setpoint
Average Percent RLA a) 2-10 VDC input, or
Provides the current capacity level b) 4-20 mA input
via %RLA
Chiller hardwire outputs include:
Active Current Limit Setpoint
Provides the current capacity level Compressor running indication
setpoint via %RLA
Alarm indication (Ckt1/Ckt 2)
Leaving Chilled Water Temperature
Provides the current leaving water Maximum capacity
temperature Ice making status
Entering Chilled Water Temperature
Alarm Indication Contacts
Provides the current entering water
The unit provides three single-pole/
temperature
double-throw contact closures to
Alarm Descriptor indicate:
Provides alarm messages based on
a) Compressor on/off status
predetermined criteria
Chiller Status b) Compressor running at
Indicates the running modes and maximum capacity
states of the chiller, i.e. Running in c) Failure has occurred (Ckt
alarm mode, chiller enabled, chiller 1/Ckt 2)
being locally controlled, etc
These contact closures may be used
Generic Building to trigger jobsite supplied alarm
Management System lights or alarm bells.

Hardwire Points Ice Making Control - option


Provides interface with ice making
GBAS may be achieved via control systems.
hardware input/output as well. The
input/outputs are as follows:
Chiller hardwire inputs include:
Chiller enable/disable
Circuit enable/disable
External chilled water setpoint -
option
External current limit setpoint -
option
Ice making enable - option
External Chilled Water Setpoint -
option
Allows the external setting
independent of the front panel
setpoint by one of two means:
a) 2-10 VDC input, or
b) 4-20 mA input

44 RLC-PRC005-E4
Controls

Tracer Summit Controls The 115-volt supply handles the provided over the twisted wire pair
freeze protection for the evaporator from a Tracer system, or a LonTalk
Interface with the Trane heaters. Communication Interface but will
Integrated Comfort A single twisted pair of wires tied require the communication boards
directly between the air-cooled provided with the Ice Making
System (ICS) Series R chiller and a Tracer Control Option.
Trane Chiller Plant Control Summit system provides control, Additional Options That May Be
The Tracer Chiller Plant Manager monitoring, and diagnostic Used
building management system capabilities. Control functions Failure Indication Contacts
provides building automation and include auto/stop, adjustment of Communications Interface (For
energy management functions leaving-water-temperature set point, Tracer Systems)
through stand-alone control. The compressor operation lockout for Chilled-Water Temperature Reset
Chiller Plant Control is capable of kW demand limiting, and control of
monitoring and controlling your ice-making mode. The Tracer system
entire chiller plant system. reads monitoring information such
Application software available: as entering- and leaving-evaporator-
water temperatures and outdoor air
Time-of-day scheduling temperature. Over 60 individual
Demand limiting diagnostic codes can be read by the
Chiller sequencing Tracer system. In addition, the
Process control language Tracer system can provide
Boolean processing sequencing control for up to
Zone control 25 units on the same chilled-water
Reports and logs loop. Pump sequencing control can
Custom messages be provided from the Tracer system.
Run time and maintenance Tracer ICS is not available in
conjunction with the external set
Trend log
point capability.
PID control loops
And of course, the Trane Chiller Required Options
Plant Control can be used on a
stand-alone basis or tied into a
complete building automation 1
system. Tracer Interface
When the air-cooled Series R Additional Options that May Be
chiller is used in conjunction with a Used
Trane Tracer Summit system, the Ice-Making Control
unit can be monitored and External Trane Devices Required
controlled from a remote location. Tracer Summit, Tracer 100 System
The air-cooled Series R chiller can or Tracer Chiller Plant Control
be controlled to fit into the overall
Ice-Making Systems Controls
building automation strategy by
An ice-making option may be
using time-of-day scheduling, timed
ordered with the air-cooled Series
override, demand limiting, and
R chiller. The unit will have two
chiller sequencing. A building
operating modes, ice making and
owner can completely monitor the
normal daytime cooling. In the ice-
air-cooled Series R chiller from the
making mode, the air-cooled Series
Tracer system, since all of the
R chiller will operate at full
monitoring information indicated
compressor capacity until the return
on the microcomputer can be read
chilled-fluid temperature entering
on the unit controllers Tracer system
the evaporator meets the ice-
display. In addition, all the powerful
making set point. Two input signals
diagnostic information can be read
are required to the air-cooled Series
back at the Tracer system. Best of
R chiller for the ice-making option.
all, this powerful capability comes
The first is an auto/stop signal for
over a single twisted pair of wires!
scheduling, and the second is
Air-cooled Series R chillers can
required to switch the unit between
interface with many different
the ice-making mode and normal
external control systems, from
daytime operation. The signals are
simple stand-alone units to ice-
provided by a remote job site
making systems. Each unit requires
building-automation device such as
a single-source, three-phase power
a time clock or a manual switch. In
supply and a 115-volt power supply.
addition, the signals may be

RLC-PRC005-E4 45
Job Site Data

Table J-1 - Customer Wire Selection RTAC 120 - 200


Unit without Unit with
Disconnect Switch Disconnect Switch
Voltage Wire Selection Size to
400/3/50 Main Terminal Block Wire Selection Size to Disconnect Switch
Unit Maximum cable Disconnect Switch Maximum cable
Size size mm size (Amps) size mm2
Standard
140 2x240 625 2x240
155 2x240 925 2x240
170 2x240 925 2x240
185 2x240 925 2x240
200 2x240 925 2x240
Standard Low Noise
140 2x240 625 2x240
155 2x240 925 2x240
170 2x240 925 2x240
185 2x240 925 2x240
200 2x240 925 2x240
High Efficiency
120 2x240 625 2x240
130 2x240 625 2x240
140 2x240 625 2x240
155 2x240 925 2x240
170 2x240 925 2x240
185 2x240 925 2x240
200 2x240 925 2x240
High Efficiency Low Noise
120 2x240 625 2x240
130 2x240 625 2x240
140 2x240 625 2x240
155 2x240 925 2x240
170 2x240 925 2x240
185 2x240 925 2x240
200 2x240 925 2x240

Table J-2 - Customer Wire Selection RTAC 250 - 400


Unit without Unit with
Disconnect Switch Disconnect Switch
Voltage Wire Selection Size to
400/3/50 Main Terminal Block Wire Selection Size to Disconnect Switch
Unit Maximum cable Disconnect Switch Maximum cable
Size size mm size (Amps) size mm2
Standard
250 4x185 1000 4x185
275 4x185 1000 4x185
300 4x195 1250 4x195
350 4x195 1250 4x195
375 6x240 1600 6x240
400 6x240 1600 6x240
Standard Low Noise
250 4x185 1000 4x185
275 4x185 1000 4x185
300 4x195 1250 4x195
350 4x195 1250 4x195
375 6x240 1600 6x240
400 6x240 1600 6x240
High Efficiency
250 4x185 1000 4x185
275 4x185 1000 4x185
300 4x195 1250 4x195
350 4x195 1250 4x195
375 6x240 1600 6x240
400 6x240 1600 6x240
High Efficiency Low Noise
250 4x185 1000 4x185
275 4x185 1000 4x185
300 4x195 1250 4x195
350 4x195 1250 4x195
375 6x240 1600 6x240
400 6x240 1600 6x240
Note: the material for busbar is copper.

46 RLC-PRC005-E4
Electrical Data

Table E-1 - Electrical Data RTAC 120 - 200 400/3/50


Unit Wiring
Unit Number Maximum Starting Power Compressor Short Circuit
Size of Power Amps (1) Amps (2) Factor (5) Fuse Size Rating (kA)
Connections (A)
Standard
140 1 398 432 0.90 250/250 35.0
155 1 437 469 0.89 315/250 35.0
170 1 475 500 0.89 315/315 35.0
185 1 525 568 0.89 400/400 35.0
200 1 574 606 0.89 400/400 35.0
Standard Low Noise
140 1 383 417 0.90 250/250 35.0
155 1 420 452 0.89 315/250 35.0
170 1 456 481 0.89 315/315 35.0
185 1 504 547 0.89 400/400 35.0
200 1 551 583 0.89 400/400 35.0
High Efficiency
120 1 330 366 0.89 250/250 35.0
130 1 369 413 0.89 250/250 35.0
140 1 407 441 0.90 250/250 35.0
155 1 444 478 0.89 315/250 35.0
170 1 484 509 0.89 315/315 35.0
185 1 534 577 0.89 400/400 35.0
200 1 583 615 0.89 400/400 35.0
High Efficiency Low Noise
120 1 315 351 0.89 250/250 35.0
130 1 352 396 0.89 250/250 35.0
140 1 388 422 0.90 250/250 35.0
155 1 423 457 0.89 315/250 35.0
170 1 461 486 0.89 315/315 35.0
185 1 509 552 0.89 315/315 35.0
200 1 557 589 0.89 315/315 35.0

Table E-1 - Continued, Electrical Data RTAC 120 - 200 400/3/50


Motor Data
Compressor (Each) Fans (Each) (6)
Unit Maximum Starting Fans fuse Evaporator
Amps (3) Amps (4) Control heater
Quantity Circuit Circuit Circuit Circuit Quantity kW FLA size VA A kW
1 2 1 2 (A)
Standard
140 2 178 178 259 259 8 2.05 4.5 80 860 2.15 2.04
155 2 214 178 291 259 9 2.05 4.5 80 860 2.15 2.04
170 2 214 214 291 291 10 2.05 4.5 80 860 2.15 2.04
185 2 259 214 354 291 11 2.05 4.5 80 860 2.15 2.04
200 2 259 259 354 354 12 2.05 4.5 80 860 2.15 2.04
Standard Low Noise
140 2 178 178 259 259 8 1.05 2.6 80 860 2.15 2.04
155 2 214 178 291 259 9 1.05 2.6 80 860 2.15 2.04
170 2 214 214 291 291 10 1.05 2.6 80 860 2.15 2.04
185 2 259 214 354 291 11 1.05 2.6 80 860 2.15 2.04
200 2 259 259 354 354 12 1.05 2.6 80 860 2.15 2.04
High Efficiency
120 2 147 147 217 217 8 2.05 4.5 80 860 2.15 2.04
130 2 178 147 259 217 9 2.05 4.5 80 860 2.15 2.04
140 2 178 178 259 259 10 2.05 4.5 80 860 2.15 2.04
155 2 214 178 291 259 11 2.05 4.5 80 860 2.15 2.04
170 2 214 214 291 291 12 2.05 4.5 80 860 2.15 2.04
185 2 259 214 354 291 13 2.05 4.5 80 860 2.15 2.04
200 2 259 259 354 354 14 2.05 4.5 80 860 2.15 2.04
High Efficiency Low Noise
120 2 147 147 217 217 8 1.05 2.6 80 860 2.15 2.04
130 2 178 147 259 217 9 1.05 2.6 80 860 2.15 2.04
140 2 178 178 259 259 10 1.05 2.6 80 860 2.15 2.04
155 2 214 178 291 259 11 1.05 2.6 80 860 2.15 2.04
170 2 214 214 291 291 12 1.05 2.6 80 860 2.15 2.04
185 2 259 214 354 291 13 1.05 2.6 80 860 2.15 2.04
200 2 259 259 354 354 14 1.05 2.6 80 860 2.15 2.04
Notes:
1. Maximum Compressors FLA + all fans FLA + control Amps
2. Starting Amps of the circuit with the largest compressor circuit including fans plus RLA of the second circuit including fans and control amps
3. Maximum FLA per compressor
4. Compressors starting amps, Star delta start
5. Compressor Power Factor
6. High static fans data - 100Pa ESP - Quantity same as standard fans, power input = 2.21kW each, FLA = 3.9 each

RLC-PRC005-E4 47
Electrical Data

Table E-2 - Electrical Data RTAC 250 - 400 400/3/50


Unit Wiring
Unit Number of Power Maximum Starting Power Compressor Short Circuit
Size Connections Amps (1) Amps (2) Factor (5) Fuse Size (A) Rating (kA)
Standard
250 1 687 696 0.89 250-250/400 35.0
275 1 768 759 0.89 315-315/400 35.0
300 1 867 836 0.89 400-400/400 35.0
350 1 955 876 0.89 315-315/315-315 35.0
375 1 1054 953 0.89 400-400/315-315 35.0
400 1 1153 1059 0.89 400-400/400-400 35.0
Standard Low Noise
250 1 660 669 0.89 250-250/400 35.0
275 1 737 728 0.89 315-315/400 35.0
300 1 832 801 0.89 400-400/400 35.0
350 1 917 838 0.89 315-315/315-315 35.0
375 1 1012 911 0.89 400-400/315-315 35.0
400 1 1107 1013 0.89 400-400/400-400 35.0
High Efficiency
250 1 696 705 0.89 250-250/400 35.0
275 1 777 768 0.89 315-315/400 35.0
300 1 876 845 0.89 400-400/400 35.0
350 1 973 894 0.89 315-315/315-315 35.0
375 1 1072 971 0.89 400-400/315-315 35.0
400 1 1171 1077 0.89 400-400/400-400 35.0
High Efficiency Low Noise
250 1 665 674 0.89 250-250/400 35.0
275 1 742 733 0.89 315-315/400 35.0
300 1 838 807 0.89 400-400/400 35.0
350 1 927 848 0.89 315-315/315-315 35.0
375 1 1022 921 0.89 400-400/315-315 35.0
400 1 1117 1023 0.89 400-400/400-400 35.0

Table E-2 - Continued, Electrical Data RTAC 250 - 400 400/3/50


Motor Data
Compressor (Each)
Unit Maximum Amps (3) Starting Amps (4)
Size Quantity cmpr 1 cmpr 2 cmpr 3 cmpr 4 cmpr 1 cmpr 2 cmpr 3 cmpr 4
Standard
250 3 178 178 259 259 259 354
275 3 214 214 259 291 291 354
300 3 259 259 259 354 354 354
350 4 214 214 214 214 291 291 291 291
375 4 259 259 214 214 354 354 291 291
400 4 259 259 259 259 354 354 354 354
Standard Low Noise
250 3 178 178 259 259 259 354
275 3 214 214 259 291 291 354
300 3 259 259 259 354 354 354
350 4 214 214 214 214 291 291 291 291
375 4 259 259 214 214 354 354 291 291
400 4 259 259 259 259 354 354 354 354
High Efficiency
250 3 178 178 259 259 259 354
275 3 214 214 259 291 291 354
300 3 259 259 259 354 354 354
350 4 214 214 214 214 291 291 291 291
375 4 259 259 214 214 354 354 291 291
400 4 259 259 259 259 354 354 354 354
High Efficiency Low Noise
250 3 178 178 259 259 259 354
275 3 214 214 259 291 291 354
300 3 259 259 259 354 354 354
350 4 214 214 214 214 291 291 291 291
375 4 259 259 214 214 354 354 291 291
400 4 259 259 259 259 354 354 354 354

48 RLC-PRC005-E4
Electrical Data

Table E-2 - Continued, Electrical Data RTAC 250 - 400 400/3/50


Fan Motor and Control Circuit Data
Fans (Each) (6) Control Evaporator
heater
Unit Fans fuse
Size Quantity kW FLA size (A) VA A kW
Standard
250 14 2.05 4.5 63/40 1730 4.32 2.04
275 16 2.05 4.5 63/40 1730 4.32 2.04
300 18 2.05 4.5 63/40 1730 4.32 2.04
350 20 2.05 4.5 63/63 1730 4.32 2.04
375 22 2.05 4.5 63/63 1730 4.32 2.04
400 24 2.05 4.5 63/63 1730 4.32 2.04
Standard Low Noise
250 14 1.05 2.6 40/20 1730 4.32 2.04
275 16 1.05 2.6 40/20 1730 4.32 2.04
300 18 1.05 2.6 40/20 1730 4.32 2.04
350 20 1.05 2.6 40/40 1730 4.32 2.04
375 22 1.05 2.6 40/40 1730 4.32 2.04
400 24 1.05 2.6 40/40 1730 4.32 2.04
High Efficiency
250 16 2.05 4.5 80/40 1730 4.32 2.04
275 18 2.05 4.5 80/40 1730 4.32 2.04
300 20 2.05 4.5 80/40 1730 4.32 2.04
350 24 2.05 4.5 80/80 1730 4.32 2.04
375 26 2.05 4.5 80/80 1730 4.32 2.04
400 28 2.05 4.5 80/80 1730 4.32 2.04
High Efficiency Low Noise
250 16 1.05 2.6 50/20 1730 4.32 2.04
275 18 1.05 2.6 50/20 1730 4.32 2.04
300 20 1.05 2.6 50/20 1730 4.32 2.04
350 24 1.05 2.6 50/50 1730 4.32 2.04
375 26 1.05 2.6 50/50 1730 4.32 2.04
400 28 1.05 2.6 50/50 1730 4.32 2.04
Notes:
1. Maximum Compressors FLA + all fans FLA + control amps
2. Starting amps of the circuit with the largest compressor circuit including fans plus RLA of the second circuit including fans and control amps
3. Maximum FLA per compressor
4. Compressors starting amps, Star delta start
5. Compressor Power Factor
6. High static fans data - 100Pa ESP - Quantity same as standard fans, power input = 2.21kW each, FLA = 3.9 each

RLC-PRC005-E4 49
Dimensional Data

50 RLC-PRC005-E4
Dimensional Data

RLC-PRC005-E4 51
Dimensional Data

52 RLC-PRC005-E4
Dimensional Data

RLC-PRC005-E4 53
Dimensional Data

54 RLC-PRC005-E4
Mechanical Specifications

General gas-cooled, hermetically sealed,


Units are leak- and pressure-tested two-pole squirrel-cage induction
at 24.5 bars [350 psi] high side and motor. Oil separator and filtration
14 bars [200 psi] low side, and then devices are provided separate from
evacuated and charged. Packaged the compressor. Check valves in the
units ship with a full operating compressor discharge and lube oil
charge of oil and refrigerant. Unit system, and a solenoid valve in the
panels, structural elements, and lube system, are provided.
control boxes are constructed of 1.5 Refrigeration Circuits
to 3 mm [11 to 16 gauge] galvanized Each unit has two refrigerant
sheet metal and mounted on a circuits, with one or two helical-
welded structural-steel base. The rotary compressors per circuit. Each
unit panels, control boxes, and refrigerant circuit includes a
structural-steel base are finished mechanical filter, liquid-line shutoff
with an air-dry paint RAL 1019. valve, liquid-line sight glass,
Evaporator charging port, and an electronic
The evaporator is a tube-in-shell expansion valve. Fully modulating
heat exchanger design, with compressors and electronic
internally-finned copper tubes roller- expansion valves provide variable
expanded into the tube sheet. The capacity modulation over the entire
evaporator is designed, tested, and operating range. (Optional
stamped in accordance with the compressor suction service valve).
appropriate pressure-vessel code Unit Controls
approval. The evaporator is All unit controls are housed in a
designed for a waterside working weather-tight enclosure, with
pressure of 14 bars[200 psi]. Water removable plates to allow for
connections are grooved pipe for customer connection of power
Victaulic couplings. Each shell wiring and remote interlocks. All
includes a vent, a drain, and fittings controls, including sensors, are
for temperature control sensors, factory-mounted and tested prior to
and is insulated with 19mm [3/4 shipment. Microcomputer controls
inch] Armaflex II (or equivalent) provide all control functions
insulation (K=0.26). Evaporator including startup and shutdown,
heaters with thermostats are leaving-chilled-water temperature
provided to protect the evaporator control, compressor and electronic
from freezing at ambient expansion-valve modulation, fan
temperatures down to -29C [20F]. sequencing, anti-recycle logic,
Condenser and Fans automatic lead/lag compressor
Air-cooled condenser coils have starting, and load limiting. The unit
aluminum fins mechanically bonded control module, utilizing the
to internally-finned seamless copper Adaptive Control microprocessor,
tubing. The condenser coil has an automatically takes action to avoid
integral subcooling circuit. unit shutdown due to abnormal
Condensers are factory proof- and operating conditions associated
leak-tested at 35 bars [500 psi]. with low refrigerant pressure, high
Direct-drive vertical-discharge airfoil condensing pressure, and motor
ZephyrWing condenser fans are current overload. Should the
dynamically balanced. Three-phase abnormal operating condition
condenser fan motors with continue until a protective limit is
permanently-lubricated ball violated, the unit will be shut down.
bearings are provided. Standard Unit protective functions include
units will start and operate from 0 to loss of chilled-water flow,
46C [32 to 115F] ambient. (High evaporator freezing, loss of
ambient option above 40C). refrigerant, low refrigerant
Compressor and Lube Oil System pressure, high refrigerant pressure,
The helical-rotary compressor is reverse rotation, compressor-
semi-hermetic, direct drive, starting and -running overcurrent,
3000 rpm, with capacity-control phase loss, phase imbalance, phase
slide valve, a load/unload valve, reversal, and loss of oil flow. The
rolling element bearings, differential Easy View digital display indicates
refrigerant pressure oil pump, and the chilled-water set point and the
oil heater. The motor is a suction- leaving-chilled-water temperature.

RLC-PRC005-E4 55
Mechanical Specifications

In addition, the Dyna View indicates


the current limit set point, the
evaporator and condenser
refrigerant pressures, and electrical
information. Both standard and
optional displays can be viewed on
the unit without opening any
control panel doors. Standard
power connections include main
three-phase power to the
compressors, condenser fans,
control power transformer, and
freeze protection on the evaporator
heaters.
Starters
Starters are housed in a weather-
tight enclosure with hinged doors to
allow for customer connection of
power wiring. Wye-Delta closed
transition starters (33% of LRA
inrush) are standard.

56 RLC-PRC005-E4
Note

RLC-PRC005-E4 57
Note

58 RLC-PRC005-E4
Note

RLC-PRC005-E4 59
Literature Order Number RLC-PRC005-E4
Date 1003
Supersedes RLC-PRC005-E4-0502
Stocking Location Europe
Trane Since The Trane Company has a policy of continuous product improvement, it reserves the right to change
A business of American Standard Companies design and specifications without notice.
www.trane.com Socit Trane Socit Anonyme au capital de 61 005 000 Euros Siege Social: 1 rue des Amriques
For more information contact your local 88190 Golbey France Siret 306 050 188-00011 RSC Epinal B 306 050 188
district office or e-mail us at comfort@trane.com Numro didentification taxe intracommunautaire: FR 83 3060501888

Potrebbero piacerti anche