STRUCTURAL DRAWINGS

GENERAL 3.0 BULK EARTHWORKS 5.07 WHERE FOOTINGS ARE OVER-EXCAVATED, FILL OVER-EXCAVATED
AREAS WITH BLINDING CONCRETE GRADE SAME AS FOOTING TO A
1.01 TECHNICAL SPECIFICATIONS OR SPECIFIC INSTRUCTIONS ON 3.01 ALL EXCAVATION WORK TO BE CARRIED OUT TO THE SATISFACTION OF MINIMUM THICKNESS OF 50mm.
DRAWINGS TAKE PRECEDENCE OVER THESE NOTES. THE GEOTECHNICAL CONSULTANT INCLUDING INSPECTION OF
STRIPPING, APPROVAL OF FILL MATERIAL AND APPROVAL OF 5.08 KEEP FOOTINGS CLEAN AND FREE OF LOOSE MATERIAL BEFORE
1.02 THESE DRAWINGS SHALL BE READ IN CONJUNCTION WITH ALL COMPACTION. INSPECTION, IMMEDIATELY PRIOR TO POURING OF CONCRETE, AND
ARCHITECTURAL AND OTHER CONSULTANTS' DRAWINGS AND DURING POURING.
SPECIFICATIONS AND WITH SUCH OTHER WRITTEN INSTRUCTIONS AS 3.02 REFER TO THE GEOTECHNICAL REPORT FOR EXCAVATION CONDITIONS,
MAY BE ISSUED DURING THE COURSE OF THE CONTRACT. ANY INCLUDING NATURAL WATER LEVELS AND GROUND CONDITIONS. 5.09 DO NOT EXCEED A RISE OF 1000mm IN A RUN OF 3000mm FOR THE LINE
DISCREPANCY SHALL BE REFERRED TO THE ENGINEER BEFORE OF SLOPE BETWEEN ADJACENT FOOTINGS OR EXCAVATIONS.
PROCEEDING WITH THE WORK. CONSTRUCTION FROM THESE 3.03 REFER TO SURVEY DRAWINGS FOR EXISTING SERVICES AND LEVELS.

STRATHFIELD NSW 2135


DRAWINGS, AND THEIR ASSOCIATED CONSULTANTS' DRAWINGS, IS 5.10 DO NOT BACKFILL RETAINING WALLS (OTHER THAN CANTILEVER WALLS)
NOT TO COMMENCE UNTIL APPROVED BY THE LOCAL AUTHORITIES. 3.04 ALL LEVELS SHOWN ARE TO AUSTRALIAN HEIGHT DATUM. UNTIL FLOOR CONSTRUCTION AT TOP AND BOTTOM IS COMPLETED.
ENSURE FREE DRAINING BACKFILL AND DRAINAGE IS IN PLACE.
1.03 ALL MATERIALS AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH
3.05 V.R.C. INDICATES VERTICAL ROCK CUT, ROCK TO BE CUT NEAR
THE RELEVANT AND CURRENT STANDARDS AUSTRALIA CODES AND 5.11 FOOTINGS ARE TO BE CONSTRUCTED AND BACKFILLED AS SOON AS
WITH BY BY-LAWS AND ORDINANCES OF THE RELEVANT BUILDING POSSIBLE FOLLOWING EXCAVATION TO AVOID SOFTENING OR DRYING
NOTED OTHERWISE.
AUTHORITIES EXCEPT WHERE VARIED BY THE PROJECT SPECIFICATION. OUT BY EXPOSURE.
1.04 ALL DIMENSIONS SHOWN SHALL BE VERIFIED BY THE BUILDER ON SITE. 3.06 OVERBURDEN OCCURRING ABOVE ROCK SHALL BE BATTERED BACK AT 5.12 FOR FOOTINGS FOUNDED ON CONTROLLED FILL, REFER TO NOTE 4.04.
15 MELVILLE AVE
ENGINEER'S DRAWINGS SHALL NOT BE SCALED FOR DIMENSIONS. 2:1 AS REQUIRED.

1.05 DURING CONSTRUCTION THE STRUCTURE, AND ANY ASSOCIATED 3.07 SITE SURFACE CONTOURS SHOWN ARE INDICATIVE ONLY. FOR TRUE 6.0 CONCRETE
EXCAVATIONS, SHALL BE MAINTAINED IN A STABLE CONDITION AND NO SURFACE LEVELS REFER SURVEY DRAWINGS. 6.01 ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH
PART SHALL BE OVERSTRESSED. TEMPORARY BRACING SHALL BE
AS 3600 CURRENT EDITION WITH AMENDMENTS, EXCEPT WHERE
PROVIDED BY THE BUILDER TO KEEP THE WORKS AND EXCAVATIONS 4.0 SLAB ON GRADE VARIED BY THE CONTRACT DOCUMENTS.
STABLE AT ALL TIMES.
4.01 REMOVE ALL TOP SOIL INCLUDING ROOTS AND ANY OTHER ORGANIC
1.06 UNLESS NOTED OTHERWISE, ALL DIMENSIONS ARE IN MILLIMETRES MATTER. STORE TOP SOIL AS REQUIRED. 6.02 PRE-MIXED CONCRETE SUPPLY SHALL COMPLY WITH AS 1379.
(mm) AND ALL LEVELS ARE IN METRES (m) TO AUSTRALIAN HEIGHT
DATUM (AHD). 4.02 WHERE SHOWN ON THE DRAWINGS, BASE AND SAND BLINDING ARE TO 6.03 NO ADMIXTURES SHALL BE USED IN CONCRETE UNLESS APPROVED IN
BE PLACED AND COMPACTED AS SPECIFIED. WRITING.
1.07 ALL ABBREVIATIONS ARE IN ACCORDANCE WITH AS 1100. ADDITIONAL 6.04 CONCRETE MIX DESIGNS TO BE SUBMITTED FOR REVIEW PRIOR TO USE
ABBREVIATIONS USED ARE AS FOLLOWS: 4.03 EXCAVATE TO THE REQUIRED FORMATION LEVEL AND PROOF ROLL OF CONCRETE.
NSOP NOT SHOWN ON PLAN FORMATION WITH 6 PASSES OF A 10 TONNE SMOOTH WHEELED
NSOE NOT SHOWN ON ELEVATION ROLLER. SOFT AREAS ARE TO BE REMOVED AND REPLACED WITH 6.05 ENSURE CLEAR COVER TO REINFORCEMENT IS AS FOLLOWS UNLESS
UNO UNLESS NOTED OTHERWISE SUITABLE FILL COMPACTED TO THE DENSITY NOMINATED BELOW. DETAILED OTHERWISE.
U/S UNDERSIDE
GL GROUND LINE 4.04 CONTROLLED FILL MATERIAL SHALL MEET THE REQUIREMENTS OF THE COVER (mm)
FFL FINISHED FLOOR LEVEL GEOTECHNICAL REPORT. PLACE IN MAXIMUM 150mm THICK LAYERS TO FORMED - FORMED - NOT NOT FORMED -
98% STANDARD COMPACTION IN ACCORDANCE WITH AS 1289-E1.1 ELEMENT
EXPOSED TO EXPOSED TO CAST AGAINST
2.0 DESIGN DATA MAXIMUM DEPTH OF FILL IS TO BE 400mm FOR COHESIVE FILL AND WEATHER (B1) WEATHER (A1) GROUND
800mm FOR GRANULAR FILL.
FOOTINGS & PILES - - 50
2.01 THE STRUCTURAL COMPONENTS DETAILED ON THESE DRAWINGS HAVE
BEEN DESIGNED IN ACCORDANCE WITH THE RELEVANT STANDARDS 4.05 CLAY SUBGRADE FORMATION IS TO BE MAINTAINED AT OPTIMUM SLABS ON GROUND
40 20 -
AUSTRALIA CODES AND LOCAL GOVERNMENT ORDINANCES FOR THE MOISTURE CONTENT -0,+3% PRIOR TO COVERING. (TOP COVER)
FOLLOWING LOADINGS. REFER TO ARCHITECTURAL DRAWINGS FOR
PROPOSED FLOOR USAGE. 5.0 FOUNDATIONS 6.06 CONCRETE SIZES SHOWN DO NOT INCLUDE THICKNESSES OF APPLIED
FINISHES.
2.02 LIVE LOADS ARE IN ACCORDANCE WITH AS 1170.1. 5.01 FOUNDATIONS HAVE BEEN DESIGNED FOR THE FOLLOWING
ALLOWABLE PRESSURES: 6.07 DEPTHS OF BEAMS ARE GIVEN FIRST AND INCLUDE SLAB THICKNESS.
SUPERIMPOSED DEAD
FLOOR USAGE LIVE LOAD (kPa) 6.08 FOR CHAMFERS, DRIP GROOVES, REGLETS, ETC., REFER TO
LOADS (kPa)
BEARING PRESSURE SHAFT ADHESION ARCHITECTURAL DETAILS. MAINTAIN COVER TO REINFORCEMENT AT
ELEMENT
RESIDENTIAL (kPa) (kPa) THESE DETAILS.
- INTERNAL 0.50 1.5 WAFFLE SLAB, PAD &
150 - 6.09 NO HOLES, CHASES OR EMBEDMENT OF PIPES OTHER THAN THOSE
- WET AREAS 1.00 1.5 STRIP FOOTINGS
SHOWN ON THE STRUCTURAL DRAWINGS SHALL BE MADE IN
PILES 300 25 CONCRETE MEMBERS WITHOUT THE PRIOR WRITTEN APPROVAL OF
- BALCONIES 0.50 2.0
THE ENGINEER.
5.02 THE FOUNDATION MATERIAL SHALL BE APPROVED BY THE
2.03 WIND LOADS ARE IN ACCORDANCE WITH AS 1170.2-2002 AS FOLLOWS: 6.10 CONSTRUCTION JOINTS WHERE NOT SHOWN SHALL BE LOCATED TO
GEOTECHNICAL ENGINEER FOR THIS BEARING CAPACITY BEFORE
REGIONAL WIND SPEED: V = 46 m/s PLACING ANY MEMBRANE, REINFORCEMENT OR CONCRETE. WHERE THE APPROVAL OF THE ENGINEER.
R
NECESSARY, THE FOOTING DESIGN MAY BE ALTERED.
ANNUAL PROBABILITY OF EXCEEDANCE = 1:1000 6.11 THE FINISHED CONCRETE SHALL BE A DENSE HOMOGENEOUS MASS,
5.03 SITE CLASSIFICATION IS ASSUMED CLASS 'M' IN ACCORDANCE WITH COMPLETELY FILLING THE FORMWORK THOROUGHLY EMBEDDING THE
REGION: A2
AS2870. THIS IS TO BE CONFIRMED ON SITE AFTER EXCAVATION HAS REINFORCEMENT AND FREE OF STONE POCKETS. ALL CONCRETE
TERRAIN CATEGORY: 3 TAKEN PLACE. INCLUDING SLABS ON GROUND AND FOOTINGS SHALL BE COMPACTED
WITH MECHANICAL VIBRATORS.
5.04 THE BUILDER SHALL BE RESPONSIBLE FOR MAINTAINING ANY
2.04 THE CONCRETE ELEMENTS HAVE BEEN DESIGNED FOR THE 6.12 CURING OF ALL CONCRETE IS TO BE ACHIEVED BY KEEPING SURFACES
EXCAVATIONS IN A STABLE CONDITION WITHOUT ADVERSELY
FOLLOWING EXPOSURE CLASSIFICATIONS IN ACCORDANCE WITH AS CONTINUOUSLY WET FOR A PERIOD OF 3 DAYS, AND PREVENTION OF
AFFECTING SURROUNDING PROPERTIES INCLUDING SERVICES. THIS
3600. LOSS OF MOISTURE FOR A TOTAL OF 7 DAYS FOLLOWED BY A
INCLUDES OBTAINING ALL NECESSARY APPROVALS FOR SHORING AND
ANCHORING SYSTEMS. GRADUAL DRYING OUT. APPROVED SPRAYED ON CURING COMPOUNDS
ELEMENT CLASSIFICATION THAT COMPLY WITH AS 3799 MAY BE USED WHERE FLOOR FINISHES
5.05 FOOTINGS SHALL BE LOCATED CENTRALLY UNDER WALLS AND WILL NOT BE AFFECTED (REFER MANUFACTURER'S SPECIFICATION).
EXTERIOR CONCRETE B1 COLUMNS UNLESS NOTED OTHERWISE. POLYTHENE SHEETING OR WET HESSIAN MAY BE USED TO RETAIN
INTERNAL CONCRETE A1
CONCRETE MOISTURE WHERE PROTECTED FROM WIND AND TRAFFIC.
5.06 FOOTINGS NEAR BOUNDARIES MUST NOT BE LOCATED HIGHER OR
LOWER THAN FOOTINGS OF ADJACENT PROPERTIES UNLESS
APPROVED.

P/ (02) 8678 2629 AMENDMENTS DRAWN: PB DESIGNED: PB PROJECT: CLIENT:


F/ (02) 4744 2479 ALL DIMENSIONS IN 'mm'
E/ info@danmorconsulting.com.au NO. DESCRIPTION DATE UNLESS OTHERWISE STATED
APPROVED: DATE: 15/07/16
MR JOE SALIBA
A/ PO BOX 489 St Marys NSW 1790
DANNY MORCHED
PROPOSED DWELLING
1 ISSUED FOR CONSTRUCTION CERTIFICATE 15/07/16
B.E CIVIL JOB NO.
M.E STRUCTURAL 15 MELVILLE AVE TITLE: D16168
CPEng,MIEAust,NPER
COPYRIGHT
THIS DRAWING AND THE INFORMATION SHOWN HEREON MEMB. NO: 2320868 STRATHFIELD NSW 2135 GENERAL NOTES SHEET 1 DRAWING NO.
IS THE PROPERTY OF DANMOR CONSULTING ENGINEERS P/L AND MAY
NOT BE USED FOR ANY OTHER PURPOSE THAN FOR WHICH SUPPLIED. SCALE AT A3: 1:100 S01
6.0 CONCRETE (CONT.) 9.07 UNLESS NOTED OTHERWISE ALL BOLTS SHALL BE M20 CATEGORY 8.8/S.
NO CONNECTION SHALL HAVE LESS THAN 2 BOLTS. ALL BOLTS, NUTS
6.13 CONSTRUCTION SUPPORT PROPPING IS TO BE LEFT IN PLACE WHERE AND WASHERS SHALL BE HOT DIPPED GALVANISED.
NEEDED TO AVOID OVERSTRESSING THE STRUCTURE DUE TO UNLESS NOTED OTHERWISE, ALL HOLDING DOWN BOLTS SHALL BE M20
A MAXIMUM OF THREE SHEETS OF FABRIC SHALL BE LAPPED AT ANY POINT.
CONSTRUCTION LOADING. NO MASONRY OR PARTITION WALLS ARE TO CATEGORY 4.6/S. ALL BOLTS, NUTS AND WASHERS SHALL BE HOT
BE CONSTRUCTED ON SUSPENDED LEVELS UNTIL ALL PROPPING IS DIPPED GALVANISED.
REMOVED AND THE SLAB HAS ABSORBED ITS DEAD LOAD DEFLECTION. 8.0 STRUCTURAL MASONRY
9.08 FABRICATION SHALL COMPLY WITH AS 4100, SECTION 14.
6.14 THE ENGINEER SHALL BE GIVEN 24 HOURS NOTICE FOR 8.01 ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH
REINFORCEMENT INSPECTION AND CONCRETE SHALL NOT BE AS 3700 CURRENT ADDITION WITH AMENDMENTS AND OTHER RELEVANT 9.09 ERECTION SHALL COMPLY WITH AS 4100, SECTION 15.
DELIVERED UNTIL FINAL APPROVAL OBTAINED. CODES.
9.10 UNLESS NOTED OTHERWISE, ALL FILLET WELDS SHALL BE 6mm
6.15 CONDUITS, PIPES, ETC. SHALL ONLY BE LOCATED IN THE MIDDLE THIRD 8.02 MORTAR ADMIXTURES SHALL NOT BE USED WITHOUT THE WRITTEN CONTINUOUS CATEGORY GP USING E41XX ELECTRODES. ALL BUTT
OF THE SLAB DEPTH. PIPES OR CONDUITS SHALL NOT BE PLACED APPROVAL OF THE ENGINEER. WELDS SHALL BE COMPLETE PENETRATION BUTT WELDS CATEGORY
WITHIN THE COVER TO REINFORCEMENT. SP TO AS 1554.1.
8.03 NON LOAD BEARING WALLS SHALL BE SEPARATED FROM CONCRETE UNLESS NOTED OTHERWISE, ALL PURLIN CLEAT WELDS SHALL BE 6mm
6.16 SLABS AND BEAMS SHALL BE CONSTRUCTED TO BEAR ONLY ON THE ABOVE BY 25mm GAP. PROVIDE JOINT FILLER TO THE ARCHITECTS' CONTINUOUS CATEGORY GP USING E41XX ELECTRODES.
BEAMS, WALLS, COLUMNS, ETC. SHOWN ON THE DRAWINGS. ALL DETAILS.
OTHER BUILDING ELEMENTS SHALL BE KEPT 20mm MINIMUM CLEAR 9.11 PROVIDE SEAL PLATES TO THE ENDS OF ALL HOLLOW SECTIONS, WITH
FROM SOFFITS OF STRUCTURE. 8.04 NO CHASES OR RECESSES ARE PERMITTED IN LOAD BEARING 'BREATHER' HOLES IF MEMBERS TO BE HOT DIP GALVANISED.
MASONRY WITHOUT THE APPROVAL OF THE ENGINEER.
6.19 CONCRETE QUALITY SHOWN IN CONCRETE MIX DESIGN TABLE. 9.12 STRUCTURAL STEELWORK NOT ENCASED IN CONCRETE SHALL HAVE
CONCRETE MIX TABLE THE FOLLOWING SURFACE TREATMENT IN ACCORDANCE WITH THE
8.05 REINFORCED BRICKWORK SHALL COMPLY WITH THE FOLLOWING U.N.O.: SPECIFICATION.
STRENGTH (MPa)
EXPOSURE
U.N.O.
CLASSIFICATION (i) FILL ALL BED JOINTS AND PERPENDS WITH MORTAR EXCEPT
ELEMENT
F'c AT
SURFACE SECOND THIRD
(AS 3600)
COVER ELEMENT PRIME COAT
28 DAYS AT WEEP HOLES. PREPARATION COAT COAT

FOOTINGS A1 25 50 2 COATS R.O.Z.P


(ii) PROVIDE CLEAN-OUTS AT BASE OF REINFORCED CORES AND ABRASIVE
(MIN. DRY FILM REFER REFER
WALLS/COLUMNS A1 32 40
CAVITIES. REMOVE MORTAR PROTRUSIONS BEFORE CORE OR ALL U.N.O BLAST
INTERNAL THICKNESS TO ARCHITECT ARCHITECT
CAVITY FILLING. CLASS 2.5
WALLS/COLUMNS 75 MICRONS)
B1 32 40
EXTERNAL
(iii) COMPACT GROUT FILLING BY RODDING OR MECHANICAL ALL EXTERNAL HOT DIP REFER REFER
SLABS ON GROUND A1 25 40 VIBRATION. STEELWORK -
GALVANISED ARCHITECT ARCHITECT
INTERNAL (INCL. LINTELS)
A1 32 25 (iv) MAXIMUM HEIGHT OF POUR FOR CAVITY FILLED WALLS TO BE
SUSPENDED SLABS
EXTERNAL 1200mm. 9.13 THE BUILDER SHALL PROVIDE ALL CLEATS AND DRILL ALL HOLES
B1 32 40
SUSPENDED SLABS NECESSARY FOR FIXING STEEL TO STEEL AND TIMBER TO STEEL
8.06 WATERPROOF REAR FACE OF RETAINING WALLS AS SPECIFIED BY THE
PILES A1 25 75 WHETHER OR NOT DETAILED IN THE DRAWINGS.
ARCHITECT.

7.0 REINFORCEMENT 8.07 UNLESS NOTED OTHERWISE, PROVIDE VERTICAL CONTROL JOINTS AT
9.14 FREE ALL MEMBERS FROM TWISTS AND DISTORTIONS BEFORE AND
AFTER WELDING.
7.01 REINFORCEMENTS SYMBOLS: 12.0m MAXIMUM CENTRES, AND 6.0m MAXIMUM FROM CORNERS IN ALL
S DENOTES GRADE 250 S HOT ROLLED DEFORMED BARS TO MASONRY WALLS U.N.O. 9.15 ALL MEMBERS TO BE IN ONE LENGTH, UNLESS OTHERWISE APPROVED.
AS 4671
N DENOTES GRADE D 500 N BARS TO AS 4671 GRADE N 8.08
SL & RL DENOTES GRADE 250 HOT ROLLED PLAIN BARS TO AS 4671
BACKFILL TO RETAINING WALLS TO BE FREE DRAINING GRANULAR
MATERIAL U.N.O. PROVIDE SUBSOIL DRAIN OR WEEP HOLES.
10.0 STRUCTURAL TIMBER
SQUARE & RECTANGULAR MESH RESPECTIVELY 10.01 ALL TIMBER DESIGN, CONSTRUCTION AND MATERIAL TO BE AS 1720.1
R DENOTES GRADE 250 HOT ROLLED PLAIN BARS TO AS 4671 8.09 ALL CAVITY CONSTRUCTION TO HAVE GALVANISED WALL TIES AND AS 1720.2 U.N.O.
W DENOTES HARD-DRAWN PLAIN WIRE TO AS 4671 INSTALLED AS PER CLAUSE 3.4 AND 4.10, AS 3700.
DW DENOTES COLD ROLLED RIBBED WIRE TO A.S 4671 10.02 AS 1684 SHALL BE APPLIED TO DOMESTIC CONSTRUCTION IN

NUMBER OF BARS IN GROUP BAR GRADE AND TYPE


9.0 STRUCTURAL STEELWORK SHELTERED LOCATIONS.

10.03 SOFTWOOD TO BE MINIMUM GRADE F7 U.N.O. HARDWOOD TO BE


9.01 ALL WORKMANSHIP AND MATERIAL SHALL BE IN ACCORDANCE WITH AS
17N20 - 250 MINIMUM GRADE F14.
4100 EXCEPT WHERE VARIED BY THE CONTRACT DOCUMENTS.
NOMINAL BAR SIZE IN mm BAR SPACING IN mm 10.04 EXTERNAL TIMBER TO BE EITHER HARDWOOD DURABILITY CLASS I OR CLASS II AS PER
9.02 UNLESS NOTED OTHERWISE, ALL STEEL SHALL BE IN ACCORDANCE AS 1720.2 OR IMPREGNATED PINE GRADE F7, PRESSURE TREATED TO AS 1604 AND
WITH AS 3678 GRADE 250, OR AS 3679 GRADE 300, OR AS 1163 GRADE RE-DRIED PRIOR TO USE. SUPPLEMENTARY TREATMENT SHALL BE APPLIED TO ALL CUT
THE FIGURES FOLLOWING THE FABRIC SYMBOL IS THE REFERENCE
C350 AS APPROPRIATE. SURFACES. SUPPLY SUPPORTING DOCUMENTATION FOR PRESERVATIVE TREATMENT.
NUMBER FOR FABRIC TO AS 4671
9.03 TWO (2) COPIES OF WORKSHOP FABRICATION DRAWINGS SHALL BE
7.02 ALL REINFORCEMENT SHALL BE FIRMLY SUPPORTED ON MILD STEEL 10.05 TIMBER TRUSSES TO BE PRE-CAMBERED AN AMOUNT EQUAL TO DEAD
SUBMITTED TO THE ENGINEER FOR REVIEW AT LEAST 7 DAYS PRIOR TO
PLASTIC TIPPED CHAIRS, PLASTIC CHAIRS OR CONCRETE CHAIRS AT LOAD DEFLECTION. THREE (3) COPIES OF SHOP DRAWINGS ARE TO BE
COMMENCEMENT OF FABRICATION. FABRICATION IS NOT TO
NOT GREATER THAN 1 METRE CENTRES BOTH WAYS. BARS SHALL BE SUBMITTED TO THE ENGINEER FOR APPROVAL CLEARLY SHOWING THE
COMMENCE WITHOUT ENGINEER'S APPROVAL OF WORKSHOP
TIED AT ALTERNATE INTERSECTIONS. IN EXPOSURE CONDITIONS DESIGN LOADS ON THE ROOF AND CEILING AND TRUSS NODE POINT
DRAWINGS. ALL DIMENSIONS AND SETOUTS TO BE OBTAINED FROM
GREATER THAN B1 USE ONLY PLASTIC CHAIRS. LOADS AND PRECAMBER.
ARCHITECTURAL DRAWINGS WHERE NOT INDICATED ON STRUCTURAL
DRAWINGS.
7.03 REINFORCEMENT IS REPRESENTED DIAGRAMMATICALLY AND NOT 10.06 ALL BOLTS IN TIMBER CONSTRUCTION TO BE MINIMUM M12 U.N.O.
NECESSARILY IN TRUE PROJECTION. 9.04 BOLT CATEGORY: COMMENTS BOLT HOLES TO BE DRILLED EXACT SIZE. WASHERS UNDER HEADS
4.6/S COMMERCIAL BOLTS OF GRADE 4.6 TO AS 1111 AND NUTS TO BE AT LEAST 2.5 TIMES BOLT DIAMETER.
7.04 SLAB REINFORCEMENT SHALL EXTEND AT LEAST 75mm ONTO MASONRY SNUG TIGHTENED
SUPPORT WALLS AND 50 PERCENT OF BOTTOM REINFORCEMENT 8.8/S HIGH STRENGTH STRUCTURAL BOLTS OF GRADE 8.8 TO AS 1252 10.07 TIMBER DIMENSIONS ON THE FINISHED WIDTH AND THICKNESS TO BE:
SHALL BE COGGED TO ACHIEVE ANCHORAGE AT SIMPLY SUPPORTED SNUG TIGHTENED (i) SEASONED SOFTWOOD: 5, -0mm
ENDS. (ii) UNSEASONED SOFTWOOD: >F7:+3, -3mm OR F7:+2, -4mm
9.05 UNLESS NOTED OTHERWISE ALL CLEAT PLATES SHALL BE MINIMUM (iii) SEASONED HARDWOOD: +2, -0mm
7.05 SPLICES IN REINFORCEMENT SHALL BE MADE ONLY IN POSITIONS 10mm THICK. (iv) UNSEASONED HARDWOOD: +3, - 3mm
SHOWN OR OTHERWISE APPROVED IN WRITING BY THE ENGINEER. (SEE ALSO CLAUSE 1.6.2 IN AS 2082)
LAPS SHALL BE IN ACCORDANCE THE FOLLOWING: 9.06 UNLESS NOTED OTHERWISE ALL BOLTS SHALL BE M20 CATEGORY 8.8/S. NO CONNECTION
SHALL HAVE LESS THAN 2 BOLTS. ALL BOLTS, NUTS AND WASHERS SHALL BE HOT DIPPED
FABRIC SHALL BE LAPPED SUCH THAT THE TWO OUTERMOST WIRES OF 10.08 ALL TIMBER JOINTS AND NOTCHES ARE TO BE 100mm MINIMUM AWAY
GALVANISED. UNLESS NOTED OTHERWISE, ALL HOLDING DOWN BOLTS SHALL BE M20
ONE SHEET OVERLAP THE TWO OUTERMOST WIRES OF THE OTHER FROM LOOSE KNOTS, SEVERE SLOPING GRAIN, GUM VEINS OR OTHER
CATEGORY 4.6/S. ALL BOLTS, NUTS AND WASHERS SHALL BE HOT DIPPED GALVANISED.
SHEET BY 25mm MINIMUM. MINOR DEFECTS.

P/ (02) 8678 2629 AMENDMENTS DRAWN: PB DESIGNED: PB PROJECT: CLIENT:


F/ (02) 4744 2479 ALL DIMENSIONS IN 'mm'
E/ info@danmorconsulting.com.au NO. DESCRIPTION DATE UNLESS OTHERWISE STATED
APPROVED: DATE: 15/07/16
MR JOE SALIBA
A/ PO BOX 489 St Marys NSW 1790
DANNY MORCHED
PROPOSED DWELLING
1 ISSUED FOR CONSTRUCTION CERTIFICATE 15/07/16
B.E CIVIL JOB NO.
M.E STRUCTURAL 15 MELVILLE AVE TITLE: D16168
CPEng,MIEAust,NPER
COPYRIGHT
THIS DRAWING AND THE INFORMATION SHOWN HEREON MEMB. NO: 2320868 STRATHFIELD NSW 2135 GENERAL NOTES SHEET 2 DRAWING NO.
IS THE PROPERTY OF DANMOR CONSULTING ENGINEERS P/L AND MAY
NOT BE USED FOR ANY OTHER PURPOSE THAN FOR WHICH SUPPLIED. SCALE AT A3: 1:100 S02
BRICK WALL OVER ONLY
CONCRETE MIX TABLE
STRENGTH (MPa)
EXPOSURE
U.N.O.
BRICK WALL UNDER ONLY CLASSIFICATION
ELEMENT
(AS 3600) F'c AT
COVER
28 DAYS

BRICK WALL OVER & UNDER FOOTINGS A1 32 50

SLABS ON GROUND A1 32 40
INTERNAL
A1 32 20
SUSPENDED SLABS
EXTERNAL
B1 32 40
SUSPENDED SLABS
PILES A1 32 75

P1 P1 P1

SF4
P1 P1 P1 P1 P1 P1 P1 P1

SF1 SF1 SF1 SF1 SF1

P1

SF4
P1 P1

SF2

SF1
P1 P1

SF2
SF2
P1

SF2

SF4
P1

SF1
EXISTING SWIMMING
POOL SHOWN P1

HATCHED P1 P1 P1

SF2
P1 P1 P1 P1 P1 P1 SF2 SF1

SF1
P1

SF1 SF2 SF2 SF2


P1 P1 P1 P1
EXISTING SLAB

SF2
SF2

SF2
P1

SF2
SF1
P1 SF1 SF1

SF1
P1 P1 P1 P1 P1 P1 P1 P1

SF2
SF4 SF2 SF2 SF2
NEW SLAB TO BE AT P1 P1
THE SAME LEVEL OF P1 P1

SF2
SF4

THE EXISTING SLAB P1 P1


SF2 SF2
P1

SF2
SF2

SF2
SF1

P1

SF1
SF2
P1
P1 SF1

SF1
SF1

SF1
P1 P1 P1 P1 P1 P1 P1 P1 P1
P1

SF4 SF1 SF1 P1


SF1

STRIP FOOTING PLAN


SCALE 1:100
P1
P1: 450DIA MASS CONCRETE PIER TO 300KPa IF SOFT CLAY IS ENCOUNTERED
BEARING OR TO HARD STRATA (SCREW PILES PLEASE CONTACT THE ENGINEER
MAY ALSO BE USED) FOR REVISED FOOTING DEPTHS.

ARTICULATION JOINTS ARE TO BE


PLACED AT 6m MAXIMUM CENTERS
AT WEAK POINT OF THE WALL AND
AT NEW/OLD WALL INTERSECTIONS

P/ (02) 8678 2629 AMENDMENTS DRAWN: PB DESIGNED: PB PROJECT: CLIENT:


F/ (02) 4744 2479 ALL DIMENSIONS IN 'mm'
E/ info@danmorconsulting.com.au NO. DESCRIPTION DATE UNLESS OTHERWISE STATED
APPROVED: DATE: 15/07/16
MR JOE SALIBA
A/ PO BOX 489 St Marys NSW 1790
DANNY MORCHED
PROPOSED DWELLING
1 ISSUED FOR CONSTRUCTION CERTIFICATE 15/07/16
B.E CIVIL JOB NO.
M.E STRUCTURAL 15 MELVILLE AVE TITLE: D16168
CPEng,MIEAust,NPER
COPYRIGHT
THIS DRAWING AND THE INFORMATION SHOWN HEREON MEMB. NO: 2320868 STRATHFIELD NSW 2135 FOOTING PLAN DRAWING NO.
IS THE PROPERTY OF DANMOR CONSULTING ENGINEERS P/L AND MAY
NOT BE USED FOR ANY OTHER PURPOSE THAN FOR WHICH SUPPLIED. SCALE AT A3: 1:100 S03
NEW SLAB TO BE
PLACED OVER
EXISTING POOL
COVING

120 W 120
EXISTING SWIMMING
POOL SHOWN 120
TR TR
HATCHED

TBC
TBC
TR 120
TR TR
EXISTING SLAB
TBC
TR

TBC

120
120
120
W
TR
TR

GROUND FLOOR SLAB ON GRADE PLAN


SCALE 1:100

SLAB THICKNESS TO BE 120mm


ONE LAYER OF MESH SL82 TOP
MIN COVER 30mm TOP, f'C = 32 MPa
SEE TYPICAL SECTIONS FOR DETAILS

120 DENOTES SLAB THICKNESS

DENOTES 20mm WET


W
AREA SET DOWN

TR DENOTES 2N16 TRIMMER BARS


EXTENDING 600mm PAST
CORNERS (1500 MIN. LENGTH)

P/ (02) 8678 2629 AMENDMENTS DRAWN: PB DESIGNED: PB PROJECT: CLIENT:


F/ (02) 4744 2479 ALL DIMENSIONS IN 'mm'
E/ info@danmorconsulting.com.au NO. DESCRIPTION DATE UNLESS OTHERWISE STATED
APPROVED: DATE: 15/07/16
MR JOE SALIBA
A/ PO BOX 489 St Marys NSW 1790
DANNY MORCHED
PROPOSED DWELLING
1 ISSUED FOR CONSTRUCTION CERTIFICATE 15/07/16
B.E CIVIL JOB NO.
M.E STRUCTURAL 15 MELVILLE AVE TITLE: D16168
CPEng,MIEAust,NPER
COPYRIGHT
THIS DRAWING AND THE INFORMATION SHOWN HEREON MEMB. NO: 2320868 STRATHFIELD NSW 2135 SLAB ON GRADE PLAN DRAWING NO.
IS THE PROPERTY OF DANMOR CONSULTING ENGINEERS P/L AND MAY
NOT BE USED FOR ANY OTHER PURPOSE THAN FOR WHICH SUPPLIED. SCALE AT A3: 1:100 S04
250 SL92 MESH TOP
MIN. COVER 30 mm.
SL92 MESH TOP
FLASHING & MIN. COVER 30 mm.

120
WEEPHOLES
SL92 MESH TOP

120
50mm MORTAR OR MIN. COVER 30 mm. COMPACT FILL
CONCRETE COMPACT FILL WATER PROOFING MEMBRANE

120
ON 50mm SAND BED
WATER PROOFING MEMBRANE
ON 50mm SAND BED
750 MAX.

COMPACT FILL 110mm BRICKWORK 110mm BRICKWORK


270
100 MIN.

NGL

600
WATER PROOFING MEMBRANE
ON 50mm SAND BED

600
600

300
3-L12 TRENCH MESH
450 TOP & BOT. WITH R10
4-L12 TRENCH MESH P1
TIES @ 900 C/C 50mm
P1 TOP & BOT. WITH R10
COVER MIN.
450 TIES @ 900 C/C 50mm
4-L12 TRENCH MESH COVER MIN.
P1 TOP & BOT. WITH R10 TYPICAL INTERNAL SF3
TIES @ 900 C/C 50mm SCALE 1:20
COVER MIN. TYPICAL INTERNAL SF2
SCALE 1:20 110
SL92 MESH TOP
TYPICAL EXTERNAL SF1 MIN. COVER 30 mm.
SCALE 1:20 270

1N16

120
SL92 MESH TOP SL82 MESH TOP
N12-400 Z-BARS MIN. COVER 30 mm.

800 MAX
MIN. COVER 30 mm. 85/50
500 LEGS
COMPACT FILL
120

COMPRESSIBLE FILLER

120
WATER PROOFING MEMBRANE
ON 50mm SAND BED
600 MAX.

120
230 COMPACT FILL
COMPACT FILL
100 MIN.

NGL COMPACT FILL WATER PROOFING MEMBRANE COMPACT FILL


ON 50mm SAND BED
WATER PROOFING MEMBRANE
ON 50mm SAND BED
600

600
450 450
4-L12 TRENCH MESH 4-L12 TRENCH MESH
TOP & BOT. WITH R10 P1
P1 P1 TOP & BOT. WITH R10
TIES @ 900 C/C 50mm TIES @ 900 C/C 50mm
COVER MIN. COVER MIN.
TYPICAL EXTERNAL STEP DOWN
TYPICAL EXTERNAL SF4 SCALE 1:20 TYPICAL STEPDOWN SF5
SCALE 1:20 SCALE 1:20

P/ (02) 8678 2629 AMENDMENTS DRAWN: PB DESIGNED: PB PROJECT: CLIENT:


F/ (02) 4744 2479 ALL DIMENSIONS IN 'mm'
E/ info@danmorconsulting.com.au NO. DESCRIPTION DATE UNLESS OTHERWISE STATED
APPROVED: DATE: 15/07/16
MR JOE SALIBA
A/ PO BOX 489 St Marys NSW 1790
DANNY MORCHED
PROPOSED DWELLING
1 ISSUED FOR CONSTRUCTION CERTIFICATE 15/07/16
B.E CIVIL JOB NO.
M.E STRUCTURAL 15 MELVILLE AVE TITLE: D16168
CPEng,MIEAust,NPER
COPYRIGHT
THIS DRAWING AND THE INFORMATION SHOWN HEREON MEMB. NO: 2320868 STRATHFIELD NSW 2135 FOOTING DETAILS SHEET 1 DRAWING NO.
IS THE PROPERTY OF DANMOR CONSULTING ENGINEERS P/L AND MAY
NOT BE USED FOR ANY OTHER PURPOSE THAN FOR WHICH SUPPLIED. SCALE AT A3: 1:100 S05
10 JOINTEX OR APPROVED
EQUIVALENT SEALANT
GENERALS: STOP REINF. 30mm SAWCUT TO BE T/4 DEEP SL82 MESH TOP
EITHER SIDE OF SAWCUT SLAB TO BE SAWN NO LATER 40mm COVER 1N12 PERIMETER BAR
G1 Read these drawings in conjunction with all THAN 24 HRS AFTER POUR.
architectural and service drawings and specification.
G2 All dimensions shall be checked on site before
fabrication or shop work drawings are commenced.
G3 Do not obtain dimensions by scaling the
structural drawings.
G4 All dimensions are in millimetres unless noted COMPACT FILL COMPACT FILL
otherwise on the drawings.
WATER PROOFING
FOUNDATIONS:
F1 Footings have been designed for an allowable
SAWCUT JOINT MEMBRANE ON 50mm ISOLATION JOINT
bearing intensity as follows: DENOTED 'SCJ' ON PLAN SAND BED DENOTED 'IJ' ON PLAN

ELEMENT STRATA BEARING


PRESSURE
KPa

Strip footings CLAY CLASS M 150


Slab on ground COMPACTED FILL 100 EXTEND FOOTING GREATER THAN 200
REINFORCEMENT 250 LESS THAN 2xD
F2 The builder shall obtain the Engineer's approval INTO NEXT LEVEL
of the foundation material before placing concrete. OF FOOTING 1.5 x D
CONCRETE:
C1 Carry out all concrete work in accordance with
AS 1480 (current edition) and the specification. MESH 4 MESH 2
MESH 2 CUT CORNER CUT CORNER
C2 Concrete Quality F'c at 28 days:
MESH 1
ELEMENT F'c MAX SIZE NOM. CEMENT
MPa AGG. SLUMP TYPE MESH 1
MESH 3 MESH 3

D
CUT CORNER
FOOTINGS 25 20 80 A
SQUARE & 25 LAP SQUARE & 25 LAP
SLAB ON 1N12 Z-BAR E.F.
GROUND 25 20 80 A
ALL LAPS TO COMPLY WITH CONSTRUCTION NOTES FOR EACH LONGITUDINAL
BAR IN STRIP FOOTING 400 LEGS
SUSPENDED
SLABS 32 20 80 A
COLUMNS &
BEAMS MESH LAPPING DETAIL
NTS STEP IN STRIP FOOTING DETAIL
C3 Provide the following clear cover to all SCALE 1:20
reinforcement unless noted otherwise on the
drawings (clear cover to ties)
500
ELEMENT MIN. COVER (mm)

STRIP FOOTINGS 50
LESS THAN 200 TO
SLABS (INTERNAL) 20
SUIT COURSING

500
SLABS (EXTERNAL) 40
SLABS (ON GROUND) 40
1N12 CORNER BAR
TOP & BOTTOM
G5 At the connection line of internal and external slabs AS REQUIRED
on ground DJ must be used.
G6 SCJ for external slabs on ground Max. 6.0m apart.

1
D

10 MAX.

SLOPPED FOOTING DETAIL STRIP FOOTING JUNCTION DETAILS


SCALE 1:20 SCALE 1:20
P/ (02) 8678 2629 AMENDMENTS DRAWN: PB DESIGNED: PB PROJECT: CLIENT:
F/ (02) 4744 2479 ALL DIMENSIONS IN 'mm'
E/ info@danmorconsulting.com.au NO. DESCRIPTION DATE UNLESS OTHERWISE STATED
APPROVED: DATE: 15/07/16
MR JOE SALIBA
A/ PO BOX 489 St Marys NSW 1790
DANNY MORCHED
PROPOSED DWELLING
1 ISSUED FOR CONSTRUCTION CERTIFICATE 15/07/16
B.E CIVIL JOB NO.
M.E STRUCTURAL 15 MELVILLE AVE TITLE: D16168
CPEng,MIEAust,NPER
COPYRIGHT
THIS DRAWING AND THE INFORMATION SHOWN HEREON MEMB. NO: 2320868 STRATHFIELD NSW 2135 FOOTING DETAILS SHEET 2 DRAWING NO.
IS THE PROPERTY OF DANMOR CONSULTING ENGINEERS P/L AND MAY
NOT BE USED FOR ANY OTHER PURPOSE THAN FOR WHICH SUPPLIED. SCALE AT A3: 1:100 S06
CONCRETE MIX TABLE
STRENGTH (MPa)
EXPOSURE BRICK WALL OVER ONLY
U.N.O.
CLASSIFICATION
ELEMENT
(AS 3600) F'c AT
COVER
28 DAYS BRICK WALL UNDER ONLY
FOOTINGS A1 25 50

SLABS ON GROUND A1 25 40 BRICK WALL OVER & UNDER


INTERNAL
A1 32 20
SUSPENDED SLABS
EXTERNAL
B1 32 40
SUSPENDED SLABS

PILES A1 25 75

200
200

200
200
1
S11
W

FIRST FLOOR SLAB GA PLAN


SCALE 1:100

SLAB THICKNESS TO BE 200mm UNO


f'C = 32 MPa
SEE TYPICAL SECTIONS FOR DETAILS

200 DENOTES SLAB THICKNESS

DENOTES 20mm WET


W
AREA SET DOWN

P/ (02) 8678 2629 AMENDMENTS DRAWN: PB DESIGNED: PB PROJECT: CLIENT:


F/ (02) 4744 2479 ALL DIMENSIONS IN 'mm'
E/ info@danmorconsulting.com.au NO. DESCRIPTION DATE UNLESS OTHERWISE STATED
APPROVED: DATE: 15/07/16
MR JOE SALIBA
A/ PO BOX 489 St Marys NSW 1790
DANNY MORCHED
PROPOSED DWELLING
1 ISSUED FOR CONSTRUCTION CERTIFICATE 15/07/16
B.E CIVIL JOB NO.
M.E STRUCTURAL 15 MELVILLE AVE TITLE: D16168
CPEng,MIEAust,NPER
COPYRIGHT
THIS DRAWING AND THE INFORMATION SHOWN HEREON MEMB. NO: 2320868 STRATHFIELD NSW 2135 FIRST FLOOR SLAB GA PLAN DRAWING NO.
IS THE PROPERTY OF DANMOR CONSULTING ENGINEERS P/L AND MAY
NOT BE USED FOR ANY OTHER PURPOSE THAN FOR WHICH SUPPLIED. SCALE AT A3: 1:100 S07
REINFORCEMENT NOTES TRIMMER DETAIL (ALL PENETRATIONS AND BALCONY EDGES UNO) BARS AT PENETRATIONS

BAR LAYING SEQUENCE (U.N.O)

N12-200
N16-200
N12-200

N16-200

N12-200 N12-200

TYPICAL COG DETAILS


N12-200
N12-200 N12-200 TO BE PLACED AT ALL ENDS OF REINF.

N12-200
N16-200

N12-200
W BOT. REINF.

TOP REINF.

FIRST FLOOR SLAB BOTTOM REINFORCEMENT PLAN BRICK WALL OVER ONLY

SCALE 1:100
BRICK WALL UNDER ONLY

BRICK WALL OVER & UNDER

P/ (02) 8678 2629 AMENDMENTS DRAWN: PB DESIGNED: PB PROJECT: CLIENT:


F/ (02) 4744 2479 ALL DIMENSIONS IN 'mm'
E/ info@danmorconsulting.com.au NO. DESCRIPTION DATE UNLESS OTHERWISE STATED
APPROVED: DATE: 15/07/16
MR JOE SALIBA
A/ PO BOX 489 St Marys NSW 1790
DANNY MORCHED
PROPOSED DWELLING
1 ISSUED FOR CONSTRUCTION CERTIFICATE 15/07/16
B.E CIVIL JOB NO.
M.E STRUCTURAL 15 MELVILLE AVE TITLE: D16168
CPEng,MIEAust,NPER
COPYRIGHT
THIS DRAWING AND THE INFORMATION SHOWN HEREON MEMB. NO: 2320868 STRATHFIELD NSW 2135 FIRST FLOOR SLAB BOT. REINFORCEMENT DRAWING NO.
IS THE PROPERTY OF DANMOR CONSULTING ENGINEERS P/L AND MAY
NOT BE USED FOR ANY OTHER PURPOSE THAN FOR WHICH SUPPLIED. SCALE AT A3: 1:100 S08
REINFORCEMENT NOTES TRIMMER DETAIL (ALL PENETRATIONS AND BALCONY EDGES UNO) BARS AT PENETRATIONS

BAR LAYING SEQUENCE (U.N.O)

N12-200

N16-400 EXTRA L=3m


N12-200

N12-200
3N16-200 L=3m
EXTRA
2N16-200 L=3m

N12-200
N12-200 N12-200 N12-200 TYPICAL COG DETAILS
EXTRA

N16-400 EXTRA L=3m TO BE PLACED AT ALL ENDS OF REINF.


2N16-200 L=3m
N16-400 EXTRA L=3m
N12-200 N12-200 EXTRA
BOT. REINF.
N12-200

N12-200
W

TOP REINF.

2N16-200 L=3m
EXTRA

BRICK WALL OVER ONLY

BRICK WALL UNDER ONLY

FIRST FLOOR SLAB TOP REINFORCEMENT PLAN BRICK WALL OVER & UNDER

SCALE 1:100

P/ (02) 8678 2629 AMENDMENTS DRAWN: PB DESIGNED: PB PROJECT: CLIENT:


F/ (02) 4744 2479 ALL DIMENSIONS IN 'mm'
E/ info@danmorconsulting.com.au NO. DESCRIPTION DATE UNLESS OTHERWISE STATED
APPROVED: DATE: 15/07/16
MR JOE SALIBA
A/ PO BOX 489 St Marys NSW 1790
DANNY MORCHED
PROPOSED DWELLING
1 ISSUED FOR CONSTRUCTION CERTIFICATE 15/07/16
B.E CIVIL JOB NO.
M.E STRUCTURAL 15 MELVILLE AVE TITLE: D16168
CPEng,MIEAust,NPER
COPYRIGHT
THIS DRAWING AND THE INFORMATION SHOWN HEREON MEMB. NO: 2320868 STRATHFIELD NSW 2135 FIRST FLOOR SLAB TOP REINFORCEMENT DRAWING NO.
IS THE PROPERTY OF DANMOR CONSULTING ENGINEERS P/L AND MAY
NOT BE USED FOR ANY OTHER PURPOSE THAN FOR WHICH SUPPLIED. SCALE AT A3: 1:100 S09
LANDING
N12-200

600 LAP

200
N12-200

N12-200

N12-200 STARTER
BARS 800 LAP
SCABBLE N12-200
SURFACE 17
5

GROUND FLOOR

FIRST FLOOR SLAB

SF2 REFER TO PLAN FOR


N12-200 E/W REINFORCEMENT
200

60
0
P1

N12-200

CONCRETE STAIR - GROUND FLOOR TO LANDING


SCALE 1:20
60
0
N12-200
N12-200
LANDING

N12-200 E/W

5
17
CONCRETE STAIR - LANDING TO FIRST FLOOR
SCALE 1:20

P/ (02) 8678 2629 AMENDMENTS DRAWN: PB DESIGNED: PB PROJECT: CLIENT:


F/ (02) 4744 2479 ALL DIMENSIONS IN 'mm'
E/ info@danmorconsulting.com.au NO. DESCRIPTION DATE UNLESS OTHERWISE STATED
APPROVED: DATE: 15/07/16
MR JOE SALIBA
A/ PO BOX 489 St Marys NSW 1790
DANNY MORCHED
PROPOSED DWELLING
1 ISSUED FOR CONSTRUCTION CERTIFICATE 15/07/16
B.E CIVIL JOB NO.
M.E STRUCTURAL 15 MELVILLE AVE TITLE: D16168
CPEng,MIEAust,NPER
COPYRIGHT
THIS DRAWING AND THE INFORMATION SHOWN HEREON MEMB. NO: 2320868 STRATHFIELD NSW 2135 STAIR DETAILS DRAWING NO.
IS THE PROPERTY OF DANMOR CONSULTING ENGINEERS P/L AND MAY
NOT BE USED FOR ANY OTHER PURPOSE THAN FOR WHICH SUPPLIED. SCALE AT A3: 1:100 S10
270
REFER TO PLAN FOR
REINFORCEMENT
REFER TO PLAN FOR
REINFORCEMENT

20
2N16 TOP & BOT. AT
SLAB PERIMETER

20

20
SLIP
JOINT

20
SLIP
JOINT
FOR EVERY TWO BARS STOPPED BY
PENETRATION ADD ONE BAR EACH SIDE OF
SAME SIZE AND GRADE. WHERE NO TOP AND
BOTTOM BARS ARE SHOWN, ADD 2N16 TOP AND
110 BOTTOM EACH SIDE OF PENETRATION.
TYPICAL
TYPICAL SLAB EXTERNAL SUPPORT
SCALE 1:20

TYPICAL INTERNAL WALL SUPPORT

600
SCALE 1:20
STANDARD COG
TYPICAL

PENETRATION
270 SLAB EDGE

MAXIMUM
1000
REFER TO PLAN FOR
REINFORCEMENT
2N16 TOP & BOT. AT

20
SLAB PERIMETER 85 STEP
40

40

20
20

SLIP TENSION LAP TENSION LAP


JOINT 600 1000
300
MAXIMUM

STANDARD SUSPENDED SLAB PENETRATION DETAILS


270 SECTION 1 NOTES:
1:20 S07 THESE DETAILS APPLY UNLESS SPECIFICALLY NOTED OTHERWISE.
REFER ARCHITECTURAL AND HYDRAULIC DRAWINGS FOR LOCATION AND SIZE OF PENETRATIONS.
LOCATION OF PENETRATIONS SHALL BE APPROVED BY THE ENGINEER.
TYPICAL STEP AT PREIMETER WALLS FOR PENETRATIONS LESS THAN 300 x 300mm, MAIN BARS TO BE DISPLACED EACH SIDE OF THE
PENETRATION. ADDITIONAL TRIMMING REINFORCEMENT NOT REQUIRED.
SCALE 1:20

P/ (02) 8678 2629 AMENDMENTS DRAWN: PB DESIGNED: PB PROJECT: CLIENT:


F/ (02) 4744 2479 ALL DIMENSIONS IN 'mm'
E/ info@danmorconsulting.com.au NO. DESCRIPTION DATE UNLESS OTHERWISE STATED
APPROVED: DATE: 15/07/16
MR JOE SALIBA
A/ PO BOX 489 St Marys NSW 1790
DANNY MORCHED
PROPOSED DWELLING
1 ISSUED FOR CONSTRUCTION CERTIFICATE 15/07/16
B.E CIVIL JOB NO.
M.E STRUCTURAL 15 MELVILLE AVE TITLE: D16168
CPEng,MIEAust,NPER
COPYRIGHT
THIS DRAWING AND THE INFORMATION SHOWN HEREON MEMB. NO: 2320868 STRATHFIELD NSW 2135 SLAB REINFORCEMENT DETAILS SHEET 1 DRAWING NO.
IS THE PROPERTY OF DANMOR CONSULTING ENGINEERS P/L AND MAY
NOT BE USED FOR ANY OTHER PURPOSE THAN FOR WHICH SUPPLIED. SCALE AT A3: 1:100 S11
S = GREATER THAN 0.65T S = UP TO 0.65T

top

bot

top

bot
Top Reo Top Reo
Top Reo Top Reo

Bot Reo Bot Reo


Bot Reo Bot Reo

top

bot
top

bot
TENSION LAP

20
TENSION LAP
3N20 TOP & BOT.
375 1.5T

PROVIDE N16-250 TENSION LAP TENSION LAP WET AREA SETDOWN (option 1)
T

EACH FACE LAP 500


AS REQUIRED NSOP
S

TENSION LAP

S
T

STANDARD COG
BARS CRANKED AT
TYPICAL
SLOPE OF 1:6 MAXIMUM

20
'Z' BARS TO MATCH
SLAB REINFORCEMENT TENSION LAP TENSION LAP
NSOP
TENSION LAP
TENSION LAP
WET AREA SETDOWN (option 2)

SUSPENDED SLAB STEP DETAILS

P/ (02) 8678 2629 AMENDMENTS DRAWN: PB DESIGNED: PB PROJECT: CLIENT:


F/ (02) 4744 2479 ALL DIMENSIONS IN 'mm'
E/ info@danmorconsulting.com.au NO. DESCRIPTION DATE UNLESS OTHERWISE STATED
APPROVED: DATE: 15/07/16
MR JOE SALIBA
A/ PO BOX 489 St Marys NSW 1790
DANNY MORCHED
PROPOSED DWELLING
1 ISSUED FOR CONSTRUCTION CERTIFICATE 15/07/16
B.E CIVIL JOB NO.
M.E STRUCTURAL 15 MELVILLE AVE TITLE: D16168
CPEng,MIEAust,NPER
COPYRIGHT
THIS DRAWING AND THE INFORMATION SHOWN HEREON MEMB. NO: 2320868 STRATHFIELD NSW 2135 SLAB REINFORCEMENT DETAILS SHEET 2 DRAWING NO.
IS THE PROPERTY OF DANMOR CONSULTING ENGINEERS P/L AND MAY
NOT BE USED FOR ANY OTHER PURPOSE THAN FOR WHICH SUPPLIED. SCALE AT A3: 1:100 S12
MEMBER SCHEDULE
MARK SIZE REMARKS

RJ1 200x45 hySPAN LVL AT 600 CTS


RJ2 200x45 hySPAN LVL AT 400 CTS
B1 230BT37 -
B2 240x9.5 (V) 250x8 (B) CAVI-T-BAR -
B3 180x8 (V) 250x8 (B) CAVI-T-BAR -
B4 300x45 hySPAN LVL -
B5 150x100x6 ANGLE BAR -
B8
B6 100x100x6 ANGLE BAR -

B10
B7 240x45 hySPAN LVL - B6

B8 200x10 TRADITIONAL T-BAR - B6

B9 400x63 hySPAN LVL OR 2/300x63 hySPAN LVL -


B10 200x7 MULTI-RIB T-BAR -
C1 50x50x5 SHS -

B3
B1

B2
DS DOUBLE STUD -

B3

B10

B3

B2
B1

NOTES:
1. ALL EXTERNAL STEELWORK TO BE HOT DIPPED GALVANISED B10
2. WALL STUDS TO BE 100x50 F7 @ 450 C/C
3. ALL TIMBER TO BE SEASONED
4. ALL BEAMS TO HAVE MINIMUM 150mm BEARING
5. hySPAN LVL TO BE INSTALLED AS PER MANUFACTURERS INSTRUCTIONS
6. EXTERNAL hySPAN LVL TO BE H2-S TREATED FOR TERMITE PROTECTION
7. WALL BRACING AND TIMBER FRAMING TO AS1684 FIRST FLOOR FRAMING PLAN
SCALE 1:100
8. TIMBER BEAM TO TIMBER BEAM CONNECTIONS TO BE WITH PRYDA BEAM HANGERS UNO
9. STEELWORK CUT ON SITE TO BE PAINTED WITH COLD-GAL OR EQUIVALENT NOTES:
10. ALL WELDS 6mm SP CFW UNO DOUBLE STUD TO BE PLACED UNDER BEAM ENDS U.N.O
11. DOUBLE JOIST TO BE PLACED UNDER WALLS PARALLEL TO JOISTS
12. ALL EXTERNAL TIMBER TO BE TREATED SEE TYPICAL SECTIONS FOR DETAILS
13. BEAMS DOUBLED UP TO BE BOLTED WITH M10-600 STAGGERED BOLTS
14. ALL BEAMS/JOISTS SPANNING MORE THAN 3m TO HAVE CENTRAL AND END BLOCKING

P/ (02) 8678 2629 AMENDMENTS DRAWN: PB DESIGNED: PB PROJECT: CLIENT:


F/ (02) 4744 2479 ALL DIMENSIONS IN 'mm'
E/ info@danmorconsulting.com.au NO. DESCRIPTION DATE UNLESS OTHERWISE STATED
APPROVED: DATE: 15/07/16
MR JOE SALIBA
A/ PO BOX 489 St Marys NSW 1790
DANNY MORCHED
PROPOSED DWELLING
1 ISSUED FOR CONSTRUCTION CERTIFICATE 15/07/16
B.E CIVIL JOB NO.
M.E STRUCTURAL 15 MELVILLE AVE TITLE: D16168
CPEng,MIEAust,NPER
COPYRIGHT
THIS DRAWING AND THE INFORMATION SHOWN HEREON MEMB. NO: 2320868 STRATHFIELD NSW 2135 FIRST FLOOR FRAMING PLAN DRAWING NO.
IS THE PROPERTY OF DANMOR CONSULTING ENGINEERS P/L AND MAY
NOT BE USED FOR ANY OTHER PURPOSE THAN FOR WHICH SUPPLIED. SCALE AT A3: 1:100 S13
MEMBER SCHEDULE
MARK SIZE REMARKS

RJ1 200x45 hySPAN LVL AT 600 CTS


RJ2 200x45 hySPAN LVL AT 400 CTS
B1 230BT37 -
B2 240x9.5 (V) 250x8 (B) CAVI-T-BAR -
B3 180x8 (V) 250x8 (B) CAVI-T-BAR -
B4 300x63 hySPAN LVL - 4
MITRE AT 45 DEGREES
S15
B5 150x100x6 ANGLE BAR - AND WELD CAVI-T-BARS
B6 100x100x6 ANGLE BAR - TOGETHER
B5 B5
B7 240x45 hySPAN LVL - B3
B8 200x10 TRADITIONAL T-BAR - B5 B5
B9 400x63 hySPAN LVL OR 2/300x63 hySPAN LVL -
B10 200x7 MULTI-RIB T-BAR -

B7
B5

B5
C1 50x50x5 SHS -

RJ1

B3
DS DOUBLE STUD -

B3

B6

B6
RJ1 RJ1

RJ1

B9
B5

B5

B4
RJ1
B5 B5

B3
B5 B5
B3 B3
NOTES: RJ1 RJ2

1. ALL EXTERNAL STEELWORK TO BE HOT DIPPED GALVANISED


2. WALL STUDS TO BE 100x50 F7 @ 450 C/C
3. ALL TIMBER TO BE SEASONED
4. ALL BEAMS TO HAVE MINIMUM 150mm BEARING MITRE AT 45 DEGREES
5. hySPAN LVL TO BE INSTALLED AS PER MANUFACTURERS INSTRUCTIONS
AND WELD CAVI-T-BARS
6. EXTERNAL hySPAN LVL TO BE H2-S TREATED FOR TERMITE PROTECTION TOGETHER
7. WALL BRACING AND TIMBER FRAMING TO AS1684 ROOF FRAMING PLAN
SCALE 1:100
8. TIMBER BEAM TO TIMBER BEAM CONNECTIONS TO BE WITH PRYDA BEAM HANGERS UNO
9. STEELWORK CUT ON SITE TO BE PAINTED WITH COLD-GAL OR EQUIVALENT NOTES:
10. ALL WELDS 6mm SP CFW UNO DOUBLE STUD TO BE PLACED UNDER BEAM ENDS U.N.O
11. DOUBLE JOIST TO BE PLACED UNDER WALLS PARALLEL TO JOISTS
12. ALL EXTERNAL TIMBER TO BE TREATED SEE TYPICAL SECTIONS FOR DETAILS
13. BEAMS DOUBLED UP TO BE BOLTED WITH M10-600 STAGGERED BOLTS
14. ALL BEAMS/JOISTS SPANNING MORE THAN 3m TO HAVE CENTRAL AND END BLOCKING

P/ (02) 8678 2629 AMENDMENTS DRAWN: PB DESIGNED: PB PROJECT: CLIENT:


F/ (02) 4744 2479 ALL DIMENSIONS IN 'mm'
E/ info@danmorconsulting.com.au NO. DESCRIPTION DATE UNLESS OTHERWISE STATED
APPROVED: DATE: 15/07/16
MR JOE SALIBA
A/ PO BOX 489 St Marys NSW 1790
DANNY MORCHED
PROPOSED DWELLING
1 ISSUED FOR CONSTRUCTION CERTIFICATE 15/07/16
B.E CIVIL JOB NO.
M.E STRUCTURAL 15 MELVILLE AVE TITLE: D16168
CPEng,MIEAust,NPER
COPYRIGHT
THIS DRAWING AND THE INFORMATION SHOWN HEREON MEMB. NO: 2320868 STRATHFIELD NSW 2135 ROOF FRAMING PLAN DRAWING NO.
IS THE PROPERTY OF DANMOR CONSULTING ENGINEERS P/L AND MAY
NOT BE USED FOR ANY OTHER PURPOSE THAN FOR WHICH SUPPLIED. SCALE AT A3: 1:100 S14
TIMBER BEAM 75x75x6 EA EACH SIDE
DEPTH TO SUIT BEAM FLASHING
JOIST HANGER
BOX GUTTER

50mm BATTENS

FLOOR JOIST FLOOR JOIST TIMBER BEAM

3M16 4.6/S
RJ1/RJ2
3M16 4.6/S
TIMBER BEAM TO JOIST CONNECTION
SCALE 1:10
40mm REBATE IN
TIMBER BEAM TO ROOF JOIST
TIMBER BEAM CONNECTION JOIST HANGER M16 RAMSET
M10@900C/C ANKASCREW AT
SCALE 1:10 BEAM TO MATCH RJ1
STAGGERED 900 C/C
STAGGERED

SECTION 4
3
- 1:10 S14

DOUBLE BEAM CONNECTION


SCALE 1:10

30 x 0.8mm METAL STRAP


OR TIMBER STRUT

SECTION A
1:10 -

BLOCK

LATERAL RESTRAINT OF ROOF STRUTTING BEAMS


SCALE 1:10
SECTION 03
IMPORTANT NOTE: LATERAL RESTRAINTS TO BE
APPLIED AT BOTH ENDS OF STRUTTING BEAM, AT
1500C/C AND AT ALL STRUT LOCATIONS.
DETAIL 2 1:10 -
1:10 S14

P/ (02) 8678 2629 AMENDMENTS DRAWN: PB DESIGNED: PB PROJECT: CLIENT:


F/ (02) 4744 2479 ALL DIMENSIONS IN 'mm'
E/ info@danmorconsulting.com.au NO. DESCRIPTION DATE UNLESS OTHERWISE STATED
APPROVED: DATE: 15/07/16
MR JOE SALIBA
A/ PO BOX 489 St Marys NSW 1790
DANNY MORCHED
PROPOSED DWELLING
1 ISSUED FOR CONSTRUCTION CERTIFICATE 15/07/16
B.E CIVIL JOB NO.
M.E STRUCTURAL 15 MELVILLE AVE TITLE: D16168
CPEng,MIEAust,NPER
COPYRIGHT
THIS DRAWING AND THE INFORMATION SHOWN HEREON MEMB. NO: 2320868 STRATHFIELD NSW 2135 FRAMING DETAILS DRAWING NO.
IS THE PROPERTY OF DANMOR CONSULTING ENGINEERS P/L AND MAY
NOT BE USED FOR ANY OTHER PURPOSE THAN FOR WHICH SUPPLIED. SCALE AT A3: 1:100 S15

Potrebbero piacerti anche